Download as pdf or txt
Download as pdf or txt
You are on page 1of 46

Power Cables

Prysmian Group Prysmian Group Baltics

International reach, local expertise - we’re an innovative world We offer the widest range of services and know-how in the Our manufacturing plant in Keila was established in 1968 Success factors:
leader when it comes to cable technology, and we match that business. Each year, the Group manufactures thousands of and nowadays belongs to Prysmian Group. From our strategic
with our worldwide presence. Spanning 50 countries, 106 kilometers of underground and submarine cables and systems • we guarantee quality (ISO 9001, ISO 14001)
location we provide support to both local and foreign
plants, 25 research and development centres, and with about for power transmission and distribution, as well as medium customers for power and telecommunication cables and • we monitor occupational safety (ISO 45001)
29,000 employees, we’ve a strategic footprint that allows us to and low voltage cables for the construction and infrastructure related accessories. In the Baltics, with the plant and main
service emerging markets and communities across the globe sectors. We also produce a comprehensive range of optical office in Keila, Estonia, and offices in Riga, Latvia and Vilnius, • we have continuous production, 24/7
with ease. fibres, copper cables and connectivity systems for voice, video Lithuania, we employ about 160 people in plant operations,
• we are constantly looking for improvement opportunities
and data transmission for the telecommunications sector. sales and marketing, customer care, logistics, purchasing,
We’re proud to be a public company; it’s central to who we are
finances and administration. • we enhance the working environment with the 6S method
as a business. And our employees agree – around 50% of them We’re linking the world with the future of cable technology.
are shareholders. Listed on the Milan Stock Exchange in the
FTSE MIB Index, our core focus is to create innovative products
and deliver groundbreaking projects that secure long-term
profit, ensure value for our shareholders, and inspire continued
market confidence in the company.
Power Cables Table of Contents

Power cables are the backbone of energy systems. Therefore, Product range covers a broad spectrum of power cables based Bare Conductors 4 Power Cables 24 kV 48
the quality of these cables are essential in ensuring on the market needs. Cables are available from low-voltage
continuous energy flow to consumers. Using cables with poor bare conductors to high-voltage watertight underground
A 4 AXLJ-TTCL TSLF 12/20(24) kV 48
quality can significantly increase the probability of faults in cables and even submarine cables. ACSR 6 AXLJ-TTCL TSLF Triplex 12/20(24) kV 50
energy systems that can be very costly or even dangerous to
people. Application, compliance with standards and important
HK 8 AHXAMK-W 12/20 (24) kV 52
parameters regarding specific cable are shown on the product AXLJ-RMF 12/20(24) kV 54
Our cables are tested in accordance with all applicable page of each cable. In addition to the products included in this
standards and are produced according to the needs of our catalogue, also other types of power cables are available, as
Aerial Cables 10 AXQJ-RMF Pure 12/20(24) kV 56
customers. Continuous improvement regarding materials and agreed separately with the customer. AMKA 0,6/1(1,2) kV 10 AXCLJ-TT 12/20(24) kV 58
technology to provide the best quality on the market is our
priority. Prysmian Group represents the three well-known Commercial
EX 0,6/1(1,2) kV 12 AXALJ-TT 12/20(24) kV 60
Brands: Prysmian, Draka and General Cable. SAX-W 0,6/1(1,2) kV
®
14 AXQJ-TT Pure TSLI 12/20(24) kV 62
CCST-W 0,6/1(1,2) kV 16 FXLJ-TT TSLE 12/20(24)kV 64
CCSX AL3 WK 0,6/1(1,2) kV 18 FXQJ-TT Pure TSLI 12/20(24) kV 66

Power Cables 1 kV 20 Power Cables 36 kV 68


AXPK 1 core and AXPK-Plus 1 core 20 AXLJ-TTCL TSLF 18/30(36) kV 68

XPK 1 core and XPK-Plus 1 core 22 AXQJ-TT Pure TSLI 18/30(36) kV 70

AXPK 0,6/1(1,2) kV 24

AXPK-PLUS 0,6/1(1,2) kV 26 Power Cables 52 kV 72


ARLC ja ARLC-PLUS 0,6/1(1,2) kV 28 AXLJ-TTCL TSLF 26/45(52) kV 72

Power Cables 12 kV 30 Cable designations 74


AXQJ-TT Pure TSLI 6/10(12) kV 30 Cable designations used in Sweden 74

AXLJ-TTCL TSLF Triplex 6/10(12) kV 32 Cable designations used in Norway 75

AXQJ-TT Pure TSLI Triplex 6/10(12) kV 34 Cable designations used in Finland 76

AXQJ-RMF Pure 6/10(12) kV 36 Correction factors 78


AHXAMK-W 6/10(12) kV 38 General terms and conditions of supply 81
AXLJ-RMF 6/10(12) kV 40 Standard drums, dimensions and weights 81
AXCLJ-TT 6/10(12) kV 42 Drum handling guide 82
AXALJ-TT 6/10(12) kV 44 Recommendations for cable laying 84
FXLJ-TT 6/10(12) kV 46 Sheath testing in medium voltage cables 86
Bare Conductors Bare Conductors

Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
A 25 4000 K8 4741532250117 20074932
A 35 4000 K9 4741532250124 20074933
A 50 3500 K11 4741532250131 20074934
A 70 2500 K11 4741532250148 20074935

Product name Diameter over wire Cross section Weight Number of Min tensile strength
Application [mm] [mm2] [kg/km] wires of the conductor [kN]
Bare conductor for overhead power transmission. A 25 6,5 24,9 68 7 4,50
A 35 7,5 34,3 94 7 5,91
A 50 9 49,5 135 7 8,19
Approval
A 70 11 69,3 189 7 11,28
CE

Product Initial modulus Final modulus Coefficient of Max DC resistance at Current rating Max permissible

Standard name of elasticity of


conductor
of elasticity of
conductor
linear expansion
of messenger
(20˚C)
[Ω/km]
in air
[A]
short circuit
current for 1 sec.
GOST 889-80 [N/mm2] [N/mm2] [N/mm2] [kA]
EN 50182 A 25 41000 60000 23x10-6 1,498 136 2,5
A 35 41000 60000 23x10-6 0,835 170 3,4
A 50 41000 60000 23x10-6 0,578 215 5,0
Construction A 70 41000 60000 23x10-6 0,413 265 7,0
Cable shape Round
Conductors Stranded aluminium conductor
Conductor screen No insulation
Marking of cores No marking

Temperature
Maximum operating temperature 80°C

Features
Fire propagation Not applicable
UV resistance Good
REACH/SVHC declaration The cable does not contain any substances on the REACH/SVHC list
RoHS declaration All substances of the cable meet the requirements of RoHS directive

Electrical
Max short circuit temperature 200°C

POWER CABLES 4 Prysmian Group Baltics AS • baltics.prysmiangroup.com 5


Bare Conductors Bare Conductors

ACSR

Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
ACSR 34/6 SPARROW 2500 K9 4741532250254 20074938
ACSR 54/9 RAVEN 2200 K11 4741532250278 20074939
ACSR 85/14 PIGEON 2000 K12 4741532250285 20074940
ACSR 242/39 HAWK 2500 K20 4741532250322 20166519
ACSR 305/39 DUCK 2200 K26 4741532250339 20074941
ACSR 565/72 FINCH 1200 K22 4741532250353 20074942
Application
Bare conductor for overhead power transmission
Product name Number of wires Diameter over wire Cross section Weight Max permissible short circuit
(aluminium / steel) [mm] [mm2] [kg/km] current for 1 sec.** [kA]
ACSR 34/6 SPARROW 6/1 8,1 39,5 137,0 3,7
Flame retardance
ACSR 54/9 RAVEN 6/1 10,1 62,4 216,0 5,8
Not applicable
ACSR 85/14 PIGEON 6/1 12,8 99,3 344,0 9,2
ACSR 242/39 HAWK 26/7 21,8 281,0 976,0 26,1

Approval ACSR 305/39 DUCK 54/7 24,1 344,0 1151,0 32,5


CE ACSR 565/72 FINCH 54/19 32,9 637,0 2123,0 60,1

Product name Max DC resistance at 20˚C Min tensile Initial Final modulus Coefficient Current rating
Standard [Ω/km] strength of the modulus of of of linear in air*
IEC 61089 conductor elasticity of elasticity of expansion of [A]
[kN] conductor conductor conductor
EN 50182 [N/mm2] [N/mm2] [1/k]
SFS 5701 ACSR 34/6 SPARROW 0,848 12,20 64000 78000 19,2x10-6 210
ACSR 54/9 RAVEN 0,536 17,11 64000 78000 19,2x10-6 280
ACSR 85/14 PIGEON 0,337 24,13 64000 78000 19,2x10-6 360
Construction
ACSR 242/39 HAWK 0,120 84,90 61000 75500 19,2x10-6 745
Cable shape Round
Conductors Stranded aluminium and galvanized steel wires ACSR 305/39 DUCK 0,095 96,80 50000 67000 19,3x10-6 845

Center conductor Steel ACSR 565/72 FINCH 0,051 174,00 46000 63000 19,3x10-6 1250
Conductor screen No insulation *Air temperature 25°C
Marking of cores No marking **Initial temperature of conductor before short circuit 40°C, final temperature of conductor after short circuit 200°C

Temperature
Maximum operating temperature 80°C

Features
Fire propagation Not applicable
UV resistance Good
REACH/SVHC declaration The cable does not contain any substances on the REACH/SVHC list
RoHS declaration All substances of the cable meet the requirements of RoHS directive

Electrical
Max short circuit temperature 200°C

POWER CABLES 6 Prysmian Group Baltics AS • baltics.prysmiangroup.com 7


Bare Conductors Bare Conductors

HK

Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
HK 16 1000 K6 4741532250018 20162343
HK 25 500 K6 4741532250025 20162344
HK 35 1000 K6 4741532250032 20162345
HK 50 1000 K7 4741532250049 20162346
HK 70 1000 K8 4741532250056 20162347
HK 95 1000 K9 4741532250063 20162348
Application
HK 150 500 K11 4741532250087 20194993
Grounding wire for fixed installations.
HK 120 500 K9 4741532250070 20162349

Flame retardance Product name Diameter over wire Cross section Number of Weight Max DC resistance Max permissible short
[mm] [mm2] wires [kg/km] at 20˚C circuit current for 1 sec.*
Not applicable [Ω/km] [kA]
HK 16 5,1 15,5 7 140 1,15 2,3
HK 25 6,4 24,7 7 222 0,727 3,8
Approval
HK 35 7,5 34,4 7 309 0,524 5,3
CE
HK 50 8,9 46,8 19 422 0,387 7,2
HK 70 10,6 67,1 19 606 0,268 10,3
Standard HK 95 12,5 93,3 19 843 0,193 14,3
IEC 60228 HK 150 14,1 117 19 1062 0,153 18
HK 120 15,6 148 37 1338 0,124 22,6

Construction *Initial temperature of conductor before short circuit 40°C, final temperature of conductor after short circuit 200°C
Cable shape Round
Conductors Concentric stranded annealed copper conductor
Conductor screen No insulation
Marking of cores No marking

Features
Fire propagation Not applicable
UV resistance Good
REACH/SVHC declaration The cable does not contain any substances on the REACH/SVHC list
RoHS declaration All substances of the cable meet the requirements of RoHS directive

Electrical
Max short circuit temperature 200°C

POWER CABLES 8 Prysmian Group Baltics AS • baltics.prysmiangroup.com 9


Aerial Cables Aerial Cables

AMKA 0,6/1(1,2) kV

Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
AMKA 1x16+25, 1kV 2000 K11 4741532100009 20074959
AMKA 3x16+25, 1kV 1000 K12 4741532100023 20074961
AMKA 3x25+35, 1kV 1000 K14 4741532100047 20074963
AMKA 3x35+50, 1kV 1000 K16 4741532100054 20074964
AMKA 3x50+70, 1kV 1000 K18 4741532100061 20074965
AMKA 3x70+95, 1kV 500 K14 4741532100078 20074966
Application
AMKA 3x120+95, 1kV 500 K18 4741532100085 20074967
Aerial bundled power cable with aluminum conductor.

Product name Diameter over bare Diameter over Effective diameter in wind* Weight
conduc [mm] messenger [mm] [mm] [kg/km]
Flame retardance
AMKA 1x16+25, 1kV 4,4 5,8 11 135
Not applicable
AMKA 3x16+25, 1kV 4,4 5,8 20 270
AMKA 3x25+35, 1kV 5,8 6,8 23 390

Approval AMKA 3x35+50, 1kV 6,8 8,0 27 530


CE AMKA 3x50+70, 1kV 8,0 9,6 31 700
AMKA 3x70+95, 1kV 9,6 11,3 36 1000
AMKA 3x120+95, 1kV 12,7 11,3 42 1500
Standard
* Circumferance divided by π (Pi)
SFS 2200
HD 626-5D
Product name Min permissible Min permissible Min tensile Initial modulus Final modulus Coefficient of
IEC 60228 bending radius bending radius strength of elasticity of elasticity linear expansion
during laying at final installation of messenger of messenger of messenger of messenger
[m] [m] [kN] [N/mm2] [N/mm2] [N/mm2]

Construction AMKA 1x16+25, 1kV 0,28 0,20 7,4 55000 63000 23x10-6

Cable shape Insulated conductors are laid up around the messenger AMKA 3x16+25, 1kV 0,42 0,30 7,4 55000 63000 23x10-6

Conductors 16 mm²: round and solid aluminium conductor; AMKA 3x25+35, 1kV 0,50 0,35 10,3 55000 63000 23x10-6
25-120 mm²: round, stranded and compacted aluminium conductor AMKA 3x35+50, 1kV 0,58 0,41 14,2 55000 63000 23x10-6
Center conductor Carrier cable: round, stranded and compacted aluminium alloy conductor AMKA 3x50+70, 1kV 0,66 0,47 20,6 55000 63000 23x10-6
Conductor screen Black UV and weather resistant PE compound AMKA 3x70+95, 1kV 0,78 0,55 27,9 55000 63000 23x10-6
Core assembly Insulated cores are wrapped together
AMKA 3x120+95, 1kV 0,92 0,65 27,9 55000 63000 23x10-6
Marking of cores Phase conductors: 2,3 or 4 longitudinal ridges; Optional conductor: no ridges
Example of marking on sheath AMKA 3x16+35 1kV DRAKA “Production number”, “Date and time”, metre marked
Product name Max DC AC resistance Max DC Inductance Max permissible Max permissible
resistance of phase** resistance [mH/km] short circuit current short circuit current
of phase* [Ω/km] of messenger* for 1 sec., for 1 sec.,
Features [Ω/km] [Ω/km] phase conductor** messenger **
[kA] [kA]
UV resistance Good
AMKA 1x16+25, 1kV 1,910 2,300 1,380 0,29 1,0 1,5
Min bending radius during installation 20 x D
Min bending radius at final installation 14 x D AMKA 3x16+25, 1kV 1,910 2,300 1,380 0,35 1,0 1,5

REACH/SVHC declaration The cable does not contain any substances on the REACH/SVHC list AMKA 3x25+35, 1kV 1,200 1,400 0,986 0,34 1,6 2,1
RoHS declaration All substances of the cable meet the requirements of RoHS directive AMKA 3x35+50, 1kV 0,868 1,000 0,720 0,34 2,3 3,0
AMKA 3x50+70, 1kV 0,641 0,770 0,493 0,33 3,2 4,3
AMKA 3x70+95, 1kV 0,443 0,530 0,363 0,31 4,5 5,9
Electrical AMKA 3x120+95, 1kV 0,253 0,300 0,363 0,30 5,9 5,9
Max short circuit temperature 135°C (5s)
**Initial temperature of conductor before short circuit 70°C, final temperature of conductor after short circuit 135°C

POWER CABLES 10 Prysmian Group Baltics AS • baltics.prysmiangroup.com 11


Aerial Cables Aerial Cables

EX 0,6/1(1,2) kV

Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
EX 2x25 500 K9 4741532100108 20074968
EX 3x25 500 K9 4741532100115 20074969
EX 3x50 500 K11 4741532100139 20074971
EX 3x95 500 K14 4741532100177 20074974
EX 4x16 1000 K11 4741532100191 20130697
EX 4x25 500 K11 4741532100122 20074970
Application
EX 4x35 500 K11 4741532100153 20141393
Aerial bundled power cable with aluminium conductor.
EX 4x50 500 K11 4741532100146 20074972
EX 4x50 1000 K18 4741532100221 20204660

Alternative Product name Flame retardance EX 4x70 1000 K18 4741532100160 20074973
CENELEC N1ED4-AR Not applicable EX 4x95 500 K14 4741532100184 20074975
EX 4x95 1000 K20 4741532100184 20204661

Approval
Product Cable Weight Min permissible Min permissible Min strength of Max DC resistance Max permissible
CE name diameter [kg/km] bending radius bending radius at conductor of conductor short circuit
[mm] during laying final installation [kN] [Ω/km] current for 1 sec.*
[m] [m] [kA]

Standard EX 2x25 18 205 0,40 0,28 4,1 1,200 1,8

HD 626-3I EX 3x25 20 305 0,50 0,35 4,1 1,200 1,8


IEC 60228 EX 3x50 25 525 0,44 0,31 7,3 0,641 3,6
EX 3x95 34 1000 0,64 0,45 13,7 0,320 6,8
EX 4x16 18 265 0,36 0,25 2,6 1,910 1,1
Construction EX 4x25 22 405 0,68 0,48 4,1 1,200 1,8
Cable shape Round
EX 4x35 24 520 0,35 0,25 5,6 0,868 2,5
Conductors Round, stranded and compacted aluminium conductor
EX 4x50 28 700 0,47 0,33 7,3 0,641 3,6
Conductor screen Black UV and weather resistant PE compound
EX 4x70 32 1000 0,56 0,39 10,4 0,443 5,0
Core assembly Insulated cores are wrapped together
Marking of cores Marked with longitudinal ridges, 2-core: Neutral-conductor - no ridge, EX 4x95 38 1350 0,76 0,53 13,7 0,320 6,8

Phase 1 - 1 ridge, 3-core: Phase 1 – 1 ridge, Phase 2 – 2 ridges,


*Initial temperature of conductor before short circuit 40°C, final temperature of conductor after short circuit 135°C
Phase 3 – 3 ridges, 4-core: Neutral-conductor - no ridge, Phase 1 - 1 ridge,
Phase 2 - 2 ridges, Phase 3 - 3 ridges
Example of marking on sheath EX 4x50 1kV DRAKA “Production number”, “Date and time”, metre marked

Temperature
Maximum operating temperature 70°C

Features
UV resistance Yes
Min bending radius during installation 20 x D
Min bending radius at final installation 14 x D
REACH/SVHC declaration The cable does not contain any substances on the REACH/SVHC list
RoHS declaration All substances of the cable meet the requirements of RoHS directive

Electrical
Max short circuit temperature 135°C (5s)

POWER CABLES 12 Prysmian Group Baltics AS • baltics.prysmiangroup.com 13


Aerial Cables Aerial Cables

SAX-W® 12/20(24)kV

Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
SAX-W 35 2000 K11 4741532130709 20074926
SAX-W 50 2000 K11 4741532130716 20074927
SAX-W 70 2000 K12 4741532130723 20074928
SAX-W 95 2000 K14 4741532130730 20074929
SAX-W 120 2000 K16 4741532130747 20074930
SAX-W 150 2000 K18 4741532130754 20074931
Application
Aerial power cable with stranded and compacted aluminium conductor.
Product name Diameter over Diameter over Weight Min permissible Min permissible Min tensile
conductor covered [kg/km] bending radius during bending radius at final strength
[mm] conductor laying installation of conductor
Alternative Product name [mm] [m] [m] [kN]

PAS-W / CCX-WK SAX-W 35 6,9 11,5 160 0,16 0,11 11,2


SAX-W 50 8,0 12,7 200 0,18 0,13 15,5
SAX-W 70 9,7 14,3 270 0,2 0,14 22,5
Flame retardance SAX-W 95 11,3 16,1 350 0,22 0,16 30,4
Not applicable SAX-W 120 12,8 17,6 425 0,25 0,18 38,0
SAX-W 150 14,2 18,9 510 0,27 0,19 47,3

Approval
CE Product name Initial modulus Final modulus Coefficient of Max DC resistance Current rating Max permisible
of elasticity of of elasticity of linear expansion of conductor in air * short circuit
conductor conductor of messenger [Ω/km] [A] current for 1 sec.**
[N/mm2 ] [N/mm2 ] [1/K] [kA]

Standard SAX-W 35 61000 62500 23x10-6 0,986 200 3,2


IEC 60228 SAX-W 50 61000 62500 23x10-6 0,720 245 4,3
EN 50397-1 SAX-W 70 61000 62500 23x10-6 0,493 310 6,4
SAX-W 95 61000 62500 23x10-6 0,363 370 8,6
SAX-W 120 53000 62000 23x10-6 0,288 430 11,0
Construction
SAX-W 150 53000 62000 23x10-6 0,239 485 13,5
Cable shape Round
Conductors Watertight aluminium alloy, round, stranded and compacted *Air temperature 25°C, conductor temperature 80°C
Outer sheath Black weather resistant XLPE compound **Initial temperature of conductor before short circuit 40°C, final temperature of conductor after short circuit 200°C
Example of marking on sheath EX 4x50 1kV DRAKA “Production number”, “Date and time”, metre marked

Temperature
Maximum operating temperature 80°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended

Features
UV resistance Good

Electrical
Max short circuit temperature 200°C

POWER CABLES 14 Prysmian Group Baltics AS • baltics.prysmiangroup.com 15


Aerial Cables Aerial Cables

CCST-W 12/20(24)kV

Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
CCST-39 W 2000 K12 4741532130808 20163991
CCST-62 W 5000 K20 4741532130839 20159492
CCST-99 W 4000 K20 4741532130846 20163988
CCST-159 W 1000 K14 4741532130860 20163989
CCST-241 W 1000 K18 4741532130884 20163989

Application
Product name Diameter over Diameter over Weight Min permissible Min permissible Min tensile
Covered conductor with a semiconductive layer for pole installation. conductor covered [kg/km] bending radius during bending radius at strength
[mm] conductor laying final installation of conductor
[mm] [m] [m] [kN]

Alternative Product name CCST-39 W 8,1 13,1 225 0,2 0,14 12,2

BLL 20 kV CCST-62 W 10,1 15,1 309 0,23 0,16 8,64


CCST-99 W 12,8 17,8 449 0,27 0,19 29,22
CCST-159 W 16,3 21,3 575 0,32 0,22 43,61
Flame retardance CCST-241 W 20,1 25,1 829 0,38 0,27 61,49
Not applicable
Product name Initial modulus Final modulus Coefficient of Max DC resistance Current rating Max permissible
of elasticity of of elasticity of linear expansion of conductor in air * short circuit
Approval conductor conductor of messenger [Ω/km] [A] current for 1 sec.**
[N/mm2 ] [N/mm2 ] [1/K] [kA]
CE
CCST-39 W 64000 78000 19,2 x 10-6 0,848 170 3,2
CCST-62 W 64000 78000 19,2 x 10-6 0,536 225 5,0

Standard CCST-99 W 64000 78000 19,2 x 10-6 0,337 310 8,0


IEC 60228 CCST-159 W 53000 62000 23 x 10-6 0,193 440 15,3
EN 50397-1 CCST-241 W 53000 62000 23 x 10-6 0,127 580 23,0

*Conductor temperature 70°C


Construction **Initial temperature of conductor before short circuit 40°C, final temperature of conductor after short circuit 200°C
Cable shape Round
Conductors CCST-W 39, 62 ja 99: Round stranded aluminium steel reinforced conductor
CCST-W 159 ja 241: Round, stranded aluminium steel reinforced conductor
Conductor screen Semiconductive compound
Outer sheath Weather resistant PE, black
Example of marking on sheath CCST-99W 20kV DRAKA, “Production number”, “Date and time”, metre marked.

Temperature
Maximum operating temperature 70°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended

POWER CABLES 16 Prysmian Group Baltics AS • baltics.prysmiangroup.com 17


Aerial Cables Aerial Cables

CCSX AL3 WK 12/20(24)kV

Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
CCSX 35 AL3 WK 2000 K11 4741532130600 20134348
CCSX 50 AL3 WK 2000 K12 4741532130617 20134349
CCSX 70 AL3 WK 2000 K12 4741532130624 20134350
CCSX 95 AL3 WK 2000 K14 4741532130631 20134351
CCSX 120 AL3 WK 2000 K18 4741532130648 20134352
CCSX 150 AL3 WK 2000 K18 4741532130655 20134353
Application
Covered conductor for pole installation.
Product name Diameter Diameter over Weight Min permissible Min permissible Min tensile strength
over covered [kg/km] bending radius bending radius of conductor
conductor conductor during laying at final installation [kN]
Flame retardance [mm] [mm] [m] [m]

Not applicable CCSX 35 AL3 WK 6,9 12 170 0,18 0,13 11,2


CCSX 50 AL3 WK 8 13,2 220 0,20 0,14 15,5
CCSX 70 AL3 WK 9,7 14,8 290 0,22 0,16 22,5
Standard CCSX 95 AL3 WK 11,3 16,5 370 0,25 0,17 30,4
IEC 60228 CCSX 120 AL3 WK 12,8 18 455 0,27 0,19 38,0
EN 50397-1
CCSX 150 AL3 WK 14,2 19,4 545 0,29 0,20 47,3

Construction Product name Initial modulus


of elasticity of
Final modulus
of elasticity of
Coefficient of
linear expansion
Max DC
resistance of
Current rating
in air *
Max permissible
short circuit
Cable shape Round conductor conductor of messenger conductor [A] current for 1 sec. **
Conductors Round, stranded and compacted watertight aluminium alloy conductor [N/mm2 ] [N/mm2 ] [1/K] [Ω/km] [kA]

Conductor screen Cross-linkable semiconductive compound CCSX 35 AL3 WK 61000 62500 23x10-6 0,986 200 3,2
Outer sheath Black weather resistant XLPE compound CCSX 50 AL3 WK 61000 62500 23x10-6 0,720 245 4,3
Example of marking on sheath CCSX 70 AL3 WK DRAKA “Production number”, “Date and time”, metre marked CCSX 70 AL3 WK 61000 62500 23x10-6 0,493 310 6,4
CCSX 95 AL3 WK 61000 62500 23x10-6 0,363 370 8,6
CCSX 120 AL3 WK 61000 62500 23x10-6 0,288 430 11,0
Temperature
CCSX 150 AL3 WK 61000 62500 23x10-6 0,230 485 13,5
Maximum operating temperature 80°C
Minimum temperature at installation -20°C *Conductor temperature 70°C
**Initial temperature of conductor before short circuit 40°C, final temperature of conductor after short circuit 200°C

POWER CABLES 18 Prysmian Group Baltics AS • baltics.prysmiangroup.com 19


Power Cables 1 kV Power Cables 1 kV

AXPK 1 core 0,6/1(1,2) kV


AXPK-Plus 1 core 0,6/1(1,2) kV
Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
AXPK 1x185 1000 K14 4741532130006 20074943
AXPK 1x240 1000 K18 4741532130013 20074944
AXPK 1x300 1000 K18 4741532130020 20074945
AXPK 1x400 1000 K18 4741532130037 20074946
AXPK 1x500 500 K18 4741532130044 20074947
AXPK 1x630 500 K18 4741532130051 20074948
Application
AXPK 1x800 500 K20 4741532130068 20074949
Power cable with round, stranded and compacted aluminium conductor.
AXPK-PLUS 1x300 500 K14 6410006019311 20140296
For fixed installations indoors and outdoors, perfect for ploughing down.
Suitable for cable ducts and house connections. AXPK-PLUS 1x800 500 K20 6410006019359 20140297

AXPK-Plus is the halogen-free version of the cable.


Product name Cable Weight Min.permissible Min permissible Max permissible Max permissible
diameter [kg/km] bending radius bending radius pulling force pulling force
[mm] during laying at final installation with a pulling grip with a pulling eye
Alternative Product name [m] [m] [kN] [kN]
AXMK AXPK 1x185 24 745 0,360 0,260 2,7 9,2
AXPK 1x240 27 940 0,405 0,290 3,6 12
AXPK 1x300 29 1150 0,435 0,310 4,5 15
Flame retardance
AXPK 1x400 32 1460 0,480 0,340 6 20
EN 60332-1-2 Vertical flame propagation for a single insulated wire or cable
AXPK 1x500 36 1850 0,540 0,380 7,0 20
AXPK 1x630 40 2350 0,600 0,420 8,1 20
Standard AXPK 1x800 44 2950 0,660 0,470 8,5 20
IEC 60502-1 AXPK-PLUS 1x300 29 2160 0,435 0,310 4,5 15
HD 603 part 5D AXPK-PLUS 1x800 44 2900 0,660 0,470 8,5 20
EN 50575:2014
EN 60228
Product name Current rating Current rating Current rating Current rating Max permissible Max DC resistance
in air (conductor in air (conductor in air (conductor in air (conductor short circuit of conductor
70°C) [A]; 70°C) [A]; 90°C) [A]; 90°C) [A]; current for 1 sec. * [Ω/km]
flat formation trefoil formation flat formation trefoil formation [kA]
Construction
AXPK 1x185 340 325 425 410 17,5 0,1640
Cable shape Round
Conductors Round, compacted and stranded aluminium conductor AXPK 1x240 405 390 510 485 22,6 0,1250

Conductor screen Black XLPE compound AXPK 1x300 470 450 590 565 28,3 0,1000
Outer sheath AXPK - black PVC AXPK 1x400 570 545 720 685 37,6 0,0778
AXPK-Plus - black self-extinguishing halogen-free compound AXPK 1x500 665 630 835 800 47,00 0,0605
Example of marking on sheath AXPK-PLUS 1kV DRAKA “Date and time”, metre marked AXPK 1x630 775 735 975 930 59,2 0,0467
AXPK 1x800 1000 830 1300 1050 75,6 0,0367
AXPK-PLUS 1x300 470 450 590 565 28,3 0,1000
Temperature
AXPK-PLUS 1x800 1000 830 1300 1050 75,6 0,0367
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended
* Initial temperature of conductor before short circuit 90°C, final temperature of conductor after short circuit 250°C
The ratings are based on the following conditions : maximum conductor temperature- 90°C, ground temperature- 15°C, air temperature- 25°C,
Features thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,7m

CPR performance class Eca


UV resistance Good

Electrical
Max short circuit temperature 250°C

POWER CABLES 20 Prysmian Group Baltics AS • baltics.prysmiangroup.com 21


Power Cables 1 kV Power Cables 1 kV

XPK 1 core 0,6/1(1,2) kV


XPK-Plus 1 core 0,6/1(1,2) kV
Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
XPK 1x185 500 K11 4741532120502 20140290
XPK 1x240 500 K12 4741532120519 20180995
XPK 1x300 500 K14 4741532120526 20140291
XPK-PLUS 1X185 500 K11 4741532120533
XPK-PLUS 1X300 500 K14 4741532120557

Application
Product name Cable Weight Min permissible Min permissible Max permissible Max permissible
Power cable with round, stranded and compacted copper conductor. diameter [kg/km] bending radius bending radius pulling force pulling force
For fixed installations indoors and outdoors, perfect for ploughing down. [mm] during laying at final installation with a pulling grip with a pulling eye
[m] [m] [kN] [kN]
Suitable for cable ducts and house connections.
XPK-Plus is the halogen-free version of the cable. XPK 1x185 23 1900 0,350 0,240 2,7 18,5
XPK 1x240 26 2400 0,390 0,270 3,6 20
XPK 1x300 29 3050 0,440 0,310 4,5 20
Alternative Product name XPK-PLUS1x185 23 1900 0,350 0,240 2,7 18,5
XMK XPK-PLUS1x300 29 3000 0,440 0,310 4,5 20

Product name Current rating Current rating Current rating Current rating Max permissible Max DC resistance
Flame retardance in air (conductor in air (conductor in air (conductor in air (conductor short circuit of conductor
EN 60332-1-2 Vertical flame propagation for a single insulated wire or cable 70°C) [A]; 70°C) [A]; 90°C) [A]; 90°C) [A]; current for 1 sec. * [Ω/km]
flat formation trefoil flat formation trefoil [kA]
formation formation
XPK 1x185 440 425 550 530 26,4 0,0991
Approval
XPK 1x240 525 500 655 630 34,2 0,0745
CE
XPK 1x300 610 580 765 730 42,8 0,0601
XPK-PLUS1x185 440 425 550 530 26,4 0,0991

Standard XPK-PLUS1x300 610 580 765 730 42,8 0,0601


IEC 60502-1 EN 50575:2014
* Initial temperature of conductor before short circuit 90°C, final temperature of conductor after short circuit 250°C
HD 603 part 5D EN 60228
The ratings are based on the following conditions : maximum conductor temperature- 90°C, ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,7m

Construction
Cable shape Round
Conductors Round, compacted and stranded copper conductor
Conductor screen Black XLPE compound
Outer sheath XPK - black PVC
XPK-Plus - black self-extinguishing halogen-free compound
Example of marking on sheath XPK-PLUS ANNEALED 1KV DRAKA “Date and time”, metre marked

Temperature
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended

Features
UV resistance Good

Electrical
Max short circuit temperature 250°C

POWER CABLES 22 Prysmian Group Baltics AS • baltics.prysmiangroup.com 23


Power Cables 1 kV Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
AXPK 4G16 RE 1000 K12 4741532130105 20076220

AXPK 0,6/1(1,2) kV AXPK 4G16 RM


AXPK 5G16 RE
1000
1000
K12
K12
4741532130112
4741532130129
20076221
20074980
AXPK 4G25 1000 K14 4741532130136 20076222
AXPK 5G25 1000 K16 4741532130150 20074981
AXPK 4G35 1000 K16 4741532130167 20076224
AXPK 4G50 1000 K16 4741532130181 20076226
AXPK 4G70 1000 K20 4741532130204 20076228
AXPK 4G95 1000 K20 4741532130228 20076230
AXPK 4G120 1000 K22 4741532130235 20076231
AXPK 4G150 500 K20 4741532130259 20076233
AXPK 4G185 500 K20 4741532130266 20076234
AXPK 4G240 500 K22 4741532130273 20076235

Application AXPK 4G300 500 K24 4741532130280 20076236


Power cable with aluminium conductor. For fixed installation indoors and outdoors, perfect for ploughing down.
Suitable for cable ducts and house connections. Product name Cable Weight Min permissible bending Min permissible bending Max permissible short
diameter [kg/km] radius during laying radius at final installation circuit current for 1 sec.*
[mm] [m] [m] [kA]

Approval AXPK 4G16 RE 19 355 0,22 0,16 1,5

CE AXPK 4G16 RM 20 370 0,23 0,16 1,5


AXPK 5G16 RE 20 420 0,24 0,17 1,5
AXPK 4G25 21 535 0,27 0,19 2,4
Flame retardance AXPK 5G25 25 640 0,30 0,21 2,4
EN 60332-1-2 Vertical flame propagation for a single insulated wire or cable AXPK 4G35 23 645 0,27 0,19 3,3
AXPK 4G50 27 820 0,31 0,22 4,7

Standard AXPK 4G70 30 1120 0,36 0,25 6,6


AXPK 4G95 34 1450 0,40 0,28 8,9
IEC 60502-1 HD 603 part 5D
HD 308 S2 EN 60228 AXPK 4G120 38 1820 0,45 0,32 11,3
AXPK 4G150 42 2210 0,50 0,35 14,1
AXPK 4G185 47 2760 0,56 0,39 17,4
Construction AXPK 4G240 53 3605 0,63 0,44 22,6
Cable shape Round AXPK 4G300 58 4380 0,69 0,48 28,2
Conductors 16 mm2 – s tranded and compacted or solid round aluminium conductor;
* Initial temperature of conductor before short circuit 90°C, final temperature of conductor after short circuit 250°C
25 mm2 - stranded, compacted and annealed aluminium conductor;
35–300 mm2 – stranded, compacted and annealed sector shaped Product name Max Max Current rating Current rating Current rating Current rating Max DC
aluminium conductor permissible permissible in ground** in ground** in air in air resistance
Conductor screen XLPE compound pulling force pulling force (conductor (conductor 70°C) (conductor 70°C) (conductor 90°C) at 20°C
with a pulling with a pulling 70°C) [A] [A] [A] [Ω/km]
Core assembly Insulated cores are wrapped together grip [kN] eye [kN] [A]
Outer sheath Black PVC AXPK 4G16 RE 0,9 1,9 78 61 63 80 1,91
Example of marking on sheath AXPK 1KV 4G16 DRAKA “Date and time”, metre marked
AXPK 4G16 RM 0,9 2,4 78 61 63 80 1,91
AXPK 5G16 RE 1,1 1,9 78 61 63 80 1,91

Temperature AXPK 4G25 1,5 3 100 78 81 101 1,20

Maximum operating temperature 90°C AXPK 5G25 1,8 3,7 100 78 81 101 1,20

Minimum temperature at installation -15°C, below 0°C special precautions are recommended AXPK 4G35 2,1 4,2 125 94 100 125 0,868
AXPK 4G50 3 6 150 111 122 152 0,641
AXPK 4G70 4,2 8,4 185 137 156 194 0,443
Features AXPK 4G95 5,7 11,4 220 161 190 236 0,320
CPR performance class Eca
AXPK 4G120 7,2 14,4 255 184 220 274 0,253
UV resistance Good
AXPK 4G150 8,5 18 280 207 255 316 0,206
Bending radius 12 xD
AXPK 4G185 8,5 20 330 233 291 367 0,164
AXPK 4G240 8,5 20 375 267 343 425 0,125

Electrical AXPK 4G300 8,5 20 430 303 396 490 0,100


Max short circuit temperature 250°C
** The ratings are based on the following conditions : maximum conductor temperature- 90°C, ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,7m

POWER CABLES 24 Prysmian Group Baltics AS • baltics.prysmiangroup.com 25


Power Cables 1 kV Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
AXPK-PLUS 4G16 RE 1000 K12 4741532120106 20079318

AXPK-PLUS 0,6/1(1,2) kV AXPK-PLUS 5G16 RE


AXPK-PLUS 4G16 RM
1000
1000
K12
K12
4741532120120
4741532120090
20097601
20079317
AXPK-PLUS 4G25 1000 K14 4741532120137 20076250
AXPK-PLUS 5G25 1000 K14 4741532120281 20163987
AXPK-PLUS 4G35 1000 K16 4741532120151 20076251
AXPK-PLUS 5G35 1000 K16 4741532120274 20163932
AXPK-PLUS 4G50 1000 K18 4741532120168 20076252
AXPK-PLUS 4G70 1000 K20 4741532120175 20076253
AXPK-PLUS 4G95 1000 K20 4741532120182 20076254
AXPK-PLUS 4G120 1000 K22 4741532120199 20076255
AXPK-PLUS 4G150 500 K20 4741532120205 20076256
AXPK-PLUS 4G185 500 K22 4741532120212 20076257

Application AXPK-PLUS 4G240 500 K22 4741532120229 20076258


Power cable with stranded compacted aluminium conductor. The cable is halogen free. AXPK-PLUS 4G300 500 K24 4741532120236 20076259
For fixed installation indoors and outdoors, perfect for ploughing down.
Suitable for cable ducts and house connections. Product name Cable Weight Min permissible bending Min permissible bending Max permissible short
diameter [kg/km] radius during laying radius at final installation circuit current for 1 sec.*
[mm] [m] [m] [kA]

Approval Flame retardance AXPK-PLUS 4G16 RE 19 320 0,22 0,15 1,5

CE EN 60332-1-2 Vertical flame propagation for a single insulated wire or cable AXPK-PLUS 5G16 RE 21 380 0,24 0,17 1,5
AXPK-PLUS 4G16 RM 20 340 0,22 0,16 1,5
AXPK-PLUS 4G25 21 490 0,27 0,19 2,4
Standard AXPK-PLUS 5G25 25 590 0,30 0,21 2,4
IEC 60502-1
AXPK-PLUS 4G35 23 600 0,27 0,19 3,3
HD 603 part 5D
AXPK-PLUS 5G35 27 760 0,33 0,23 3,3
HD 60364-5-52
AXPK-PLUS 4G50 27 770 0,31 0,22 4,7
EN 50575:2014
EN 60228 AXPK-PLUS 4G70 30 1050 0,36 0,25 6,6
AXPK-PLUS 4G95 34 1370 0,40 0,28 8,9
AXPK-PLUS 4G120 38 1700 0,44 0,31 11,3
Construction AXPK-PLUS 4G150 42 2100 0,49 0,35 14,1
Cable shape Round AXPK-PLUS 4G185 47 2620 0,55 0,39 17,4
Conductors 16 mm2 – s tranded and compacted or solid round aluminium conductor;
AXPK-PLUS 4G240 53 3470 0,63 0,44 22,6
25 mm2 - stranded, compacted and annealed aluminium conductor;
AXPK-PLUS 4G300 58 4220 0,69 0,48 28,2
35–300 mm2 – stranded, compacted and annealed sector shaped
aluminium conductor
Conductor screen XLPE compound Product name Max Max Current rating Current rating Current rating Current rating Max DC
permissible permissible in ground** in ground** in air in air resistance
Core assembly Insulated cores are wrapped together pulling force pulling force (conductor (conductor (conductor (conductor at 20°C
Outer sheath Black halogen-free self-extinguishing PE compound with a pulling with a pulling 70°C) 70°C) 70°C) 90°C) [Ω/km]
grip [kN] eye [kN] [A] [A] [A] [A]
Example of marking on sheath AXPK-PLUS 1KV 4G16 DRAKA “Date and time”, metre marked
AXPK-PLUS 4G16 RE 0,9 1,9 78 61 63 80 1,91
AXPK-PLUS 5G16 RE 1,2 2,4 78 61 63 80 1,91

Temperature AXPK-PLUS 4G16 RM 0,9 1,9 78 61 63 80 1,91


Maximum operating temperature 90°C AXPK-PLUS 4G25 1,5 3,0 100 78 81 101 1,20
Minimum temperature at installation -20°C, below 0°C special precautions are recommended AXPK-PLUS 5G25 1,8 3,7 100 78 81 101 1,20
AXPK-PLUS 4G35 2,1 4,2 125 94 100 125 0,868
AXPK-PLUS 5G35 2,6 5,2 125 94 100 125 0,868
Features
AXPK-PLUS 4G50 3,0 6,0 150 111 122 152 0,641
CPR performance class Eca
AXPK-PLUS 4G70 4,2 8,4 185 137 156 194 0,443
UV resistance Good
Bending radius 12 xD AXPK-PLUS 4G95 5,7 11,4 220 161 190 236 0,320
AXPK-PLUS 4G120 7,2 14,4 255 184 220 274 0,253
AXPK-PLUS 4G150 8,5 18,0 280 207 255 316 0,206
Electrical AXPK-PLUS 4G185 8,5 20.0 330 233 291 367 0,164
Max short circuit temperature 250°C AXPK-PLUS 4G240 8,5 20.0 375 267 343 425 0,125
AXPK-PLUS 4G300 8,5 20,0 430 303 396 490 0,100

** The ratings are based on the following conditions : maximum conductor temperature- 90°C, ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,7m

POWER CABLES 26 Prysmian Group Baltics AS • baltics.prysmiangroup.com 27


Power Cables 1 kV Power Cables 1 kV

ARLC 0,6/1(1,2) kV
ARLC-PLUS 0,6/1(1,2) kV
Product name Standard delivery length [m] Delivery package EAN/GTIN number Product code
ARLC 4G16 + 2.5Cu 1kV 1000 K12 4741532130440 20111654
ARLC 4G25 + 2.5Cu 1kV 1000 K14 4741532130457 20076248
ARLC 4G35 + 2.5Cu 1kV 500 K14 4741532130464 20076249
ARLC-PLUS 4G16 + 2.5Cu 1kV 1000 K12 4741532130471 20112072
ARLC-PLUS 4G25 + 2.5Cu 1kV 1000 K14 4741532130488 20164811
ARLC-PLUS 4G35 + 2.5Cu 1kV 500 K14 4741532130495 20172988
Application
Road lighting cable with aluminium conductor and copper signal conductor. ARLC-PLUS is halogen free version.
Product name Cable diameter Weight Min permissible bending radius Min permissible bending radius
[mm] [kg/km] during laying at final installation
[m] [m]
Alternative Product name Flame retardance ARLC 4G16 + 2.5Cu 18,1 380 0,24 0,17
ARLC - HF IEC 60332-1-2 - Vertical flame propagation for a single insulated wire or cable ARLC 4G25 + 2.5Cu 22,6 545 0,26 0,19
ARLC 4G35 + 2.5Cu 26,1 715 0,28 0,2
ARLC-PLUS 4G16 + 2.5Cu 18,1 355 0,24 0,17
Approval
ARLC-PLUS 4G25 + 2.5Cu 22,6 515 0,26 0,19
CE
ARLC-PLUS 4G35 + 2.5Cu 26,1 690 0,28 0,2

Standard Product name Max permissible pulling force Max permissible pulling force Max DC resistance at 20°C
IEC 60502-1 HD 603 Part 5 Section D with a pulling grip with a pulling eye [Ω/km]
[kN] [kN]
ARLC 4G16 + 2.5Cu 0,9 3,2 1,910

Construction ARLC 4G25 + 2.5Cu 1,5 5,0 1,200

Cable shape Round ARLC 4G35 + 2.5Cu 2,1 7,0 0,868

Conductors 16 mm2: solid round aluminium conductor; ARLC-PLUS 4G16 + 2.5Cu 0,9 3,2 1,910
25 mm2: stranded round aluminium conductor; ARLC-PLUS 4G25 + 2.5Cu 1,5 5,0 1,200
35 mm2: sector shaped aluminium conductor ARLC-PLUS 4G35 + 2.5Cu 2,1 7,0 0,868
Center conductor 2,5 mm2: solid round insulated copper signal conductor
Conductor screen XLPE
Product name Current rating Current rating in air* Current rating in air* Max permisible short
Lay up / Shielding Four insulated conductors stranded together in ground* (conductor 70°C) (conductor 90°C) circuit current for 1 sec.**
Core assembly The cores are wrapped around a compact copper signal conductor (conductor 70°C) [A] [A] [kA]
[A]
Marking of cores Phase conductors: brown, black, grey; PEN conductor: yellow-green;
ARLC 4G16 + 2.5Cu 78,0 64 75 1,5
Signal conductor: black
Outer sheath ARLC: black PVC ARLC 4G25 + 2.5Cu 100,0 83 105 2,3

ARLC-PLUS: black self-extinguishing halogen-free compound ARLC 4G35 + 2.5Cu 125,0 105 130 3,3
Example of marking on sheath ARLC DRAKA “Date and time”, metre marked ARLC-PLUS 4G16 + 2.5Cu 78,0 64 75 1,5
ARLC-PLUS 4G25 + 2.5Cu 100,0 83 105 2,3
ARLC-PLUS 4G35 + 2.5Cu 125,0 105 130 3,3
Temperature
Maximum operating temperature 90°C *T
 he ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m
Minimum temperature at installation ARLC: -15°C, below 0°C special precautions are recommended
** Initial temperature of conductor before short circuit 90°C, final temperature of conductor after short circuit 250°C
ARLC-PLUS: -20°C, below 0°C special precautions are recommended

Features
UV resistance Good
Bending radius 12 xD

Electrical
Max short circuit temperature 250°C

POWER CABLES 28 Prysmian Group Baltics AS • baltics.prysmiangroup.com 29


Power Cables 12 kV
Power Cables 12 kV

AXQJ -TT Pure TSLI 6/10(12) kV Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
1x50/16 15,9 23,5 500 K11 7330384720878 20218299
1x70/16 16,9 24,5 500 K11 7330384720885 20218300
1x95/25 18,6 26,5 500 K12 7330384720892 20218371
1x120/25 20,2 28,0 500 K12 7330384720908 20218372
1x150/25 21,5 29,5 500 K12 7330384720915 20218373
1x185/25 23,2 31,5 500 K14 7330384720922 20218374
1x240/35 25,4 33,5 500 K14 7330384720939 20218375
1x300/35 27,9 36,5 500 K16 7330384720946 20218376
1x400/35 31,1 38,0 500 K16 7330384720953 20218377
Application
1x500/35 34,0 43,0 500 K18 7330384720960 20218378
Halogen-free, flame retardant and self-extinguishing in case of fire.
1x630/35 37,9 47,0 500 K20 7330384720977 20218379
Smoke in the event of fire is limited, transparent (to facilitate evacuation) and not harmful to electronic equipment.
Radial and longitudinal water sealed distribution cable for use indoors and outdoors for 3-phase formation. Installation in 1x800/50 42,2 51,6 500 K20 7330384720984 20218380

pipes and ground. Ploughing down is not recommended. Ripcords for easier and safer stripping of the outer sheath.
Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance in trefoil/in flat* in trefoil/in flat* [µF/km] current / phase current
[mm2] [Ω/km] [Ω/km] [mH/km] [Ω/km] [A/km] [A/km]
Alternative Product name
1x50/16 0,6410 1,150 0,40 / 0,72 0,13 / 0,23 0,25 0,5 1,4
SE-N10XC7A5Z1-AR
1x70/16 0,4430 1,150 0,37 / 0,69 0,12 / 0,22 0,28 0,5 1,6
1x95/25 0,3200 0,727 0,36 / 0,66 0,11 / 0,21 0,32 0,6 1,8

Standard 1x120/25 0,2530 0,727 0,34 / 0,64 0,11 / 0,20 0,35 0,7 2,0
HD 620 Part 10 Section M HD 604 1x150/25 0,2060 0,727 0,33 / 0,62 0,10 / 0,20 0,38 0,7 2,1
HD 620 Part 10 Section K EN 50575:2014 1x185/25 0,1640 0,727 0,32 / 0,60 0,10 / 0,18 0,41 0,8 2,3
1x240/35 0,1250 0,524 0,31 / 0,58 0,09 / 0,17 0,46 0,9 2,6
1x300/35 0,1000 0,524 0,30 / 0,59 0,09 / 0,17 0,50 1,0 3,0
Construction
1x400/35 0,0778 0,524 0,29 / 0,54 0,09 / 0,16 0,57 1,1 3,3
Cable shape Round
1x500/35 0,0605 0,524 0,28 / 0,52 0,09 / 0,16 0,58 1,1 3,3
Conductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2,
longitudinal water sealed 1x630/35 0,0469 0,524 0,27 / 0,50 0,09 / 0,16 0,64 1,2 3,6

Inner semi-conducting layer Extruded 1x800/50 0,0367 0,387 0,27 / 0,49 0,09 / 0,15 0,79 1,5 4,5
Conductor screen XLPE, min thickness = 2,96 mm * Cable distance, installation in flat formation = 70 mm
Outer semi-conducting layer Bonded
Longitudinal water tightness Semi conducting water blocking tape Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
Shield / Screen Annealed copper wires in contact with aluminum tape screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
[mm2] in ground** in air** in air** during 1s during 1s
Radial water blocking Aluminium laminate bonded to the sheath [A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
Ripcord Aramid [kA] [kA]
Outer sheath Halogen free compound, black 1x50/16 155 160 195 5,2 4,7
Example of marking on sheath AXQJ-TT Pure TSLI 12kV 1x240 AFR/35 D-s2d2a2 DRAKA 1x70/16 200 190 235 7,2 6,6
“Date and time”, metre marked 1x95/25 235 230 280 9,9 8,9
1x120/25 265 265 325 12,4 11,3

Temperature 1x150/25 300 300 370 15,6 14,2

Maximum operating temperature 90°C 1x185/25 330 345 425 19,2 17,5

Minimum temperature at installation -20°C, below 0°C special precautions are recommended 1x240/35 385 400 490 25,0 22,7
1x300/35 435 460 565 31,0 28,3
1x400/35 510 555 680 41,6 37,8
Features 1x500/35 570 635 775 52,0 47,2
CPR performance class Dca-s2d2a2 1x630/35 635 720 880 65,6 59,5
Bending radius In fixed installation: 10 x D
1x800/50 695 822 1010 83,2 75,6
When pulling-in: 15 x D
When plowing down: 8 x D ** Trefoil with screen grounded in both end.
The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.

Electrical Note: screen resistance is the sum of copper wires and aluminum tape.

Impulse voltage 75 kV

POWER CABLES 30 Prysmian Group Baltics AS • baltics.prysmiangroup.com 31


Power Cables 12 kV Power Cables 12 kV

AXLJ-TTCL TSLF Triplex 6/10(12) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x1x50/16 15,9 50,5 500 K20 7330384709057 20087880
3x1x70/16 16,9 54,0 500 K20 7330384721851 20114706
3x1x95/25 18,6 58,0 500 K22 7330384721868 20114707
3x1x120/25 20,2 61,0 500 K22 7330384721875 20114708

Application 3x1x150/25 21,5 64,5 500 K24 7330384721882 20114709

Single-core, distribution cable for outdoor use in triplex formation. Installation in pipes and ground/water. 3x1x185/35 23,2 68,5 500 K24 7330384721899 20114710

Both radial and longitudinal water sealed. Can be ploughed down. The outer sheath has a conductive layer 3x1x240/35 25,4 73,5 500 K26 7330384709002 20102177
that greatly extends the possibilities to do a sheath testing before, during and after installation. 3x1x300/35 27,9 79,5 500 K26 7330384721905 20114711
Ripcords for easier and safer stripping of the outer sheath. 3x1x400/35 31,1 86,5 500 K28 7330384721912 20114712
3x1x500/35 34,0 93,5 500 K28 7330384721929 20114713

Alternative Product name Flame retardance


Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
SE-N10XC7A5T5E-AR Not applicable screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
[mm2] [Ω/km] [Ω/km] phase [A/km]
[A/km]

Standard 3x1x50/16 0,6410 1,150 0,40 0,13 0,25 0,5 1,4

HD 620 Part 10 Section K 3x1x70/16 0,4430 1,150 0,38 0,12 0,28 0,5 1,6
HD 620 Part 10 Section M 3x1x95/25 0,3200 0,727 0,36 0,11 0,32 0,6 1,8
3x1x120/25 0,2530 0,727 0,35 0,11 0,35 0,7 2,0
3x1x150/25 0,2060 0,727 0,34 0,11 0,38 0,7 2,1
Construction 3x1x185/35 0,1640 0,524 0,32 0,10 0,41 0,8 2,3
Cable shape Round
3x1x240/35 0,1250 0,524 0,31 0,10 0,46 0,9 2,6
Conductors Stranded, round, compacted aluminium acc. to IEC 60228 class 2,
3x1x300/35 0,1000 0,524 0,30 0,09 0,51 1,0 2,9
longitudinally watertight
Inner semi-conducting layer Extruded 3x1x400/35 0,0778 0,524 0,29 0,09 0,58 1,1 3,3

Conductor screen XLPE, min thickness = 2,96 mm 3x1x500/35 0,0605 0,524 0,28 0,09 0,64 1,2 3,6
Outer semi-conducting layer Bonded
Longitudinal water tightness Semi conducting water blocking tape Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
Shield / Screen Annealed copper wires in contact with aluminum tape screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
[mm2] in ground** in air** in air** during 1s during 1s
Radial water blocking Aluminum-PE laminate, bonded to sheath [A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
Ripcord Aramid [kA] [kA]
Outer sheath PE, natural UV-protected 3x1x50/16 155 160 195 5,2 4,7
Example of marking on sheath AXLJ-TTCL TSLF 12kV 1x240 AFR/35 DRAKA “Date and time”, metre marked 3x1x70/16 200 190 235 7,2 6,6
Semi-conducting layer in outer sheath Yes (facilitates sheath testing) 3x1x95/25 235 230 280 9,9 8,9
3x1x120/25 265 265 325 12,4 11,3
3x1x150/25 300 300 370 15,6 14,2
Temperature
3x1x185/35 330 345 425 19,2 17,5
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended 3x1x240/35 385 400 490 25,0 22,7
3x1x300/35 435 460 565 31,0 28,3
3x1x400/35 510 555 680 41,6 37,8
Features 3x1x500/35 570 635 775 52,0 47,2
Bending radius In fixed installation: 10 x D
** Trefoil with screen grounded in both end.
When pulling-in: 15 x D
The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
When plowing down: 8 x D thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Note: screen resistance is the sum of copper wires and aluminum tape.

Electrical
Impulse voltage 75 kV

POWER CABLES 32 Prysmian Group Baltics AS • baltics.prysmiangroup.com 33


Power Cables 12 kV Power Cables 12 kV

AXQJ-TT Pure TSLI Triplex 6/10(12) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x1x50/16 15,9 51,0 500 K20 7330384720991 20218381
3x1x70/16 16,9 53,0 500 K20 7330384721004 20218382
3x1x95/25 18,6 57,0 500 K22 7330384721011 20218383
3x1x120/25 20,2 50,0 500 K24 7330384721028 20218384

Application 3x1x150/25 21,5 63,5 500 K24 7330384721035 20218385

Halogen-free, flame retardant and self-extinguishing in case of fire. Smoke in the event of fire is limited, 3x1x185/35 23,2 67,0 500 K24 7330384721042 20218386

transparent (to facilitate evacuation) and not harmful to electronic equipment. Radial and longitudinal water sealed 3x1x240/35 25,4 72,5 500 K24 7330384721059 20218387
distribution cable for use indoors and outdoors for 3-phase formation. Installation in pipes and ground. 3x1x300/35 27,9 78,0 500 K26 7330384721066 20218388
Ploughing down is not recommended. Ripcords for easier and safer stripping of the outer sheath. 3x1x400/35 31,1 85,8 500 K28 7330384721073 20218389
3x1x500/35 34,0 92,5 500 K28 7330384721080 20218390

Alternative Product name


Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
SE-N10XC7A5Z1-AR screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
[mm2] [Ω/km] [Ω/km] phase [A/km]
[A/km]

Standard 3x1x50/16 0,6410 1,150 0,40 0,13 0,25 0,5 1,4

HD 620 Part 10 Section M HD 604 3x1x70/16 0,4430 1,150 0,38 0,12 0,28 0,5 1,6
HD 620 Part 10 Section K EN 50575:2014 3x1x95/25 0,3200 0,727 0,36 0,11 0,32 0,6 1,8
3x1x120/25 0,2530 0,727 0,35 0,11 0,35 0,7 2,0
3x1x150/25 0,2060 0,727 0,34 0,11 0,38 0,7 2,1
Construction 3x1x185/35 0,1640 0,524 0,32 0,10 0,41 0,8 2,3
Cable shape Round
3x1x240/35 0,1250 0,524 0,31 0,10 0,46 0,9 2,6
Conductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2,
3x1x300/35 0,1000 0,524 0,30 0,09 0,51 1,0 2,9
longitudinal water sealed
Inner semi-conducting layer Extruded 3x1x400/35 0,0778 0,524 0,29 0,09 0,58 1,1 3,3

Conductor screen XLPE, min thickness = 2,96 mm 3x1x500/35 0,0605 0,524 0,28 0,09 0,64 1,2 3,6
Outer semi-conducting layer Bonded
Longitudinal water tightness Semi conducting water blocking tape Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
Shield / Screen Annealed copper wires in contact with aluminum tape screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
[mm2] in ground** in air** in air** during 1s during 1s
Radial water blocking Aluminium laminate bonded to the sheath [A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
Ripcord Aramid [kA] [kA]
Outer sheath Halogen free compound, black 3x1x50/16 155 160 195 5,2 4,7
Example of marking on sheath AXQJ-TT Pure TSLI 12kV 1x240 AFR/35 D-s2d2a2 DRAKA 3x1x70/16 200 190 235 7,2 6,6
“Date and time”, metre marked 3x1x95/25 235 230 280 9,9 8,9
3x1x120/25 265 265 325 12,4 11,3
3x1x150/25 300 300 370 15,6 14,2
Temperature
3x1x185/35 330 345 425 19,2 17,5
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended 3x1x240/35 385 400 490 25,0 22,7
3x1x300/35 435 460 565 31,0 28,3
3x1x400/35 510 555 680 41,6 37,8
Features 3x1x500/35 570 635 775 52,0 47,2
CPR performance class Dca-s2d2a2
** Trefoil with screen grounded in both end.
Bending radius In fixed installation: 10 x D
The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
When pulling-in: 15 x D thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
When plowing down: 8 x D Note: screen resistance is the sum of copper wires and aluminum tape.

Electrical
Impulse voltage 75 kV

POWER CABLES 34 Prysmian Group Baltics AS • baltics.prysmiangroup.com 35


Power Cables 12 kV Power Cables 12 kV

AXQJ-RMF Pure 6/10(12) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x50/16 15,9 43,5 500 K18 7330384720113 20303881
3x95/25 18,6 49,9 500 K20 7330384720137 20203883
3x150/25 21,5 56,8 500 K22 7330384720151 20203885
3x240/35 25,4 65,6 500 K24 7330384720182 20203887

Application 3x300/35 27,9 71,0 500 K26 7330384720212 20203888

Halogen-free, flame retardant and self-extinguishing in case of fire. Smoke in the event of fire is limited, transparent
(to facilitate evacuation) and not harmful to electronic equipment. The cable is primarily designed for indoor installation, Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
tunnels, etc. The cable can be installed outdoors and in ground but ploughing is not recommended. [mm2] [Ω/km] [Ω/km] phase [A/km]
Ripcords for easier and safer stripping of the outer sheath.. [A/km]
3x50/16 0,6410 1,2 0,33 0,10 0,25 0,5 1,4
3x95/25 0,3200 0,8 0,30 0,09 0,32 0,6 1,8
Alternative Product name 3x150/25 0,2060 0,8 0,28 0,09 0,38 0,7 2,0
SE-N10XC7Z1-AR
3x240/35 0,1250 0,6 0,26 0,09 0,46 0,8 2,5
3x300/35 0,1000 0,6 0,26 0,08 0,51 1,0 2,9

Standard
IEC 60502-2 EN 60754-1,-2 Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
SS 424 14 16 EN 61034-1, -2 [mm2] in ground in air in air during 1s during 1s
HD 620 Part 10 Section M EN 50575:2014 [A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
[kA] [kA]
HD 604
3x50/16 145 130 160 5,2 4,7
3x95/25 205 190 230 9,9 8,9
Construction 3x150/25 260 250 305 15,6 14,2
Cable shape Triangular 3x240/35 340 330 400 25,0 22,7
Conductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2, 3x300/35 380 375 460 31,2 28,3
longitudinal water sealed
Inner semi-conducting layer Extruded The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Conductor screen XLPE, min thickness = 2,96 mm
Outer semi-conducting layer Bonded
Inner covering Conductive tape
Shield / Screen Annealed copper wires
Ripcord Aramid
Outer sheath Halogen free compound, black
Example of marking on sheath AXQJ-RMF Pure 12kV 3x50/16 LT C-s1d1a1 DRAKA “Date and time”, metre marked

Temperature
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended

Features
CPR performance class B2ca-s1d2a1
Bending radius In fixed installation: 8 x D; When pulling-in: 12 x D; When plowing down: 8 x D

Electrical
Max short circuit temperature 250°C
Impulse voltage 75kV

POWER CABLES 36 Prysmian Group Baltics AS • baltics.prysmiangroup.com 37


Power Cables 12 kV Power Cables 12 kV

AHXAMK-W 6/10(12) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x50+35 15,9 55,5 500 K20 7330384715218 20118178
3x70+35 16,9 57,5 500 K22 7330384715225 20118179
3x95+35 18,6 61,0 500 K24 7330384710374 20088773
3x120+35 20,2 64,0 500 K24 7330384705554 20078178

Application 3x150+35 21,5 67,5 500 K24 7330384707695 20102199

AHXAMK-W (Wiski™) is a assembled from 3-single core cables wrapped around a compact copper conductor. 3x185+35 23,2 71,0 500 K24 7330384705783 20102200

Each cable is radial and longitudinal water sealed. For fixed outdoor installation, can be ploughed down. 3x240+35 26,7 75,5 500 K26 7330384705578 20102201
3x300+35 27,9 81,0 500 K26 7330384709507 20102202

Alternative Product name Flame retardance Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
FI-N10XA4EC-AR Not applicable screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
[mm2] [Ω/km] [Ω/km] phase [A/km]
[A/km]

Standard 3x50+35 0,6410 0,524 0,40 0,13 0,25 0,5 1,4


3x70+35 0,4430 0,524 0,38 0,12 0,28 0,5 1,6
HD 620 Part 10 Section F
3x95+35 0,3200 0,524 0,36 0,11 0,32 0,6 1,8
3x120+35 0,2530 0,524 0,35 0,11 0,35 0,7 2,0
Construction 3x150+35 0,2060 0,524 0,34 0,11 0,38 0,7 2,1
Cable shape Round 3x185+35 0,1640 0,524 0,32 0,10 0,41 0,8 2,3
Conductors Stranded, round, compacted aluminium acc. to IEC 60228 class 2, 3x240+35 0,1250 0,524 0,31 0,10 0,46 0,9 2,6
longitudinally watertight 3x300+35 0,1000 0,524 0,30 0,09 0,51 1,0 2,9
Inner semi-conducting layer Extruded
Conductor screen XLPE, min thickness = 2,96 mm
Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
Outer semi-conducting layer Bonded screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Longitudinal water tightness Semi conducting water blocking tape [mm2] in ground** in air** in air** during 1s during 1s
[A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
Core assembly The cores are wrapped around a compact copper conductor.
[kA] [kA]
Stranded, round and compacted copper acc. IEC 60228 class 2
3x50+35 155 160 195 5,2 4,7
Radial water blocking Aluminum-PE laminate, bonded to sheath
3x70+35 200 190 235 7,2 6,6
Outer sheath PE, black
Example of marking on sheath AHXAMK-W 6/10 kV 3x150Al+35Cu DRAKA 3x95+35 235 230 280 9,9 8,9

Phase 1 + “Date and time”, 1 core is metre marked 3x120+35 265 265 325 12,4 11,3
3x150+35 300 300 370 15,6 14,2
3x185+35 330 345 425 19,2 17,5
Temperature 3x240+35 385 400 490 25,0 22,7
Maximum operating temperature 90°C 3x300+35 435 460 565 31,0 28,3
Minimum temperature at installation -20°C, below 0°C special precautions are recommended
** Trefoil with screen grounded in both end.
The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
Features thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.

Bending radius In fixed installation: 10 x D


When pulling-in: 15 x D
When plowing down: 8 x D

Electrical
Impulse voltage 75 kV

POWER CABLES 38 Prysmian Group Baltics AS • baltics.prysmiangroup.com 39


Power Cables 12 kV Power Cables 12 kV

AXLJ-RMF 6/10(12) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x50/16 15,9 43,5 500 K18 7330384701129 20078179
3x95/25 18,6 49,9 500 K20 7330384701143 20095493
3x150/25 21,5 56,8 500 K22 7330384701068 20078182
3x240/35 25,4 65,6 500 K24 7330384701099 20087130

Application 3x300/35 27,9 71,0 500 K26 7330384715065 20118045

AXLJ-RMF is a 3-core cable designed for replacement of bare overhead lines. Primary developed to be ploughed down
but thanks to the robust design the cable can stand the stresses that appears when laid in water with moderate currents Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
and limited depth. Ripcords for easier and safer stripping of the outer sheath. screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
[mm2] [Ω/km] [Ω/km] phase [A/km]
[A/km]
3x50/16 0,6410 1,2 0,33 0,10 0,25 0,5 1,4
Alternative Product name Flame retardance 3x95/25 0,3200 0,8 0,30 0,09 0,32 0,6 1,8
SE-N10XC7E-AR Not applicable
3x150/25 0,2060 0,8 0,28 0,09 0,38 0,7 2,0
3x240/35 0,1250 0,6 0,26 0,09 0,46 0,8 2,5

Standard 3x300/35 0,1000 0,6 0,26 0,08 0,51 1,0 2,9

IEC 60502-2 HD 620 Part 10 Section M


SS 424 14 16 Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
[mm2] in ground in air in air during 1s during 1s
[A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
Construction [kA] [kA]

Cable shape Triangular 3x50/16 145 130 160 5,2 4,7


Conductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2, 3x95/25 205 190 230 9,9 8,9
longitudinal water sealed 3x150/25 260 250 305 15,6 14,2
Inner semi-conducting layer Extruded 3x240/35 340 330 400 25,0 22,7
Conductor screen XLPE, min thickness = 2,96 mm
3x300/35 380 375 460 31,2 28,3
Outer semi-conducting layer Bonded
Inner covering Conductive tape The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Shield / Screen Annealed copper wires
Ripcord Aramid
Outer sheath Composite PE, Black
Example of marking on sheath AXLJ-RMF 12kV 3x150/25 LT DRAKA “Date and time”, metre marked

Temperature
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended

Features
Fire propagation Cable is not flame retardant
UV resistance Good
Bending radius In fixed installation: 8 x D
When pulling-in: 12 x D
When plowing down: 8 x D

Electrical
Max short circuit temperature 250°C
Impulse voltage 75 kV

POWER CABLES 40 Prysmian Group Baltics AS • baltics.prysmiangroup.com 41


Power Cables 12 kV Power Cables 12 kV

AXCLJ-TT 6/10(12) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x50/16 15,9 42,5 500 K18 7330384721783 20206411
3x70/16 16,9 46,0 500 K20 20206412
3x95/25 18,6 50,0 500 K20 7330384721776 20206413
3x120/25 20,2 54,0 500 K22 20206414

Application 3x150/25 21,5 57,0 500 K24 7330384721769 20206415

AXCLJ-TT is just as AXALJ-TT totally water sealed. Radial water sealed by an aluminum laminate bonded to outer sheath 3x185/35 23,2 61,0 500 K24 20206416

and longitudinally water sealed with swellable tapes. The screen is made up of circular copper wires like AXALJ-TT, 3x240/35 25,4 65,5 500 K24 7330384721752 20206417
water blocking tapes (replacing water blocking yarns) and the cable has been complemented with two strong ripcords 3x300/35 27,9 71,5 500 K26 7330384723244 20206418
for easier and safer opening of the outer sheath. The cable is primarily designed for ploughing down in ground, but thanks
to its robust design can handle the stresses resulting from installation in lakes with limited currents and of limited depth. Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
[mm2] [Ω/km] [Ω/km] phase [A/km]
[A/km]
Alternative Product name Flame retardance
3x50/16 0,6410 1,2 0,33 0,10 0,25 0,5 1,4
SE-N10XC7A5T5E-AR Not applicable
3x70/16 0,4430 1,2 0,31 0,10 0,28 0,5 1,6
3x95/25 0,3200 0,8 0,30 0,09 0,32 0,6 1,8

Standard 3x120/25 0,2530 0,8 0,28 0,09 0,35 0,7 2,0


SS 424 14 16 HD 620 Part 10 Section M 3x150/25 0,2060 0,8 0,28 0,09 3,80 0,7 2,1
3x185/35 0,1640 0,6 0,27 0,09 0,41 0,8 2,3
3x240/35 0,1250 0,6 0,26 0,08 0,46 0,9 2,6
Construction 3x300/35 0,1000 0,6 0,26 0,08 0,51 1,0 2,9
Cable shape Triangular
Conductors Stranded, round, compacted aluminum acc. to IEC 60228 class 2,
Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
longitudinal water sealed screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Inner semi-conducting layer Extruded [mm2] in ground in air in air during 1s during 1s
[A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
Conductor screen XLPE, min thickness = 2,96 mm
[kA] [kA]
Outer semi-conducting layer Bonded
3x50/16 145 130 160 5,2 4,7
Longitudinal water tightness Semi conducting water blocking tape
3x70/16 175 155 190 7,2 6,6
Filler PE-profiles
Inner covering Conductive tape 3x95/25 205 190 230 9,9 8,9

Shield / Screen Round copper wires in contact with aluminum laminate 3x120/25 230 220 265 12,4 11,3
Radial water blocking Aluminum-PE laminate, bonded to sheath 3x150/25 260 250 305 15,6 14,2
Ripcord Aramid 3x185/35 290 280 340 19,2 17,5
Outer sheath Composite PE, Black 3x240/35 340 330 400 25,0 22,7
Example of marking on sheath AXCLJ-TT 12kV 3x50/16 DRAKA “Date and time”, metre marked
3x300/35 380 375 460 31,2 28,3

The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
Temperature thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Note: screen resistance is the sum of copper wires and aluminum tape.
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended

Features
UV resistance Good
Bending radius In fixed installation: 8 x D
When pulling-in: 12 x D
When plowing down: 8 x D

Electrical Max short circuit temperature 250°C


Impulse voltage 75 kV
POWER CABLES 42 Prysmian Group Baltics AS • baltics.prysmiangroup.com 43
Power Cables 12 kV Power Cables 12 kV

AXALJ-TT 6/10(12) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x50/25 15,9 42,5 500 K18 7330384717014 20151640
3x70/25 16,9 46,0 500 K20 7330384717021 20151641
3x95/35 18,6 50,0 500 K20 7330384717038 20151642
3x120/35 20,2 54,0 500 K22 7330384717045 20151643

Application 3x150/35 21,5 57,0 500 K24 7330384717052 20151644

AXALJ-TT is just like its predecessor AXLJ-TT, totally water sealed. Radially water sealed by an aluminium laminate bonded 3x185/50 23,2 61,0 500 K24 7330384717069 20151645

to the outer sheath longitudinally water sealed with swellable tapes. The screen is made up of circular aluminium wires, 3x240/50 25,4 65,5 500 K24 7330384717076 20151646
water blocking tapes (replacing the water swellable yarns) and the cable has been complemented with two strong ripcords 3x300/50 27,9 71,5 500 K26 7330384717144 20152032
for easier and safer opening of the outer sheath. The cable is primarily designed for ploughing down in ground, but thanks
to its robust design can handle the stresses resulting from installation in lakes with limited currents and of limited depth. Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
[mm2] [Ω/km] [Ω/km] phase [A/km]
[A/km]
Alternative Product name Flame retardance
3x50/25 0,6410 1,2 0,33 0,10 0,25 0,5 1,4
SE-N10XA5E-AR Not applicable
3x70/25 0,4430 1,2 0,31 0,10 0,28 0,5 1,6
3x95/35 0,3200 0,8 0,30 0,09 0,32 0,6 1,8

Standard 3x120/35 0,2530 0,8 0,28 0,09 0,35 0,7 2,0


SS 424 14 16 HD 620 Part 10 Section M 3x150/35 0,2060 0,8 0,28 0,09 3,80 0,7 2,1
3x185/50 0,1640 0,6 0,27 0,09 0,41 0,8 2,3
3x240/50 0,1250 0,6 0,26 0,08 0,46 0,9 2,6
Construction 3x300/50 0,1000 0,6 0,26 0,08 0,51 1,0 2,9
Cable shape Triangular
Conductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2,
Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
longitudinal water sealed screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Inner semi-conducting layer Extruded [mm2] in ground in air in air during 1s during 1s
[A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
Conductor screen XLPE, min thickness = 2,96 mm
[kA] [kA]
Outer semi-conducting layer Bonded
3x50/25 145 130 160 5,2 4,7
Longitudinal water tightness Semi conducting water blocking tape
3x70/25 175 155 190 7,2 6,6
Filler PE-profiles
Shield / Screen Round aluminium wires in contact with aluminium laminate 3x95/35 205 190 230 9,9 8,9

Radial water blocking Aluminium laminate bonded to the sheath 3x120/35 230 220 265 12,4 11,3
Ripcord Aramid 3x150/35 260 250 305 15,6 14,2
Outer sheath Composite PE, black 3x185/50 290 280 340 19,2 17,5
Example of marking on sheath AXALJ-TT 12kV 3x50/25 AL DRAKA “Date and time”, metre marked 3x240/50 340 330 400 25,0 22,7
3x300/50 380 375 460 31,2 28,3

Temperature The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended

Features
UV resistance Good
Bending radius In fixed installation: 8 x D
When pulling-in: 12 x D
When plowing down: 8 x D

Electrical Max short circuit temperature 250°C


Impulse voltage 75 kV

POWER CABLES 44 Prysmian Group Baltics AS • baltics.prysmiangroup.com 45


Power Cables 12 kV Power Cables 12 kV

FXLJ-TT 6/10(12) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x35/16 14,3 38,0 500 K16 7330384714761 20117462
3x50/16 15,9 42,5 500 K18 7330384714778 20117463
3x70/16 16,9 46,0 500 K18 7330384714785 20117464
3x95/25 18,6 50,0 500 K20 7330384714792 20117465

Application 3x120/25 20,2 54,0 500 K20 7330384714808 20117491

FXLJ-TT is a three core cable primary developed to be ploughed down but thanks to the robust design the cable can 3x150/25 21,5 57,0 500 K22 7330384714815 20117497

withstand the stress that appears when laid in water with moderate currents and limited depth. The design with 3x185/35 23,2 61,0 500 K22 7330384714822 20117513
water swellable yarn and aluminum foil bonded to the sheath makes the cable both radial and longitudinal water sealed, 3x240/35 25,4 65,5 500 K24 7330384714839 20117514
which enhances the expected life length of the cable. Ripcords for easier and safer stripping of the outer sheath.
Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
Alternative Product name Flame retardance [mm2] [Ω/km] [Ω/km] phase
[A/km]
[A/km]

SE-N10XC7A5T5E-R Not applicable


3x35/16 0,524 1,2 0,34 0,11 0,22 0,04 1,2
3x50/16 0,387 1,2 0,33 0,10 0,25 0,5 1,4

Standard 3x70/16 0,268 1,2 0,31 0,10 0,28 0,5 1,6

SS 424 14 16 3x95/25 0,193 0,8 0,30 0,09 0,32 0,6 1,8


HD 620 Part 10 Section M 3x120/25 0,153 0,8 0,28 0,09 0,35 0,7 2,0
3x150/25 0,124 0,8 0,28 0,09 3,80 0,7 2,1
3x185/35 0,0991 0,6 0,27 0,09 0,41 0,8 2,3
Construction 3x240/35 0,0754 0,6 0,26 0,08 0,46 0,9 2,6
Cable shape Triangular
Conductors Stranded, round and compacted copper acc. to IEC 60228 class 2,
Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
longitudinal water sealed screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Inner semi-conducting layer Extruded [mm2] in ground in air in air during 1s during 1s
[A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
Conductor screen XLPE, min thickness = 2,96 mm
[kA] [kA]
Outer semi-conducting layer Bonded
3x35/16 140 135 165 5,5 5,0
Longitudinal water tightness Semi conducting water blocking tape and swellable yarn
3x50/16 175 165 205 7,8 7,1
Shield / Screen Annealed copper wires
Radial water blocking Aluminium laminate bonded to the sheath 3x70/16 210 205 250 11,0 10,0

Ripcord Aramid 3x95/25 250 240 295 14,9 13,6


Outer sheath PE, black 3x120/25 285 280 340 18,9 17,2
Semi-conducting layer in outer sheath Yes (facilitates sheath testing) 3x150/25 325 320 390 23,6 21,5
Example of marking on sheath FXLJ-TT 12kV 3x95/25 DRAKA “Date”, metre marked 3x185/35 360 360 435 29,1 26,5
3x240/35 415 420 515 37,7 34,4

Temperature The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended

Features
Bending radius In fixed installation: 8 x D
When pulling-in: 12 x D
When plowing down: 8 x D

Electrical
Impulse voltage 75 kV

POWER CABLES 46 Prysmian Group Baltics AS • baltics.prysmiangroup.com 47


Power Cables 24 kV Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length

AXLJ-TTCL TSLF 12/20(24) kV


[mm2] [mm] [mm] [m]
1x50/16 19,5 27,9 500 K12 7330384707893 20102178
1x70/16 21,1 29,7 500 K12 7330384714006 20113275
1x95/25 22,8 31,3 500 K12 7330384707299 20102179
1x120/25 24,4 32,9 500 K14 7330384714013 20113276
1x150/25 25,7 34,4 500 K14 7330384707879 20102180
1x185/35 27,4 36,3 500 K16 7330384714020 20113277
1x240/35 29,5 38,7 500 K16 7330384707701 20102181
1x300/35 32,1 41,2 500 K18 7330384714037 20113278
1x400/35 35,3 44,5 500 K18 7330384707022 20102182
1x500/35 38,2 47,6 500 K20 7330384714044 20113279
1x630/50 41,2 51,7 500 K20 7330384709392 20102183
1x800/50 45,6 55,6 500 K22 7330384714051 20113280
Application 1x1000/50 52,1 63,0 500 K24 7330384720656 20118907
Single-core, distribution cable for outdoor use in 3-phase formation. Installation in pipes and ground/water.
1x1200/50 54,3 67,2 500 K26 7330384720038 20118927
Both radial and longitudinal water sealed. Can be ploughed down. The outer sheath has a conductive layer that greatly
extends the possibilities to do a sheath testing before, during and after installation.
Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
Ripcords for easier and safer stripping of the outer sheath. screen area resistance resistance in trefoil/in flat* [Ω/km] [µF/km] current / current
[mm2] [Ω/km] [Ω/km] [mH/km] phase [A/km]
[A/km]

Alternative Product name Flame retardance 1x50/16 0,6410 1,150 0,43/0,73 0,23 0,17 0,6 1,9
SE-N20XC7A5T5E-AR Not applicable 1x70/16 0,4430 1,150 0,41/0,70 0,22 0,19 0,7 2,1
1x95/25 0,3200 0,727 0,39/0,67 0,21 0,21 0,8 2,4
1x120/25 0,2530 0,727 0,38/0,65 0,20 0,23 0,9 2,6
Standard 1x150/25 0,2060 0,727 0,36/0,63 0,20 0,25 0,9 2,8
SS 424 14 16
1x185/35 0,1640 0,534 0,35/0,61 0,19 0,27 1,0 3,1
HD 620 Part 10 Section M
1x240/35 0,1250 0,534 0,34/0,59 0,19 0,30 1,1 3,4
HD 620 Part 10 Section K
1x300/35 0,1000 0,534 0,33/0,57 0,18 0,33 1,2 3,7
1x400/35 0,0778 0,534 0,30/0,55 0,17 0,37 1,4 4,2
Construction 1x500/35 0,0605 0,534 0,31/0,53 0,17 0,40 1,5 4,5
Cable shape Round 1x630/50 0,0469 0,387 0,29/0,51 0,16 0,45 1,7 5,1
Conductors Stranded, round, compressed aluminium acc. to IEC 60228 class 2, 1x800/50 0,0367 0,387 0,29/0,50 0,16 0,45 1,7 5,1
longitudinally watertight 1x1000/50 0,0291 0,387 0,27/0,48 0,15 0,47 1,8 5,3
Inner semi-conducting layer Extruded
1x1200/50 0,0247 0,387 0,29/0,48 0,15 0,51 1,9 5,8
Conductor screen XLPE, min thickness = 4,85 mm
Outer semi-conducting layer Bonded * Cable distance, installation in flat formation = 70 mm

Longitudinal water tightness Semi conducting water blocking tape


Shield / Screen Annealed copper wires in contact with aluminum laminate Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Radial water blocking Aluminium laminate, bonded to sheath [mm2] in ground** in air** in air** during 1s during 1s
Ripcord Aramid [A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
[kA] [kA]
Outer sheath PE, natural UV protected
1x50/16 155 160 195 5,2 4,7
Semi-conducting layer in outer sheath Yes (facilitates sheath testing)
Example of marking on sheath AXLJ-TTCL TSLF 24kV 1x150 AFR/25 DRAKA “Date and time”, metre marked 1x70/16 200 190 235 7,2 6,6
1x95/25 235 230 280 9,9 8,9
1x120/25 265 265 325 12,4 11,3
Temperature 1x150/25 300 300 370 15,6 14,2
Maximum operating temperature 90°C 1x185/35 330 345 425 19,2 17,5
Minimum temperature at installation -20°C, below 0°C special precautions are recommended
1x240/35 385 400 490 25,0 22,7
1x300/35 435 460 565 31,0 28,3

Features 1x400/35 510 555 680 41,6 37,8

Bending radius In fixed installation: 10 x D 1x500/35 570 635 775 52,0 47,2

When pulling-in: 15 x D 1x630/50 635 720 880 65,6 59,5


When plowing down: 8 x D 1x800/50 695 822 1010 83,2 75,6
1x1000/50 760 920 1130 103,7 94,5
1x1200/50 815 1000 1230 124,0 113,0
Electrical
Impulse voltage 125 kV ** Trefoil with screen grounded in both end.
The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
POWER CABLES 48 Prysmian Group Baltics AS • baltics.prysmiangroup.com 49
Note: screen resistance is the sum of copper wires and aluminum tape.
Power Cables 24 kV Power Cables 24 kV

AXLJ-TTCL TSLF Triplex 12/20(24) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x1x50/16 19,5 60 500 K22 7330384708999 20102184
3x1x70/16 21,1 64 500 K24 7330384721936 20115022
3x1x95/25 22,8 67,5 500 K24 7330384709019 20102185
3x1x120/25 24,4 71,5 500 K24 7330384721943 20115023

Application 3x1x150/25 25,7 74 500 K26 7330384709125 20102186

Single-core, distribution cable for outdoor use in triplex formation. Installation in pipes and ground/water. 3x1x185/35 27,4 78,5 500 K26 7330384721950 20115024

Both radial and longitudinal water sealed. Can be ploughed down. The outer sheath has a conductive layer that greatly 3x1x240/35 29,6 83,5 500 K28 7330384709026 20102187
extends the possibilities to do a sheath testing before, during and after installation. 3x1x300/35 32,1 89 500 K28 7330384721967 20115025
Ripcords for easier and safer stripping of the outer sheath. 3x1x400/35 35,3 96 500 K28 7330384713320 20111044

Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
Alternative Product name Flame retardance screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
SE-N20XC7A5T5E-AR Not applicable [mm2] [Ω/km] [Ω/km] phase [A/km]
[A/km]
3x1x50/16 0,6410 1,150 0,44 0,14 0,17 0,6 1,9

Standard 3x1x70/16 0,4430 1,150 0,41 0,13 0,19 0,7 2,1

HD 620 Part 10 Section K 3x1x95/25 0,3200 0,727 0,39 0,12 0,21 0,8 2,4
HD 620 Part 10 Section M 3x1x120/25 0,2530 0,727 0,38 0,12 0,23 0,9 2,6
3x1x150/25 0,2060 0,727 0,36 0,11 0,25 0,9 2,8
3x1x185/35 0,1640 0,524 0,35 0,11 0,27 1,0 3,1
Construction 3x1x240/35 0,1250 0,524 0,34 0,11 0,30 1,1 3,4
Cable shape Round
3x1x300/35 0,1000 0,524 0,33 0,10 0,33 1,2 3,7
Conductors Stranded, round and compacted aluminum acc. to IEC 60228 class 2,
3x1x400/35 0,0778 0,524 0,31 0,10 0,37 1,4 4,2
longitudinally watertight
Inner semi-conducting layer Extruded
Conductor screen XLPE, min thickness = 4,85 mm Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Outer semi-conducting layer Bonded [mm2] in ground** in air** in air** during 1s during 1s
Longitudinal water tightness Semi conducting water blocking tape [A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
[kA] [kA]
Shield / Screen Annealed copper wires in contact with aluminum tape
Radial water blocking Aluminum-PE laminate, bonded to sheath 3x1x50/16 155 160 195 5,2 4,7

Ripcord Aramid 3x1x70/16 200 190 235 7,2 6,6


Outer sheath PE, natural UV-protected 3x1x95/25 235 230 280 9,9 8,9
Semi-conducting layer in outer sheath Yes (facilitates sheath testing) 3x1x120/25 265 265 325 12,4 11,3
Example of marking on sheath AXLJ-TTCL TSLF 24kV 1x50 AFR/16 DRAKA “Date and time”, 1-core is metre marked 3x1x150/25 300 300 370 15,6 14,2
3x1x185/35 330 345 425 19,2 17,5
3x1x240/35 385 400 490 25,0 22,7
Temperature
3x1x300/35 435 460 565 31,0 28,3
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended 3x1x400/35 510 555 680 41,6 37,8

** Trefoil with screen grounded in both end.


The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
Features thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Bending radius In fixed installation: 10 x D Note: screen resistance is the sum of copper wires and aluminum tape.
When pulling-in: 15 x D
When plowing down: 8 x D

Electrical
Impulse voltage 125 kV

POWER CABLES 50 Prysmian Group Baltics AS • baltics.prysmiangroup.com 51


Power Cables 24 kV Power Cables 24 kV

AHXAMK-W 12/20(24) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x50+35 20,5 64,0 500 K24 6410006242504 20022490
3x95+35 22,8 71,0 500 K26 6410006242528 20022491
3x120+35 24,4 74,0 500 K26 6410006242535 20022492
3x150+35 25,7 76,0 500 K26 6410006242542 20022493

Application 3x185+35 27,4 80,0 500 K26 6410006242559 20022495

Medium voltage power cable with stranded and compacted aluminium longitudinal and radial water sealed conductor. 3x240+35 29,6 89,0 500 K28 6410006242566 20022499

For fixed outdoor installation, can be ploughed down. 3x240+70 29,6 89,0 500 K28 6410006242566 20022498
3x300+35 32,1 92,0 500 K28 6410006242597 20022502
3x300+70 32,1 93,0 500 K28 6410006242573 20022501
Alternative Product name Flame retardance
WISKI® Not applicable
Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
[mm2] [Ω/km] [Ω/km] phase [A/km]

Standard [A/km]
3x50+35 0,6410 0,524 0,46 0,14 0,17 0,6 1,8
IEC 60502-2
HD 620 Part 10 Section F 3x95+35 0,3200 0,524 0,40 0,12 0,21 0,8 2,3
3x120+35 0,2530 0,524 0,39 0,12 0,23 0,8 2,5
3x150+35 0,2060 0,524 0,37 0,11 0,24 0,9 2,6
Construction 3x185+35 0,1640 0,524 0,36 0,11 0,26 1,0 2,9
Cable shape Round 3x240+35 0,1250 0,524 0,35 0,11 0,30 1,1 3,2
Conductors Stranded, round, compacted aluminium, longitudinally watertight 3x240+70 0,1250 0,268 0,35 0,11 0,30 1,1 3,2
Center conductor Round, stranded and compacted copper conductor
3x300+35 0,1000 0,524 0,34 0,10 0,32 1,2 3,5
Inner semi-conducting layer Semi-conducting PEX
3x300+70 0,1000 0,268 0,34 0,10 0,32 12,0 3,5
Conductor screen PEX
Individual screen for parts Semi-conducting PEX
Core assembly Three cores are stranded around the centre conductor Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Inner covering Conductive tap [mm2] in ground** in air** in air** during 1s during 1s
Shield / Screen Aluminium foil bonded tightly to sheath [A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
[kA] [kA]
Outer sheath Black PE
Semi-conducting layer in outer sheath Semi-conducting tape 3x50+35 155 160 195 5,2 4,7

Example of marking on sheath AHXAMK-W 12/20 kV 3x150+35 DRAKA “Date and time”, 1 core is metre marked 3x95+35 235 230 280 9,9 8,9
3x120+35 265 265 325 12,4 11,3
3x150+35 300 300 370 15,6 14,2
Temperature 3x185+35 330 345 425 19,2 17,5
Maximum operating temperature 90°C 3x240+35 385 400 490 25,0 22,7
Minimum temperature at installation -20°C, below 0°C special precautions are recommended
3x240+70 385 400 490 25,0 22,7
3x300+35 435 460 565 31,0 28,3

Features 3x300+70 435 460 565 31,0 28,3

Bending radius In fixed installation: 10 x D


** Trefoil with screen grounded in both end.
When pulling-in: 15 x D The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
When plowing down: 8 x D thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.

Electrical
Max short circuit temperature 250°C

POWER CABLES 52 Prysmian Group Baltics AS • baltics.prysmiangroup.com 53


Power Cables 24 kV Power Cables 24 kV

AXLJ-RMF 12/20(24) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x50/16 19,5 52,0 500 K20 7330384701136 20078233
3x95/25 22,8 59,5 500 K22 7330384701150 20102136
3x150/25 25,7 66,0 500 K24 7330384701075 20078234
3x240/35 29,6 75,6 500 K26 7330384714167 20091033

Application 3x300/35 32,1 80,5 500 K26 7330384715072 20118046

AXLJ-RMF is a 3-core cable designed for replacement of bare overhead lines. Primary developed to be ploughed down but
thanks to the robust design the cable can stand the stresses that appears when laid in water with moderate currents and Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
limited depth. Ripcords for easier and safer stripping of the outer sheath. [mm2] [Ω/km] [Ω/km] phase [A/km]
[A/km]
3x50/16 0,6410 1,2 0,37 0,12 0,17 0,6 1,9
Alternative Product name Flame retardance 3x95/25 0,3200 0,8 0,34 0,11 0,21 0,8 2,4
SE-N20XC7E-AR Not applicable
3x150/25 0,2060 0,8 0,31 0,10 0,25 0,9 2,8
3x240/35 0,1250 0,6 0,29 0,09 0,30 1,1 3,4

Standard 3x300/35 0,1000 0,6 0,28 0,09 0,33 1,2 3,7

SS 424 14 16
HD 620 Part 10 Section M Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
[mm2] in ground in air in air during 1s during 1s
[A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
Construction [kA] [kA]

Cable shape Triangular 3x50/16 145 130 160 5,2 4,7

Conductors Stranded, round, compacted aluminum acc. to IEC 60228 class 2, 3x95/25 205 190 230 9,9 8,9
longitudinal water sealed 3x150/25 260 250 305 15,6 14,2
Inner semi-conducting layer Extruded 3x240/35 340 330 400 25,0 22,7
Conductor screen XLPE, min thickness = 4,85 mm 3x300/35 380 375 460 31,2 28,3
Outer semi-conducting layer Bonded
Inner covering Conductive tape The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Shield / Screen Annealed copper wires
Ripcord Aramid
Outer sheath Composite PE, black
Example of marking on sheath AXLJ-RMF 24kV 3x150/25 LT DRAKA “Date and time”, metre marked

Temperature
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended

Features
Bending radius In fixed installation: 8 x D
When pulling-in: 12 x D
When plowing down: 8 x D

Electrical
Max short circuit temperature 250°C
Impulse voltage 125kV

POWER CABLES 54 Prysmian Group Baltics AS • baltics.prysmiangroup.com 55


Power Cables 24 kV Power Cables 24 kV

AXQJ-RMF Pure 12/20(24) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x50/16 19,5 52,0 500 K22 7330384720236 20203889
3x70/16 21,1 55,5 500 K22 7330384720243 20203890
3x95/25 22,8 59,5 500 K24 7330384720250 20203891
3x120/25 24,4 63,0 500 K24 7330384720267 20203892

Application 3x150/25 25,7 66,5 500 K24 7330384720274 20203893

Halogen-free, flame retardant and self-extinguishing in case of fire. 3x185/35 27,4 70,0 500 K24 7330384720281 20203894

Smoke in the event of fire is limited, transparent (to facilitate evacuation) and not harmful to electronic equipment. 3x240/35 29,6 75,5 500 K26 7330384720298 20203895
The cable is primarily designed for indoor installation, tunnels, etc. The cable can be installed outdoors and in ground but 3x300/35 32,1 81,0 500 K26 7330384720311 20203896
ploughing is not recommended. Ripcords for easier and safer stripping of the outer sheath.
Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
Alternative Product name [mm2] [Ω/km] [Ω/km] phase
[A/km]
[A/km]

SE-N20XC7Z1-AR
3x50/16 0,641 1,2 0,37 0,12 0,17 0,6 1,9
3x70/16 0,443 1,2 0,35 0,11 0,19 0,7 2,1

Standard 3x95/25 0,320 0,8 0,34 0,11 0,21 0,8 2,4

IEC 60502-2 HD 604 3x120/25 0,253 0,8 0,32 0,10 0,23 0,9 2,6
SS 424 14 16 EN 60754-1,-2 3x150/25 0,206 0,8 0,31 0,10 0,25 0,9 2,8
SS-EN 61034-1, -2 EN 50575:2014 3x185/35 0,164 0,6 0,3 0,09 0,27 1,00 3,10
HD 620 Part 10 Section M 3x240/35 0,125 0,6 0,29 0,09 0,30 1,1 3,4
3x300/35 0,1 0,6 0,28 0,09 0,33 1,2 3,7

Construction
Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
Cable shape Triangular screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Conductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2, [mm2] in ground in air in air during 1s during 1s
[A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
longitudinal water sealed
[kA] [kA]
Inner semi-conducting layer Extruded
3x50/16 145 130 160 5,2 4,7
Conductor screen XLPE, min thickness = 4,85 mm
3x70/16 175 155 190 7,2 6,6
Outer semi-conducting layer Bonded
Inner covering Conductive tape 3x95/25 205 190 230 9,9 8,9

Shield / Screen Annealed copper wires 3x120/25 230 220 265 12,4 11,3
Ripcord Aramid 3x150/25 260 250 305 15,6 14,2
Outer sheath Halogen free compound, black 3x185/35 290 280 340 19,2 17,5
Example of marking on sheath AXQJ-RMF Pure 24kV 3x50/16 LT C-s1d1a1 DRAKA “Date and time”, metre marked 3x240/35 340 330 400 25,0 22,7
3x300/35 380 375 460 31,2 29,8

Temperature The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended

Features
CPR performance class Cca-s1d1a1
Bending radius In fixed installation: 8 x D
When pulling-in: 12 x D When plowing down: 8 x D

Electrical
Max short circuit temperature 250°C
Impulse voltage 125kV

POWER CABLES 56 Prysmian Group Baltics AS • baltics.prysmiangroup.com 57


Power Cables 24 kV Power Cables 24 kV

AXCLJ-TT 12/20(24) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x50/16 19,5 54,0 500 K22 7330384721745 20206420
3x70/16 21,1 56,0 500 K22 20206421
3x95/25 22,8 60,0 500 K24 7330384721738 20206422
3x120/25 24,4 63,5 500 K24 20206423

Application 3x150/25 25,7 66,5 500 K24 7330384721721 20206424

AXCLJ-TT is just as AXALJ-TT totally water sealed. Radial water sealed by an aluminum laminate bonded to outer sheath 3x185/35 27,4 70,5 500 K26 20206425

and longitudinally water sealed with swellable tapes. The screen is made up of circular copper wires like AXALJ-TT, 3x240/35 29,6 76,0 500 K26 7330384721714 20206426
water blocking tapes (replacing water blocking yarns) and the cable has been complemented with two strong ripcords for 3x300/35 32,1 83,0 500 K26 20206427
easier and safer opening of the outer sheath. The cable is primarily designed for ploughing down in ground, but thanks to
its robust design can handle the stresses resulting from installation in lakes with limited currents and of limited depth. Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
[mm2] [Ω/km] [Ω/km] phase [A/km]
[A/km]
Alternative Product name Flame retardance
3x50/16 0,6410 1,2 0,37 0,12 0,17 0,6 1,9
SE-N20XC7A5T5E-AR Not applicable
3x70/16 0,4430 1,2 0,35 0,11 0,70 0,5 2,1
3x95/25 0,3200 0,8 0,34 0,11 0,80 0,6 2,4

Standard 3x120/25 0,2530 0,8 0,32 0,10 0,90 0,7 2,6


SS 424 14 16 HD 620 Part 10 Section M 3x150/25 0,2060 0,8 0,31 0,10 0,90 0,7 2,8
3x185/35 0,1640 0,6 0,30 0,10 1,00 0,8 3,1
3x240/35 0,1250 0,6 0,29 0,09 1,10 0,9 3,4
Construction 3x300/35 0,1000 0,6 0,28 0,09 1,20 1,0 3,7
Cable shape Triangular
Conductors Stranded, round, compacted aluminum acc. to IEC 60228 class 2,
Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
longitudinal water sealed screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Inner semi-conducting layer Extruded [mm2] in ground in air in air during 1s during 1s
[A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
Conductor screen XLPE, min thickness = 4,85 mm
[kA] [kA]
Outer semi-conducting layer Bonded
3x50/16 145 130 160 5,2 4,7
Longitudinal water tightness Semi conducting water blocking tape
3x70/16 175 155 190 7,2 6,6
Filler PE-profiles
Inner covering Conductive tape 3x95/25 205 190 230 9,9 8,9

Shield / Screen Round copper wires in contact with aluminum laminate 3x120/25 230 220 265 12,4 11,3
Radial water blocking Aluminum-PE laminate, bonded to sheath 3x150/25 260 250 305 15,6 14,2
Ripcord Aramid 3x185/35 290 280 340 19,2 17,5
Outer sheath Composite PE, Black 3x240/35 340 330 400 25,0 22,7
Example of marking on sheath AXCLJ-TT 24kV 3x50/16 DRAKA “Date and time”, metre marked
3x300/35 380 375 460 31,2 28,3

The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
Temperature thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Note: screen resistance is the sum of copper wires and aluminum tape.
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended

Features
Bending radius In fixed installation: 8 x D
When pulling-in: 12 x D
When plowing down: 8 x D

Electrical
Max short circuit temperature 250°C, Impulse voltage 125kV

POWER CABLES 58 Prysmian Group Baltics AS • baltics.prysmiangroup.com 59


Power Cables 24 kV Power Cables 24 kV

AXALJ-TT 12/20(24) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
3x50/25 19,5 54,0 500 K22 7330384717083 20151647
3x70/25 21,1 56,0 500 K22 7330384717090 20151648
3x95/35 22,8 60,0 500 K24 7330384717106 20151649
3x120/35 24,4 63,5 500 K24 7330384717151 20152033

Application 3x150/35 25,7 66,5 500 K24 7330384717113 20151650

AXALJ-TT is just like its predecessor AXLJ-TT, totally water sealed. Radially water sealed by an aluminium laminate bonded 3x185/50 27,4 70,5 500 K26 7330384717168 20152034

to the outer sheath longitudinally water sealed with swellable tapes. The screen is made up of circular aluminium wires, 3x240/50 29,6 76,0 500 K26 7330384717120 20151651
water blocking tapes (replacing the water swellable yarns) and the cable has been complemented with two strong ripcords 3x300/50 32,1 83,0 500 K26 7330384717175 20152035
for easier and safer opening of the outer sheath. The cable is primarily designed for ploughing down in ground, but thanks
to its robust design can handle the stresses resulting from installation in lakes with limited currents and of limited depth. Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance [mH/km] [Ω/km] [µF/km] current / current
[mm2] [Ω/km] [Ω/km] phase [A/km]
[A/km]
Alternative Product name Flame retardance
3x50/25 0,6410 1,2 0,37 0,12 0,17 0,6 1,9
SE-N20XA5E-AR Not applicable
3x70/25 0,4430 1,2 0,35 0,11 0,70 0,5 2,1
3x95/35 0,3200 0,8 0,34 0,11 0,80 0,6 2,4

Standard 3x120/35 0,2530 0,8 0,32 0,10 0,90 0,7 2,6


SS 424 14 16 3x150/35 0,2060 0,8 0,31 0,10 0,90 0,7 2,8
HD 620 Part 10 Section M 3x185/50 0,1640 0,6 0,30 0,10 1,00 0,8 3,1
3x240/50 0,1250 0,6 0,29 0,09 1,10 0,9 3,4
3x300/50 0,1000 0,6 0,28 0,09 1,20 1,0 3,7
Construction
Cable shape Triangular
Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
Conductors Stranded, round, compacted aluminium acc. to IEC 60228 class 2, screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
longitudinal water sealed [mm2] in ground in air in air during 1s during 1s
[A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
Inner semi-conducting layer Extruded
[kA] [kA]
Conductor screen XLPE, min thickness = 4,85 mm
3x50/25 145 130 160 5,2 4,7
Outer semi-conducting layer Bonded
3x70/25 175 155 190 7,2 6,6
Longitudinal water tightness Semi conducting water blocking tape
Filler PE-profiles 3x95/35 205 190 230 9,9 8,9

Shield / Screen Round aluminium wires in contact with aluminium laminate 3x120/35 230 220 265 12,4 11,3
Radial water blocking Aluminium laminate, bonded to sheath 3x150/35 260 250 305 15,6 14,2
Ripcord Aramid 3x185/50 290 280 340 19,2 17,5
Outer sheath Composite PE, Black 3x240/50 340 330 400 25,0 22,7
Example of marking on sheath AXALJ-TT 24kV 3x50/25 AL DRAKA “Date and time”, metre marked
3x300/50 380 375 460 31,2 28,3

The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
Temperature thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.

Maximum operating temperature 90°C


Minimum temperature at installation -20°C, below 0°C special precautions are recommended

Features
Bending radius In fixed installation: 8 x D
When pulling-in: 12 x D When plowing down: 8 x D

Electrical
Max short circuit temperature 250°C
Impulse voltage 125kV

POWER CABLES 60 Prysmian Group Baltics AS • baltics.prysmiangroup.com 61


Power Cables 24 kV Power Cables 24 kV

AXQJ-TT Pure TSLI 12/20(24) kV

Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
1x50/16 19,5 27,50 500 K12 7330384720663 20217589
1x95/25 22,8 31,00 500 K12 7330384720687 20217591
1x150/25 25,7 34,00 500 K14 7330384720700 20217593
1x240/35 29,6 38,00 500 K16 7330384720724 20217595

Application 1x400/35 35,3 44,00 500 K18 7330384720748 20217597

Halogen-free, flame retardant and self-extinguishing. 1x500/35 38,2 47,00 500 K20 7330384720755 20217598

Smoke in the event of fire is limited, transparent (to facilitate evacuation) and not harmful to electronic equipment. 1x630/50 42,1 51,50 500 K20 7330384720762 20217599
Radial and longitudinal water sealed distribution cable for use indoors and outdoors for 3-phase formation. Installation in
pipes and ground. Ploughing down is not recommended. Ripcords for easier and safer stripping of the outer sheath. Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance in trefoil/in flat* in trefoil/in flat* [µF/km] current / current
[mm2] [Ω/km] [Ω/km] [mH/km] [Ω/km] phase [A/km]
[A/km]
Alternative Product name
1x50/16 0,6410 1,150 0,43 / 0,73 0,14 / 0,23 0,17 0,6 1,9
SE-N20XC7A5Z1-AR
1x95/25 0,3200 0,727 0,39 / 0,67 0,12 / 0,21 0,21 0,8 2,4
1x150/25 0,2060 0,727 0,36 /0,63 0,11 / 0,20 0,25 0,9 2,8

Standard 1x240/35 0,1250 0,524 0,34 / 0,59 0,11 / 0,19 0,30 1,2 3,4
HD 620 Part 10 Section M HD 604 1x400/35 0,0778 0,524 0,31 / 0,55 0,10 / 0,17 0,37 1,4 4,2
HD 620 Part 10 Section K EN 50575:2014 1x500/35 0,0605 0,524 0,30 / 0,53 0,09 / 0,17 0,40 1,5 4,5
1x630/50 0,0469 0,387 0,29 / 0,51 0,09 / 0,16 0,45 1,7 5,1

Construction * Cable distance, installation in flat formation = 70 mm


Cable shape Round
Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
Conductors Stranded, round, compressed aluminium acc. to IEC 60228 class 2, screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
longitudinally watertight [mm2] in ground** in air** in air** during 1s during 1s
[A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
Inner semi-conducting layer Extruded [kA] [kA]
Conductor screen XLPE, min thickness = 4,85 mm
1x50/16 155 160 195 5,2 4,7
Outer semi-conducting layer Bonded
1x95/25 235 230 280 9,9 8,9
Longitudinal water tightness Semi conducting water blocking tape
Shield / Screen Annealed copper wires in contact with aluminum laminate 1x150/25 300 300 370 15,6 14,2

Radial water blocking Aluminium laminate, bonded to sheath 1x240/35 385 400 490 25,0 22,7
Ripcord Aramid 1x400/35 510 555 680 41,6 37,8
Outer sheath Halogen free compound, black 1x500/35 570 635 775 52,0 47,2
Example of marking on sheath AXQJ-TT Pure TSLI 24kV 1x120 AFR/25 D-s2d2a2 DRAKA 1x630/50 635 720 880 65,6 59,5
“Date and time”, metre marked
** Trefoil with screen grounded in both end.
The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Temperature Note: screen resistance is the sum of copper wires and aluminum tape.
Maximum operating temperature 90°C
Minimum temperature at installation -20°C, below 0°C special precautions are recommended

Features
CPR performance class Dca-s2d2a2
Bending radius In fixed installation: 10 x D
When pulling-in: 15 x D
When plowing down: 8 x D

Electrical
Impulse voltage 125kV

POWER CABLES 62 Prysmian Group Baltics AS • baltics.prysmiangroup.com 63


Power Cables 24 kV Power Cables 24 kV

FXLJ-TT TSLE 12/20(24) kV


Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
1x50/16 19,5 27,5 500 K12 7330384714327 20117071
1x70/16 21,1 29,0 500 K12 7330384714334 20117078
1x95/25 22,8 31,0 500 K14 7330384714341 20117079
1x120/25 24,1 32,5 500 K14 7330384714358 20117080
1x150/25 25,7 34,0 500 K14 7330384714365 20117081
1x185/35 27,5 36,0 500 K16 7330384714372 20117125
1x240/35 29,8 38,5 500 K16 7330384714389 20117126
Application
1x300/35 32,1 41,0 500 K16 7330384714396 20117135
Single-core distribution cable suitable for laying outdoors in 3-phase formation.
1x400/35 35,5 44,1 500 K20 7330384714402 20117136
Installation in pipes and in ground/water. Both radial and longitudinal water sealed. Can be ploughed down.
1x500/35 38,1 47,0 500 K20 7330384714419 20117137
1x630/50 41,9 51,0 500 K22 7330384714426 20117138
Alternative Product name Flame retardance
SE-20XC7A5T5E-R Not applicable Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance in trefoil/in flat* in trefoil/in flat* [µF/km] current / current
[mm2] [Ω/km] [Ω/km] [mH/km] [Ω/km] phase [A/km]
[A/km]
Standard 1x50/16 0,3870 1,150 0,43 / 0,73 0,14 / 0,23 0,17 0,6 1,9
HD 620 Part 10 Section M
1x70/16 0,2680 1,150 0,41 / 0,70 0,13 / 0,22 0,19 0,7 2,1
HD 620 Part 10 Section K
1x95/25 0,1930 0,727 0,39 / 0,67 0,11 / 0,21 0,21 0,8 2,4
1x120/25 0,1530 0,727 0,38 / 0,65 0,12 / 0,21 0,23 0,9 2,6

Construction 1x150/25 0,1240 0,727 0,36 / 0,63 0,11 / 0,20 0,25 0,9 2,8
Cable shape Round 1x185/35 0,0991 0,524 0,35 / 0,61 0,11 / 0,19 0,27 1,0 3,1
Conductors Stranded, round and compacted copper acc. to IEC 60228 class 2, 1x240/35 0,0754 0,524 0,34 / 0,59 0,11 / 0,19 0,30 1,1 3,4
longitudinally water sealed 1x300/35 0,0601 0,524 0,32 / 0,57 0,10 / 0,18 0,33 1,2 3,7
Inner semi-conducting layer Extruded 1x400/35 0,0470 0,524 0,31 / 0,55 0,10 / 0,17 0,37 1,4 4,2
Conductor screen XLPE, min thickness = 4,85 mm
1x500/35 0,0366 0,524 0,30 / 0,53 0,09 / 0,17 0,40 1,5 4,5
Outer semi-conducting layer Bonded
1x630/50 0,0283 0,387 0,29 / 0,51 0,09 / 0,16 0,45 1,7 5,4
Longitudinal water tightness Semi conducting water blocking tape
Shield / Screen Annealed copper wires in contact with aluminum tape * Cable distance, installation in flat formation = 70 mm
Radial water blocking Aluminium laminate, bonded to sheath
Outer sheath PE, black Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Example of marking on sheath FXLJ-TT TSLE 24kV 1x50 FR/16 DRAKA “Date and time”, metre marked [mm2] in ground** in air** in air** during 1s during 1s
[A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
[kA] [kA]

Temperature 1x50/16 205 205 250 7,8 7,1

Maximum operating temperature 90°C 1x70/16 255 240 295 11,0 10,0
Minimum temperature at installation -20°C, below 0°C special precautions are recommended 1x95/25 295 300 355 14,9 13,6
1x120/25 335 335 410 18,9 17,2
1x150/25 380 380 465 23,6 21,5
Features 1x185/35 425 435 535 29,1 26,5
Bending radius In fixed installation: 10 x D
1x240/35 485 505 620 37,7 34,4
When pulling-in: 15 x D
1x300/35 545 575 705 47,2 43,0
When plowing down: 8 x D
1x400/35 625 680 835 62,9 57,4
1x500/35 695 765 940 78,7 71,7
Electrical 1x630/50 755 845 1035 99,1 90,4
Impulse voltage 125kV
** Trefoil with screen grounded in both end.
The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Note: screen resistance is the sum of copper wires and aluminum tape.

POWER CABLES 64 Prysmian Group Baltics AS • baltics.prysmiangroup.com 65


Power Cables 24 kV Power Cables 24 kV

FXQJ-TT Pure TSLI 12/20(24) kV


Conductors and Diameter over Diameter over Standard Delivery package EAN/GTIN number Product code
screen area insulation sheath delivery length
[mm2] [mm] [mm] [m]
1x50/16 19,5 27,5 500 K12 7330384722254 20115904
1x70/16 21,1 29,0 500 K12 7330384722223 20164338
1x95/25 22,8 31,0 500 K14 7330384722216 20164339
1x120/25 24,1 32,5 500 K14 7330384722209 20164340
1x150/25 25,7 34,0 500 K14 7330384722452 20235166
1x185/35 27,5 36,0 500 K16 7330384722193 20164341
1x240/35 29,8 38,5 500 K16 7330384722247 20164335
Application
1x300/35 32,1 41,0 500 K16 7330384722421 20232877
Halogen-free, flame retardant and self-extinguishing.
1x400/35 35,5 44,1 500 K20 7330384722186 20164342
Single-core distribution cable suitable for laying outdoors in 3-phase formation.
Installation in pipes and in ground/water. Both radial and longitudinal water sealed. Can be ploughed down. 1x500/35 38,1 47,0 500 K20 7330384722438 20233884
1x630/50 41,9 51,0 500 K22 7330384722179 20164343

Alternative Product name Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
SE-20XC7A5T5E-R screen area resistance resistance in trefoil/in flat* in trefoil/in flat* [µF/km] current / current
[mm2] [Ω/km] [Ω/km] [mH/km] [Ω/km] phase [A/km]
[A/km]
1x50/16 0,3870 1,150 0,43 / 0,73 0,14 / 0,23 0,17 0,6 1,9
Standard 1x70/16 0,2680 1,150 0,41 / 0,70 0,13 / 0,22 0,19 0,7 2,1
HD 620 Part 10 Section M
1x95/25 0,1930 0,727 0,39 / 0,67 0,11 / 0,21 0,21 0,8 2,4
HD 620 Part 10 Section K
1x120/25 0,1530 0,727 0,38 / 0,65 0,12 / 0,21 0,23 0,9 2,6
1x150/25 0,1240 0,727 0,36 / 0,63 0,11 / 0,20 0,25 0,9 2,8
Construction 1x185/35 0,0991 0,524 0,35 / 0,61 0,11 / 0,19 0,27 1,0 3,1
Cable shape Round 1x240/35 0,0754 0,524 0,34 / 0,59 0,11 / 0,19 0,30 1,1 3,4
Conductors Stranded, round and compacted copper acc. to IEC 60228 class 2, 1x300/35 0,0601 0,524 0,32 / 0,57 0,10 / 0,18 0,33 1,2 3,7
longitudinally water sealed 1x400/35 0,0470 0,524 0,31 / 0,55 0,10 / 0,17 0,37 1,4 4,2
Inner semi-conducting layer Extruded
1x500/35 0,0366 0,524 0,30 / 0,53 0,09 / 0,17 0,40 1,5 4,5
Conductor screen XLPE, min thickness = 4,85 mm
1x630/50 0,0283 0,387 0,29 / 0,51 0,09 / 0,16 0,45 1,7 5,4
Outer semi-conducting layer Bonded
Longitudinal water tightness Semi conducting water blocking tape * Cable distance, installation in flat formation = 70 mm
Shield / Screen Annealed copper wires in contact with aluminum tape
Radial water blocking Aluminium laminate, bonded to sheath Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Outer sheath PE, black [mm2] in ground** in air** in air** during 1s during 1s
Example of marking on sheath FXQJ-TT Pure TSLI 24kV 1x50 FR/16 DRAKA “Date and time”, metre marked [A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
[kA] [kA]
1x50/16 205 205 250 7,8 7,1

Temperature 1x70/16 255 240 295 11,0 10,0


Maximum operating temperature 90°C 1x95/25 295 300 355 14,9 13,6
Minimum temperature at installation -20°C, below 0°C special precautions are recommended 1x120/25 335 335 410 18,9 17,2
1x150/25 380 380 465 23,6 21,5
1x185/35 425 435 535 29,1 26,5
Features
1x240/35 485 505 620 37,7 34,4
CPR performance class Dca-s2d2a2
1x300/35 545 575 705 47,2 43,0
Bending radius In fixed installation: 10 x D
When pulling-in: 15 x D 1x400/35 625 680 835 62,9 57,4

When plowing down: 8 x D 1x500/35 695 765 940 78,7 71,7


1x630/50 755 845 1035 99,1 90,4

** Trefoil with screen grounded in both end.


Electrical
The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
Impulse voltage 125kV thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Note: screen resistance is the sum of copper wires and aluminum tape.

POWER CABLES 66 Prysmian Group Baltics AS • baltics.prysmiangroup.com 67


Power Cables 36 kV Power Cables 36 kV

AXLJ-TTCL TSLF 18/30(36) kV Conductors and


screen area
Diameter over
insulation
Diameter over
sheath
Standard
delivery length
Delivery package EAN/GTIN number Product code

[mm2] [mm] [mm] [m]


1x50/25 24,3 33,1 500 K14 7330384719087 20114470
1x70/25 25,9 34,7 500 K14 7330384719094 20114471
1x95/25 27,6 36,6 500 K16 7330384713665 20102188
1x120/35 28,9 37,9 500 K16 7330384719100 20114472
1x150/35 30,5 39,7 500 K18 7330384719117 20114473
1x185/35 32,2 41,4 500 K18 7330384713658 20102189
1x240/35 34,4 43,8 500 K18 7330384719124 20114474
1x300/35 36,9 46,5 500 K20 7330384713689 20102190
1x400/35 40,1 49,9 500 K20 7330384713702 20102191

Application 1x500/35 43,0 52,9 500 K22 7330384713672 20102192

Single-core, distribution cable for outdoor use in 3-phase formation. Installation in pipes and ground/water. 1x630/50 46,9 57,0 500 K22 7330384716772 20114469

Both radial and longitudinal water sealed. Can be ploughed down. The outer sheath has a conductive layer that greatly 1x800/50 50,4 60,9 500 K24 7330384718158 20114475
extends the possibilities to do a sheath testing before, during and after installation.
Ripcords for easier and safer stripping of the outer sheath. Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance in trefoil/in flat* in trefoil/in flat* [µF/km] current / current
[mm2] [Ω/km] [Ω/km] [mH/km] [Ω/km] phase [A/km]
[A/km]
Alternative Product name Flame retardance 1x50/25 0,6410 0,727 0,47 / 0,75 0,15 / 0,24 0,13 0,7 2,2
SE-N30XC7A5T5E-AR Not applicable
1x70/25 0,4430 0,727 0,44 / 0,71 0,14 / 0,22 0,14 0,8 2,4
1x95/25 0,3200 0,727 0,42 / 0,68 0,13 / 0,21 0,16 0,9 2,7

Standard 1x120/35 0,2530 0,524 0,41 / 0,66 0,13 / 0,21 0,17 1,0 2,9

SS 424 14 16 1x150/35 0,2060 0,524 0,39 / 0,64 0,12 / 0,20 0,19 1,1 3,2

HD 620 Part 10 Section K 1x185/35 0,1640 0,524 0,38 / 0,62 0,12 / 0,20 0,20 1,1 3,4
HD 620 Part 10 Section M 1x240/35 0,1250 0,524 0,36 / 0,60 0,11 / 0,19 0,22 1,2 3,7
1x300/35 0,1000 0,524 0,35 / 0,58 0,11 / 0,18 0,24 1,4 4,1
1x400/35 0,0778 0,524 0,34 / 0,56 0,11 / 0,18 0,27 1,5 4,6
Construction 1x500/35 0,0605 0,524 0,32 / 0,54 0,10 / 0,17 0,29 1,6 4,9
Cable shape Round
1x630/50 0,0469 0,387 0,31 / 0,52 0,10 / 0,16 0,33 1,9 5,9
Conductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2,
1x800/50 0,0367 0,387 0,30 / 0,50 0,09 / 0,16 0,36 2,0 6,1
longitudinal water sealed
Inner semi-conducting layer Extruded * Cable distance, installation in flat formation = 70 mm
Conductor screen XLPE, min thickness = 7,1 mm
Outer semi-conducting layer Bonded Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Longitudinal water tightness Semi conducting water blocking tape [mm2] in ground** in air** in air** during 1s during 1s
Shield / Screen Annealed copper wires in contact with aluminum tape [A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
[kA] [kA]
Radial water blocking Aluminium-PE laminate, bonded to sheath
Ripcord Aramid 1x50/25 155 160 195 5,2 4,7

Outer sheath PE, natural, UV-protected 1x70/25 200 190 235 7,2 6,6
Example of marking on sheath AXLJ-TTCL TSLF 36kV 1x95 AFR/25 DRAKA “Date and time”, metre marked 1x95/25 235 230 280 9,9 8,9
1x120/35 265 265 325 12,4 11,3
1x150/35 300 300 370 15,6 14,2
Temperature 1x185/35 330 345 425 19,2 17,5
Maximum operating temperature 90°C
1x240/35 385 400 490 25,0 22,7
Minimum temperature at installation -20°C, below 0°C special precautions are recommended
1x300/35 435 460 565 31,2 28,3
1x400/35 510 555 680 41,6 37,8

Features 1x500/35 570 635 775 52,0 47,2


Bending radius In fixed installation: 10 x D 1x630/50 635 720 880 65,6 59,5
When pulling-in: 15 x D 1x800/50 695 822 1010 83 75,6
When plowing down: 8 x D
** Trefoil with screen grounded in both end.
The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Electrical Note: screen resistance is the sum of copper wires and aluminum tape.
Max short circuit temperature 250°C
Impulse voltage 170kV

POWER CABLES 68 Prysmian Group Baltics AS • baltics.prysmiangroup.com 69


Power Cables 36 kV Power Cables 36 kV

AXQJ-TT Pure TSLI 18/30(36) kV Conductors and


screen area
Diameter over
insulation
Diameter over
sheath
Standard
delivery length
Delivery package EAN/GTIN number Product code

[mm2] [mm] [mm] [m]


1x50/25 24,3 32,5 500 K14
1x70/25 25,9 34,0 500 K14
1x95/25 27,6 36,0 500 K16
1x120/35 29,2 37,5 500 K16
1x150/35 30,5 39,0 500 K16
1x185/35 32,2 41,0 500 K18
1x240/35 34,4 43,5 500 K18
1x300/35 36,9 46,0 500 K20
1x400/35 40,1 49,5 500 K20

Application 1x500/35 43,0 52,5 500 K22

Halogen-free, flame retardant and self-extinguishing. 1x630/50 46,9 56,5 500 K22

Smoke in the event of fire is limited, transparent (to facilitate evacuation) and not harmful to electronic equipment. 1x800/50 51,2 61,5 500 K24
Radial and longitudinal water sealed distribution cable for use indoors and outdoors for 3-phase formation.
Installation in pipes and ground. Ploughing down is not recommended. Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
Ripcords for easier and safer stripping of the outer sheath. screen area resistance resistance in trefoil/in flat* in trefoil/in flat* [µF/km] current / current
[mm2] [Ω/km] [Ω/km] [mH/km] [Ω/km] phase [A/km]
[A/km]
1x50/25 0,6410 0,727 0,47 / 0,75 0,15 / 0,24 0,13 0,7 2,2
Alternative Product name 1x70/25 0,4430 0,727 0,44 / 0,71 0,14 / 0,22 0,14 0,8 2,4
SE-N30XC7A5Z1-AR
1x95/25 0,3200 0,727 0,42 / 0,68 0,13 / 0,21 0,16 0,9 2,7
1x120/35 0,2530 0,524 0,41 / 0,66 0,13 / 0,21 0,17 1,0 2,9

Standard 1x150/35 0,2060 0,524 0,39 / 0,64 0,12 / 0,20 0,19 1,1 3,2

HD 620 Part 10 Section M HD 604 1x185/35 0,1640 0,524 0,38 / 0,62 0,12 / 0,20 0,20 1,1 3,4
HD 620 Part 10 Section K EN 50575:2014 1x240/35 0,1250 0,524 0,36 / 0,60 0,11 / 0,19 0,22 1,2 3,7
1x300/35 0,1000 0,524 0,35 / 0,58 0,11 / 0,18 0,24 1,4 4,1
1x400/35 0,0778 0,524 0,34 / 0,56 0,11 / 0,18 0,27 1,5 4,6
Construction 1x500/35 0,0605 0,524 0,32 / 0,54 0,10 / 0,17 0,29 1,6 4,9
Cable shape Round
1x630/50 0,0469 0,387 0,31 / 0,52 0,10 / 0,16 0,33 1,9 5,9
Conductors Stranded, round, compacted aluminium acc. to IEC 60228 class 2,
1x800/50 0,0367 0,387 0,30 / 0,50 0,09 / 0,16 0,36 2,0 6,1
longitudinally watertight
Inner semi-conducting layer Extruded * Cable distance, installation in flat formation = 70 mm
Conductor screen XLPE, min thickness = 7,6 mm
Outer semi-conducting layer Bonded Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Longitudinal water tightness Semi conducting water blocking tape [mm2] in ground** in air** in air** during 1s during 1s
Shield / Screen Annealed copper wires in contact with aluminum laminate [A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
[kA] [kA]
Radial water blocking Aluminium laminate, bonded to sheath
Ripcord Aramid 1x50/25 155 160 195 5,2 4,7

Outer sheath Halogen free compound, black 1x70/25 200 190 235 7,2 6,6
Example of marking on sheath AXQJ-TT Pure TSLI 36kV 1x120 AFR/25 D-s2d2a2 DRAKA “Date and time”, 1x95/25 235 230 280 9,9 8,9
metre marked 1x120/35 265 265 325 12,4 11,3
1x150/35 300 300 370 15,6 14,2
1x185/35 330 345 425 19,2 17,5
Temperature
1x240/35 385 400 490 25,0 22,7
Maximum operating temperature 90°C
1x300/35 435 460 565 31,2 28,3
Minimum temperature at installation -20°C, below 0°C special precautions are recommended
1x400/35 510 555 680 41,6 37,8
1x500/35 570 635 775 52,0 47,2
Features 1x630/50 635 720 880 65,6 59,5
CPR performance class Dca-s2d2a2 1x800/50 695 822 1010 83 75,6
Bending radius In fixed installation: 10 x D
When pulling-in: 15 x D When plowing down: 8 x D ** Trefoil with screen grounded in both end.
The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Note: screen resistance is the sum of copper wires and aluminum tape.
Electrical
Impulse voltage 170kV

POWER CABLES 70 Prysmian Group Baltics AS • baltics.prysmiangroup.com 71


Power Cables 52 kV Power Cables 52 kV

AXLJ-TTCL TSLF 26/45(52) kV Conductors and


screen area
Diameter over
insulation
Diameter over
sheath
Standard
delivery length
Delivery package EAN/GTIN number Product code

[mm2] [mm] [mm] [m]


1x50/25 27,2 36,6 500 K16
1x70/25 28,8 38,2 500 K16
1x95/25 30,5 40,1 500 K16
1x120/35 32,1 41,7 500 K16
1x150/35 33,4 43,1 500 K18
1x185/35 35,1 44,8 500 K18
1x240/35 37,3 47,2 500 K20 7330384713580 20111047
1x300/35 39,7 49,8 500 K20 7330384718325 20165484
1x400/35 42,9 53,2 500 K22 7330384718042 20159537

Application 1x500/35 45,8 56,0 500 K22 7330384719384 20183095

Single-core, distribution cable for outdoor use in 3-phase formation. Installation in pipes and ground/water. 1x630/50 49,7 60,4 500 K24 7330384714075 20113584

Both radial and longitudinal water sealed. Can be ploughed down. The outer sheath has a conductive layer 1x800/50 53,2 66,1 500 K24 7330384719070 20173864
that greatly extends the possibilities to do a sheath testing before, during and after installation.
Ripcords for easier and safer stripping of the outer sheath. Conductors and Conductor Screen Inductance Reactance Capacitance Charging Earth fault
screen area resistance resistance* in trefoil/in flat* in flat* [µF/km] current / current
[mm2] [Ω/km] [Ω/km] [mH/km] [Ω/km] phase [A/km]
[A/km]
Alternative Product name Flame retardance 1x50/25 0,6410 0,727 0,49 / 0,75 0,24 0,12 1,0 2,9
SE-N45XC7A5T5E-AR Not applicable
1x70/25 0,4430 0,727 0,46 / 0,72 0,23 0,13 1,1 3,2
1x95/25 0,3200 0,727 0,44 / 0,69 0,22 0,14 1,1 3,4

Standard 1x120/35 0,2530 0,524 0,42 / 0,67 0,21 0,16 1,3 3,9

IEC 60840 1x150/35 0,2060 0,524 0,41 / 0,65 0,2 0,17 1,4 4,2
1x185/35 0,1640 0,524 0,39 / 0,63 0,2 0,18 1,5 4,4
1x240/35 0,1250 0,524 0,38 / 0,61 0,19 0,19 1,6 4,7
Construction 1x300/35 0,1000 0,524 0,36 / 0,59 0,19 0,21 1,7 5,1
Cable shape Round 1x400/35 0,0778 0,524 0,35 / 0,56 0,18 0,24 2,0 5,9
Conductors Stranded, round, compressed aluminium acc. to IEC 60228 class 2, 1x500/35 0,0605 0,524 0,34 / 0,55 0,17 0,26 2,1 6,4
longitudinally watertight
1x630/50 0,0469 0,387 0,33 / 0,53 0,17 0,28 2,3 6,9
Inner semi-conducting layer Extruded
1x800/50 0,0367 0,387 0,32 / 0,51 0,16 0,31 2,5 7,6
Conductor screen XLPE, nom thickness = 9,0 mm
Outer semi-conducting layer Bonded * Cable distance, installation in flat formation = 70 mm
Longitudinal water tightness Semi conducting water blocking tape
Shield / Screen Annealed copper wires in contact with aluminum tape Conductors and Current rating Current rating Current rating Max short circuit Max short circuit
screen area at core temp. 65°C at core temp. 65°C at core temp. 90°C current on conductor current on conductor
Radial water blocking Aluminium-PE laminate, bonded to sheath [mm2] in ground** in air** in air** during 1s during 1s
Ripcord Aramid [A] [A] [A] at initial temp. 65°C, at initial temp. 90°C,
[kA] [kA]
Outer sheath PE, natural UV protected
Semi-conducting layer in outer sheath Yes (facilitates sheath testing) 1x50/25 155 160 195 5,2 4,7

Example of marking on sheath AXLJ-TTCL TSLF 52kV 1x50 AFR/25 DRAKA “Date and time”, metre marked 1x70/25 200 190 235 7,2 6,6
1x95/25 235 230 280 9,9 8,9
1x120/35 265 265 325 12,4 11,3
Temperature 1x150/35 300 300 370 15,6 14,2
Maximum operating temperature 90°C
1x185/35 330 345 425 19,2 17,5
Minimum temperature at installation -20°C, below 0°C special precautions are recommended
1x240/35 385 400 490 25,0 22,7
1x300/35 435 460 565 31,2 28,3

Features 1x400/35 510 555 680 41,6 37,8

Bending radius In fixed installation: 10 x D 1x500/35 570 635 775 52,0 47,2
When pulling-in: 15 x D 1x630/50 635 720 880 65,6 59,5
When plowing down: 8 x D 1x800/50 695 822 1010 83 75,6

** Trefoil with screen grounded in both end.

Electrical The ratings are based on the following conditions: ground temperature- 15°C, air temperature- 25°C,
thermal resistivity of soil- 1,0 K · m/W, depth of burial- 0,65m, frequency- 50Hz.
Max short circuit temperature 250°C Note: screen resistance is the sum of copper wires and aluminum tape.
Impulse voltage 250kV

POWER CABLES 72 Prysmian Group Baltics AS • baltics.prysmiangroup.com 73


Cable Designations used in Sweden Cable Designations used in Norway
A cable code of 2 - 4 letters is used to descriebe the construction.
The interpretation (per letter) can be read from the table below:

Extracts from SS 424 17 01

Letter 1st letter 2nd letter 3rd letter 4th letter 5th letter 1st letter: 2nd letter 3rd letter 3rd letter
Core Insulation Sheath or other Design detail or Design detail or Insulation Bedding / inner sheath Armouring / screen Armouring / screen
design detail usage usage
A Aluminium Screen of aluminiumfoil
and/or aluminium wire A Fibre, tight cladded
A Aluminium (optional
with corrosion protection) A Strength member yarn
A Yarn + bitumen

B Aluminium alloy Flame retardant


thermoplastic polyolefine
Flame retardant
thermoplastic polyolefine
Vehicle cable
B Fire resistant tape + insulation
(Halogen-free) B Corrogated aluminium
(o.w.c.p.) B Steel tapes, 2 off
B Hydrocarbon resistant sheath

(Halogen free, low smoke) (Halogen free, low smoke)


C Polychloroprene
(Neoprene) PCP, or C Polychloroprene
(Neoprene) PCP, or C Galvanized steel wire braid
C Polychloroprene
(Neoprene) PCP, or
Lead sheath Connection wire chlorinated polyethylene chlorinated polyethylene chlorinated polyethylene
- CPE - CPE - CPE
Lead sheath
D Impregnated paper
Drip free D Aluminium + Plastics
D Oil filled cable reinforcement
(Longitudinal / Transverse) D
C Impregnated paper Concentric copper screen Concentric copper screen
E Polyethylene - PE
Polypropylene - PP E Polyethylene - PE
Polypropylene - PP E Oil filled cable reinforcement
(Transverse only) E Polyethylene - PE
Polypropylene - PP
D Rubber

F F F F
with outer rubber sheath PE orPP+ Bedding or taping Flat steel wire armour Semi-conducting PE

E Copper, solid
(class 1)
Ethylene propylene
rubber
Reinforced design Reinforced design
Filling compound (Halogen-free)

F Copper, stranded
(class 2)
Braid of copper wire Braid of copper or
steel wire G Polyamid - PA
G G G PE + PA

H Silicon rubber Lift cable Suspension cable


H Chlorosulphonated
polyethylene - CSP H Chlorosulphonated
polyethylene - CSP H Steel tape + steel wires
H Chlorosulphonated
polyethylene - CSP

I Polyurethane Polyurethane
I Thermoplastic compound
(Halogen-free) I Thermoplastic compound
(Halogen-free) I Steel tapes, 4 off
I Thermoplastic compound
(Halogen-free)
J Steel wire Steel tape armouring For laying in ground
K Paper
K Lead
K Steel wire,
plastics or rubber coated K Lead

K PVC PVC PVC PVC


L Air + plastics
L Aluminium laminate
L Aluminium
L
(Coaxial cable) + plastics sheath (laminated to outer jacket)
L Polyethylene (PE) Screen of plastic coated Polyethylene (PE) Polyethylene (PE)
aluminium tape ev.
together with screen of copper
M Expanded PE or
PP + filling compound M Polyester
M M Polyester

Polyethylene (PE) N Impregnated paper


N Polyurethane
N Steel
(laminated to outer jacket) N Polyurethane

M Copper, stranded O Impregnated paper,


oilfilled cable O Lead + Plastics
O Copper wire braid
(Tinned or bare) O
O Chloroprene rubber Chloroprene rubber Oil cable
P Polyvinylchloride - PVC
P Polyvinylchloride - PVC
P Phosphorbronze wire braid
P Polyvinylchloride - PVC

P Galvanised steel tape


armouring
Galvanised steel tape
armouring Q Fibre in loose tube
Q Q Steel wires
+ counter steel tape (optional) Q
Q Halogen free plastic Flame retardant
thermoplastic polyolefine
Flame retardant
thermoplastic polyolefine
R Ethylenepropylene rubber -
EPR R Ethylenepropylene rubber -
EPR R Steel wires (round)
+ filling compound R Ethylenepropylene rubber -
EPR
(Halogen free, low smoke) (Halogen free, low smoke)
S Silicone rubber
S Bedding or taping
+ concentric conductor S Concentric conductor (Screen)
S Silicone rubber

R Copper, flexible Plastic coated aluminium tape Control cable


(class 5) armouring
T Cross-linked polyethylene XLPE
T PE + aluminium wire
+ steel tape T T Cross-linked polyethylene
XLPE
S Copper, extra flexible Self-supporting
(class 6) U Halogen-free thermoset
compound EMA or EVA U Halogen-free thermoset
compound EMA or EVA U U Halogen-free thermoset
compound EMA or EVA
T Copper, very flexible Fluorethylene resin Steel wire armouring Heavy connection cable or
galvanised steel wire
Steel wire armouring
V Fibre, slotted core
V Aluminium screen
V Double wire armour
V Other halogen-free thermoset
(two layers) materials
armouring

U Without outer sheath W Other materials


W Other materials
W Catenary wire
W Other materials

No bedding or equivalent
V Rubber Ethylene propylene rubber For laying in water For laying in water X No insulation
X X No armour
X No sheath

without outer sheath


Y Y Screen
Y Y
X Cross-linked polyethylene PVC, ovaalne ristlõige
(XLPE)
Z Fluor plastics PTFE / FEP
Z Fluor plastics
Z Z Fluor plastics

Z Flame retardant
cross-linked polyolefine
Flame retardant
cross-linked polyolefine
Cable for neon equipment

(Halogen free, low smoke) (Halogen free, low smoke)


-J Earth conductor

-O Optical fiber

- OJ Optical fiber and earth conductor

POWER CABLES 74 Prysmian Group Baltics AS • baltics.prysmiangroup.com 75


Cable Designations used in Finland

Designations in the cross-section: Exceptions to the previous, trademarks:

x Separating the number of phase cores and the cross-section (mm²) , for example AXMK
1x300 1 kV SAX™-W Covered conductor. A standardized Finnish name for this product is PAS.

Aerial bundled MV cable, completely watertight.


+ Product having an external conductor (centre conductor, messenger or auxiliary phase core), for example
AHXAM K-W 3x 240+70 20 kV, AHXAM K-WM 3x95+62I 20kV,
SAXKA®-W
AMKA 4 x25+35 1 kV
Fire retardant halogen-free cable (or material).
AFUMEX®
/ Separating numbers or letters from each other:
- separates the cross-section of the concentric conductor (metallic screen) from the phase core, Flexible, cold resistant (-50°C) rubber insulated cable.
for example MCMK 3x25/16 1kV, AHXCMK-WTC 3x240/35 20kV ATON®
- separates the cross-section of the aluminium and the steel core in overhead conductors, for example
ACSR 54/9 R AVEN
Wiski™ The nickname and trademark of AHXAMK-W.

The most common letters used in domestic products Multi-Wiski™ The nickname and trademark of AHXAMK-WM.

(current product selection): WiskiPlain™ The nickname and trademark of AHXAMK-WP.

A Aluminium or aluminium alloy (for alumiini in Finnish)


- in the beginning of the type designation means Al conductor, for example AXMK
Aluminium conductor steel reinforced.
(exception: SAX-W means Al alloy); ACSR These overhead conductors have often nickname of bird, city etc, for example Sparrow, Duck, Savo
- in the middle of the type designation means Al foil laminate, for example AHXAMK-W;
- aluminium alloy messenger, for example AMKA;
Aluminium alloy conductor steel reinforced (overhead conductor).
- aluminium alloy armouring, for example AHXKAJ-W. AACSR
Copper conductor (no A letter in the beginning), for example MCMK, XMK, HXCMK-WTC. All aluminium conductor (overhead conductor).
AAC
M - plastic insulation (general expression), for example MCMK, AMKA. Usually plastic insulation is either PVC or PE (for muovi in Finnish);
- plastic sheath (general expression), for example MCMK, AHXAMK-W. HK Copper conductor with annealed wires (for hehkutettu kupari in Finnish).
Plastic sheath can be PVC, PE or fire-retardant and halogen-free thermoplastic compound.
Steel conductor.
FE
K Cable, for example XMK, AHXAMK-W (for kaapeli in Finnish).
Overhead contact conductor for electric locomotives and trolleys.
TRL
X XLPE insulation, for example AXMK, AHXAMK-W, AMKA-X, SAX-W (for PEX in Finnish).

H - extruded semi-conducting layer below and over the insulation (in MV and HV cables), for example AHXAMK-W (for hohtosuoja in Finnish);
- sheath made of special material, for example TASH having heat resistant sheath. Exceptions to the previous, bare conductors, overhead conductors, etc
Typical Finnish cable with trade name Wiski™
C - concentric layer of copper wires (metallic screen), for example MCMK, AHXCMK-WTC;
- uniform copper layer (Cu helical tape or Cu foil laminate) MCCMK, HXCCMK.

S Copper braid, for example LSM-HF.

L - lead sheath, for example AHXLMK-W (for lyijy in Finnish);


- marine cable (the 1st letter in the type designation), for example LM-HF (for laiva in Finnish).

P Round steel wire armouring, for example AHXAMKPJ-W.

J - a conductor or a lead, for example MMJ, LJST-HF (for johdin in Finnish);


- jute tape layer, for example AHXAMKPJ-W.

O Control cable, for example MMO (for ohjaus in Finnish).

CHB Metallic screen having Cu wires, semi-conducting tape layer and Al foil laminate, for example HXCHBMK.
The cross-section of the metallic screen given in type designation is solely based on the cross-section of Cu wires.

CA Metallic screen having Cu wires, semi-conducting tape layer and Al foil laminate, for example AHXCAMK-W.
The cross-section of the metallic screen given in the type designation is a total cross-section of Cu wires and Al foil laminate combined.

Y Each phase core having a separate metallic screen (in a 3-core cable), for example HXYLMKPJ-W 3x95 10kV.
This letter is not used with 3-core cables having Al foil laminate only (AHXAMK-W).

FR Fire Resistant cable remaining functional during fire, for example FRHF.

T Heat resistant, for example TASH, AMKA-T.

E Cable having a special feature compared to standard cable, for example XMKE 1x300 1kV,
having a flexible Class 5 conductor (for erikoinen in Finnish).

POWER CABLES 76 Prysmian Group Baltics AS • baltics.prysmiangroup.com 77


Correction factors
Correction factors for installation
The effect of several adjacent cables in the ground
The factor of three core cables Thermal resistivity in the ground
and for groups of three single core cables Ambient air temperature

Clear space Thermal resistivity Conductor temperature Ambient air temperature, ˚C


between the cables Number of adjacent cables in the ground 0,7 1,0 1,2 1,5 2,0 2,5 3,0
or between the or groups of single core cables Km/W ˚C 10 15 20 25 30 35 40 45 50 55
groups of single
core cables Correction factor 1,10 1,00 0,92 0,85 0,75 0,69 0,63 90 1,12 1,08 1,04 1,00 0,95 0,90 0,85 0,80 0,74 0,68

mm 2 3 4 5 6 8 9 80 1,14 1,09 1,05 1,00 0,95 0,89 0,48 0,77 0,69 0,61
Thermal resistivity in different types of soil:
0 0,75 0,65 0,60 0,55 0,50 0,43 0,41 70 1,18 1,12 1,06 1,00 0,95 0,86 0,79 0,71 0,62 0,52
– dry sand (moisture content 0%) . . . . . . . . . . . . . . . . . . . . . . 3,0 Km/W
70 0,80 0,70 0,60 0,55 0,55 0,48 0,46 65 1,20 1,14 1,07 1,00 0,95 0,85 0,77 0,68 0,57 0,45
– dry gravel and clay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,5 Km/W
250 0,90 0,80 0,75 0,70 0,70 0,65 0,63 – semi-dry gravel, bog earth and sand (moisture 10%) . . . 1,2 Km/W
– semi-dry clay and damp gravel . . . . . . . . . . . . . . . . . . . . . . . 1,0 Km/W
– damp clay and sand (moisture content 25 %) . . . . . . . . . 0,7 Km/W
Correction factors for aerial installation
Laying depth or for installation type B
Cable Laying depth, m Cables in air = the same cooling conditions as when freely in air
0,50–0,70 0,71–0,90 0,91–1,10 1,11–1,301,31–1,50
0,61/1,0 kV 1,00 0,97 0,95 0,93 0,92
Installation type A Installation type B
6/10–18/30 kV 1,00 0,99 0,98 0,96 0,95 The cable is laid on the surface or so that between the cable and The cable is laid on the surface or so that between the cable and
the surface of the covering material the thermal transmission factor the surface of the covering material the thermal transmission factor
Ground temperature is 11–50 W/˚C m2. is K>50 W/˚C m2.
Installation type A includes one of the following: Installation type B includes one of the following:
Conductor temperature Ground temperature,˚C
– surface installation – surface installation (also in a tube) with short lead-through
˚C -5 0 5 10 15 20 25 30 35 40 45
– installation on a cable rack with short lead-through – installation on a cable rack with short lead-through
90 1,13 1,10 1,06 1,03 1,00 0,96 0,93 0,89 0,86 0,82 0,77 – disaccording to installation type B – sunk installation in stone structures (concrete, brick, etc.)
80 1,14 1,11 1,07 1,04 1,00 0,96 0,92 0,88 0,83 0,78 0,73 – installation in a riser shaft or in a cable duct
70 1,17 1,13 1,09 1,04 1,00 0,95 0,90 0,85 0,80 0,73 0,67
65 1,18 1,14 1,10 1,05 1,00 0,95 0,89 0,84 0,77 0,71 0,63
The effect of grouping in aerial installation on the loading of Multicore alternating current cables
Underground installation in PE or PVC tubes, with one three core cable or three single core cables. and on single core direct current cables
The tubes lie side by side. If the correction factors of this table are applied, the factors in the topmost table are not used.
Arrangement of the cables Clear space = cable diameter (d); The cables touch one another and the wall
The tubes lie side by side. distance from the wall ≥ 20 mm
Clear distance of the tubes Number of adjacent tubes
If the correction factors Number of adjacent cables 1 2 3 6 9 Drawing 1 2 3 6 9 Drawing
mm 2 3 4 5 6 8 10 of this table applied, 20 mm
0 0,85 0,75 0,70 0,65 0,60 0,54 0,49 the factors in the topmost table Correction factor Correction factor
Põrandal või laes d
are not used. 0,95 0,90 0,88 0,85 0,84 0,90 0,84 0,80 0,75 0,73
250 0,90 0,85 0,80 0,80 0,80 0,74 0,72
500 0,95 0,90 0,85 0,85 0,80 0,78 0,79 No, of racks
0,3 m 0,3 m
1 0,95 0,90 0,88 0,85 0,84 0,95 0,84 0,80 0,75 0,73
Unperforated trays
The effect of cable cover slabs and troughs 2 0,90 0,85 0,83 0,81 0,80 d
0,95 0,80 0,75 0,71 0,69
3 0,88 0,83 0,81 0,79 0,78 0,95 0,78 0,74 0,70 0,68
d
Type of covering Correction factor 6 0,86 0,81 0,79 0,77 0,76 20 mm 0,95 0,76 0,72 0,68 0,66
1 1,00 0,98 0,96 0,93 0,92 0,95 0,84 0,80 0,75 0,73
A concrete or brick slab more than 10 cm above the cable in well-compacted sandy ground 1,00
2 1,00 0,95 0,93 0,90 0,89 0,3 m 0,95 0,80 0,76 0,71 0,69 0,3 m
Bricks all around the cable, gaps sealed up tightly with sand 0,90 Ladder supports, 3 1,00 0,94 0,92 0,89 0,88 0,95 0,78 0,74 0,70 0,68
cleats, etc. d
A concrete trough on the cable, compacted sand between the trough and the cable 0,90
6 1,00 0,93 0,90 0,87 0,86 0,95 0,76 0,72 0,68 0,66
A concrete or plastic trough on the cable, loose sand filler between the cable and the trough 0,80 d
20 mm

Number of overlying cables 1 2 3 6 9 1 2 3 6 9


d
d
On racks or on the wall 1,00 0,93 0,90 0,87 0,86 0,95 0,78 0,73 0,68 0,66
20 mm

2d 0,3 m
Installation with no need Unrestricted number of overlying cables d Unrestricted number of adjacent cables
2d
to reduce the load current
20 mm d
20 mm

The data is valid, provided that the ambient temperature does not rise significantly in result of the increasing heat by dissipation in the cable.

POWER CABLES 78 Prysmian Group Baltics AS • baltics.prysmiangroup.com 79


General terms and Drum dimensions
conditions of supply and weights
The effect of grouping in aerial installation on the loading of single core alternating current cables Unless agreed otherwise, the ”General Terms and
Conditions of Supply NL09” are applied.
Length tolerances
Flat formation, clear space = cable diameter (d);
Arrangement of the cables distance from the wall >20 mm Cables touch one another and the wall

Number of adjacent systems 1 2 3 Drawing 1 2 3 Drawing Installation cables, standard length: ± 3%


Correction factor
20 mm
d
d Correction factor
20 mm
2d
2d
Rubber cables, standard length: ± 5%
On the floor or on the ceiling Power cables, standard length: + 3% –2%
0,92 0,89 0,88 0,95 0,90 0,88

No, of racks 20 mm
d
d
20 mm
2d
2d Reel label
1 0,92 0,89 0,88 0,95 0,80 0,73 0,3 m
The reel label is supplied with large, distinctive
0,3 m
Unperforated trays 2 0,87 0,84 0,83 0,95 0,76 0,69 text and a bar code for faster and safer handling
3 0,84 0,82 0,81 0,95 0,74 0,68
of goods, also at the clients’ sites. The bar code
system chosen by us (code 39) is an alphanumeric
6 0,82 0,80 0,79 0,95 0,72 0,66
20 mm 20 mm 2d
bar code with a high safety level.
The image below shows an example of a reel label.
1 1,00 0,97 0,96 d
d 1,00 0,98 0,96 2d

2 0,97 0,94 0,93


0,3 m
1,00 0,95 0,93
0,3 m The actual labels are at least 160 mm wide.
Ladder supports,
cleats, etc. 3 0,96 0,93 0,92 1,00 0,94 0,92

6 0,94 0,91 0,90 1,00 0,93 0,90

Number of overlying systems 1 2 3 1 2 3


20 mm

On racks or on the wall 0,94 0,91 0,89 d 0,89 0,88 0,84 2d


d Carrying
Drum Dimensions, mm Weight
capacity
20 mm 2d
4d type A B C D E kg kg
With a longer distance, there are more reduce losses in the metal sheath and in the armouring,
Installation with no need while cooling improves. 0,3 m K6 600 468 250 400 75 12 300
to the load current Each case must be calculated separately.
K7 700 580 325 500 75 20 400

K8 800 580 375 500 75 25 500


The data is valid, provided that the ambient temperature does not rise significantly in result of the increasing heat by dissipation in the cable. K9 900 630 425 550 75 34 600

9FV 900 675 425 550 82 50 700

K10 1000 712 500 600 75 54 800

K11 1100 762 575 650 106 55 850

11GV 1100 755 500 600 82 85 1000

K12 1200 982 675 850 106 90 1500

13G 1300 760 600 600 82 105 1600

K14 1400 982 800 850 106 115 2000

15G 1500 760 700 600 82 150 2000

K16 1600 1018 950 850 106 195 2500

K18 1800 1075 1100 850 132 230 3000

K20 2000 1190 1300 1000 132 340 3500


K22 2200 1190 1400 1000 132 410 4500
K24 2400 1205 1400 1000 132 450 5000

K26 2600 1448 1500 1200 132 900 10000

K28 2800 1610 1500 1300 132 1180 12000

K30 3000 1800 1500 1500 132 1500 13000

POWER CABLES 80 Prysmian Group Baltics AS • baltics.prysmiangroup.com 81


Drum handling guide

A cable is a valuable product. The cable transportation package is drum from touching other drums and well balanced. Take care not to Secure the drums firmly Fasten the drums firmly
usually a drum. The battens on the drum seem thick enough to remain give any impact to the drum being lowered. In case a cable drum must
unbroken. But, with a cable weighing more than 4 tons, it becomes be temporarily in a waiting position above the deck for reason of The round-shaped cable drum rolls easily. It is an a very unstable The drum is fastened to the base through the centre hole or across
very vulnerable. If the handling is done correctly, the drum will protect cargo handling, keep it hoisted and do not put it down on the deck. state because its center section is vacant and the whole weight rests the flanges with wires or ropes.
the cable from transportation damages. If the drum is damaged, the on its peripheral section. Make sure to use drags to prevent drums
cable can also be damaged. The damage might not be discovered until from rolling during storage. Large drums should be lifted from the
after installation, when repairs can be extremely expensive. base onto triangular or square wedges. The wedges should be
positioned by the flanges or the full width of drum. Sideways
The purpose of these instructions is to tell you how damages can be movement is eliminated by planks attached to the side of the drum.
avoided by correct drum handling. In case smaller drums are placed between larger ones, each drum
has to be supported separately to prevent damages.
Keep the drum upright

Always store and move the drum in an upright position. The drum is Avoid stacking
constructed to be handled in an upright position - it will not stand up
to being lifted lying flat. When kept upright, the cable layers will not Stacking of drums should be avoided. If, however, one is forced to do
entangle and cause problems when the cable is laid. Keep the cable this, same size of drums should be positioned exactly on top of each
protected until the cable is used. other. If smaller drums are stacked on larger drums, planks of the
Handling with fork-lift truck size of the larger drum is placed in between to protect the flanges.

The forks of the truck must be longer than the width of the drum, so Above method is recommended even when same size drums are
that the lagging is not damaged. Different widths of drums should be stacked.
painted on the forks enabling the operator to select the correct
position for the drum size. When moving the drum, tilt the truck mast
so that the drum remains in the fork and the points don’t touch the
ground. Raise the forks of the forklift sufficiently 15-20 cm above the
ground. Insufficient raising may cause the drum to be dragged on the
ground and eventually damaged or dropped off the forks if the ground
surface is uneven. Don’t release the drum until the truck has sopped
completely. Don’t push the drum with the truck. Leave age sufficient
room between each drum so that the fork doesn’t damage the drum.

Roll in direction of arrows only

Always roll the drum in direction of the arrow. This way the cable will Secure drums to be transported
not unwind and loosen on the drum. But, this does not mean that the
Don’t drop drums
drum can be rolled freely. When the drum must be rolled for some
To prevent movement of drums, a combination of wedges and
reason or other, roll it in the direction of arrow over a distance not
transportation support should be used and tied down front and rear. The drum must not be dropped from the vehicle. The drum is to be
exceeding 5 meters. If it is rolled beyond the 5 m limit, the cable wind
Higher drums should be tied in side direction as high up as possible. lifted either by winch of fork-lift truck as mentioned in “lifting the
will come too tight and cut o the rope holding the cable end.
drum”. If above mentioned equipment is not available, best
This will deform the cable and make it unfit for use.
The drums loaded first should rest against the front board (observing possible conditions must be created to unload the drums from the
shaft weight). If the last drum doesn’t lean against the end board or vehicle. A platform of the same height as the vehicle or a point in
the board is not strong enough, the drum must be secured. the terrain will guarantee that no damage will occur. Make sure
Nail with caution when unloading that the drum doesn’t strike another drum.

In case the planks have to be refastened, the nailing should be done


carefully in the middle of the drum flange. If label or something
similar is attached to the drum with nails, make sure that they don’t
touch the cable.

Lift the drum without damage


When lifting the drum, use a shaft through the centre of the drum
and a wire spreader. If these are not available, lift with as long a wire
as possible, so that the sides of the drum are not damaged. Make sure
that the cable head is not pinched between wire and drum. Keep the

POWER CABLES 82 Prysmian Group Baltics AS • baltics.prysmiangroup.com 83


Recommendations for cable laying This also applies during the entire construction period.
A proper fire sealing should prevent fire from spreading
between fire compartments during the whole course of
the fire – fire development and extinguishing – i.e. it shall
• Meet the requirements of the fire class:
be type approved.
1. Minimum cable temperature during cable laying
General all other equipment. Faulty or damaged equipment can • Withstand smoke, gas and extinguishing media during
Cable type Temperature °C
easily destroy many metres of cable. the fire.
Cable laying environments and cable types vary widely.
AMCMK, MCMK, AXPK -15
This section provides brief advice and recommendations Other • Withstand fire restoration after the fire AXALJ-TT, AXLJ-RMF, AXQJ-RMF, AXLJ-TT TSLF -20
for different operations during cable laying. The cable
Cable ladders are practical aids for cable laying both in- • Be easily installed and allow modifications.
weight often determines the laying method. In case of
doors and outdoors. Power cables are preferably installed
cable laying in ground, one can choose between pulling, • Withstand loads normally occurring in the installation, 2. Minimum bending radius
with a slight distance between cables for efficient coo-
driving and ploughing. If the area is easily accessible for during both operation and standby
ling. Lashing wire should be used with caution to avoid At
vehicles, driving is an easier and more cable-friendly Cable type At laying At fixing
any cuts ploughing
method. Tractor excavator is often used for reel weights
of up to approx. 1 tons, where the cable reel hangs from in the sheath, especially in case of vertical cable laying. Short circuit current capacity AMCMK, MCMK, MCCMK, AXPK
the bucket. Heavier cables are driven with crane truck Sheath damage may also occur in long horizontal cable Single-conductor, 1kV 15 x D 8xD 10 x D
Multiconductor 15 x D 8xD 8xD
or a vehicle for lift dumpers. For cable pulling, cable connections fixed with lashing wire, due to temperature Thermal stress
AXALJ-TT, AXLJ-TTCL TSLF,
reels are placed evenly distributed along the cable route changes. Clamps are less harmful to cable sheaths and AXLJ-RMF
should therefore be preferred for somewhat heavier Taking into account the mechanical and electrical
so that the cable runs freely. Pulling can be performed Single-conductor 12–36kV 15 x D 8xD 10 x D
cables and sheaths that can reach very high temperatu- strength of the insulation, thermal stress by a short circuit Multiconductor 12 x D 8xD 8xD
manually or with a machine. The reel shall be possible
res. Heat may originate both from the environment and is restricted by setting the maximum final conductor
to brake during cable laying, driving as well as pulling.
from load losses in the cable. XLPE cables installed on temperatures in a short circuit:
There are detailed manuals for ground installation indi- r
cating the installation depth, cable protection, marking ladders with uninhibited air circulation achieve a condu- D = Outer diameter of the cable
• X LPE-insulated cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . 250°C D
and combined laying with telecommunication cables ctor temperature of +90°C and a sheath temperature of
in SEK Manual 429. The organization EBR (El Byggnads approx. +70°C at the rated current. If cooling of the cable • PVC-insulated 1 kV cables
Rationalisering, Rational Electrical Installation) has is complicated by a heat-insulating layer such as sawdust
issued a manual for cable laying for max 145 kV (KJ41:09). or pulp, the conductor and sheath temperatures can ­≤ 300 mm2 . . . . . . . . . . . . . . . . 160°C
3. Sealing of cable ends
Another norm, SS 424 14 38, regulates cable laying in reach +125°C and +100°C, respectively. At this point, there
> 300 mm2 . . . . . . . . . . . . . . . . 140°C
buildings and culverts. Sharp bends can be critical mo- is a risk of deformation of the insulation and sheath layers The cable ends shall be sealed against moisture after each cutting.

ments during pulling and permanent installation, high which leads to disruptive discharge in the cable. The given values for maximum permissible short circuit
The cut length shall alsi be sealed if it is not installed immediately.

tensile stresses and laying at low temperatures. In case of open laying of single-conductor cables, the currents in cable data have been calculated assuming
Cable ploughing cables shall be bound together and fixed to the base the initial conductor temperature to be the maximum 4. Maximum pulling force
surface to avoid them being thrown apart at short-circui- operating temperature in continu­ous use.
Cable ploughing methods have been developed within Pulling equipment Pulling force
ting. Otherwise, thick cables exposed to high short-circuit The listed short circuit currents for duration of one
the latest years and entail that cable installation costs Immediate connection in all Aluminium P = 30 N/mm 2
currents may be damaged or damage their surroundings. second indicate the thermal capacity of the conductor.
have decreased compared to traditional cable laying conductors Copper P = 50 N/mm 2
Single-conductor cables are normally laid close together The maximum permissible thermal short circuit current
with trenching. Observe the following for successful
in a triangle form which both facilitates the “trussing” for duration of 0.2 to 5 seconds can be computed by the
Cable grip on the cover P = 5 x D2 Newton
cable ploughing installation:
and reduces shield losses which in its turn affects the load equation:
Cable ploughing is generally considered to be a “rough” capacity. In order to improve the load capacity in con- 5. Maximum permissible surge current in three-phase cables (kA)
installation method for cables. Uncautious handling may nections with single-conductor cables, shield losses can
It=I1s/√t Rated voltage Rated voltage
damage the cables due to rocks and other sharp objects be minimized in exceptional cases with various methods. where: Area Area
The simplest way is to only earth the metal shields of the mm 2 mm 2
in the ground pressed into cable sheaths. The planned 1kV 12-24kV 1kV 12-24kV
cables in one end of the connection, open shield. Instead I1s = 1 s thermal short circuit current [kA]
installation route shall always be ploughed in advance 50 45 55 150 60 70
of an induced shield current which causes losses, an t = duration of the short circuit [s]
to ensure that cable installation is possible along the 70 50 60 185 60 70
planned route. Choose a cable type intended for cable induced voltage is achieved between the insulated shield
Dynamic stress 95 55 65 240 60 70
ploughing. Generally, cables with polyethylene (PE) end and earth. This voltage is directly proportional to the
120 55 65 300 60 70
outer sheath has the required mechanical strength. Ha- length of the connection and the conductor current and Short circuit currents cause a mechanical load on the cable
logen-free, fire-retardant sheath can be ploughed if re- can be dangerous to people. Therefore, open shield is as well as on the accessories.
quired caution is observed. Outer sheaths have different only recommended for short connections (< 100 m) and 6. Testing voltage for 12-36 kV cables after laying
The dynamic short circuit stress is much greater near the
mechanical characteristics at different temperatures preferably in protected areas (substations, equipment Insulation AC
high volt­age network and near large power plants than Voltage kV
which can be crucial for whether a cable installation will rooms etc.). Note that in case of single-point earthing, type kV Time
farther out in the network. That is why the dynamic capac-
the insulation between the shield and the system earth
be good or less good. A cable installed on a warm sum- ity of the accessories as well as the cable fittings must be New cable
shall be checked prior to commissioning.Earth faults may installation
mer day at +30°C ambient temperature can show diffe- checked. This is especially important with high power sys-
cause electric arcs and fire hazard. 12 XLPE 12 5 min
rent performance from the same cable installed at an tems and with several parallel cables in aerial installation. 7 24 h
ambient temperature of +10°C. The choice of machines Fire sealing
Most important in a short circuit is the peak value of cur- 24 5 min
and equipment is also crucial for the final result. Expe- 24 XLPE
Fire sealing of lead-throughs is necessary in order to redu- rent, which is 2.5 times the short circuit current. To mini- 14 24 h
rience has shown that machines and equipment used for
ce the risk of fire spreading between different parts of the mize dynamic stress, the installation must be made using 36 5 min
cable laying require similar service and maintenance as 36 XLPE
building through cable connections. the right accessories and the right technique. 18 24 h

POWER CABLES 84 Prysmian Group Baltics AS • baltics.prysmiangroup.com 85


Testing after cable laying

All cables are subjected to routine testing according Sheath current can also be identified with a megger.
to the applicable standard at the factory before the The formula for sheath current is then:
reels are delivered to the client. In order to check the
dielectric strength after transport and cable laying, a I = U / (RxL)
new test shall be conducted by the installer or the owner
where I is the sheath current per length unit (A/km), U is
of the installation prior to commissioning of the cable.
the applied voltage (V), R is the detected sheath resistance
The test standard SS 424 14 17 for PEX cables indicates
(Ω) and L is the cable length (km).
the method, voltage and time that can be applied in tes-
ting. Tests may also prove necessary in technical assess- Sheath test, measurement setup
ment of older installations. Ensure that a reasonable test
• S
 trip 10 cm of the semiconductive sheath from both the
voltage is chosen, taking the general condition of the
inner and the outer end of the sheath.
installation into account. Prior to testing, it is important
to ensure that the parts of the installation which are not • C
 onnect the instrument between the semiconductive
to be tested are disconnected and earthed. Then the vol- layer of the sheath and the copper shield.
tage test is performed with the voltage indicated in the • Adjust the instrument to read the leakage current ”I”.
regulations. After testing, it is important to earth the • Start by applying 100 V.
installation to ensure that the installation and testing
• Increase the test voltage gradually.
equipment are properly discharged. Maintain earthing
until the cable is commissioned or for at least 3 hours. • Discontinue the test if a fault is detected.
• I f no fault is detected during the voltage increase, conti-
Sheath testing in medium voltage cables
nue to the test voltage within a minute.
Network owners set high requirements on the quality
of execution of cable installations. Many power plants Note! When measuring a cable on reel, ensure that the in-
require improved quality assurance for this work. The ner end is freed, dry and stripped to at least 10 cm to avoid
possibility of checking the sheath on medium voltage conduction due to moisture/water.
cables both before and after installation has therefore
Interpretation of measurement results
come into focus. This contributes to better safety for the
network owner as well as the external contractors often Suitable test voltages and acceptable leakage currents for
used for laying cables and installing them in the ground. different sheath materials are indicated below. An aged
sheath may show up to 1000 times higher leakage currents
The advantage of the semiconductive outer layer is that
than a new one without being faulty, and still be approved,
the cable can be tested for sheath faults before the cable
depending on the installation conditions.
trench is closed. If a fault is detected, it can be repaired
in an early stage, saving both time and money. Cable tes-
Newly installed cable
ting of cables installed in pipes is another positive side of Max leakage
Test
choosing this cable. Sheath
voltage Rec. max
current,
material Max leakage, repeat
(kV, DC) leakage
Measurement of sheath current current
note measurement Issue: November 2021

Required instrument: high voltage generator (DC) with a PE 5 10 μA/km 1 mA/km 1 mA/km The preparation of text and illustration has been carried out with great care.
Nevertheless mistakes can not be excluded. All photographs are the exclusive
precise ammeter for measuring the output current. The PVC 2 0,5 μA/km 10 mA/km 50 mA/km
property of Prysmian Group.
voltage shall be adjusted gradually from 0 to the maxi- LSZH* 2 2 mA/km 50 mA/km 500 mA/km
Prysmian Group does not accept any liability for casual or consequential damage in
mum of 5 kV to avoid indication of several sheath faults * LSZH halogen-free and flame-retardant sheath
connection with the use of this catalog. Improvement proposals and advices are to be
at the same time. The largest faults are then detected sent to: info.keila@prysmiangroup.com.
first. The measurement voltage depends on the type of Repairing sheath damage All rights reserved. This document may not be copied in whole or in part, be
sheath material. For our AXLJ-TTCL with PE (Polyethyle- When repairing sheath damage, 10 cm of the conductive reproduced, translated into another language or stored on electronic media.
ne), the maximum measurement voltage is 5 kV. layer shall be stripped from each side of the edges of the
Please note: Prysmian Group herewith warrants that the delivery items contained
hole/damage. This ensures that no erroneous indications in this catalogue will be of the agreed nature and quality upon passing of the risk.
are received during repeated testing after the repair. To Aforementioned nature of the delivered items shall be exclusively rated and measured
by the sales and purchase agreements made in writing between Prysmian Group and
maintain the special function of the conductive layer the purchaser about nature and quality, properties and characteristic performance
after repair and testing, a temporary connection should features of the respective delivery item. Illustrations and information contained
in catalogues, price lists and other information material disclosed to the purchaser
be made over the non-conductive repair with e.g. a copper by Prysmian Group as well as any information describing the product shall be only
net. legally binding, if expressly being referred to as binding information. Under no
10 cm 10 cm
Always consult your supplier of joint/repair sets for circumstances, such information shall be taken as guarantee for the special quality or
nature of the delivery item. Such quality guarantees must be explicitly agreed upon
recommendations. in writing. Prysmian Group herewith reserves the right to modify the content of the
catalog at any time.

© by Prysmian Group Baltics AS 2021

POWER CABLES 86
Linking the future

Prysmian Group Baltics AS


Paldiski maantee 31, 76606 Keila, Eesti
+372 674 7466
info.keila@prysmiangroup.com
baltics.prysmiangroup.com

Follow us:

You might also like