You set the specified operating state of the function via the parameter Mode. You can set the function mode
to on, off, and test. The operating principle is described in Table 2-2. You can set the parameter Mode via:
• DIGSI 5
• IEC 61850-8-1
• CFC
The superordinate state can have the values On, Relay blocked, Test, and Test/Relay blk..
The state of the function resulting from the parameter Mode, the controllable Mod, and the superordinate
state is shown in the following table. The resulting state of the functions results from the combination of all
sources (parameter Mode, controllable Mod, and superordinate state). As a simplification, the table only
shows the combination of 2 sources.
1 With the parameter (_:151) Oper.bin.outp. under test, you can set whether the relay outputs are to be activated by functions in the
Test state. If this parameter is deactivated (default setting), the Test state of a function is changed to Test/Relay blk..