Basic Structure of the Function

2.3 Function Control

You set the specified operating state of the function via the parameter Mode. You can set the function mode
to on, off, and test. The operating principle is described in Table 2-2. You can set the parameter Mode via:

• DIGSI 5

• On-site operation at the device

• Browser-based user interface

• Certain systems control protocols (IEC 61850, IEC 60870-5-103)


You can also set the target operating state of the function using the controllable Mod. You can set the function
mode to On, Off, Test, Relay blocked and Test/Relay blk.. The operating principle is described in
Table 2-2. You can set the controllable Mod via:

• IEC 61850-8-1

• CFC
The superordinate state can have the values On, Relay blocked, Test, and Test/Relay blk..
The state of the function resulting from the parameter Mode, the controllable Mod, and the superordinate
state is shown in the following table. The resulting state of the functions results from the combination of all
sources (parameter Mode, controllable Mod, and superordinate state). As a simplification, the table only
shows the combination of 2 sources.

Table 2-1 Resulting State of the Function

Inputs State of the Function


Source A Source N
On On On
On Off Off
On Test Test1
On Relay blocked Relay blocked
On Test/Relay blk. Test/Relay blk.
Test On Test1
Test Off Off
Test Test Test1
Test Relay blocked Test/Relay blk.
Test Test/Relay blk. Test/Relay blk.
Off On Off
Off Off Off
Off Test Off
Off Relay blocked Off
Off Test/Relay blk. Off
Relay blocked On Relay blocked
Relay blocked Off Off
Relay blocked Test Test/Relay blk.
Relay blocked Relay blocked Relay blocked
Relay blocked Test/Relay blk. Test/Relay blk.
Test/Relay blk. On Test/Relay blk.
Test/Relay blk. Off Off
Test/Relay blk. Test Test/Relay blk.

1 With the parameter (_:151) Oper.bin.outp. under test, you can set whether the relay outputs are to be activated by functions in the
Test state. If this parameter is deactivated (default setting), the Test state of a function is changed to Test/Relay blk..

SIPROTEC 5, High-Voltage Bay Controller, Manual 43


C53000-G5040-C015-J, Edition 08.2022