Corrigendum No. – 02
With reference to the Notice Inviting E-tender with the aforementioned details published on CPP e-
Tendering Portal on 14.04.2023, the following amendment in the NIT may please be noted:
“If the Estimated Cost of Tender is below or equal to Rs. 10 Crores, then the Bidder must
submit self-certification for Local Content as per Annexure – VII on a Non-Judicial Stamp Paper
Costing Rupees 100/- (One Hundred Only). All the Pages of the Document must be signed by
the certifying authority.”
may be read as
“If the Estimated Cost of Tender is below or equal to Rs. 10 Crores, then the Bidder must
submit self-certification for Local Content as per Annexure – VII on their company letterhead.
b. In Sub-Point-8 “Local Content Certificate” under Clause 3.1 of Section – II of the NIT:
“The Bidder must submit self-certification for Local Content as per Annexure – VII on a Non-
Judicial Stamp Paper Costing Rupees 100/- (One Hundred Only). All the Pages of the Document
must be signed by the designated executive.
“The Bidder must submit self-certification for Local Content as per Annexure – VII on their
company letterhead. All the Pages of the Document must be signed by the designated
executive.”
Page 1 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
“Power of Attorney: Power of Attorney on a Non-Judicial Stamp Paper Costing Rupees 100/-
(One Hundred Only) as per Annexure - IV authorizing the designated executive to sign all
documents on behalf of the company or firm, if the bid is not signed by the Director of the
Company or Partner / Proprietor of the Firm must be submitted.”
may be read as
may be read as
2.5. The Contractor & their OEM shall ensure proper integration & successful commissioning of
the Entire Network. It shall be the responsibility of OEM & the Contractor to resolve all the
dependencies for commissioning of the Network without any additional financial implication
to AAI.
3. Following Changes has been made in the Annexure-XX: Technical Specification Compliance:
Page 2 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Switch should support port security, Switch should support port security, DHCP
DHCP snooping, Dynamic ARP snooping, Dynamic ARP inspection, IP Source
11
inspection, IP Source guard, BPDU guard/ IP Source Lockdown, BPDU Guard,
Guard, Spanning tree root guard. Spanning tree root guard.
Page 3 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Page 4 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
The Access Points should support The Access Points should support WMM/ WMM-
21 WMM, WMM-UAPSD,802.1p, Diffserv UAPSD, 802.1p, Diffserv and TOS.
and TOS
Should have minimum 8 nos. 1G UTP Should have minimum 8 nos. 1G UTP ports, 4 nos.
ports, 4 nos. 10G SFP+ slots atleast 1 10G SFP+ slots atleast 1 nos. Expansion slots, 1
nos. Expansion slots, 1 no. Out-of-Band no. Out-of-Band Management Port /
2
Management Port, 1 no. USB 3.0 ports, Management Port, 1 no. USB 3.0 ports, 1 no.
1 no. Console Port, built-in Fans and Console Port, built-in Fans and Dual Hot-
Dual Hot-Swappable PSU from day1 Swappable PSU from day1
The system should have the flexibility to The system should have the flexibility to create
create rules for Popular web-based rules for Emails to match various mail attributes
13 webmail sites to match various mail such as Subject, From, To, CC, BCC, Message
attributes such as Subject, From, To, CC, Body, attachment (Text, Name, Size, Type) with a
BCC, Message Body, attachment (Text, wide range of composite conditional option.
Page 5 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Each IT Rack should have two rack Each IT Rack should have two rack PDU's. Rack
PDU's. Rack PDU should have minimum PDU should have minimum 24 outlets of C13 &
24 outlets of C13 & C19 types. It must C19 types. It must be 7.2KW rated each with min
3.3
be 7.2KW rated each with min 20 C13 20 C13 sockets and 4 C19 sockets.
sockets and 4 C19 sockets.
Minimum 02 nos. LTS / STS/ Automatic Transfer
Minimum 02 nos LTS with SNMP Card & Switch with SNMP Card & Sockets 6 numbers
Sockets 6 numbers must be provided. must be provided.
Fire Safety, Security & Access Control Fire Safety, Security & Access Control
Page 6 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Page 7 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
4. In reference to the Clarification / queries received through CPP Portal / Mail correspondences, following response may kindly be considered: -
RRFQ cum
Sl. RFP RFQ cum Original Content in the Draft AAI
Clarification sought/ Changes requested Bidder Justification/ Remarks
No. Volume, RFP Page RFQ cum RFP Response
Section
Item No. Switch should support As per the industry standard IPv6 routes are
1.01 - minimum 4K ACLs, 8K always be half of IPv4 routing entries hence
Please refer
1 Layer 3 99 Multicast and 100K request you to change the clause as: Switch NA
Corrigendum
Core Unicast Routes for IPv4 should support minimum 4K ACLs, 8K Multicast
Switch and IPv6 and 100K Unicast Routes for IPv4 and 50K IPv6
BGPv6 is required at the ISP environment. At
Item No. Layer-3 Routing Protocols campus environment at max BGPv4 would be
1.01 - support required from required to run the network over IPv6. Request
2 Layer 3 99 day 1: IPv4 & IPv6 Static, you to change the clause as: Layer-3 Routing NA As per NIT
Core RIP, RIPng, OSPF, OSPF Protocols support required from day 1: IPv4 &
Switch v3, BGP, BGPv6 IPv6 Static, RIP, RIPng, OSPF, OSPF v3, BGP,
BGPv4
There are multiple ways to achieve DHCP
Switch should support snooping i.e using ACL. Further in equivalence to
Item No.
port security, DHCP IP source guard, Aruba HPE support IP source
1.01 -
snooping, Dynamic ARP lockdown. Kindly change the clause as: - Switch Please refer
3 Layer 3 99 NA
inspection, IP Source should support port security, DHCP Corrigendum
Core
guard, BPDU Guard, snooping/ACL, Dynamic ARP inspection, IP
Switch
Spanning tree root guard Source guard/IP source lockdown, BPDU Guard,
Spanning tree root guard
Item No. Switch should support
1.01 - IPv6, IPv6 Snooping,
Request you to make the clause standard stating
4 Layer 3 99 IPv6 DHCP Guard, IPv6 NA As per NIT
Switch should support IPv6 security features
Core Neighbour Discovery
Switch Inspection
Page 8 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Page 9 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Page 13 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Page 14 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Fortinet
https://www.fortinet.com ›
ce...PDF
Firewall
Microsoft Azure
https://azure.microsoft.com ›
updates
Azure Firewall Premium is now
ICSA labs certified
Allied Telesis
https://www.alliedtelesis.com ›
icsa
ICSA Certified Products
GajShield
https://gajshield.com/index.php/pr
oducts/enterprise
Sophos
https://docs.sophos.com › filesPDF
FIREWALL – Certificate
Versa Networks
https://versa-networks.com › news
Versa Networks Receives Firewall
Certification from ICSA Labs
Page 15 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Page 16 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Page 17 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Page 19 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Page 20 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Page 24 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
b) IP based Biometric
Access Control System
shall be provided to serve Request you to pls amend as :
the objective of allowing b) IP based Biometric Access Control System
3.5 Fire
access to authorized shall be provided to serve the objective of
Safety, Page 117 Kindly accept door opening
personnel only. The front allowing access to authorized personnel only. Please refer
59 Security & of procedure as per OEM design
& rear rack doors will be The front & rear rack doors will be provided Corrigendum
Access 133 standard
provided with magnetic with magnetic locks and Front door will operate
Control
locks and will operate on on fail-safe principle through one common
fail-safe principle through Biometric access control system.
one common Biometric
access control system.
Touch Display Screen–
Graphical User Interface Request you to pls amend as : Minimum 9"
3.8 Page 117 Adequately sized touch screen
display should be Touch Display Screen– Graphical User Interface
60 Monitorin of display for better graphical As per NIT
mounted on the display should be mounted on the Integrated
g 133 displays
Integrated smart smart rack solution.
rack solution.
a) Min.17” LCD console
tray and 8 port IP KVM Request you to pls amend as :
3.9 KVM Page 117
switch and should occupy a) Min.18.5” LCD console tray and 8 port IP KVM
61 & Console of NA As per NIT
1U space switch and should occupy 1U space in 19”
Tray 133
in 19” standard standard rack.
rack.
Supplied KVM cables
3.9 KVM Page 117 should support Virtual
Kindly confirm server interface module for VM
62 & Console of media to map USB media NA As per NIT
support
Tray 133 devices to target servers
remotely over TCP/IP.
Additional OEM Suggest to add below OEM credentials to have best in class & market
63
Clause Credentials standard solution for Prestigious organisation like AAI:
Page 25 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
The Smart Rack OEM of the proposed solution should have minimum 07
years of experience in executing similar works (Similar works means – “SITC
of Modular Integrated Smart Server Rack infrastructure”) in
63.1 Kindly Accept As per NIT
Central/State/PSU Organizations. Completion Certificate signed by the
concerned authorities, as a proof of work execution to be submitted along
with the bid.
The Smart Server Rack OEM must have executed minimum 05 Integrated
Smart Rack Data Centre projects, with minimum 06 rack configuration in
63.2 each project, during the last 3 years from the bid submission date. Kindly Accept As per NIT
Completion Certificate signed by the concerned authorities to be submitted
along with the bid.
Smart Server rack OEM should have its own manufacturing facility in India
for wide range of Racks, UPS & Precision air conditioning units. Supporting
63.3 Kindly Accept As per NIT
document/undertaking regarding the same to be submitted along with the
bid.
3.Solution Page No. Request you to please change the clause as:
e. Microprocessor based
shall have 116 Microprocessor based Controller with capacity
Controller with capacity
63.4 following of minimum 100 event logs. for broader OEM NA As per NIT
of minimum 200 event
compone participation
logs.
nts
3.3 Power Page No. Minimum 02 nos LTS with LTS is specific to single OEM please change this
Distributio 117 SNMP Card & Sockets 6 to Rack mount Automatic transfer switch Please refer
63.5 NA
n numbers must be Corrigendum
provided.
Page 26 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
3.7 Rack Page No. 4 Nos. of 42 U racks of Smart rack design should be as per OEM so
frame and 118 dimension 800 mm x please change the clause as:-4 Nos. of 42 U
U Space minimum 1200 mm with racks of dimension 800 mm x minimum 1200
integrated hot & cold mm with integrated hot & cold aisle
aisle containment of containment of minimum 200 mm each. Both
minimum 300 mm each. Hot & Cold aisle containment should be part of
64 Both Hot & Cold aisle the rack frame. Solution should have Min 150 U NA As per NIT
containment should be (total) space available for IT and network
part of the rack frame. equipment.
Solution should have Min
150 U (total) space
available for IT and
network equipment.
3.1 Page No. Manufacturer must be IS/ Requesting you to please change the clause as
119 ISO 14001, ISO/IEC/IS this Manufacturer must be IS/ ISO 14001, Please refer
65 NA
27001 & IS/ ISO 45001 ISO/IEC/IS 27001 & IS/ ISO 45001/50001 Corrigendum
certified. certified.
Item No. Page No. 3 - Min Plug retention 3 - Min Plug retention force: 50N or 11.24 lb or
1.17 & 111 of 133 force: 133N 5.09 Kgs
The plug retention force
1.18 -
mentioned i.e. At 133N which is
CAT6A
66 approx. 30lb or 13.56 Kgs of force As per NIT
Patch
is too high and specific to a
Cord 1
particular product or an OEM.
Mtr, 2
Mtrs
Item No. Page No. 7 - Min Plug retention 3 - Min Plug retention force: 50N or 11.24 lb or The plug retention force
1.22 - 112 of 133 force: 133N 5.09 Kgs mentioned i.e. At 133N which is
67 CAT6A 24 approx. 30lb or 13.56 Kgs of force As per NIT
port Jack is too high and specific to a
Panel particular product or an OEM.
Page 27 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
(Fully
Loaded)
Item No. Page No. 2 - Cable Sheath LSZH, 2 - Cable Sheath LSZH, jacket complaint to IEC
1.24 - 114 of 133 jacket complaint to IEC 60332-1, UL 1444 / IEEE 1202/ IEEE 383 LSZH rating IEC 60332-3 is
Fibre 60332-3, UL 1685 / IEEE traditionally used for Vertical
Patch 1202/ IEEE 383 Bunch of Cables however patch
68 Cord (SM) cord are used in Horizontal cabling As per NIT
(duplex and in Single Pcs. i.e. within the
minimum Rack. Request to use the standard
2 Mtr, LC- for individual cable ie. IEC 60332-1
LC)
Annexure Page No. Switch should support Switch should support minimum 4x ACLS, 8K
XX; Item 99 minimum 4x ACLS, 8K Multicast and 32K Unicast Routes for IPv4 and
This small change will not have any
No 1.01- Multicast and 100K IPv6.
impact on performance of switch Please refer
69 Layer 3 Unicast Routes for IPv4
and will enable more vendors to Corrigendum
Core and IPv6.
qualify.
Switch;
Point 6
Annexure Page No. Switch shall support Please remove Smurf Protocol
XX; Item 99 traffic monitoring with
No 1.01- net Flow /sflow/flow This is OEM specific and not a
Please refer
70 Layer 3 entries. Should prevent general protocol. This would
Corrigendum
Core SYN Flood, Smurf, ping support only one OEM
Switch; flood, URPF
Point 14
Annexure Page No. The switch should Request to reduce ACL to 128 from 1000
XX; Item 100 support following This small change will not have any
No 1.02- security features: L2-L4 impact on performance of switch
71 As per NIT
Layer 2 ACL, at least 1000 ACL and will enable more vendors to
Switch entries, role-based policy, qualify.
Min. 48 Dynamic ARP Inspection
Page 28 of 30
भारतीय विमानपत्तन प्राधिकरण
Airports Authority of India
आईटी विभाग, क्षेत्रीय मुख्यालय (पूिी क्षेत्र), कोलकाता
IT Division, RHQ (ER), Kolkata
Layer 2 ACL, at least 1000 ACL and will enable more vendors to
POE+ entries, role-based policy, qualify.
Switch Dynamic ARP Inspection
Min. 24 (DAI), IPv6 RA Guard,
Port; Control plane DoS
Point 8 protection.
Annexure Page No. The switch should Kindly Reduce Operating temperature from 0-50
XX; Item 102 support Operating to 0-45.
No 1.04- Temperature: 0 to +50°C
Layer 2 Indoor temperature generally is
76 POE+ not more than 45 C and is optimum As per NIT
Switch temperature.
Min. 24
Port;
Point 11
Page No. When APs lose
104 communication with the
Annexure controller, User should Controller is installed in redundant
XX; Item continue to function with mode, so request to relax stateful
77 Please delete this clause. As per NIT
No. 1.08- QoS and security policies, inspection clause as No controller
Wireless including stateful scenario would not arise
Controller inspection of Layer 3
; Point 11 traffic.
Annexure Page No. Should comply to
XX; Item 104 certifications EN55022 / Please remove as this is only meant
No. 1.08- CISPR22/ IS6873-7, for hardware controller and
78 Please delete this clause. As per NIT
Wireless EN61000/ IS14700, software controllers are also
Controller EN60950/1513252, approved.
; Point 20 FCC/IRRS.
Page 30 of 30