VA2-YF00-P0BAY-145001 - Logic - GSUT - UAT - OVERALL PROT - RB - 230628
VA2-YF00-P0BAY-145001 - Logic - GSUT - UAT - OVERALL PROT - RB - 230628
VA2-YF00-P0BAY-145001 - Logic - GSUT - UAT - OVERALL PROT - RB - 230628
LAMP B
FOR REVIEW
B
A1 (841 x 594)
B 52L1 52L2
STG EXCITATION FCB 41E GSUT PROTECTION RELAY PANEL 86GT2 COIL SUPERVISION STG EXCITATION FCB 41E
ALARM RESET SHEET.12 12-21 FMS SHEET.12 12-22
GSUT PROTECTION RELAY PANEL TRIP COIL-1 P1CHB01 74GT2 TRIP COIL-1
FMS X31:5-6 P1CHB01GH002_XB103
P1CHB01
X31:1-2 P1CHB01GH001_XB101
STG EXCITATION FCB 41E STG EXCITATION FCB 41E
SHEET.12 12-31 SHEET.12 12-32
TRIP COIL-2 TRIP COIL-2
GSUT PROTECTION RELAY PANEL 86GT1 COIL SUPERVISION
FMS STG D-EHC STG D-EHC
P1CHB01 74GT1 SHEET.12 12-41 SHEET.12 12-42
X31:5-6 P1CHB01GH001_XB103 TURBINE TRIP-1 (2 OUT OF 3) TURBINE TRIP-1 (2 OUT OF 3)
FOR REVIEW
STG D-EHC STG D-EHC
SHEET.12 12-51 SHEET.12 12-52
TURBINE TRIP-2 (2 OUT OF 3) TURBINE TRIP-2 (2 OUT OF 3)
GSUT PROTECTION RELAY PANEL 86GT1 COIL SUPERVISION GSUT PROTECTION RELAY PANEL 86GT2 COIL SUPERVISION
DCS DCS
P1CHB01 74GT1 P1CHB01 74GT2
P1CHB01GH001_XB62 P1CHB01GH002_XB62
GSUT PROTECTION RELAY PANEL LOSS OF DC POWER-1 GSUT PROTECTION RELAY PANEL LOSS OF DC POWER-2
DCS DCS
P1CHB01 74DC-1 P1CHB01 74DC-2
P1CHB01GH001_XB64 P1CHB01GH002_XB64
GSUT PROTECTION RELAY PANEL LOSS OF AC POWER
DCS
P1CHB01 74AC
P1CHB01GH001_XB65
A1 (841 x 594)
B 52L1 52L2
DS(Q3)
ES(Q38)
AIS
4-20mA LOCAL/REMOTE SELECTION SW ACSR
OIL LEVEL (MAIN) HIGH ALARM GSUT CUR (L2) GSUT MDU
GSUT LCP DCS GSUT LCP DCS LOCAL CONTROLLED BY
71H (MAIN)
P1BAT01GH001_XB61 P1BAT01GH001_XQ12 OLTC TAP CHANGE SWITCH
& MANUALLY @ OLTC MOTOR DRIVE UNIT
GSUT MDU
OIL LEVEL (MAIN) LOW ALARM 4-20mA LOWER GSUT
GSUT LCP
71L (MAIN)
DCS
GSUT LCP
GSUT VOLTAGE (L3-L1)
DCS B P1BAT01
P1BAT01GH001_XB62
P1BAT01GH001_XQ23
OIL LEVEL (OLTC) HIGH ALARM LOCAL/REMOTE SELECTION SW GSUT OLTC
GSUT MDU
GSUT LCP
71H (OLTC)
DCS
GSUT ACTV PWR (MW)
4-20mA REMOTE ≥1 TAP CHANGING
GSUT LCP DCS LOWER
P1BAT01GH001_XB63
P1BAT01GH001_XQ31 GCB
OIL LEVEL (OLTC) LOW ALARM LOCAL/REMOTE SELECTION SW P1BAC01
GSUT LCP DCS GSUT RTCC UAT-1A UAT-1B
71L (OLTC) 4-20mA
P1BAT01GH001_XB64 GSUT RACTV PWR (MVAR) LOCAL (RTCC) P1BBT01 P1BBT02
GSUT LCP DCS
57GT
BUCHHOLZ ALARM P1BAT01GH001_XQ32
GSUT LCP DCS &
63B
P1BAT01GH001_XB65 GSUT RTCC
AUTO/MANUAL MODE & 89G
MANUAL CONTROLLED BY
OIL TEMPERATURE HIGH ALARM
OLTC TAP CHANGE SWITCH
& MANUALLY @ RTCC GCB
GSUT LCP DCS 52G
26OA GSUT RTCC 57UAT1A 57UAT1A 57UAT1B 57UAT1B
P1BAT01GH001_XB66 LOWER
-1 -2 -1 -2
HV WINDING TEMPERATURE HIGH ALARM ≥1 57GG
GSUT LCP DCS
26WA (HV) AUTO/MANUAL MODE 52UAT1A 52UAT1A 52UAT1B 52UAT1B
P1BAT01GH001_XB67 GSUT RTCC
AUTO CONTROLLED BY ≥1 -1 -2 -1 -2
LV WINDING TEMPERATURE HIGH ALARM & AUTOMATICALLY BY AVR
GSUT LCP DCS OLTC TAP CHANGE COMMAND
26WA (LV) TAP CHANGE AVR G
P1BAT01GH001_XB68 LOWER
GEN P1BBA01 P1BBA02 P1BBA03 P0BBA01
DGA COMMON ALARM
GSUT TMS DCS 4-20mA P1MKA01
OIL TEMPERATURE
P1BAT01GH001_XB69 GSUT LCP DCS LOCAL/REMOTE SELECTION SW
TMS COMMON ALARM P1BAT01GH001_XQ73
GSUT RTCC
REMOTE (DCS)
B
GSUT LCP DCS NOTES
4-20mA THIS DWG. 1
P1BAT01GH001_XB70 WINDING TEMPERATURE - HV WINDING
GSUT TMS DCS
SPARE FAN GROUP IN SERVICE
P1BAT01GH001_XQ74 DCS
AUTO/MANUAL MODE & 1. THIS DRAWING IS APPLICABLE FOR UNIT-1 AND UNIT-2.
GSUT LCP DCS MANUAL CONTROLLED BY
P1BAT01GH001_XB71 4-20mA P1BAT01GH002_YB62 & MANUALLY @ PLANT DCS UNIT-1 UNIT-2 DESCRIPTION
WINDING TEMPERATURE - LV WINDING OLTC TAP CHANGE SWITCH
GSUT LCP DCS DCS
AC PWR FAULT LOWER
GSUT LCP DCS P1BAT01GH001_XQ75 P1BAT01GH002_YB63 P1BAT01 P2BAT01 GSUT
P1BAT01GH001_XB72 ≥1
4-20mA THIS DWG. 2 P1BBT01 P2BBT01 UAT-1A / UAT-2A
OLTC TAP CHANGER PWR FAULT DGA MOISTURE
GSUT LCP DCS GSUT LCP DCS P1BBT02 P2BBT02 UAT-1B / UAT-2B
AUTO/MANUAL MODE
P1BAT01GH001_XB73 P1BAT01GH001_XQ79 DCS
AUTO CONTROLLED BY P1BAC01 P2BAC01 GCB
DC PWR FAULT
P1BAT01GH002_YB61 & AUTOMATICALLY BY AVR P1BBA01 P2BBA01 11KV UNIT SWGR-1
GSUT LCP DCS OLTC TAP CHANGE COMMAND
TAP CHANGE AVR
LOWER P1BBA02 P2BBA02 11KV UNIT SWGR-2
P1BAT01GH001_XB74
PRESSURE RELEF DEVICE ALARM P1BBA03 P2BBA03 11KV UNIT SWGR-3
GSUT LCP DCS
P1BAT01GH001_XB76 P0BBA01 P0BBA02 11KV COMMON SWGR
LOCAL/REMOTE SELECTION SW
GSUT MDU
FAN GROUP MCCB FLT LOCAL CONTROLLED BY
GSUT LCP DCS & 2. THE FAULT SIGNAL WILL BE TRANSFERRED TO FMS BY
OLTC TAP CHANGE SWITCH MANUALLY @ OLTC MOTOR DRIVE UNIT COMMUNICATION LINK (IEC 61850).
P1BAT01GH001_XB77 GSUT MDU
RAISE
SPARE FAN GROUP MCCB FLT 3. 49GT PROTECTION FUNCTION SETS THE 50/51GT TO OPERATE
GSUT LCP DCS
P1BAT01GH001_XB78 AS AN ALARM BEFORE TRIP OPERATION.
LOCAL/REMOTE SELECTION SW GSUT OLTC
GSUT MDU
GSUT LCP
PUMP GROUP MCCB FLT
DCS REMOTE ≥1 TAP CHANGING
4. REFERENCE SCHEMATIC DWG.
RAISE
VA2-YU03-P0ASR-140001 : SCHEMATIC PROTECTION RELAY PANEL
P1BAT01GH001_XB79
VA2-YU03-P0BAT-140003 : SCHEMATIC GSUT LCP/RTCC/TMS
SPARE PUMP GROUP MCCB FLT LOCAL/REMOTE SELECTION SW
GSUT LCP DCS GSUT RTCC
LOCAL (RTCC)
P1BAT01GH001_XB80
FAN GROUP POWER FLT &
GSUT LCP DCS
GSUT RTCC
AUTO/MANUAL MODE &
P1BAT01GH001_XB81 MANUAL CONTROLLED BY
OLTC TAP CHANGE SWITCH
& MANUALLY @ RTCC
PUMP GROUP POWER FLT GSUT RTCC
GSUT LCP DCS RAISE
P1BAT01GH001_XB82
≥1
DGA GAS HIGH HIGH ALARM
GSUT TMS DCS AUTO/MANUAL MODE
GSUT RTCC
P1BAT01GH001_XB83 AUTO CONTROLLED BY ≥1
OLTC TAP CHANGE COMMAND
& AUTOMATICALLY BY AVR
WTS (FO TEMP MONITOR) SYS FLT TAP CHANGE AVR
GSUT LCP DCS RAISE
P1BAT01GH001_XB84 FOR REVIEW
PRESSURE RELEF DEVICE ALARM (OLTC)
GSUT LCP DCS
P1BAT01GH001_XB85 LOCAL/REMOTE SELECTION SW
GSUT RTCC
REMOTE (DCS)
SUDDEN PRESSURE RELAY ALARM
GSUT LCP DCS
P1BAT01GH001_XB86
1 THIS DWG.
AUTO/MANUAL MODE &
BREATHER MAIL ERROR MANUAL
GSUT LCP DCS CONTROLLED BY
OLTC TAP CHANGE SWITCH
& MANUALLY @ PLANT DCS
P1BAT01GH001_XB87 DCS
RAISE
BREATHER OLTC ERROR P1BAT01GH002_YB64
GSUT LCP DCS ≥1
P1BAT01GH001_XB88
AUTO/MANUAL MODE
FAN GROUP IN SERVICE 2 THIS DWG.
GSUT LCP DCS AUTO CONTROLLED BY
OLTC TAP CHANGE COMMAND
& AUTOMATICALLY BY AVR
P1BAT01GH001_XB89 TAP CHANGE AVR
RAISE
DGA GAS HIGH ALARM
GSUT TMS DCS
P1BAT01GH001_XB90
VUNG ANG II THERMAL POWER PROJECT
DGA MOISTURE HIGH ALARM
GSUT TMS DCS GSUT OLTC OPERATION
P1BAT01GH001_XB91
DGA MOISTURE HIGH HIGH ALARM
GSUT TMS DCS VUNG ANG II THERMAL POWER
P1BAT01GH001_XB92 LIMITED LIABILITY COMPANY
PUMP GROUP IN SERVICE OLTC TAP CHANGING INCOMPLETE OLTC CONTROL MODE "LOCAL"
GSUT LCP DCS GSUT RTCC DCS GSUT RTCC DCS
P1BAT01GH001_XB93 P1BAT01GH002_XB61 P1BAT01GH002_XB67
DGA GAS RATE OF CHANGE OLTC TAP CHANGER IN PROGRESS OLTC CONTROL MODE "REMOTE (DCS)"
GSUT TMS DCS GSUT RTCC DCS GSUT RTCC DCS
P1BAT01GH001_XB94 P1BAT01GH002_XB62 P1BAT01GH002_XB68
SPARE PUMP GROUP IN SERVICE OLTC AVR P.T. VOLTAGE FAULT OLTC CONTROL MODE "AUTO"
GSUT LCP DCS GSUT RTCC DCS GSUT RTCC DCS
P1BAT01GH001_XB95 P1BAT01GH002_XB63 P1BAT01GH002_XB71
LCP 3PH AC MAIN PWR FAILURE OLTC AVR FAULT OLTC CONTROL MODE "MANUAL"
GSUT LCP DCS GSUT RTCC DCS GSUT RTCC DCS
P1BAT01GH001_XB97 P1BAT01GH002_XB64 P1BAT01GH002_XB72
LCP 3PH AC BACK UP PWR FAILURE GSUT RTCC AC PWR FAILURE
GSUT LCP DCS GSUT RTCC DCS
P1BAT01GH001_XB98 P1BAT01GH002_XB65 4-20mA
TAP POSITION
GSUT RTCC DC PWR FAILURE GSUT RTCC DCS
GSUT RTCC DCS P1BAT01GH002_XQ61
P1BAT01GH002_XB66
GSUT MONITORING AND ALARM
A1 (841 x 594)
B 52L1 52L2
PRESSURE RELIEF DEVICE TRIP - OLTC PRESSURE RELIEF DEVICE TRIP - OLTC GEN P1BBA01 P1BBA02 P1BBA03 P0BBA01
UAT-1A LCP 500KV AIS 52L1 UAT-1A LCP 500KV AIS 52L1 P1MKA01
63PRC SHEET.9 9-13 63PRC SHEET.9 9-14
X31:7-8 TRIP COIL-1 X31:7-8 TRIP COIL-1
FMS OIL TEMP HIGH HIGH TRIP B
500KV AIS 52L1 UAT-1A LCP 500KV AIS 52L1 NOTES
P1CHC01GH001_XB104 SHEET.9 9-23 26OT SHEET.9 9-24
OIL TEMP HIGH HIGH TRIP TRIP COIL-2 X31:9-10 TRIP COIL-2
UAT-1A LCP
26OT WINDING TEMPERATURE TRIP - HV WINDING
X31:9-10 UAT-1A LCP 1. THIS DRAWING IS APPLICABLE FOR UNIT-1 AND UNIT-2.
FMS 500KV AIS 52L1 26WTHV 500KV AIS 52L1
SHEET.9 9-33 X31:11-12 SHEET.9 9-34
50BF INITIATE-1(IF REQUIRED) 50BF INITIATE-1(IF REQUIRED)
P1CHC01GH001_XB105 UNIT-1 UNIT-2 DESCRIPTION
WINDING TEMPERATURE TRIP - HV WINDING WINDING TEMPERATURE TRIP - LV-X WINDING
UAT-1A LCP 500KV AIS 52L1 UAT-1A LCP 500KV AIS 52L1
26WTHV SHEET.9 9-43 26WTLV-X SHEET.9 9-44 P1BAT01 P2BAT01 GSUT
X31:11-12 50BF INITIATE-2(IF REQUIRED) X31:13-14 50BF INITIATE-2(IF REQUIRED)
FMS BUCHHOLZ TRIP P1BBT01 P2BBT01 UAT-1A / UAT-2A
500KV AIS 52L2 UAT-1A LCP 500KV AIS 52L2
P1CHC01GH001_XB106 SHEET.10 10-13 63B SHEET.10 10-14
WINDING TEMPERATURE TRIP - LV-X WINDING TRIP COIL-1 X31:15-16 TRIP COIL-1 P1BBT02 P2BBT02 UAT-1B / UAT-2B
UAT-1A LCP
26WTLV-X OLTC PROTECTIVE RELAY TRIP P1BAC01 P2BAC01 GCB
X31:13-14 UAT-1A LCP
FMS 500KV AIS 52L2 63OP 500KV AIS 52L2
SHEET.10 10-23 X32:1-2 SHEET.10 10-24 P1BBA01 P2BBA01 11KV UNIT SWGR-1
TRIP COIL-2 TRIP COIL-2
P1CHC01GH001_XB107
BUCHHOLZ TRIP SUDDEN PRESSURE TRIP P1BBA02 P2BBA02 11KV UNIT SWGR-2
UAT-1A LCP 500KV AIS 52L2 UAT-1A LCP 500KV AIS 52L2
63B SHEET.10 10-33 63S SHEET.10 10-34 P1BBA03 P2BBA03 11KV UNIT SWGR-3
X31:15-16 50BF INITIATE-1(IF REQUIRED) X32:3-4 50BF INITIATE-1(IF REQUIRED)
FMS PRESSURE RELIEF DEVICE TRIP - MAIN TANK P0BBA01 P0BBA02 11KV COMMON SWGR
500KV AIS 52L2 UAT-1A LCP 500KV AIS 52L2
P1CHC01GH001_XB108 SHEET.10 10-43 63PR SHEET.10 10-44
OLTC PROTECTIVE RELAY TRIP 50BF INITIATE-2(IF REQUIRED) X32:5-6 50BF INITIATE-2(IF REQUIRED)
UAT-1A LCP 2. THE FAULT SIGNAL WILL BE TRANSFERRED TO FMS BY
63OP WINDING TEMPERATURE TRIP - LV-X WINDING
X32:1-2 UAT-1A LCP COMMUNICATION LINK (IEC 61850).
FMS P1BAC01 GCB 26WTLV-Y P1BAC01 GCB
SHEET.11 11-13 X32:7-8 SHEET.11 11-14
TRIP COIL-1 TRIP COIL-1
P1CHC01GH001_XB109 3. 49UT PROTECTION FUNCTION SETS THE 50/51UT TO OPERATE
SUDDEN PRESSURE TRIP
UAT-1A LCP P1BAC01 GCB P1BAC01 GCB AS AN ALARM BEFORE TRIP OPERATION.
63S SHEET.11 11-23 SHEET.11 11-24
X32:3-4 TRIP COIL-2 TRIP COIL-2
FMS 4. REFERENCE SCHEMATIC DWG.
P1CHC01GH001_XB110 EXTERNAL TRIP INPUT EXTERNAL TRIP INPUT VA2-YU03-P0ASR-140001 : SCHEMATIC PROTECTION RELAY PANEL
PRESSURE RELIEF DEVICE TRIP - MAIN TANK SHEET.12 12-3 SHEET.12 12-4 VA2-YU03-P0BBT-140003 : SCHEMATIC UAT
UAT-1A LCP TO STG GPR-A TO STG GPR-A
63PR
X32:5-6
FMS EXTERNAL TRIP INPUT EXTERNAL TRIP INPUT
SHEET.12 12-13 SHEET.12 12-14
TO STG GPR-B TO STG GPR-B
P1CHC01GH001_XB111
WINDING TEMPERATURE TRIP - LV-X WINDING UAT-1A PROTECTION RELAY PANEL ALARM RESET
UAT-1A LCP STG EXCITATION FCB 41E STG EXCITATION FCB 41E
26WTLV-Y SHEET.12 12-23 P1CHC01 SHEET.12 12-24
X32:7-8 TRIP COIL-1 X31:1-2 TRIP COIL-1
FMS
P1CHC01GH001_XB111 STG EXCITATION FCB 41E STG EXCITATION FCB 41E
SHEET.12 12-33 UAT-1A PROTECTION RELAY PANEL 86UT2 COIL SUPERVISION SHEET.12 12-34
TRIP COIL-2 FMS TRIP COIL-2
P1CHC01 74UT2
X31:5-6 P1CHC01GH002_XB103
STG D-EHC STG D-EHC
SHEET.12 12-43 SHEET.12 12-44
TURBINE TRIP-1 (2 OUT OF 3) TURBINE TRIP-1 (2 OUT OF 3)
UAT-1A PROTECTION RELAY PANEL ALARM RESET STG D-EHC STG D-EHC
FMS SHEET.12 12-53 SHEET.12 12-54
P1CHC01 TURBINE TRIP-2 (2 OUT OF 3) TURBINE TRIP-2 (2 OUT OF 3)
X31:1-2 P1CHC01GH001_XB101
FOR REVIEW
STG D-EHC STG D-EHC
SHEET.12 12-63 SHEET.12 12-64
UAT-1A PROTECTION RELAY PANEL 86UT1 COIL SUPERVISION TURBINE TRIP-3 (2 OUT OF 3) TURBINE TRIP-3 (2 OUT OF 3)
FMS
P1CHC01 74UT1
X31:5-6 P1CHC01GH001_XB103 P1BBA01 SWGR INCOMER P1BBA01 SWGR INCOMER
SHEET.13 13-13 SHEET.13 13-14
TRIP COIL-1 TRIP COIL-1
P0BBA01 SWGR INCOMER P0BBA01 SWGR INCOMER VUNG ANG II THERMAL POWER
SHEET.14 14-23 SHEET.14 14-24
TRIP COIL-2 TRIP COIL-2 LIMITED LIABILITY COMPANY
UAT-1A PROTECTON PROTECTION ACTIVATED P0BBA01 SWGR HSBT UAT-1A PROTECTON PROTECTION ACTIVATED P0BBA01 SWGR HSBT
SHEET.14 14-33 SHEET.14 14-34
RELAY-A EXCEPT THE FUNCTIONS FAST TRANSFER INITIATION RELAY-B EXCEPT THE FUNCTIONS FAST TRANSFER INITIATION
51UT, 50/51TN-UT-X & Y X41:5-4 51UT, 50/51TN-UT-X & Y X41:5-4
UAT-1A PROTECTION RELAY PANEL 86UT1 COIL SUPERVISION UAT-1A PROTECTION RELAY PANEL 86UT2 COIL SUPERVISION
DCS DCS
P1CHC01 74UT1 P1CHC01 74UT2
P1CHC01GH001_XB62 P1CHC01GH002_XB62
UAT-1A PROTECTION RELAY PANEL LOSS OF DC POWER-1 UAT-1A PROTECTION RELAY PANEL LOSS OF DC POWER-2
DCS DCS
P1CHC01 74DC-1 P1CHC01 74DC-2
P1CHC01GH001_XB64 P1CHC01GH002_XB64
UAT-1A PROTECTION RELAY PANEL LOSS OF AC POWER
DCS
P1CHC01 74AC
P1CHC01GH001_XB65
A1 (841 x 594)
B 52L1 52L2
DS(Q3)
ES(Q38)
AIS
4-20mA LOCAL/REMOTE SELECTION SW ACSR
BUCHHOLZ ALARM UAT-1A CUR (L2) UAT-1A MDU
UAT-1A LCP DCS UAT-1A LCP DCS LOCAL CONTROLLED BY
63B
P1BBT01GH001_XB61 P1BBT01GH001_XQ12 OLTC TAP CHANGE SWITCH
& MANUALLY @ OLTC MOTOR DRIVE UNIT
UAT-1A MDU
OIL TEMP HIGH ALARM 4-20mA LOWER GSUT
UAT-1A LCP
26OA
DCS
UAT-1A LCP
UAT-1A VOLTAGE (L3-L1)
DCS B P1BAT01
P1BBT01GH001_XB62
P1BBT01GH001_XQ23
XV WINDING TEMPERATURE HIGH ALARM LOCAL/REMOTE SELECTION SW UAT-1A OLTC
UAT-1A MDU
UAT-1A LCP
26WA (XV)
DCS
UAT-1A ACTV PWR (MW)
4-20mA REMOTE ≥1 TAP CHANGING
UAT-1A LCP DCS LOWER
P1BBT01GH001_XB63
P1BBT01GH001_XQ31 GCB
YV WINDING TEMPERATURE HIGH ALARM LOCAL/REMOTE SELECTION SW P1BAC01
UAT-1A LCP DCS UAT-1A RTCC UAT-1A UAT-1B
26WA (YV) 4-20mA
P1BBT01GH001_XB64 UAT-1A RACTV PWR (MVAR) LOCAL (RTCC) P1BBT01 P1BBT02
UAT-1A LCP DCS
57GT
HV WINDING TEMPERATURE HIGH ALARM P1BBT01GH001_XQ32
UAT-1A LCP DCS &
26WA (HV)
P1BBT01GH001_XB65 UAT-1A RTCC
AUTO/MANUAL MODE & 89G
MANUAL CONTROLLED BY
OIL LEVEL (MAIN) HIGH ALARM
OLTC TAP CHANGE SWITCH
& MANUALLY @ RTCC GCB
UAT-1A LCP DCS 52G
71H (MAIN) UAT-1A RTCC 57UAT1A 57UAT1A 57UAT1B 57UAT1B
P1BBT01GH001_XB68 LOWER
-1 -2 -1 -2
OIL LEVEL (MAIN) LOW ALARM ≥1 57GG
UAT-1A LCP DCS
71L (MAIN) AUTO/MANUAL MODE 52UAT1A 52UAT1A 52UAT1B 52UAT1B
P1BBT01GH001_XB69 UAT-1A RTCC
AUTO CONTROLLED BY ≥1 -1 -2 -1 -2
OIL LEVEL (OLTC) HIGH ALARM & AUTOMATICALLY BY AVR
UAT-1A LCP DCS OLTC TAP CHANGE COMMAND
71H (OLTC) TAP CHANGE AVR G
P1BBT01GH001_XB70 LOWER
GEN P1BBA01 P1BBA02 P1BBA03 P0BBA01
OIL LEVEL (OLTC) LOW ALARM
UAT-1A LCP DCS 4-20mA P1MKA01
71L (OLTC) OIL TEMPERATURE
P1BBT01GH001_XB71 UAT-1A LCP DCS LOCAL/REMOTE SELECTION SW
AC PWR FAULT P1BBT01GH001_XQ61
UAT-1A RTCC
REMOTE (DCS)
B
UAT-1A LCP DCS NOTES
4-20mA THIS DWG. 1
P1BBT01GH001_XB72 WINDING TEMPERATURE - HV WINDING
UAT-1A LCP DCS
WTS (FO TEMP MONITOR) SYS FLT
P1BBT01GH001_XQ62 DCS
AUTO/MANUAL MODE & 1. THIS DRAWING IS APPLICABLE FOR UNIT-1 AND UNIT-2.
UAT-1A LCP DCS MANUAL CONTROLLED BY
P1BBT01GH001_XB73 4-20mA P1BBT01GH002_YB62 & MANUALLY @ PLANT DCS UNIT-1 UNIT-2 DESCRIPTION
WINDING TEMPERATURE - XV WINDING OLTC TAP CHANGE SWITCH
UAT-1A LCP DCS DCS
DC PWR FAULT LOWER
UAT-1A LCP DCS P1BBT01GH001_XQ63 P1BBT01GH002_YB63 P1BAT01 P2BAT01 GSUT
P1BBT01GH001_XB74 ≥1
4-20mA THIS DWG. 2 P1BBT01 P2BBT01 UAT-1A / UAT-2A
TAP CHANGER PWR FAULT WINDING TEMPERATURE - YV WINDING
UAT-1A LCP DCS UAT-1A LCP DCS P1BBT02 P2BBT02 UAT-1B / UAT-2B
AUTO/MANUAL MODE
P1BBT01GH001_XB75 P1BBT01GH001_XQ64 DCS
AUTO CONTROLLED BY P1BAC01 P2BAC01 GCB
FAN FAULT HV WINDING HOT SPOT PHASE U
4-20mA P1BBT01GH002_YB61 & AUTOMATICALLY BY AVR P1BBA01 P2BBA01 11KV UNIT SWGR-1
UAT-1A LCP DCS UAT-1A LCP DCS OLTC TAP CHANGE COMMAND
TAP CHANGE AVR
LOWER P1BBA02 P2BBA02 11KV UNIT SWGR-2
P1BBT01GH001_XB76 P1BBT01GH001_XQ65
SPARE FAN FAULT 4-20mA P1BBA03 P2BBA03 11KV UNIT SWGR-3
UAT-1A LCP DCS HV WINDING HOT SPOT PHASE V
UAT-1A LCP DCS P0BBA01 P0BBA02 11KV COMMON SWGR
P1BBT01GH001_XB77 LOCAL/REMOTE SELECTION SW
P1BBT01GH001_XQ66 UAT-1A MDU
FAN OVERLOAD LOCAL CONTROLLED BY
UAT-1A LCP DCS 4-20mA & 2. THE FAULT SIGNAL WILL BE TRANSFERRED TO FMS BY
HV WINDING HOT SPOT PHASE W OLTC TAP CHANGE SWITCH MANUALLY @ OLTC MOTOR DRIVE UNIT COMMUNICATION LINK (IEC 61850).
P1BBT01GH001_XB80 UAT-1A LCP DCS UAT-1A MDU
RAISE
SPARE FAN OVERLOAD P1BBT01GH001_XQ67
UAT-1A LCP DCS 3. 49UT PROTECTION FUNCTION SETS THE 50/51UT TO OPERATE
4-20mA AS AN ALARM BEFORE TRIP OPERATION.
P1BBT01GH001_XB81 XV WINDING HOT SPOT PHASE U
UAT-1A LCP DCS LOCAL/REMOTE SELECTION SW UAT-1A OLTC
UAT-1A MDU
UAT-1A LCP
FAN (GROUP A) RUNNING
DCS P1BBT01GH001_XQ68 REMOTE ≥1 TAP CHANGING
4. REFERENCE SCHEMATIC DWG.
RAISE
4-20mA VA2-YU03-P0ASR-140001 : SCHEMATIC PROTECTION RELAY PANEL
P1BBT01GH001_XB82 XV WINDING HOT SPOT PHASE V
UAT-1A LCP DCS VA2-YU03-P0BBT-140003 : SCHEMATIC UAT
FAN (GROUP B) RUNNING LOCAL/REMOTE SELECTION SW
UAT-1A LCP DCS P1BBT01GH001_XQ69 UAT-1A RTCC
LOCAL (RTCC)
P1BBT01GH001_XB84 4-20mA
XV WINDING HOT SPOT PHASE W
SPARE FAN (GROUP A) RUNNING UAT-1A LCP DCS &
UAT-1A LCP DCS
P1BBT01GH001_XQ70 UAT-1A RTCC
AUTO/MANUAL MODE &
P1BBT01GH001_XB86 MANUAL CONTROLLED BY
YV WINDING HOT SPOT PHASE U
4-20mA
OLTC TAP CHANGE SWITCH
& MANUALLY @ RTCC
SPARE FAN (GROUP B) RUNNING UAT-1A LCP DCS UAT-1A RTCC
UAT-1A LCP DCS RAISE
P1BBT01GH001_XB88 P1BBT01GH001_XQ71
≥1
LCP 3PH AC MAIN PWR FAILURE 4-20mA
UAT-1A LCP DCS YV WINDING HOT SPOT PHASE V AUTO/MANUAL MODE
UAT-1A LCP DCS UAT-1A RTCC
P1BBT01GH001_XB90 P1BBT01GH001_XQ72
AUTO CONTROLLED BY ≥1
OLTC TAP CHANGE COMMAND
& AUTOMATICALLY BY AVR
LCP 3PH AC BACK UP PWR FAILURE 4-20mA TAP CHANGE AVR
UAT-1A LCP DCS YV WINDING HOT SPOT PHASE W
UAT-1A LCP DCS RAISE
P1BBT01GH001_XB91
P1BBT01GH001_XQ73
FOR REVIEW
4-20mA
TOP OIL TEMPERATURE PHASE V LOCAL/REMOTE SELECTION SW
UAT-1A LCP DCS UAT-1A RTCC
REMOTE (DCS)
P1BBT01GH001_XQ74
4-20mA
DGA H2
UAT-1A LCP DCS
1 THIS DWG.
AUTO/MANUAL MODE &
P1BBT01GH001_XQ76 MANUAL CONTROLLED BY
OLTC TAP CHANGE SWITCH
& MANUALLY @ PLANT DCS
4-20mA DCS
DGA CO RAISE
UAT-1A LCP DCS
P1BBT01GH002_YB64
P1BBT01GH001_XQ77 ≥1
4-20mA AUTO/MANUAL MODE
DGA C2H2 2 THIS DWG.
UAT-1A LCP DCS AUTO CONTROLLED BY
P1BBT01GH001_XQ78 OLTC TAP CHANGE COMMAND
& AUTOMATICALLY BY AVR
TAP CHANGE AVR
4-20mA RAISE
DGA MOISTURE
UAT-1A LCP DCS
P1BBT01GH001_XQ79
VUNG ANG II THERMAL POWER PROJECT
UAT-1A OLTC OPERATION
UAT-1A MONITORING AND ALARM VUNG ANG II THERMAL POWER
LIMITED LIABILITY COMPANY
OLTC AVR P.T. VOLTAGE FAULT OLTC CONTROL MODE "LOCAL"
UAT-1A RTCC DCS UAT-1A RTCC DCS
P1BBT01GH002_XB62 P1BBT01GH002_XB68
OLTC AVR FAULT OLTC CONTROL MODE "REMOTE (DCS)"
UAT-1A RTCC DCS UAT-1A RTCC DCS
P1BBT01GH002_XB63 P1BBT01GH002_XB69
UAT-1A RTCC AC PWR FAILURE OLTC CONTROL MODE "AUTO"
UAT-1A RTCC DCS UAT-1A RTCC DCS
P1BBT01GH002_XB64 P1BBT01GH002_XB70
UAT-1A RTCC DC PWR FAILURE OLTC CONTROL MODE "MANUAL"
UAT-1A RTCC DCS UAT-1A RTCC DCS
P1BBT01GH002_XB65 P1BBT01GH002_XB71
OLTC TAP CHANGER IN PROGRESS
UAT-1A RTCC DCS
P1BBT01GH002_XB66 4-20mA
TAP POSITION
OLTC TAP CHANGING INCOMPLETE UAT-1A RTCC DCS
UAT-1A RTCC DCS P1BBT01GH002_XQ61
P1BBT01GH002_XB67
A1 (841 x 594)
B 52L1 52L2
PRESSURE RELIEF DEVICE TRIP - OLTC PRESSURE RELIEF DEVICE TRIP - OLTC GEN P1BBA01 P1BBA02 P1BBA03 P0BBA01
UAT-1B LCP 500KV AIS 52L1 UAT-1B LCP 500KV AIS 52L1 P1MKA01
63PRC SHEET.9 9-15 63PRC SHEET.9 9-16
X31:7-8 TRIP COIL-1 X31:7-8 TRIP COIL-1
FMS OIL TEMP HIGH HIGH TRIP B
500KV AIS 52L1 UAT-1B LCP 500KV AIS 52L1 NOTES
P1CHC02GH001_XB104 SHEET.9 9-25 26OT SHEET.9 9-26
OIL TEMP HIGH HIGH TRIP TRIP COIL-2 X31:9-10 TRIP COIL-2
UAT-1B LCP
26OT WINDING TEMPERATURE TRIP - HV WINDING
X31:9-10 UAT-1B LCP 1. THIS DRAWING IS APPLICABLE FOR UNIT-1 AND UNIT-2.
FMS 500KV AIS 52L1 26WTHV 500KV AIS 52L1
SHEET.9 9-35 X31:11-12 SHEET.9 9-36
50BF INITIATE-1(IF REQUIRED) 50BF INITIATE-1(IF REQUIRED)
P1CHC02GH001_XB105 UNIT-1 UNIT-2 DESCRIPTION
WINDING TEMPERATURE TRIP - HV WINDING WINDING TEMPERATURE TRIP - LV-X WINDING
UAT-1B LCP 500KV AIS 52L1 UAT-1B LCP 500KV AIS 52L1
26WTHV SHEET.9 9-45 26WTLV-X SHEET.9 9-46 P1BAT01 P2BAT01 GSUT
X31:11-12 50BF INITIATE-2(IF REQUIRED) X31:13-14 50BF INITIATE-2(IF REQUIRED)
FMS BUCHHOLZ TRIP P1BBT01 P2BBT01 UAT-1A / UAT-2A
500KV AIS 52L2 UAT-1B LCP 500KV AIS 52L2
P1CHC02GH001_XB106 SHEET.10 10-15 63B SHEET.10 10-16
WINDING TEMPERATURE TRIP - LV-X WINDING TRIP COIL-1 X31:15-16 TRIP COIL-1 P1BBT02 P2BBT02 UAT-1B / UAT-2B
UAT-1B LCP
26WTLV-X OLTC PROTECTIVE RELAY TRIP P1BAC01 P2BAC01 GCB
X31:13-14 UAT-1B LCP
FMS 500KV AIS 52L2 63OP 500KV AIS 52L2
SHEET.10 10-25 X32:1-2 SHEET.10 10-26 P1BBA01 P2BBA01 11KV UNIT SWGR-1
TRIP COIL-2 TRIP COIL-2
P1CHC02GH001_XB107
BUCHHOLZ TRIP SUDDEN PRESSURE TRIP P1BBA02 P2BBA02 11KV UNIT SWGR-2
UAT-1B LCP 500KV AIS 52L2 UAT-1B LCP 500KV AIS 52L2
63B SHEET.10 10-35 63S SHEET.10 10-36 P1BBA03 P2BBA03 11KV UNIT SWGR-3
X31:15-16 50BF INITIATE-1(IF REQUIRED) X32:3-4 50BF INITIATE-1(IF REQUIRED)
FMS PRESSURE RELIEF DEVICE TRIP - MAIN TANK P0BBA01 P0BBA02 11KV COMMON SWGR
500KV AIS 52L2 UAT-1B LCP 500KV AIS 52L2
P1CHC02GH001_XB108 SHEET.10 10-45 63PR SHEET.10 10-46
OLTC PROTECTIVE RELAY TRIP 50BF INITIATE-2(IF REQUIRED) X32:5-6 50BF INITIATE-2(IF REQUIRED)
UAT-1B LCP 2. THE FAULT SIGNAL WILL BE TRANSFERRED TO FMS BY
63OP WINDING TEMPERATURE TRIP - LV-X WINDING
X32:1-2 UAT-1B LCP COMMUNICATION LINK (IEC 61850).
FMS P1BAC01 GCB 26WTLV-Y P1BAC01 GCB
SHEET.11 11-15 X32:7-8 SHEET.11 11-16
TRIP COIL-1 TRIP COIL-1
P1CHC02GH001_XB109 3. 49UT PROTECTION FUNCTION SETS THE 50/51UT TO OPERATE
SUDDEN PRESSURE TRIP
UAT-1B LCP P1BAC01 GCB P1BAC01 GCB AS AN ALARM BEFORE TRIP OPERATION.
63S SHEET.11 11-25 SHEET.11 11-26
X32:3-4 TRIP COIL-2 TRIP COIL-2
FMS 4. REFERENCE SCHEMATIC DWG.
P1CHC02GH001_XB110 EXTERNAL TRIP INPUT EXTERNAL TRIP INPUT VA2-YU03-P0ASR-140001 : SCHEMATIC PROTECTION RELAY PANEL
PRESSURE RELIEF DEVICE TRIP - MAIN TANK SHEET.12 12-5 SHEET.12 12-6 VA2-YU03-P0BBT-140003 : SCHEMATIC UAT
UAT-1B LCP TO STG GPR-A TO STG GPR-A
63PR
X32:5-6
FMS EXTERNAL TRIP INPUT EXTERNAL TRIP INPUT
SHEET.12 12-15 SHEET.12 12-16
TO STG GPR-B TO STG GPR-B
P1CHC02GH001_XB111
WINDING TEMPERATURE TRIP - LV-X WINDING UAT-1B PROTECTION RELAY PANEL ALARM RESET
UAT-1B LCP STG EXCITATION FCB 41E STG EXCITATION FCB 41E
26WTLV-Y SHEET.12 12-25 P1CHC02 SHEET.12 12-26
X32:7-8 TRIP COIL-1 X31:1-2 TRIP COIL-1
FMS
P1CHC02GH001_XB111 STG EXCITATION FCB 41E STG EXCITATION FCB 41E
SHEET.12 12-35 UAT-1B PROTECTION RELAY PANEL 86UT2 COIL SUPERVISION SHEET.12 12-36
TRIP COIL-2 FMS TRIP COIL-2
P1CHC02 74UT2
X31:5-6 P1CHC02GH002_XB103
STG D-EHC STG D-EHC
SHEET.12 12-45 SHEET.12 12-46
TURBINE TRIP-1 (2 OUT OF 3) TURBINE TRIP-1 (2 OUT OF 3)
UAT-1B PROTECTION RELAY PANEL ALARM RESET STG D-EHC STG D-EHC
FMS SHEET.12 12-55 SHEET.12 12-56
P1CHC02 TURBINE TRIP-2 (2 OUT OF 3) TURBINE TRIP-2 (2 OUT OF 3)
X31:1-2 P1CHC02GH001_XB101
FOR REVIEW
STG D-EHC STG D-EHC
SHEET.12 12-65 SHEET.12 12-66
UAT-1B PROTECTION RELAY PANEL 86UT1 COIL SUPERVISION TURBINE TRIP-3 (2 OUT OF 3) TURBINE TRIP-3 (2 OUT OF 3)
FMS
P1CHC02 74UT1
X31:5-6 P1CHC02GH001_XB103 P1BBA01 SWGR INCOMER P1BBA01 SWGR INCOMER
SHEET.13 13-15 SHEET.13 13-16
TRIP COIL-1 TRIP COIL-1
P0BBA01 SWGR INCOMER P0BBA01 SWGR INCOMER VUNG ANG II THERMAL POWER
SHEET.14 14-25 SHEET.14 14-26
TRIP COIL-2 TRIP COIL-2 LIMITED LIABILITY COMPANY
UAT-1B PROTECTON PROTECTION ACTIVATED P0BBA01 SWGR HSBT UAT-1B PROTECTON PROTECTION ACTIVATED P0BBA01 SWGR HSBT
SHEET.14 14-35 SHEET.14 14-36
RELAY-A EXCEPT THE FUNCTIONS FAST TRANSFER INITIATION RELAY-B EXCEPT THE FUNCTIONS FAST TRANSFER INITIATION
51UT, 50/51TN-UT-X & Y X41:5-4 51UT, 50/51TN-UT-X & Y X41:5-4
UAT-1B PROTECTION RELAY PANEL 86UT1 COIL SUPERVISION UAT-1B PROTECTION RELAY PANEL 86UT2 COIL SUPERVISION
DCS DCS
P1CHC02 74UT1 P1CHC02 74UT2
P1CHC02GH001_XB62 P1CHC02GH002_XB62
UAT-1B PROTECTION RELAY PANEL LOSS OF DC POWER-1 UAT-1B PROTECTION RELAY PANEL LOSS OF DC POWER-2
DCS DCS
P1CHC02 74DC-1 P1CHC02 74DC-2
P1CHC02GH001_XB64 P1CHC02GH002_XB64
UAT-1B PROTECTION RELAY PANEL LOSS OF AC POWER
DCS
P1CHC02 74AC
P1CHC02GH001_XB65
A1 (841 x 594)
B 52L1 52L2
DS(Q3)
ES(Q38)
AIS
4-20mA LOCAL/REMOTE SELECTION SW ACSR
BUCHHOLZ ALARM UAT-1B CUR (L2) UAT-1B MDU
UAT-1B LCP DCS UAT-1B LCP DCS LOCAL CONTROLLED BY
63B
P1BBT02GH001_XB61 P1BBT02GH001_XQ12 OLTC TAP CHANGE SWITCH
& MANUALLY @ OLTC MOTOR DRIVE UNIT
UAT-1B MDU
OIL TEMP HIGH ALARM 4-20mA LOWER GSUT
UAT-1B LCP
26OA
DCS
UAT-1B LCP
UAT-1B VOLTAGE (L3-L1)
DCS B P1BAT01
P1BBT02GH001_XB62
P1BBT02GH001_XQ23
XV WINDING TEMPERATURE HIGH ALARM LOCAL/REMOTE SELECTION SW UAT-1B OLTC
UAT-1B MDU
UAT-1B LCP
26WA (XV)
DCS
UAT-1B ACTV PWR (MW)
4-20mA REMOTE ≥1 TAP CHANGING
UAT-1B LCP DCS LOWER
P1BBT02GH001_XB63
P1BBT02GH001_XQ31 GCB
YV WINDING TEMPERATURE HIGH ALARM LOCAL/REMOTE SELECTION SW P1BAC01
UAT-1B LCP DCS UAT-1B RTCC UAT-1A UAT-1B
26WA (YV) 4-20mA
P1BBT02GH001_XB64 UAT-1B RACTV PWR (MVAR) LOCAL (RTCC) P1BBT01 P1BBT02
UAT-1B LCP DCS
57GT
HV WINDING TEMPERATURE HIGH ALARM P1BBT02GH001_XQ32
UAT-1B LCP DCS &
26WA (HV)
P1BBT02GH001_XB65 UAT-1B RTCC
AUTO/MANUAL MODE & 89G
MANUAL CONTROLLED BY
OIL LEVEL (MAIN) HIGH ALARM
OLTC TAP CHANGE SWITCH
& MANUALLY @ RTCC GCB
UAT-1B LCP DCS 52G
71H (MAIN) UAT-1B RTCC 57UAT1A 57UAT1A 57UAT1B 57UAT1B
P1BBT02GH001_XB68 LOWER
-1 -2 -1 -2
OIL LEVEL (MAIN) LOW ALARM ≥1 57GG
UAT-1B LCP DCS
71L (MAIN) AUTO/MANUAL MODE 52UAT1A 52UAT1A 52UAT1B 52UAT1B
P1BBT02GH001_XB69 UAT-1B RTCC
AUTO CONTROLLED BY ≥1 -1 -2 -1 -2
OIL LEVEL (OLTC) HIGH ALARM & AUTOMATICALLY BY AVR
UAT-1B LCP DCS OLTC TAP CHANGE COMMAND
71H (OLTC) TAP CHANGE AVR G
P1BBT02GH001_XB70 LOWER
GEN P1BBA01 P1BBA02 P1BBA03 P0BBA01
OIL LEVEL (OLTC) LOW ALARM
UAT-1B LCP DCS 4-20mA P1MKA01
71L (OLTC) OIL TEMPERATURE
P1BBT02GH001_XB71 UAT-1B LCP DCS LOCAL/REMOTE SELECTION SW
AC PWR FAULT P1BBT02GH001_XQ61
UAT-1B RTCC
REMOTE (DCS)
B
UAT-1B LCP DCS NOTES
4-20mA THIS DWG. 1
P1BBT02GH001_XB72 WINDING TEMPERATURE - HV WINDING
UAT-1B LCP DCS
WTS (FO TEMP MONITOR) SYS FLT
P1BBT02GH001_XQ62 DCS
AUTO/MANUAL MODE & 1. THIS DRAWING IS APPLICABLE FOR UNIT-1 AND UNIT-2.
UAT-1B LCP DCS MANUAL CONTROLLED BY
P1BBT02GH001_XB73 4-20mA P1BBT02GH002_YB62 & MANUALLY @ PLANT DCS UNIT-1 UNIT-2 DESCRIPTION
WINDING TEMPERATURE - XV WINDING OLTC TAP CHANGE SWITCH
UAT-1B LCP DCS DCS
DC PWR FAULT LOWER
UAT-1B LCP DCS P1BBT02GH001_XQ63 P1BBT02GH002_YB63 P1BAT01 P2BAT01 GSUT
P1BBT02GH001_XB74 ≥1
4-20mA THIS DWG. 2 P1BBT01 P2BBT01 UAT-1A / UAT-2A
TAP CHANGER PWR FAULT WINDING TEMPERATURE - YV WINDING
UAT-1B LCP DCS UAT-1B LCP DCS P1BBT02 P2BBT02 UAT-1B / UAT-2B
AUTO/MANUAL MODE
P1BBT02GH001_XB75 P1BBT02GH001_XQ64 DCS
AUTO CONTROLLED BY P1BAC01 P2BAC01 GCB
FAN FAULT HV WINDING HOT SPOT PHASE U
4-20mA P1BBT02GH002_YB61 & AUTOMATICALLY BY AVR P1BBA01 P2BBA01 11KV UNIT SWGR-1
UAT-1B LCP DCS UAT-1B LCP DCS OLTC TAP CHANGE COMMAND
TAP CHANGE AVR
LOWER P1BBA02 P2BBA02 11KV UNIT SWGR-2
P1BBT02GH001_XB76 P1BBT02GH001_XQ65
SPARE FAN FAULT 4-20mA P1BBA03 P2BBA03 11KV UNIT SWGR-3
UAT-1B LCP DCS HV WINDING HOT SPOT PHASE V
UAT-1B LCP DCS P0BBA01 P0BBA02 11KV COMMON SWGR
P1BBT02GH001_XB77 LOCAL/REMOTE SELECTION SW
P1BBT02GH001_XQ66 UAT-1B MDU
FAN OVERLOAD LOCAL CONTROLLED BY
UAT-1B LCP DCS 4-20mA & 2. THE FAULT SIGNAL WILL BE TRANSFERRED TO FMS BY
HV WINDING HOT SPOT PHASE W OLTC TAP CHANGE SWITCH MANUALLY @ OLTC MOTOR DRIVE UNIT COMMUNICATION LINK (IEC 61850).
P1BBT02GH001_XB80 UAT-1B LCP DCS UAT-1B MDU
RAISE
SPARE FAN OVERLOAD P1BBT02GH001_XQ67
UAT-1B LCP DCS 3. 49UT PROTECTION FUNCTION SETS THE 50/51UT TO OPERATE
4-20mA AS AN ALARM BEFORE TRIP OPERATION.
P1BBT02GH001_XB81 XV WINDING HOT SPOT PHASE U
UAT-1B LCP DCS LOCAL/REMOTE SELECTION SW UAT-1B OLTC
UAT-1B MDU
UAT-1B LCP
FAN (GROUP A) RUNNING
DCS P1BBT02GH001_XQ68 REMOTE ≥1 TAP CHANGING
4. REFERENCE SCHEMATIC DWG.
RAISE
4-20mA VA2-YU03-P0ASR-140001 : SCHEMATIC PROTECTION RELAY PANEL
P1BBT02GH001_XB82 XV WINDING HOT SPOT PHASE V
UAT-1B LCP DCS VA2-YU03-P0BBT-140003 : SCHEMATIC UAT
FAN (GROUP B) RUNNING LOCAL/REMOTE SELECTION SW
UAT-1B LCP DCS P1BBT02GH001_XQ69 UAT-1B RTCC
LOCAL (RTCC)
P1BBT02GH001_XB84 4-20mA
XV WINDING HOT SPOT PHASE W
SPARE FAN (GROUP A) RUNNING UAT-1B LCP DCS &
UAT-1B LCP DCS
P1BBT02GH001_XQ70 UAT-1B RTCC
AUTO/MANUAL MODE &
P1BBT02GH001_XB86 MANUAL CONTROLLED BY
YV WINDING HOT SPOT PHASE U
4-20mA
OLTC TAP CHANGE SWITCH
& MANUALLY @ RTCC
SPARE FAN (GROUP B) RUNNING UAT-1B LCP DCS UAT-1B RTCC
UAT-1B LCP DCS RAISE
P1BBT02GH001_XB88 P1BBT02GH001_XQ71
≥1
LCP 3PH AC MAIN PWR FAILURE 4-20mA
UAT-1B LCP DCS YV WINDING HOT SPOT PHASE V AUTO/MANUAL MODE
UAT-1B LCP DCS UAT-1B RTCC
P1BBT02GH001_XB90 P1BBT02GH001_XQ72
AUTO CONTROLLED BY ≥1
OLTC TAP CHANGE COMMAND
& AUTOMATICALLY BY AVR
LCP 3PH AC BACK UP PWR FAILURE 4-20mA TAP CHANGE AVR
UAT-1B LCP DCS YV WINDING HOT SPOT PHASE W
UAT-1B LCP DCS RAISE
P1BBT02GH001_XB91
P1BBT02GH001_XQ73
FOR REVIEW
4-20mA
TOP OIL TEMPERATURE PHASE V LOCAL/REMOTE SELECTION SW
UAT-1B LCP DCS UAT-1B RTCC
REMOTE (DCS)
P1BBT02GH001_XQ74
4-20mA
DGA H2
UAT-1B LCP DCS
1 THIS DWG.
AUTO/MANUAL MODE &
P1BBT02GH001_XQ76 MANUAL CONTROLLED BY
OLTC TAP CHANGE SWITCH
& MANUALLY @ PLANT DCS
4-20mA DCS
DGA CO RAISE
UAT-1B LCP DCS
P1BBT02GH002_YB64
P1BBT02GH001_XQ77 ≥1
4-20mA AUTO/MANUAL MODE
DGA C2H2 2 THIS DWG.
UAT-1B LCP DCS AUTO CONTROLLED BY
P1BBT02GH001_XQ78 OLTC TAP CHANGE COMMAND
& AUTOMATICALLY BY AVR
TAP CHANGE AVR
4-20mA RAISE
DGA MOISTURE
UAT-1B LCP DCS
P1BBT02GH001_XQ79
VUNG ANG II THERMAL POWER PROJECT
UAT-1B OLTC OPERATION
UAT-1B MONITORING AND ALARM VUNG ANG II THERMAL POWER
LIMITED LIABILITY COMPANY
OLTC AVR P.T. VOLTAGE FAULT OLTC CONTROL MODE "LOCAL"
UAT-1B RTCC DCS UAT-1B RTCC DCS
P1BBT02GH002_XB62 P1BBT02GH002_XB68
OLTC AVR FAULT OLTC CONTROL MODE "REMOTE (DCS)"
UAT-1B RTCC DCS UAT-1B RTCC DCS
P1BBT02GH002_XB63 P1BBT02GH002_XB69
UAT-1B RTCC AC PWR FAILURE OLTC CONTROL MODE "AUTO"
UAT-1B RTCC DCS UAT-1B RTCC DCS
P1BBT02GH002_XB64 P1BBT02GH002_XB70
UAT-1B RTCC DC PWR FAILURE OLTC CONTROL MODE "MANUAL"
UAT-1B RTCC DCS UAT-1B RTCC DCS
P1BBT02GH002_XB65 P1BBT02GH002_XB71
OLTC TAP CHANGER IN PROGRESS
UAT-1B RTCC DCS
P1BBT02GH002_XB66 4-20mA
TAP POSITION
OLTC TAP CHANGING INCOMPLETE UAT-1B RTCC DCS
UAT-1B RTCC DCS P1BBT02GH002_XQ61
P1BBT02GH002_XB67
A1 (841 x 594)
B
B 52L1 52L2
B
500KV AIS 52L1 NOTES
SHEET.9 9-17
TRIP COIL-1
1. THIS DRAWING IS APPLICABLE FOR UNIT-1 AND UNIT-2.
500KV AIS 52L1
SHEET.9 9-27
TRIP COIL-2
UNIT-1 UNIT-2 DESCRIPTION
500KV AIS 52L1
SHEET.9 9-37 P1BAT01 P2BAT01 GSUT
50BF INITIATE-1(IF REQUIRED)
P1BBT01 P2BBT01 UAT-1A / UAT-2A
500KV AIS 52L1
SHEET.9 9-47 P1BBT02 P2BBT02 UAT-1B / UAT-2B
50BF INITIATE-2(IF REQUIRED)
P1BAC01 P2BAC01 GCB
500KV AIS 52L2
SHEET.10 10-17 P1BBA01 P2BBA01 11KV UNIT SWGR-1
TRIP COIL-1
P1BBA02 P2BBA02 11KV UNIT SWGR-2
500KV AIS 52L2
SHEET.10 10-27 P1BBA03 P2BBA03 11KV UNIT SWGR-3
TRIP COIL-2
P0BBA01 P0BBA02 11KV COMMON SWGR
500KV AIS 52L2
SHEET.10 10-37
50BF INITIATE-1(IF REQUIRED) 2. THE FAULT SIGNAL WILL BE TRANSFERRED TO FMS BY
COMMUNICATION LINK (IEC 61850).
500KV AIS 52L2
SHEET.10 10-47
50BF INITIATE-2(IF REQUIRED) 3. REFERENCE SCHEMATIC DWG.
VA2-YU03-P0ASR-140001 : SCHEMATIC PROTECTION RELAY PANEL
P1BAC01 GCB
SHEET.11 11-17
TRIP COIL-1
P1BAC01 GCB
SHEET.11 11-27
TRIP COIL-2
STG D-EHC
SHEET.12 12-67
TURBINE TRIP-3 (2 OUT OF 3)
OVERALL PROTECTION
A1 (841 x 594)
B
B 52L1 52L2
DS(Q3)
500KV AIS 52L1
STG GCP ES(Q38)
SYNCHRONIZED CLOSE COMMAND
AIS
B
500KV AIS 52L1 500KV AIS 52L1 NOTES
STG GCP STG GCP
OPEN COMMAND OPEN COMMAND
1. THIS DRAWING IS APPLICABLE FOR UNIT-1 AND UNIT-2.
86GT1 OPERATED 86GT1 OPERATED
9-11 SHEET.2 9-21 SHEET.2
UNIT-1 UNIT-2 DESCRIPTION
86GT2 OPERATED 86GT2 OPERATED
9-12 SHEET.2 9-22 SHEET.2
P1BAT01 P2BAT01 GSUT
86UT1(1A) OPERATED 86UT1(1A) OPERATED P1BBT01 P2BBT01 UAT-1A / UAT-2A
9-13 SHEET.3 9-23 SHEET.3
500KV AIS 52L1 500KV AIS 52L1
≥1 TRIP COIL-1 AIS INTERFACE PANEL ≥1 TRIP COIL-2 AIS INTERFACE PANEL P1BBT02 P2BBT02 UAT-1B / UAT-2B
86UT2(1A) OPERATED SUPPLIED BY PACIFIC 86UT2(1A) OPERATED SUPPLIED BY PACIFIC
9-14 SHEET.3 * SEE NOTE.3 9-24 SHEET.3 * SEE NOTE.3 P1BAC01 P2BAC01 GCB
86G3-A OR 86G4-A OR 86G3-B OR 86G4-B 86G3-A OR 86G4-A OR 86G3-B OR 86G4-B 3. THE RELEVANT SIGNALS ARE COMBINED IN THE OVERALL
STG GPR STG GPR PROTECTION PANEL AND THEN TRANSFERRED VIA HARDWIRED
OPERATED OPERATED
CONNECTION.
BREAKER FAILURE OR ARC PROTECTION BREAKER FAILURE OR ARC PROTECTION
P1BBA01 MV SWGR P1BBA01 MV SWGR
OPERATED OPERATED 4. REFERENCE SCHEMATIC DWG.
BREAKER FAILURE OR ARC PROTECTION BREAKER FAILURE OR ARC PROTECTION VA2-YU03-P0ASR-140001 : SCHEMATIC PROTECTION RELAY PANEL
P1BBA02 MV SWGR P1BBA02 MV SWGR VA2-YU03-P0AB-150003 : SCHEMATIC 500KV AIS CONTROL PROT.
OPERATED OPERATED
& METERING SYSTEM
BREAKER FAILURE OR ARC PROTECTION BREAKER FAILURE OR ARC PROTECTION
P1BBA03 MV SWGR P1BBA03 MV SWGR
OPERATED OPERATED
BREAKER FAILURE OR ARC PROTECTION BREAKER FAILURE OR ARC PROTECTION
P0BBA01 MV SWGR P0BBA01 MV SWGR
OPERATED OPERATED
FOR REVIEW
A1 (841 x 594)
B
B 52L1 52L2
DS(Q3)
500KV AIS 52L1
STG GCP ES(Q38)
SYNCHRONIZED CLOSE COMMAND
AIS
B
500KV AIS 52L1 500KV AIS 52L1 NOTES
STG GCP STG GCP
OPEN COMMAND OPEN COMMAND
1. THIS DRAWING IS APPLICABLE FOR UNIT-1 AND UNIT-2.
86GT1 OPERATED 86GT1 OPERATED
10-11 SHEET.2 10-21 SHEET.2
UNIT-1 UNIT-2 DESCRIPTION
86GT2 OPERATED 86GT2 OPERATED
10-12 SHEET.2 10-22 SHEET.2
P1BAT01 P2BAT01 GSUT
86UT1(1A) OPERATED 86UT1(1A) OPERATED P1BBT01 P2BBT01 UAT-1A / UAT-2A
10-13 SHEET.3 10-23 SHEET.3
500KV AIS 52L2 500KV AIS 52L2
≥1 TRIP COIL-1 AIS INTERFACE PANEL ≥1 TRIP COIL-2 AIS INTERFACE PANEL P1BBT02 P2BBT02 UAT-1B / UAT-2B
86UT2(1A) OPERATED SUPPLIED BY PACIFIC 86UT2(1A) OPERATED SUPPLIED BY PACIFIC
10-14 SHEET.3 * SEE NOTE.3 10-24 SHEET.3 * SEE NOTE.3 P1BAC01 P2BAC01 GCB
86G3-A OR 86G4-A OR 86G3-B OR 86G4-B 86G3-A OR 86G4-A OR 86G3-B OR 86G4-B 3. THE RELEVANT SIGNALS ARE COMBINED IN THE OVERALL
STG GPR STG GPR PROTECTION PANEL AND THEN TRANSFERRED VIA HARDWIRED
OPERATED OPERATED
CONNECTION.
BREAKER FAILURE OR ARC PROTECTION BREAKER FAILURE OR ARC PROTECTION
P1BBA01 MV SWGR P1BBA01 MV SWGR
OPERATED OPERATED 4. REFERENCE SCHEMATIC DWG.
BREAKER FAILURE OR ARC PROTECTION BREAKER FAILURE OR ARC PROTECTION VA2-YU03-P0ASR-140001 : SCHEMATIC PROTECTION RELAY PANEL
P1BBA02 MV SWGR P1BBA02 MV SWGR VA2-YU03-P0AB-150003 : SCHEMATIC 500KV AIS CONTROL PROT.
OPERATED OPERATED
& METERING SYSTEM
BREAKER FAILURE OR ARC PROTECTION BREAKER FAILURE OR ARC PROTECTION
P1BBA03 MV SWGR P1BBA03 MV SWGR
OPERATED OPERATED
BREAKER FAILURE OR ARC PROTECTION BREAKER FAILURE OR ARC PROTECTION
P0BBA01 MV SWGR P0BBA01 MV SWGR
OPERATED OPERATED
FOR REVIEW
A1 (841 x 594)
B
B 52L1 52L2
DS(Q3)
ES(Q38)
AIS
G
GEN P1BBA01 P1BBA02 P1BBA03 P0BBA01
P1MKA01
B
NOTES
LINE PROTECTION OPERATED LINE PROTECTION OPERATED 3. THE RELEVANT SIGNALS ARE COMBINED IN THE OVERALL
LINE PRP LINE PRP
(BY PACIFIC) (BY PACIFIC) PROTECTION PANEL AND THEN TRANSFERRED VIA HARDWIRED
CONNECTION.
FOR REVIEW
A1 (841 x 594)
B
B 52L1 52L2
89G
LINE PRP
LINE PROTECTION OPERATED
LINE PRP
LINE PROTECTION OPERATED B
(BY PACIFIC) (BY PACIFIC) NOTES
FOR REVIEW
A1 (841 x 594)
B
B 52L1 52L2
DS(Q3)
86GT1 NOT OPERATED 86GT1 OPERATED 86GT1 OPERATED ES(Q38)
13-1 SHEET.2 13-11 SHEET.2 13-21 SHEET.2 AIS
86GT2 NOT OPERATED 86GT2 OPERATED 86GT2 OPERATED ACSR
13-2 SHEET.2 13-12 SHEET.2 13-22 SHEET.2
86UT1(1A) NOT OPERATED P1BBA01 SWGR 86UT1(1A) OPERATED P1BBA01 SWGR 86UT1(1A) OPERATED P1BBA01 SWGR
13-3 SHEET.3 13-13 SHEET.3 13-23 SHEET.3
SWGR INCOMER SWGR INCOMER SWGR INCOMER
& CLOSE PERMISSIVE P1BBA01 MV SWGR ≥1 TRIP COIL-1 P1BBA01 MV SWGR
≥1 TRIP COIL-2 P1BBA01 MV SWGR GSUT
86UT2(1A) NOT OPERATED 86UT2(1A) OPERATED 86UT2(1A) OPERATED P1BAT01
13-4 SHEET.3 * SEE NOTE.3 13-14 SHEET.3 * SEE NOTE.3 13-24 SHEET.3 * SEE NOTE.3
86UT1(1B) NOT OPERATED 86UT1(1B) OPERATED 86UT1(1B) OPERATED
13-5 SHEET.4 13-15 SHEET.4 13-25 SHEET.4
86UT2(1B) NOT OPERATED 86UT2(1B) OPERATED GCB
13-6 SHEET.4 13-16 SHEET.4 86UT2(1B) OPERATED
13-26 SHEET.4 P1BAC01 UAT-1A UAT-1B
86OA NOT OPERATED 86OA OPERATED P1BBT01 P1BBT02
13-7 SHEET.5 13-17 SHEET.5 86OA OPERATED 57GT
13-27 SHEET.5
89G
LINE PROTECTION OPERATED
LINE PRP
(BY PACIFIC)
INTERFACE BETWEEN TRANSFORMER PROTECTION AND P1BBA01 MV SWGR GCB
52G
57UAT1A 57UAT1A 57UAT1B 57UAT1B
-1 -2 -1 -2
57GG
52UAT1A 52UAT1A 52UAT1B 52UAT1B
-1 -2 -1 -2
G
GEN P1BBA01 P1BBA02 P1BBA03 P0BBA01
P1MKA01
B
86GT1 NOT OPERATED 86GT1 OPERATED 86GT1 OPERATED NOTES
13-31 SHEET.2 13-41 SHEET.2 13-51 SHEET.2
86GT2 NOT OPERATED 86GT2 OPERATED 86GT2 OPERATED 1. THIS DRAWING IS APPLICABLE FOR UNIT-1 AND UNIT-2.
13-32 SHEET.2 13-42 SHEET.2 13-52 SHEET.2
86UT1(1A) NOT OPERATED P1BBA02 SWGR 86UT1(1A) OPERATED P1BBA02 SWGR UNIT-1 UNIT-2 DESCRIPTION
13-33 SHEET.3 13-43 SHEET.3 86UT1(1A) OPERATED P1BBA02 SWGR
SWGR INCOMER SWGR INCOMER 13-53 SHEET.3
& CLOSE PERMISSIVE P1BBA02 MV SWGR ≥1 TRIP COIL-1 P1BBA02 MV SWGR SWGR INCOMER P1BAT01 P2BAT01 GSUT
86UT2(1A) NOT OPERATED 86UT2(1A) OPERATED ≥1 TRIP COIL-2 P1BBA02 MV SWGR
13-34 SHEET.3 13-44 SHEET.3 86UT2(1A) OPERATED P1BBT01 P2BBT01 UAT-1A / UAT-2A
* SEE NOTE.3 * SEE NOTE.3 13-54 SHEET.3 * SEE NOTE.3
86UT1(1B) NOT OPERATED 86UT1(1B) OPERATED P1BBT02 P2BBT02 UAT-1B / UAT-2B
13-35 SHEET.4 13-45 SHEET.4 86UT1(1B) OPERATED
13-55 SHEET.4 P1BAC01 P2BAC01 GCB
86UT2(1B) NOT OPERATED 86UT2(1B) OPERATED 86UT2(1B) OPERATED P1BBA01 P2BBA01 11KV UNIT SWGR-1
13-36 SHEET.4 13-46 SHEET.4 13-56 SHEET.4
P1BBA02 P2BBA02 11KV UNIT SWGR-2
86OA NOT OPERATED 86OA OPERATED 86OA OPERATED
13-37 SHEET.5 13-47 SHEET.5 13-57 SHEET.5 P1BBA03 P2BBA03 11KV UNIT SWGR-3
P0BBA01 P0BBA02 11KV COMMON SWGR
LINE PROTECTION OPERATED
LINE PRP
(BY PACIFIC)
INTERFACE BETWEEN TRANSFORMER PROTECTION AND P1BBA02 MV SWGR 2. THE FAULT SIGNAL WILL BE TRANSFERRED TO FMS BY
COMMUNICATION LINK (IEC 61850).
A1 (841 x 594)
B
B 52L1 52L2
DS(Q3)
14-35 SHEET.4
UAT-1B PROTECTION-A B
ACTIVATED NOTES
UAT-1B PROTECTION-B
14-36 SHEET.4
ACTIVATED 1. THIS DRAWING IS APPLICABLE FOR UNIT-1 AND UNIT-2.
OVERALL PROTECTION
14-37 SHEET.5
ACTIVATED UNIT-1 UNIT-2 DESCRIPTION
FOR REVIEW
A1 (841 x 594)
B
B 52L1 52L2
DS(Q3)
ES(Q38)
AIS
ACSR
VA II POWER PLANT OVERALL TRIP MATRIX DIAGRAM
VA II POWER PLANT 500KV AIS GSUT
COMMON P1BAT01
MASTER EXTERNAL
PROTECTION GCB 11KV CB 11KV CB 11KV CB 11KV CB 500KV AIS CB-1 500KV AIS CB-2 DCS MV SWGR
RELAY TRIP 41E TURB FMS TRIP
FUNCTION (52G) (52UAT1A-1) (52UAT1A-2) (52UAT1B-1) (52UAT1B-2) (52L1) (52L2) /TCS HSBT
LOCK-OUT RELAY TO GPR-A/B
INITIATE
TC1 TC2 IBF B/C TC1 TC2 B/C TC1 TC2 B/C TC1 TC2 B/C TC1 TC2 B/C TRIP TRIP TC1 TC2 IBF B/C TC1 TC2 IBF B/C
GENERATOR 27TN, 32-2, 40-1, 40-2, GCB
PROTECTION RELAY-A/B 46-2, 49G, 50G-2, 50/27, P1BAC01 UAT-1A UAT-1B
(G60-A/B) 59N, 81U-3, 87G P1BBT01 P1BBT02
EXCITATION TRANSFORMER 57GT
PROTECTION RELAY-A/B 87ET, 50/51ET
89G
(T60-A/B)
86G1-A GCB
EXCITATION AVR 86E (AVR FAILURE) X X X X X X X X
86G1-B 52G
57UAT1A 57UAT1A 57UAT1B 57UAT1B
EXCITATION TRANSFORMER WINDING TEMP TRIP -1 -2 -1 -2
57GG
ROTOR 52UAT1A 52UAT1A 52UAT1B 52UAT1B
64F-2
PROTECTION
(SEE NOTE.3)
GENERATOR
86GT1
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
GSUT 63PRC, 63B, 63OP, 86GT2 2. REFERENCE DWG.
GSUT
UAT
PROTECTION RELAY-A/B 49UT X X
(RET 670-A/B)
UAT
PROTECTION RELAY-A/B 49UT X X
(RET 670-A/B)
PROTECTION
OVERALL
OVERALL
PROTECTION RELAY 87OA 86OA X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
(RET 670)
VUNG ANG II THERMAL POWER PROJECT
PROTECTION
11KV CB'S
MV SWGR
A1 (841 x 594)
B
B 52L1 52L2
DS(Q3)
ES(Q38)
AIS
ACSR
GSUT
P1BAT01
89G
500KV AIS VA II TPP
GCB
GSUT GEN MV MV MV MV MV MV MV MV 52G
LINE DS LINE ES GEN DS GCB GEN FCB 57UAT1A 57UAT1A 57UAT1B 57UAT1B
(Q3) (Q38) SIDE ES (89G) (52G) SIDE ES (41E) INCOMER ES INCOMER CB INCOMER ES INCOMER CB INCOMER ES INCOMER CB INCOMER ES INCOMER CB -1 -2 -1 -2
(57GT) (57GG) (57UAT1A-1) (52UAT1A-1) (57UAT1A-2) (52UAT1A-2) (57UAT1B-1) (52UAT1B-1) (57UAT1B-2) (52UAT1B-2) 57GG
52UAT1A 52UAT1A 52UAT1B 52UAT1B
500KV AIS
LINE DS (Q3) -1 -2 -1 -2
G
LINE ES (Q38) GEN P1BBA01 P1BBA02 P1BBA03 P0BBA01
P1MKA01
GEN DS (89G)
1. THIS DRAWING IS APPLICABLE FOR UNIT-1 AND UNIT-2.
PRECONDITIONS FOR OPERATING OF EQUIPMENT
MV INCOMER ES
(57UAT1A-2) 2. REFERENCE DWG.
VA2-YU02-P1BAY-145001 : OVERALL PROTECTION & METERING
MV INCOMER CB TEST OR TEST OR TEST OR TEST OR TEST OR TEST OR SINGLE LINE DIAGEAM
(52UAT1A-2) EXTRACTED EXTRACTED EXTRACTED EXTRACTED EXTRACTED EXTRACTED
3. ALL INTERLOCK SIGNALS SHALL BE HARDWIRED.
MV INCOMER ES
(57UAT1B-1)
MV INCOMER ES
(57UAT1B-2)
LEGEND
: CLOSED STATE
: OPENED STATE
FOR REVIEW
TEST OR EXTRACTED : TEST OR EXTRACTED STATE OF WITHDRAWABLE TYPE VACUUM CIRCUIT BREAKER
A1 (841 x 594)