Liebert PEX+ Chilled Water Series Technical Manual
Liebert PEX+ Chilled Water Series Technical Manual
Liebert PEX+ Chilled Water Series Technical Manual
Version V1.0
Revision date 2013-10-25
BOM
Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.
Chapter 1 Preface
Liebert.PEX+ chilled water series precision air conditioner (“Chilled water AC” for short hereafter) is professional
equipment and is applicable to the site that is not accessible by common public.
The Liebert.PEX+ chilled water series is a medium-large size precision environmental control system, which is
developed based on the Global R&D Platform of Emerson Network Power Co., Ltd (“Emerson” for short hereafter). It is
specially designed to meet the special requirement of data center environment. It has a wide range of cooling capacity
from 30kW to 210kW which is available for big, middle and small data centers.
This chapter mainly introduces the special requirement of data center environment and the features and advantages
of the Liebert.PEX+.
The Liebert.PEX chilled water series air conditioner adopts electric water flow regulating valve to precisely adjust the
chilled water flow according to the cooling demand, rendering high reliability. High efficient EC fan is used, featuring
energy saving, space saving, low noise and elaborate structure design. For downflow unit, the solution of air supply by
putting fan unit under floor is designed, which can significantly improve the efficiency of air supply. The efficient finned
tube evaporator and the unique V shape layout effectively increase the heat exchange efficiency. Special branch
design and verification have been conducted for each model to ensure the even distribution of chilled water in each
loop and make full use of the heat exchanger. The precise system matching design can maximize the performance of
the entire system.
Table 1-1 Comparisons between the Chilled water AC and common civil air conditioner
Key designed Common civil air conditioner Chilled water AC
Precision Generally ± 3°C ± 1°C, ± 1%RH
Humidity control Generally no humidity control Humidity and dehumidity control
Monitoring None Local and remote monitoring
Operation all year No refrigeration required in winter Refrigerating operation all year
Air filtering No standard requirement Compliant with ASHRAE 52-76
Commissioning in factory Simple commissioning Strict commissioning
Simple temperature control, non Intelligent micro processor automatic
Control design
intelligent control
This chapter introduces the appearance, model description, features, standard and optional components of the Chilled
water AC.
2.2 Appearance
The unit of the Chilled water AC is shown in Figure 2-1 with P3180UC series unit as an example.
2.3 Features
1. Type diversification
The Chilled water AC is classified into upflow type and downflow type by the airflow mode. The diversified modes can
adjust to different installation modes and using environments.
2. Precision control
The Liebert.PEX chilled water series air conditioner can have precise temperature and humidity control. Temperature
can be configured at ±1 ºC, and humidity can be configured at ±1%RH.
The Liebert.PEX chilled water series air conditioner adopts unique V shape finned tube heat exchanger, precisely
designed flow path and more rationalized internal layout to realize smooth and even internal air flow and more rational
chilled water distribution, thus greatly improving the heat exchange efficiency of the heat exchanger and realizing high
efficiency of the air conditioner.
3. Convenience and durability
Durable components, compact structure and low profile design; unique frame is not only stable and firm but can also
dismantled easily for transportation in extreme conditions; contributing to good insulation performance; the structure
components of one bay, two bay and three bay with high generality can greatly reduce the specifications of some
consumable components (such as Filter).
4. High efficient EC fan
High efficient EC fan is used, featuring energy saving, space saving, low noise and elaborate structure design. For
downflow unit, the solution of air supply by putting fan unit under floor is designed, which can significantly improve the
efficiency of air supply.
5. Infrared humidification
The Chilled water AC adopts an advanced infrared humidification technology to effectively reduce the dependence on
water quality. The humidity control will be more precise and quicker.
6. Multiple protections
Perfect automatic alarm and diagnosis functions provide all-around protections for the air conditioner unit, effectively
prevent faults, locate the faults more quickly and ultimately prolong the life span of the system.
7. Easy maintenance
The unit adopts front door access design. The maintenance of all the components can be performed through front
access, thus saving the operating space.
Heat exchanger
Finned-tube heat exchanger with high heat emission efficiency is adopted. The fins are hydrophilic fins with windows
and high heat exchange efficiency. The model-specific distributions can ensure the even flow path of chilled water in
each loop and greatly improve the efficiency of the heat exchanger.
Fan
High efficient and high reliable EC fan is used as shown in Figure 2-2, featuring big airflow, long airflow distance, easy
disassembly and convenient maintenance. The overheat protecting device can protect the motor effectively. The
advanced airflow loss protection can sense reduce of airflow that results from abnormal operation of the belt or motor
and stop the refrigeration, heating or humidifying, and generate the alarm signal in the meantime.
Infrared humidifier
The infrared humidifier (as shown in Figure 2-3) is controlled by a microprocessor. It features simple structure and
easy for disassembly, cleaning and maintenance. The quartz light, hanged over the moistening water pan of stainless
steel, generates the infrared ray and far infrared ray. In 5 ~ 6 seconds, these rays make the water molecule absorb the
radiation to cast off the strain of water and evaporate in the state of purity. The application of infrared humidifier
reduces the dependence on water quality. The function of automatic swashing makes the water pan cleaner.
PTC heater
The aluminum sheet mechanical gripper thermistor PTC heater is used, as shown in Figure 2-4. It features fast
temperature rising speed, automatic regulation of air temperature and power consumption, safety and reliability. The
heat quantity not only keeps the dry bulb temperature, but also compensates the temperature drop caused by
dehumidifying. The lower surface temperature of heater element can prevent the air from forming ionization and
prolong its using life.
LCD screen
The micro-processing controller of the Chilled water AC adopts 240 × 128 dot matrix, blue backlight LCD screen to
display the present temperature, humidity, temperature and humidity setting values, unit output percentage graph (fan,
compressor, refrigeration, heating, dehumidification, and humidification) and alarm information. You can browse or set
all setting values, event records, graph data, sensor data and alarm setting through the main menus on the screen.
The backlight of LCD screen is designed for saving energy. If there is not key operation over some time (the factory
default is 5 minutes, configured by the menu), the backlight will be off. Once any key is pressed, the backlight is on.
Micro-processing controller
The advanced micro-processing controller enables the Chilled water AC to control the temperature and humidity of the
machine room accurately. Its features are as follows:
Easy operation interface, multiple password protection to prevent unlawful operation.
The controller has the restoration of a power-down and high, low voltage protection functions.
Getting the operating time of important components through menu operation.
Malfunction diagnosis system of expert class can automatically display the present malfunction information to
make the maintenance easy.
It can store 200 historical records.
RS485 interface. Adopting the Modbus communication protocol .
The micro-processing controller can monitor and configure the following parameters:
Temperature setting value: the range is 18°C ~ 32°C.
Humidity setting value: the range is 20%RH ~ 80%RH.
Humidity control mode: two control modes contain absolute and Relative.
Air supply temperature limit setting value: the range is 8°C ~ 30°C.
AlarmSignal
The microprocessor is capable of generating audible and visual alarms. The standard signals contain: High
temperature alarm, low temperature alarm, high humidity alarm, low humidity alarm, high pressure alarm, low pressure
alarm, high air discharge temperature and low air discharge temperature, coil frost, Filter blockage alarm, no air flow
alarm and some self-defined alarms.
Upflow plenum
The plenum of the same size with the unit can be selected for upflow system. All plenums have grilles to make the air
flow even. You also can regulate the grills manually for different air direction. See Table 4-4 Plenum Dimensions for
plenum dimensions.
Analog water leakage alarm
The area mode or dot mode leak detector can supply units or a stand-alone monitoring system with analog alarm
signal to trigger the alarm of air conditioner unit and cut the humidify system. The zoster leakage alarm can accurately
show the location of water leakage.
Smoke and fire detectors
The smoke detector can trigger the alarm system at once and turn off the unit when smoke is detected. The fire
detector can monitor the field return air temperature. Once it detects high temperature, it will cut off the air conditioner
unit at once. Both detectors are indispensable to some key data centers.
High efficient Filter
The Filter with high efficiency is applicable to the environment requiring the higher air cleanliness.
Electrode humidifier
The electrode humidifier uses electrodes to boil the water in humidifier tank to produce steam to achieve the
humidifying purpose.
Three-way MBV
Three-way MBV can better regulate water flow system, to adapt to more environmental requirements
Fan pressure sensor
Sensor signal can be fed to the controller, more precisely control the fan speed, so as to achieve the constant air
pressure.
Dual power source auto-changeover switch
Double power source auto-changeover switch provides two power switching mode, you can run based on the actual
demand for automatic power switching
Dual power source manua-changeover switch
Dual power source manua-changeover switch provides two power switching mode, you can run based on the actual
needs of manual power switch
This chapter expounds the technical data of air cooled unit, and the environment parameters of the libert.PEX+ units.
Technical data Model P1030U P1040U P1050U P1060U P2070U P2080U P2090U P2100U P2110U
The unit’s cooling capacity test: the inlet temperature of chilled water is 7 ºC, and the outlet temperature is 12 ºC.
Cooling
Cooling capacity
and Sensible
24℃ dB capacity
30.4 40.6 51.2 60.6 71.8 80.8 92.7 100.5 112.5
50%RH sensible
cooling capacity
cooling 27.0 34.4 41.4 48.1 61.0 70.1 75.2 83.2 89.7
(kW)
capacity
Cooling
Cooling capacity 27.6 36 47.6 56.3 63.8 72.5 85.1 94.3 103.2
and Sensible ℃
24 dB
capacity
sensible
cooling capacity 45%RH
cooling 27.6 34.6 43.0 49.9 63.8 72.5 77.6 87 92.6
(kW)
capacity
Standard blast volume (m3/h) 9200 9600 10200 11200 17000 20400 18600 21300 21300
Fan number 1 1 1 1 2 2 2 2 2
Fan
Static pressure outside the fan 50 50 50 50 50 50 50 50 50
(Pa)
Fan power (outside of unit 1.4 1.59 1.91 2.14 2.81 4.33 3.59 5 4.35
:50Pa)(kW)
heat exchanger Front face area (m2) 1.48 1.48 1.48 1.48 2.63 2.63 2.63 2.63 2.96
coil 2 Head-on wind speed (m/s) 1.73 1.8 1.81 2.1 1.79 2.15 1.96 2.25 2
Electric heater power (KW) 6 6 6 6 9 9 9 9 9
Humidification amount (kg/h) 4.5 4.5 4.5 4.5 10 10 10 10 10
Infrared
humidifier Stainless Stainless Stainless Stainless Stainless Stainless Stainless Stainless Stainless
Humidifier water pan
steel steel steel steel steel steel steel steel steel
Size (mm) 950×425×46 950×425×46 950×425×46 950×425×46 850×425×46 850×425×46 850×425×46 850×425×46 950×425×46
Filter
Qty. 4 4 4 4 8 8 8 8 8
Interface Chilled water in and out pipes 32 32 32 42 42 42 54 54 54
dimensions (mm)
Infrared humidifier pipe (mm) 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35
(outer diameter) Condensation water drainage 19 19 19 19 19 19 19 19 19
pipe Inlet
water 1.45 1.93 2.44 2.89 3.42 3.85 4.42 4.79 5.36
24 ºC dB
flow (l/s)
50%RH
Pressure
drop 52 57.2 92.5 68.9 61.5 77 72.1 84 94.1
Chilled water
(KPa)
supply
Inlet
requirement
water 1.31 1.72 2.27 2.68 3.04 3.46 4.05 4.49 4.91
℃
24 dB flow (l/s)
45%RH Pressure
drop 43.1 45.5 80.6 60 48.9 62.5 61.6 74.6 80.4
(KPa)
Net Weight (kg) 280 305 330 335 590 590 600 600 310
Electric parameters FLA5(A) 13.5 13.5 13.5 13.5 22.6 22.6 22.6 22.6 22.6
main MCB(A)
(complete system)
100 100 100 100 100 100 100 100 100
Note:
1. the standard model is EC fan optional.
2. V shape copper pipe finned tube.
3. the standard model is PTC heating.
4. Based on ASHRAE52.1-1992, manual weight record method, the average filtering efficiency is above 90%; filter efficiency grade G4 (EN779).
5. The standard model is two-way valve, with three-way valve optional. Compression strength of the valve is 4000kPa.
6. Full load currentThe largest full-load current value is not the sum of the rated full load current of all components, but the sum of the largest rated full load current of the
relevant operational components under the maximum power load operation.
7.For net capacities, deduct fan input power. For net capacities, deduct fan input power. Refer to the Liebert PEX +Chilled Water Rating Program for specific input conditions,
air flow, and configuration.
Technical data Model P2120U P2130U P2140U P3150U P3160U P3170U P3180U P3190U P3200U
The unit’s cooling capacity test: the inlet temperature of chilled water is 7 ºC, and the outlet temperature is 12 ºC.
Cooling
Cooling capacity 120.5 131 138 149.2 161.7 172.1 180.4 189.1 207
and Sensible 24 ℃ dB capacity
cooling capacity
50%RH sensible
(kW) cooling 100.1 104.9 108.4 123.2 132.1 137.9 146 154.6 162.6
capacity
Cooling
Cooling capacity 112.3 120.9 126.5 138.9 150.4 157.9 167.7 177 189.8
capacity
24℃dB
and Sensible
cooling capacity
45%RH sensible
(kW) cooling 104.3 108.5 111.5 128.3 137.4 142.3 151.7 161.3 167.3
capacity
Standard blast volume (m3/h) 25900 24800 24000 31400 33100 33000 35500 38200 36900
Fan number 2 2 2 3 3 3 3 3 3
Fan
Static pressure outside the fan 50 50 50 50 50 50 50 50 50
(Pa)
Fan power (outside of unit 5.2 5.28 5.34 7.18 6.97 7.08 7.26 7.88 8.01
:50Pa)(kW)
heat exchanger Front face area (m2) 2.96 2.96 2.96 3.95 4.44 4.44 4.44 4.44 4.44
coil 2 Head-on wind speed (m/s) 2.43 2.33 2.31 2.21 2.07 2.06 2.22 2.39 2.31
Electric heater power (KW) 9 9 9 12 12 12 12 12 12
Humidification amount (kg/h) 10 10 10 10 10 10 10 10 10
Infrared
humidifier Stainless Stainless Stainless Stainless Stainless Stainless Stainless Stainless Stainless
Humidifier water pan
steel steel steel steel steel steel steel steel steel
Size (mm) 950×425×46 950×425×46 950×425×46 850×425×46 850×425×46 950×425×46 950×425×46 950×425×46 950×425×46
Filter
Qty. 8 8 8 12 12 12 12 12 12
Chilled water in and out pipes 54 54 54 66.8 66.8 66.8 66.8 66.8 66.8
Interface
(mm)
Infrared humidifier pipe (mm) 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35
dimensions
(outer diameter) Condensation water drainage 19 19 19 19 19 19 19 19 19
pipe
Inlet
5.74 6.24 6.57 7.11 7.7 8.2 8.59 9.01 9.86
24 ºC dB water
50%RH Pressure
drop 107.4 93.8 103.6 80.3 84.5 95 103.9 113.5 99.6
Chilled water (KPa)
supply Inlet
requirement water 5.35 5.76 6.03 6.62 7.47 7.52 7.99 8.43 9.04
24℃dB
flow (l/s)
45%RH
Pressure
drop 94.3 80.6 88 70.4 74 81.1 90.7 100.5 84.6
(KPa)
Net Weight (kg) 660 710 760 860 875 890 890 895 970
Electric parameters FLA (A)
5
22.3 22.3 22.3 31.5 31.5 31.5 31.1 31.1 31.1
(complete system) main MCB(A) 100 100 100 100 100 100 100 100 100
Note:
1. the standard model is EC fan optional.
2. V shape copper pipe finned tube.
3. the standard model is PTC heating.
4. Based on ASHRAE52.1-1992, manual weight record method, the average filtering efficiency is above 90%; filter efficiency grade G4 (EN779).
5. The standard model is two-way valve, with three-way valve optional. Compression strength of the valve is 4000kPa.
6. Full load currentThe largest full-load current value is not the sum of the rated full load current of all components, but the sum of the largest rated full load current of the
relevant operational components under the maximum power load operation.
7.For net capacities, deduct fan input power. For net capacities, deduct fan input power. Refer to the Liebert PEX +Chilled Water Rating Program for specific input conditions,
air flow, and configuration.
Model P1030D P1040D P1050D P1060D P2070D P2080D P2090D P2100D P2110D
Technical data
The unit’s cooling capacity test: the inlet temperature of chilled water is 7 ºC, and the outlet temperature is 12 ºC.
Cooling capacity Cooling capacity 30.4 40.6 51.2 60.6 71.8 80.7 92.7 100.5 112.5
24 ºC dB
and Sensible
50%RH sensible cooling
cooling capacity 29.2 34.4 41.4 48.1 61 72.5 75.2 83.2 89.7
(kW) capacity
Cooling capacity
and Sensible ℃
24 dB
Cooling capacity 27.6 36.0 47.6 56.3 63.8 72.5 85.1 94.3 103.2
cooling capacity 45%RH sensible cooling
27.6 36.0 43.0 49.9 63.8 69.0 77.6 87.0 92.6
(kW) capacity
Standard blast volume (m3/h) 9200 9600 10200 11200 17000 20400 18600 21300 21300
Fan number 1 1 1 1 2 2 2 2 2
Fan
Static pressure outside the fan (Pa) 20 20 20 20 20 20 20 20 20
heat exchanger Front face area (m2) 1.48 1.48 1.48 1.48 2.63 2.63 2.63 2.63 2.96
coil 2
Head-on wind speed (m/s) 1.73 1.8 1.81 2.1 1.79 2.15 1.96 2.25 2
Electric heater power (KW) 6 6 6 6 9 9 9 9 9
Size (mm) 950×425×46 950×425×46 950×425×46 950×425×46 850×425×46 850×425×46 850×425×46 850×425×46 950×425×46
Filter
Qty. 4 4 4 4 8 8 8 8 8
Chilled water in and out pipes (mm) 32 32 32 42 42 42 54 54 54
Interface
dimensions Infrared humidifier pipe (mm) 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35
(outer diameter)
Condensation water drainage pipe 19 19 19 19 19 19 19 19 19
24 ºC dB Inlet water flow (l/s) 1.45 1.93 2.44 2.89 3.42 3.85 4.42 4.79 5.36
50%RH
Chilled water Pressure drop (KPa) 52 57.2 92.5 68.9 61.5 77 72.1 84 94.1
supply
℃
requirement Inlet water flow (l/s) 1.31 1.72 2.27 2.68 3.04 3.46 4.05 4.49 4.91
24 dB
45%RH
Pressure drop (KPa) 43.1 45.5 80.6 60 48.9 62.5 61.6 74.6 80.4
Net Weight (kg) 280 305 330 335 590 590 600 600 310
Electric parameters FLA5(A) 13.5 13.5 13.5 13.4 22.6 22.6 22.6 22.6 22.6
(complete system)
main MCB(A) 100 100 100 100 100 100 100 100 100
Note:
1. the standard model is EC fan optional.
2. V shape copper pipe finned tube.
3. the standard model is PTC heating.
4. Based on ASHRAE52.1-1992, manual weight record method, the average filtering efficiency is above 90%; filter efficiency grade G4 (EN779).
5. The standard model is two-way valve, with three-way valve optional. Compression strength of the valve is 4000kPa.
6. Full load currentThe largest full-load current value is not the sum of the rated full load current of all components, but the sum of the largest rated full load current of the relevant
operational components under the maximum power load operation.
7.For net capacities, deduct fan input power. For net capacities, deduct fan input power. Refer to the Liebert PEX +Chilled Water Rating Program for specific input conditions, air
flow, and configuration.
Model P2120D P2130D P2140D P3150D P3160D P3170D P3180D P3190D P3200D
Technical data
The unit’s cooling capacity test: the inlet temperature of chilled water is 7 ºC, and the outlet temperature is 12 ºC.
Cooling capacity Cooling capacity 120.5 131 141.9 149.2 161.7 172.1 180.4 189.1 211.8
24 ºC dB
and Sensible
50%RH
cooling capacity sensible cooling
(kW) 100.1 104.9 112 123.2 132.1 137 146 154.6 167.1
capacity
Cooling capacity 112.3 120.9 130.1 138.9 150.4 157.9 167.7 177 194.2
Cooling capacity
and Sensible ℃
24 dB
cooling capacity 45%RH sensible cooling
104.3 108.5 115.3 128.3 137.4 142.3 151.7 161.3 172
(kW) capacity
Standard blast volume (m3/h) 25900 24800 25600 31400 33100 33000 35500 38200 38200
Fan number 2 2 2 3 3 3 3 3 3
Fan
Static pressure outside the fan (Pa) 20 20 20 20 20 20 20 20 20
heat exchanger Front face area (m2) 2.96 2.96 2.96 3.95 4.44 4.44 4.44 4.44 4.44
coil 2 Head-on wind speed (m/s) 2.43 2.33 2.31 2.21 2.07 2.06 2.22 2.39 2.31
Size (mm) 950×425×46 950×425×46 950×425×46 850×425×46 850×425×46 950×425×46 950×425×46 950×425×46 950×425×46
Filter
Qty. 8 8 8 12 12 12 12 12 12
Chilled water in and out pipes (mm) 54 54 54 66.8 66.8 66.8 66.8 66.8 66.8
Interface
dimensions Infrared humidifier pipe (mm) 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35
(outer diameter)
Condensation water drainage pipe 19 19 19 19 19 19 19 19 19
Inlet water flow (l/s) 5.74 6.24 6.76 7.11 7.7 8.2 8.59 9.01 10.09
24 ºC dB
50%RH
Pressure drop (KPa) 107.4 93.8 109.3 80.3 84.5 95 103.9 113.5 103.9
Chilled water
supply
requirement Inlet water flow (l/s) 5.35 5.76 62 6.62 7.17 7.52 7.99 8.43 9.25
℃
24 dB
45%RH
Pressure drop (KPa) 94.3 80.6 92.9 70.4 74 81.1 90.7 100.5 88.3
Net Weight (kg) 660 710 760 860 875 890 890 895 970
Electric parameters
FLA
5
(A) 22.3 22.3 22.3 31.5 31.5 31.5 31.1 31.1 31.1
()
(complete system)
main MCB A 100 100 100 100 100 100 100 100 100
Note:
1. the standard model is EC fan optional.
2. V shape copper pipe finned tube.
3. the standard model is PTC heating.
4. Based on ASHRAE52.1-1992, manual weight record method, the average filtering efficiency is above 90%; filter efficiency grade G4 (EN779).
5. The standard model is two-way valve, with three-way valve optional. Compression strength of the valve is 4000kPa.
6. Full load currentThe largest full-load current value is not the sum of the rated full load current of all components, but the sum of the largest rated full load current of the relevant
operational components under the maximum power load operation.
7.For net capacities, deduct fan input power. For net capacities, deduct fan input power. Refer to the Liebert PEX +Chilled Water Rating Program for specific input conditions, air
flow, and configuration.
Note
The residual pressure out of units of upflow unit is 50pa,downflow unit is 20pa.
Please consult Emerson Network Power Co., Ltd, if the data, which you need, is not included in preceding tables.
Note
When the unit is used in the following condition, please contact Emerson:
If the unit voltage exceeds the operating voltage range.
Derating for altitude above 1000m.
Other applications outside of applicable scopes.
Chapter 4 Dimensions
This chapter introduces the mechanical dimensions, the mounting base dimensions of indoor units and the dimensions
of plenums.
D
D W W
D W
H H H
Figure 4-1 Mechanical dimensions of the units of upflow unit (unit: mm)
W D
D W D
W
H
H
H
Figure 4-2 Mechanical dimensions of the units of downflow unit (unit: mm)
H
D
CO B
E
CI
F
P
H: Water inlet for humidifier CI/CO: chilled water inlet / outlet pipe holes
Figure 4-3 Cut-out location dimensions of at the base of P1030-P3100unit (unit: mm)
Table 4-2 Dimensions of air outlet on base palletr of upflow unit (unit:mm)
Model A B C E F D H CI CO
P1030~P1060 850 900 930 206 273 35 35 110 110
P2070~P2100 1600 900 1680 206 273 35 35 110 110
P2110~P2140 1750 900 1830 206 273 35 35 110 110
P3150 2425 900 2505 206 273 35 35 110 110
P3160 ~P3200 2650 900 2730 206 273 35 35 110 110
Figure 4-4 Cut-out location dimensions of top cover of upflow unit for air discharge (unit: mm)
Table 4-3 Cut-out location dimensions of top cover of upflow unit for air discharge (unit: mm)
Model A B C
P1030~P1060 850 850 930
P2070~P2100 1600 850 1680
P2110~P2140 1750 850 1830
P3150 2425 850 2505
P3160 ~P3200 2650 850 2730
Note
The equipment has knock-outs, be sure to mount sleeve to the cable holes to avoid cutting the cables.
A B
A B
A
B
~
Figure 4-8 Plenum dimensions of P3150 P3200 upflow unit
Note
If the height of the plenum selected exceeds 600mm, consult Emerson for non-standard production.
This chapter describes the piping for refrigerant tubing system of water system and wind system and the connection of
controller.
隔离阀* 压力表*
Isolating valve * Pressure gauge *
活动地板
Raised floor
冷冻水进水口
Chilled water inlet
冷冻水出水口
Chilled water outlet
过滤网*
filter * 地板下的隔热层 地板Floor
Heart insulation layer under the floor
Note
Thers components are not provided by Emerson Network Power Co., Ltd, but they are recommended to be used for the
normal operation of the system and maintenance.
5.1.4 Piping
1. The Chilled water AC in and out pipes adopt soldering method, as shown in Figure 5-3. Table 5-1 shows the
connecting dimensions of chilled water supply and return pipes of various units.
出水管
进水管
Air inlet
Air outlet
Air outlet
Air inlet
5.3 Controller
Teamwork parameters
After connecting the hardware, networking can be realized after corresponding parameters are set through the display
board.
TEAMWORK: Available modes are single mode, teamwork mode 1, teamwork mode 2, and teamwork mode 3.
#UNIT: The unit number in teamwork mode
#STANDBY: The number of standby units in teamwork mode
CASCADE: Whether the cascade mode is enabled
ROT BY: The number of rotation units
DO ROT: Perform one rotation manually
ROTATION: The time for realizing one automatic rotation
ROT TIME: The rotation time
Note
Control board address shall be set via DIP switch and the address of display board shall be set via menus.
The address must be allocated starting from 0, and #0 unit is the master unit.
The IP address of all units in the same network cannot be same.
Teamwork mode 2
Some parameters are shared (temperature and humidity setting value and precision, dead band). If setting in any of
the units, all other units will follow with the same settings. The master unit does not send request command to slave
units. This mode is used in the occasions with an uneven heat load distribution and will not cause fighting operation.
Standby is enabled in teamwork mode 2, but rotation and cascade are not supported.
Teamwork mode 3
Some parameters are shared (temperature and humidity setting value and precision, dead band). If setting in any of
the units, all other units will follow with the same settings. The master unit does not send request command to slave
units. This mode is used in the occasions with a severe uneven heat load distribution and will not cause fighting
operation. Standby and cascade are enabled in teamwork mode 3, but rotation is not supported.
Note
Prior to entering standby mode, units will operate the fan only for a time of 3 minutes to cool down the electric heater and
remove steam out of the unit.
5.3.4 Comparision
The comparison between the teamwork modes is listed in Table 5-2. The rotation and cascade function is based on
the standby function. No standby, no rotation or cascade.
#STANDBY: 3
ROT BY: 2
第一周三 前
NO.1 Before 10:00 on Wednessday
10:00 1 2 3 4 5 6 7 8 9 10
第一周三
NO.2 After 10:00 on 10:00 后
Wednessday 1 2 3 4 5 6 7 8 9 10
第二周三 后
NO.3 After 10:00 on Wednessday
10:00 1 2 3 4 5 6 7 8 9 10
第三周三
NO.4 After 10:00 on 10:00 后
Wednessday 1 2 3 4 5 6 7 8 9 10
第四周三
NO.1 After 10:00 on 10:00 后
Wednessday 1 2 3 4 5 6 7 8 9 10
第五周三
NO.1 After 10:00 on 10:00 后
Wednessday 1 2 3 4 5 6 7 8 9 10
备用机型
Backup unit
运行机型
Running unit
Balanced load (small groups of units inside the same environment: teamwork 1.
Unbalanced load (not all units will have the same load in large equipment rooms): teamwork 2/3.
Q2: Which control mode do we recommend to set the temperature and humidity in teamwork mode?
Q3: Will all units in same group select the same teamwork mode?
A3: Yes. All units in same group must select the same teamwork mode.
Q4: May the standby units in teamwork mode 1 turn on if an operating unit is in "alarm" condition and has been shut
down?
A4: Yes. As soon as an operating unit does not operate (because of an alarm or switched off), the standby unit will
start immediately in order to keep the number of operating units.
Q5: Do all of the networked units have the same proportional band, dead band and set point?
A5: In teamwork modes 1, 2 and 3, these parameters are the same. Changing one of these three parameters will be
automatically taken over from all connected units.
Q6: How do the cascade units participate in system calculating in teamwork mode 1?
A6: The master averages from the temperature and humidity of operating units and comprises them with the set points
to calculate the request. Then the calculated request is multiplied by the usable unit number in system to get the
total request. The request is allocated to the operating units firstly. If there are remaining, it is the standby units’
turn.
2. IEC61000-3-2-2000 Electromagnetic compatibility (EMC) - Part 3-2: Limits - Limits for harmonic current emissions
(equipment input current <= 16 A per phase).
3. IEC61000-3-4-1998 Electromagnetic compatibility (EMC)-Part 3-4: Limits-Limitation of emission of harmonic
currents in low-voltage power supply systems for equipment with rated current greater than 16A.