Professional Documents
Culture Documents
Manual PW
Manual PW
Manual PW
l�-'
---------- ,
User manual
E-51028230XT/BG -1
2 - E-51028230XT/BG
Contents
Introduction
General characteristics of MGE™ Galaxy™ PW UPSs ......................................... 5
System description .................................................................................................. 6
Different types of MGE™ Galaxy™ PW systems ................................................... 7
Isolation and protection devices .............................................................................. 7
Operation in on-line mode ....................................................................................... 8
Operation in "eco" mode ......................................................................................... 10
Operation with an engine generator set .................................................................. 11
Inverter shutdown or overload ................................................................................ 12
Output voltage quality and continuity ...................................................................... 12
Control panel
General ................................................................................................................... 14
Presentation ............................................................................................................ 15
Start-up
System start-up ....................................................................................................... 17
Start-up of a module ............................................................................................... 18
Shutdown
Shutdown of the inverter ......................................................................................... 19
Shutdown of a rectifier/charger ............................................................................... 19
Control-panel display
General organisation ............................................................................................... 20
Display of messages ............................................................................................... 20
Measurement system .............................................................................................. 24
Voltage measurementsi .......................................................................................... 24
Current measurements ........................................................................................... 24
Power and frequency measurements ..................................................................... 24
Battery measurements ............................................................................................ 25
Selections and settings ........................................................................................... 25
Alarms
General ................................................................................................................... 28
Maintenance bypass ............................................................................................... 28
Environment information
Signal reception ...................................................................................................... 29
Signal transmission ................................................................................................. 29
Maintenance
Maintenance configuration ...................................................................................... 34
Battery maintenance ............................................................................................... 37
Visual check ............................................................................................................ 37
Functional check ..................................................................................................... 37
Training center ........................................................................................................ 38
Options
Isolating and voltage matching transformer for the normal and bypass AC
Source and the load ................................................................................................ 39
Harmonics filter and power factor improvement ..................................................... 39
Safety of life and property ....................................................................................... 39
Empty cubicles ........................................................................................................ 40
Electrical supervision .............................................................................................. 40
E-51028230XT/BG -3
All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to
competitors of APC by Schneider Electric.
To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning
technical characteristics and dimensions are not binding unless confirmed by APC by Schneider Electric.
This document may be copied only with the written consent of APC by Schneider Electric. Authorised copies must be marked
"MGE™ Galaxy™ PW User Manual, N° 51028230XT".
4 - E-51028230XT/BG
Introduction
E-51028230XT/BG -5
Introduction (cont.)
battery (D):
backup power
isolation:
Q4S static bypass (C):
(2)
bypass
AC input
maintenance bypass:
Q3BP
Fig. 1
6 - E-51028230XT/BG
Introduction (cont.)
E-51028230XT/BG -7
Introduction (cont.)
8 - E-51028230XT/BG
Introduction (cont.)
Operation with the normal The battery charge cycle takes place in Note 1:
two steps (see figure 10): If the normal AC source failure is
AC source restored ◗ step 1: the battery is recharged at a shorter than 0 to 255 seconds (default
See figure 9. constant current limited to 0.1C10 (i.e. value = 30 seconds) (parameter
When normal AC source power (1) is 1/10th of the battery capacity specified defined by after-sales support
restored or its voltage returns to within for a 10 hour discharge). The DC department), the charger automatically
specified tolerances, the system voltage increases with the battery supplies the floating voltage given the
automatically returns to its normal charge until the charge level is low battery discharge.
operating mode described above (on reached;
◗ step 2: the battery is recharged at
Note 2:
the condition it did not reach the end of In frequency converters without battery
battery power). If the end of battery constant voltage equal to the charge
level (maximum value 463 V). power, the return of normal AC source
power was reached (with the resulting power results in the automatic restart of
inverter shutdown), the rectifier/charger The charging current gradually
decreases until reaching a specified the rectifier/charger and the inverter.
(A) restarts automatically, but the
inverter (B) must be restarted manually. low value (floating current).
The rectifier/charger recharges the For vented lead-acid batteries, the
battery (D) which was discharged rectifier/charger supplies the charging
during the mains outage. During battery voltage for 0 to 255 hours (parameter
charging, light 2 flashes green. defined by the after-sales support
The message "BATTERY CHARGING" department) and then the floating
is displayed, together with the value of voltage. For sealed lead-acid batteries,
the recharging current and battery the charging and floating voltages are
voltage. the same.
1
U/I U charge/floating
voltage (sealed batteries)
2
U "floating"
A B (vented batteries)
1
0,1 C10
D
C
current
2
Fig. 10
E-51028230XT/BG -9
Introduction (cont.)
A B
1
D
C
2
Fig. 11
10 - E-51028230XT/BG
Introduction (cont.)
1,25 In
1,15 In
1,10 In
1,05 In
In
1 2 3 4 5 6 7 8 9 10 30 120 t (min)
Fig. 14
E-51028230XT/BG - 11
Introduction (cont.)
Operation with an Output voltage quality When the bypass AC source frequency
returns to within the specified
engine generator set and continuity tolerances, the inverter is gradually re-
synchronised to the bypass line at a
See figure 15 below. The output voltage is stable in rate of 0.5 Hz to 2 Hz/s (as per the
If a stand-by generator is included in amplitude and frequency and is free of value personalised by the after-sales
the installation, it is generally started interruptions or transients outside support department), thus avoiding
automatically in the event of a normal specified tolerances, irrespective of exposing the load to sudden frequency
AC source failure and connected to the normal AC source or load disturbances variations.
main low voltage switchboard. It is (outages, load step changes, etc.).
disconnected when normal AC source Transient voltage
power is restored. Steady state voltage regulation
With such a system, the required
battery time may be reduced to the time regulation The inverter output voltage is not
necessary for starting and bringing on For stable or slowly varying load notably affected by instantaneous
line the stand-by generator. The battery conditions, the inverter output voltage is major variations in load characteristics.
(D) supplies power to the inverter (B) This is made possible by the PWM
regulated to within ±0.5% in amplitude.
during the transfers: The frequency of the output voltage can (Pulse Width Modulation) chopping
◗ normal AC source to the generator; technique and the microprocessor-
theoretically be regulated to within
◗ generator to the normal AC source. based regulation system that instantly
0.1% of the rated value, however the
The transfer sequences described output frequency range may be compensates for any variation. In
above (normal AC source ➜ battery, intentionally extended to a maximum of particular, the inverter output voltage
battery ➜ generator, generator ➜ remains within +/- 2% of the rated
±2 Hz so that the inverter can remain
battery, and battery ➜ normal AC synchronised with the bypass AC voltage for load step changes of 0 to
source) are fully automatic. They in no source and its inherent frequency 100% or of 100 to 0%.
way affect the load and require no
fluctuations, thus enabling transfer of
manual operation by the user. the load to the bypass line at any time.
Note: Note:
To avoid load surges on the generator, The output frequency range can be
the rectifier/charger is started with a 10 personalised and if necessary modified
second maximum current consumption on the customer site by a qualified APC
walk-in (lasting 3 to 10 seconds,
by Schneider Electric support
depending on the percent load). technician from ±0.25 Hz to ±2 Hz in
To avoid overloading an undersized 0.25 HZ steps.
engine generator set, it is possible to
When the bypass AC source voltage
set a maximum power level drawn by moves outside this frequency range,
the normal AC input. Any additional the inverter is desynchronised and
power required is supplied by the
operates in "free running" mode, with
battery. This modification can be made the output frequency regulated to a
on site by an APC by Schneider high level of accuracy by a quartz
Electric technician.
oscillator.
MGE Galaxy PW
generator main LV switchboard C
Mains 2
G
A B
HV system Mains 1
Fig. 15
12 - E-51028230XT/BG
Description of MGE™ Galaxy™ PW cubicles
UPS cubicle
The rated outputs for
MGE™ Galaxy™ PW UPSs (or
frequency converters) are 20, 30, 40,
50, 60, 80, 100, 120 , 160 and 200kVA.
See figure 16 for the layout of the
various cubicle components. 11
1 2 2 2 3
11
11
12
1
4 4
2 3
12
5 3 6
5 6
7 8 9 10
7 8 9 10
Fig. 16
E-51028230XT/BG - 13
Control panel
14 - E-51028230XT/BG
Control panel (cont.)
"Static-bypass" light 3 1 2 3 4 5 6 7
◗ light off: bypass AC source within 1
specified tolerances and static bypass
open; 2
◗ light shines green: static bypass 8
closed;
◗ light shines red: the stored alarm 23 9
indicates one or several of the following
faults:
◗ bypass AC source voltage or 10 11 12 13 14 15 16
frequency outside specified tolerances,
V A W.Hz
◗ static-bypass fault, 18
◗ abnormally high internal static-
17 19
bypass temperature,
◗ static-bypass ventilation fault, fault
◗ power-supply fault for the static-
bypass control function,
20 21 22
◗ fault on the electronic board
controlling the transfer function,
◗ non-calibration or non-
personalisation of the electronic control
board for the inverter, Fig. 19
◗ fault on the electronic power-supply
board,
◗ fault on monitoring the "inverter
ready" response channels (parallel
UPS system).
E-51028230XT/BG - 15
Control panel (cont.)
16 - E-51028230XT/BG
Start-up
QF1
4
0 I
1 1 1 1
5 0 0 0 0
6 4
Fig. 20 Fig. 21
E-51028230XT/BG - 17
Start-up (cont.)
Single-UPS unit
◗ the inverter starts, then, if the bypass
AC source transfer conditions are
satisfied, the load is transferred to the
inverter if the on-line mode is selected,
or the load remains on the static
bypass if the "ECO" mode is selected.
For on-line mode:
◗ the green "inverter" light 4 remains
on,
◗ the "static-bypass" light 3 goes off.
◗ For "ECO" mode:
◗ the green "inverter" light 4 flashes,
◗ the "static-bypass" light 3 remains
on.
18 - E-51028230XT/BG
Shutdown
E-51028230XT/BG - 19
Control-panel display
The display is structured around In addition to keypad operations, the primary message
primary and secondary messages, graphical display brings up a window
measuring tables and setting screens. giving the overall device status. The
As a rule, the message displayed on message displayed is then said to be (ALARM MESSAGE N° 1)
the screen is always a primary one. primary (see list in the paragraph
The secondary messages, if any, are below). A primary message can be
accessed by pressing keys 10 and used to access the measuring tables
11 (see figure 19). using keys 14 , 15 , 16 and 19 on
The presence of secondary messages the keypad (see figure 21 in the general (ALARM MESSAGE N° 2)
is indicated by the arrow at the end appendix). The configuration screens
of the primary message. Return to the can be accessed by pressing key 13 .
primary messages is automatic if the A flashing arrow appears at the end of
keypad is not used for 2 minutes, or a primary message if there is a problem (LAST ALARM MESSAGE)
direct by pressing key 18 (see figure or an alarm; secondary messages can
19). The display screen lights up when be accessed by pressing key 10 on
a key is pressed, and goes off if no key the keypad (see the list of secondary
is pressed for 5 minutes. messages). The presence of another main screen
message is indicated by the arrows
Note: and at the end of the secondary
Most functions may be directly Fig. 22
message. They can be accessed by
accessed. For example, when voltage pressing keys 10 and 11 on the
measurements are currently displayed, keypad.
it is possible to directly access current The return to the primary message is
measurements by pressing the "A" automatic after a 2 minute time delay or
button. by pressing key 18 on the keypad.
1 2 3 4 5 6 7
2
8
23 9
10 11 12 13 14 15 16
V A W.Hz
18
17 19
fault
20 21 22
Fig. 19
20 - E-51028230XT/BG
Control-panel display (cont.)
E-51028230XT/BG - 21
Control-panel display (cont.)
List of secondary
MAINS 1 OUTSIDE TOLERANCES, INVERTER NOT IN PHASE WITH
messages CHECK MAINS 1 MAINS 2.
TRANSFER DISABLED,
The normal AC source (M1) frequency CHECK MAINS 2
LOAD ON MAINS 2
or voltage is outside specified tolerances
and the rectifier/charger has shut down. The phase difference between the
The load has been transferred to the The inverter is on battery power. inverter and the bypass AC source
bypass AC source (M2) and is no
(M2) is outside tolerances. Transfer of
longer protected (only in on-line mode).
the load between the inverter and the
The buzzer sounds continuously. MAINS 1 INPUT SWITCH Q1 bypass AC source (M2) will result in an
IS OPEN interruption in the supply of power to
the load.
MAINS 2 OUTSIDE TOLERANCES The normal AC input (M1) switch Q1 is For parallel UPSs, this message should
TRANSFER DISABLED be interpreted as meaning the phase
open. It must be closed for rectifier/
CHECK MAINS 2 difference between the inverter for which
charger start-up. The buzzer sounds
slowly and discontinuously. the message is displayed and the other
The bypass AC source (M2) frequency inverters is outside tolerances.
or voltage is outside tolerances and the
inverter is unable to synchronise. INTERNAL UPS FAULT,
Transfer of the load from the inverter to UPS SHUTDOWN
LOAD TRANSFER FAULT,
the bypass AC source (M2) or vice- BY AN EXTERNAL COMMAND
CALL MAINTENANCE
versa will result in an interruption of the
supply of power to the load. The buzzer The inverter has received a command
A fault has occurred in the static switch
sounds slowly and discontinuously. to shut down. The command is in the
that transfers the load between the
inverter and the bypass AC source form of a signal from received the
(M2). Servicing by the after-sales remote-indications relay board which
BATTERY OVERTEMPERATURE, has been set for this function.
support department is required. The
CHECK VENTILATION buzzer sounds continuously.
The battery temperature is outside FREQUENCY CHANGE
tolerances. The buzzer sounds slowly OVERLOAD BY AN EXTERNAL COMMAND
and discontinuously. RATED CURRENT PER PHASE =
XXX A The inverter has received a command
CHECK LOAD LEVEL to change its output frequency (50 Hz
BATTERY ROOM VENTILATION or 60 Hz). This command is not
FAULT, effective unless the inverter has first
This display informs the user that load
CHECK VENTILATION current is greater than rated current, been shut down. The frequency is
and gives the value. The buzzer changed when the inverter is started
A fault requiring servicing has occurred again.
sounds continuously.
in the battery room ventilation system.
The rectifier/charger shuts down after a
30-second time delay. MAINS 2 INPUT SWITCH Q4S IS
UPS SHUTDOWN DUE TO AN
The user must take steps to re- OVERLOAD, OPEN
establish correct operation of the CHECK LOAD LEVEL
ventilation system. The bypass AC source (M2) input
If a harmonic filter is present in the This message follows the preceding switch Q4S is open, i.e. backup power
installation, this message also signals when the overload persists. The UPS for the load via the bypass AC source
an abnormally high temperature in the (M2) is not available.
has shut down and the buzzer sounds
filter inductor. continuously.
The buzzer sounds slowly and
discontinuously. INVERTER OUTPUT SWITCH Q5N
IS OPEN
22 - E-51028230XT/BG
Control-panel display (cont.)
BYPASS SWITCH Q3BP THE BATTERY C.B. QF1 IS OPEN, THE NUMBER OF UPS READY IS
IS CLOSED CHECK THE INSTALLATION INSUFFICIENT,
LOAD TRANSFER IN STAND BY
Maintenance bypass switch Q3BP is Battery circuit breaker QF1 is open.
closed. The system is in maintenance The load is no longer protected This message may be displayed in non-
configuration and the load is supplied because battery power is no longer redundant, parallel UPS systems,
by the bypass AC source. available in the event of a normal AC when the number of ready inverters in
source outage. The buzzer sounds not sufficient to supply the load.
continuously.
STATIC SWITCH (M2) OFF
DUE TO AN OVERLOAD INVERTER NOT CONNECTED
LOW BATTERY SHUTDOWN
The load is no longer supplied by the This message may be displayed in
bypass AC source (M2), due to an The inverter has shut down at the end parallel UPS systems, when the
extended overload. The buzzer sounds of battery power. The buzzer sounds inverter is not connected to the load.
continuously. continuously.
PARALLEL UPS,
BATTERY CHARGING INTERNAL UPS FAULT, FORCED TRANSFER INHIBITED
I BAT. = XXX A U BAT. = XXX V INVERTER FAULT,
CALL MAINTENANCE This message is displayed when forced
The battery is currently being connection is requested on a parallel
recharged. A fault has occurred in the inverter. UPS system for a power extension.
Servicing by the after-sales support
department is required. The buzzer
BATTERY AT END OF SERVICE sounds continuously. INTERNAL UPS FAULT,
LIFE SELF-TEST FAULT
CALL MAINTENANCE
INTERNAL UPS FAULT, Communication between the system
The battery is nearing the end of its CHARGER FAULT, and the display is faulty. The buzzer
estimated service life. This information CALL MAINTENANCE sounds slowly and discontinuously.
is based on average service-life
calculations since its initial installation. A fault has occurred in the rectifier/
The buzzer sounds slowly and charger. Servicing by the after-sales FORCED TRANSFER TO M2
discontinuously. support department is required. REQUESTED,
The buzzer sounds slowly and POWER TO LOAD MAY BE
discontinuously. INTERRUPTED
EMERGENCY OFF OR FULL CONFIRM YOUR REQUEST WITH
SHUTDOWN KEY
FORCED TRANSFER TO INVERTER
This message is displayed when either REQUESTED, POWER TO LOAD This message is displayed following
the external emergency-off pushbutton MAY BE INTERRUPTED, pressing of the "forced-transfer" key
or the full-shutdown button 7 on the CONFIRM YOUR REQUEST WITH 20, when the load is supplied via the
control panel are pressed. The result is: KEY inverter.
◗ shutdown of the inverter;
◗ shutdown of the rectifier/charger; The requested transfer to the inverter
◗ opening of the battery circuit breaker; may provoke an interruption in the UPS SUPPLIED BY A GENERATOR
◗ activation of a relay contact on the supply of power to the load if Mains 2 SET
remote-indications relay board. characteristics are not within the
To fully de-energise the installation, specified tolerances. This message informs the user that the
these functions must also open the UPS has received the order to limit the
external, upstream circuit breakers on current drawn by the rectifier/charger.
the normal and bypass AC supply lines. It is displayed when the corresponding
The buzzer sounds continuously. signal is transmitted by the remote
indications board which must be
configured for this function.
E-51028230XT/BG - 23
Control-panel display (cont.)
1 3 4 6
U -I-F U-I F U-V-I-F-P
A B
Q1 Q5N
1
QF1
D
2
U-V-I-F C
Q4S
2
Fig. 23
24 - E-51028230XT/BG
Control-panel display (cont.)
Battery measurements
These measurements may be
accessed by pressing the "battery" key BATTERY
19 . The following data is displayed.
U = ---- V REMAINING TIME = ---- MIN
I = ---- A PL / PN = ---- %
T° = ---- °C
◗ Lamp test:
When this function is selected, all the
lights shine orange for three seconds.
E-51028230XT/BG - 25
Control-panel display (cont.)
◗ Inverse video:
When this function is selected, the text
and background colours are reversed
(white text on black or black text on
white).
◗ Past events:
See section "logging and time-
stamping".
◗ Battery test:
◗ the screen opposite is displayed CHARGE LEVEL = -- %
when a battery test is requested. It
indicates the battery charge status and REMAINING SERVICE LIFE = -- MONTH
the remaining service life. A manual or
automatic test may be requested, ◗ MANUAL TEST press key
26 - E-51028230XT/BG
Control-panel display (cont.)
E-51028230XT/BG - 27
Alarms
28 - E-51028230XT/BG
Environment information
E-51028230XT/BG - 29
Logging and time-stamping
by pressing the key. and keys to scroll up and down Setting the date and time
General instructions for through the screens.
for the UPS
For time-stamped events, the display
using most screens begins with the last event logged. When the DATE AND TIME command
To access older events, press the is selected, the screen presented
You can display the desired information
key. If during consultation, you wish to
and enter commands using the , opposite is displayed:
review more recent events, press the ◗ the current values are automatically
and keys.
key. displayed;
Press the key to exit the time-
stamping consultation mode and return ◗ you can modify any of the displayed
to the main menu. If no commands are values;
entered for five minutes, the system ◗ position the ">" sign opposite the
automatically returns to the normal value to be modified. Then press the
display mode. key;
You can scroll through the screens ◗ use the and keys to modify
displaying information. Press the the value;
◗ the key increments the value by
one;
◗ the key decrements the value by
one;
◗ the selected value can be confirmed
by pressing the key. A second
value may then be selected for
modification, again using the and
keys;
◗ modifications are made and
confirmed value by value;
◗ press the key at any time to exit
the DATE AND TIME function.
30 - E-51028230XT/BG
Logging and time-stamping (cont.)
E-51028230XT/BG - 31
Logging and time-stamping (cont.)
◗ total time with Tbatt > 25° C (h): Use the and keys to shift between the beginning and the end of the display.
this is the total time of operation with
the battery temperature greater than
25° C since initial startup of the UPS.
FIGURES SINCE RESET
It is expressed in hours;
◗ last reset: this is the date that the
nb of backups: 0
information was last set to zero by the
Teleservice function;
nb of backups < 1 min: 0
◗ elapsed backup time (min): this is
the total time of operation on battery
1 min < nb of backups < 3 min: 0
power since the last reset. It is
expressed in minutes.
nb of backups > 3 min: 0
◗ nb of backups: this is the number of
times the load was supplied by the UPS
nb of overloads < 5 s: 0
from battery power since the last reset;
◗ nb of backups < 1 min: this is the
nb of overloads > 5 s: 0
number of times the load was supplied
by the UPS from battery power for less
nb of times TBatt. > 25°C: 0
than one minute, since the last reset;
◗ 1 min < nb of backups < 3 min: this
is the number of times the load was ◗ nb of backups > 3 min: this is the ◗ nb of overloads > 5 s: this is the
supplied by the UPS from battery number of times the load was supplied number of times the UPS was
power for more than one minute and by the UPS from battery power for overloaded (output current greater than
less than three minutes, since the last more than three minutes, since the last In) for more than five seconds, since
reset; reset; the last reset;
◗ nb of overloads < 5 s: this is the ◗ nb of times TBatt. > 25° C: this is
number of times the UPS was the number of times the battery
overloaded (output current greater than temperature was measured at over
In) for less than five seconds, since the 25° C, since the last reset.
last reset;
32 - E-51028230XT/BG
Logging and time-stamping (cont.)
Utilisation via
Teleservice
When the optional JBUS RS232/485
communications board is installed, the
time-stamped information can be sent
to the Teleservice centre.
The centre can remotely consult the
same information and carry out the
same modifications as the user locally
on the display. Note that only the
Teleservice centre can reset the
counters for the statistical data.
E-51028230XT/BG - 33
Maintenance
Maintenance A B
configuration 1
Q1 Q5N
QF1
Single-UPS unit or UPS in
"ECO" mode D
C
Q4S
See figure 24. During maintenance, the
2
UPS must be isolated from the normal
and bypass AC source, the battery and Q3BP
the load.
◗ UPS isolation
Proceed in the following order (see
figure 25): Fig. 24
◗ shut down the inverter (press the
"inverter OFF" button 9 for three
seconds),
◗ close bypass switch Q3BP, Q1 Q4S Q3BP Q5N
◗ open isolating switches Q5N, Q4S,
1 1 1
1 0 OFF
0 OFF
Caution
◗ work should be carried out in
accordance with applicable safety Fig. 25 Fig. 26
regulations;
◗ to avoid interrupting the load, the
various switching operations must be
carried out in the correct order.
Operations are explained in diagrams
placed next to the switches;
◗ the system cubicle is only partially
powered down. The load is still
supplied via the bypass AC source and
switch Q3BP.
34 - E-51028230XT/BG
Maintenance (cont.)
E-51028230XT/BG - 35
Maintenance (cont.)
Note:
We recommend that you call on the
after-sales support department to carry
out these operations. Q1 Q4S Q5N 2 3 4 5
Note that for parallel UPSs for 5 0
1
0
1
0
1
bypass 600 kVA
increased output, the entire installation
must be bypassed because it is not QF1 Q4S 1 1 1
possible to isolate just one UPS unit. 6
0 0 0
Q3BP 1 1 1
0 I 0 0 0
1 1 1 Q5N 1 1 1
7 0 0 0
0 0 0
Fig. 30
Q4S 0 1 1 1
0 0
Q3BP 0 1 1 1
0 0
Q5N 0 1 1 1
0 0
Q1 Q4S Q5N
1 1 1 2 3 4 5
5 0 0 0
bypass 600 kVA
QF1
6 Q4S 1 1 1
0 0
0 I
Q3BP 1 1 1
7 0 0 0
Q5N 1 1 1
0 0
Fig. 31
36 - E-51028230XT/BG
Maintenance (cont.)
Pb Pb
E-51028230XT/BG - 37
Maintenance (cont.)
Training center
To allow you to useAPC by Schneider Electric products effectively and carry out basic maintenance, we offer a complete range of
technical training courses in English and French.
Internet : Http://powerlearning.apc.com
On-line catalogue and registration.
38 - E-51028230XT/BG
Options
E-51028230XT/BG - 39
Options (cont.)
40 - E-51028230XT/BG