NOARK A32

Air Circuit Breaker


Power circuit breakers and switches from 800A to 3200A are certified to

Usage
UL1066 , ANSIManual
C37.13 and CSA C22.2 NO.31

User Manual

ZA32202209UL
Installation manual
Overview 01

Selection Guide 02

Product parameters 06

Environmental Conditions 07

Pckage identification 08

Storage 09

Necessary tools 10

Unpacking 11

Handling 13
Installation Dimension 16

Terminal Adjustment 36

Neutral Current Transformer 39

ELM10 41

Accesories 44

Conrtol ciruit wiring 50

Smart Unit Operating Instruction


Profile of SU 54

Main Menus 61

Menu 62

Overview of Functions 65

Appendix 66
Overview

This device should be installed, operated, serviced and maintained only by professional personnel.
Noark Electric is not responsible for any consequences caused by non-compliance with this the manual.
 After unpacking the product, check for any damage and the integrity of other items.
 Do not install the product in inflammable, explosive, humid and condensing environment.
1
 Do not install the product at places where gas medium can cause metal corrosion and insulation damage. 2
 Connect the product to the proper power supply and standard wires.
 Leave sufficient space and safe distance around the product.
3
 Do not touch the conductive parts during operation.
4
 Disconnect all the power sources during installation and maintenance.
5
 Failure to follow the above instructions may result in equipment damage, personal injury or even death.
6

Environmental protection
To protect environment, this product and its components should be disposed properly as industrial waste upon
end of life; or delivered to recycling plant who will dismantle and recycle the product according to relevant
national regulations.

Codes and Standards

UL 1066、ANSI C37.13、ANSI C37.16、ANSI C37.17、ANSI C37.50,CSA C22.2 NO.31


UL file number: E502732 16 15 14 13 12 11 10 9 8 7

1. Brand 10. Rotary handle operation hole


2. Opening push-button (O) 11. Main contact position indicator
3. Closing push-button (I)
4. Manual spring charge handle a) opening
OFF

5. Nameplate b) closing ON

6. Closing ready indicator


12. Indicator for Disconnect, Test,Connect
position
a) ready OK
13. Rotary handle
b) not ready OK 14. Smart Unit
7. Cassette position lock(manually 15. Trip reset button
reset after injection)
16. Control circuit wiring terminal
8. Padlock

9. Spring charged/discharged indicator

a) Spring charged Charged

b) Spring discharged Discharged

User Manual 01
Selection Guide Selection Guide

A 32 H 3 F H 800 Catalog Designation for Auxiliary contact


I II III IV V VI VII
Noark UL1066 power circuit breakers AX 12 N 44
I A: Power circuit breakers I II III IV
ASD: Non-automatic switches
Frame Size
II I AX: Auxiliary contact
32: 3200A
Interrupting/short time withstand current II 12: For 3200A PCB
III
Q: 65kA, R: 85kA, H: 100kA III N: UL
Number of poles: Contact configuration
IV 3– 3 Pole IV 44: 4NO+4NC, 66: 6NO+6NC
4 – 4 Pole 44C: 4NO/NC, 66C: 6NO/NC
Installation
V
F: Fixed ; D: withdrawable
H: Horizontal ; V: Vertical
Catalog Designation for Shunt Trip
VI * 3200A only provided with vertical type.
* contact Noark sales for other configuration. SHT 12 N A
Rated current: I II III IV
800– 800A
1600 – 1600A SHT: Shunt trip release
VII I
2000 – 2000A SHTD: second shunt trip release
2500 – 2500A II 12: For 3200A PCB
3200 – 3200A III N: UL
Control voltage
IV
A: 24-30VDC, B: 48-60VDC, C: 110-130VAC/DC, D: 208-240VAC/DC

Catalog designation for cassette


CAS 12 N 3 V 3200
Catalog Designation for Closing Release/Shunt Close
I II III IV V VI

XF 12 N A
I CAS: Cassette
Frame size I II III IV
II
12: 3200A
III N: UL
I XF: Shunt close
Pole
IV 3: 3P II 12: For 3200A PCB

4: 4P III N: UL
H: Horizontal Control voltage
IV
V V: Vertical A: 24-30VDC, B: 48-60VDC, C: 110-130VAC/DC, D: 208-240VAC/DC
* 3200A only available with vertical wiring.
Rated current
1600: 800A, 1600A,
VI
2500: 2000A, 2500A, Catalog Designation for Under voltage Trip
3200: 3200A
UVT 12 N A
I II III IV
Catalog Designation for Trip unit
I UVT: Under voltage trip
II 12: For 3200A PCB
SU 30 N H A III N: UL
I II III IV V Control voltage
IV
A: 24VDC, B: 48VDC, C: 110 - 130VAC/DC, D: 208 - 240VAC/DC E: 380-415VAC
I SU: Smart unit
Protection type
II
20: LI, 30: LSI, 40: LSIG
III N: UL
Measurement type
Catalog Designation for Motor Operator Device
M: Basic without measurement (LED display)
IV
A: Ammeter (LCD display)
MD 12 N C
H: Harmonics (LCD display)
Control voltage I II III IV
V
A: 24VDC,C: 110-130VAC, D: 208-240VAC
I MD: Motor operator Device
II 12: For 3200A PCB
III N: UL
Control voltage
IV
A: 24-30VDC, B: 48-60VDC, C: 110-130VAC/DC, D: 208-240VAC/DC

User Manual 02 User Manual 03


Selection Guide Selection Guide

Catalog Designation for Position indicator Catalog Designation for Pushbutton lock device

EF 12 N VBP 12 N
I II III I II III

I EF: Position indicator


I VBP: Pushbutton lock device
II 12: For 3200A PCB
II 12: For 3200A PCB
III N: UL
III N: UL

Catalog Designation for OFF position keylock


Catalog Designation for Mechanical Interlocks with cables
KLK 12 N 1
IPA 12 N
I II III IV
I II III

I KLK: OFF position keylock


I IPA: Mechanical Interlocks with cables
II 12: For 3200A PCB
II 12: For 3200A PCB
III N: UL
III N: UL
IV 1: 1 lock 1 key, 2: 2 locks 1 key, 3: 3 locks 2 keys

Catalog Designation for Doorframes for fixed type Catalog Designation for Door interlocks for withdrawable type
CDP 12 N VPEC 12 N S
I II III I II III IV

I CDP: Doorframes for fixed type I VPEC: Door interlocks for withdrawable type
II 12: For 3200A PCB II 12: For 3200A PCB
III N: UL III N: UL
P: Position interlock
IV
S: Status interlock
Catalog Designation for Doorframes for withdrawable type

DDP 12 N Catalog Designation for External current transformer for Neutral


I II III

NCT 12 N
I DDP: Doorframes for withdrawable type
Ⅰ Ⅱ Ⅲ
II 12: For 3200A PCB
III N: UL Ⅰ NCT: External Current transformer for Neutral
Ⅱ 12: For 3200A PCB
Catalog Designation for Phase barrier for fixed type Ⅲ N: UL

PHS 12 N 2
I II III IV Catalog Designation for Energy-Limiting Maintenance Switch (ELM Switch)

I PHS: Phase barrier for fixed type ELM 10


II 12: For 3200A PCB Ⅰ Ⅱ
III N: UL
2: 2 pcs for 3P Ⅰ ELM: Energy-Limiting Maintenance Switch
IV
3: 3 pcs for 4P Ⅱ 10: For UL PCB

Catalog Designation for Phase barrier for withdrawable type Catalog Designation for Lockable switch cover for ELM Switch
DPS 12 N 2 LSC 10
I II III IV Ⅰ Ⅱ

I DPS: Phase barrier for withdrawable type Ⅰ LSC: Lockable switch cover for ELM Switch
II 12: For 3200A PCB Ⅱ 10: For UL PCB
III N: UL
2: 2 pcs for 3P Note: LSC10 is an optional unit, please comment if it is required when purchasing.
IV
3: 3 pcs for 4P

User Manual 04 User Manual 05


Product parameters Environmental Conditions

Ambient temperature
Type A32Q A32R A32H ASD32Q ASD32R ASD32H
A32 Circuit breakers can operate in the following environmental conditions:
Pole 3P/4P 3P/4P
With M Smart Unit: -40℃ ~ 70℃;
Installation Fixed/Withdrawable Fixed/Withdrawable
With H Smart Unit: -20℃ ~ 70℃;
Fixed:800/1600/2000/2500
Rated current(A) 800/1600/2000/2500/3200
Withdrawable:800/1600/2000/2500/3200
A32 Circuit breakers can operate at higher temperatures than the reference temperature 40℃,in this case,the derating coefficients
Rated Maximum Valatge(V) 254/508/635 254/508/635 shown in the table must be applied.
Frequency(Hz) 50/60 50/60 Rated Temperature(℃ )
254V 65 85 100 / / / Current(A) <40 45 50 55 60 65 70
Interrupting rating at rated maximum voltage (kA) 508V 65 85 100 / / /
800 100% 100% 100% 100% 100% 100% 100%
635V 65 85 100 / / /
254V 65 85 100 65 85 100 1600 100% 100% 100% 100% 100% 100% 100%
Short time withstand current (kA) 508V 65 85 100 65 85 100 2000 100% 100% 100% 100% 100% 100% 93%
635V 65 85 100 65 85 100 2500 100% 95% 92% 88% 83% 80% 75%
open <70 <70
operating time(ms) 3200 100% 95% 92% 88% 83% 80% 75%
close <40 <40
without maintenance 10000 10000 10000 10000 10000 10000
mechanical
life cycle(time)
with maintenance / / / / / / Altitude
without maintenance 6000 6000 6000 6000 6000 6000
electrical
with maintenance / / / / / / A32 Circuit breakers do not undergo changes in rated performance up to 2000m.Beyond this altitude ,the derating coefficients shown in
21.65×23.62×18.11 21.65×23.62×18.11
the table must be applied.
(550×520×460) (550×520×460)
3P
Ventilation Area Top: 9092mm² Ventilation Area Top: 9092mm² Altitude(m)
Bottom:9092mm² Bottom: 9092mm² <2000 2600 3900 4900
withdrawable
21.65×25×18.11 21.65×25×18.11 Rated Voltage(V) 1xUe 0.95xUe 0.8xUe 0.7xUe
Enclosure dimension (550×635×460) (550×635×460)
4P Rated Current(A) 1xIn 0.99xIn 0.96xIn 0.94xIn
H×W×D(in/mm) Ventilation Area Top: 11963mm² Ventilation Area Top: 11963mm²
Bottom: 11963mm² Bottom: 11963mm²
21.65×20.47×14.17 21.65×20.47×14.17 Humidity
3P
(550×520×360) (550×520×360)
fixed The relative humidity does not exceed 85% at 40℃,the monthly average maximum of relative humidity in the wettest month does not
21.65×25×14.17 21.65×25×14.17
4P
(550×635×360) (550×635×360) exceed 90%.
The effect of surface condensation caused by temperature changes on product performance should be taken into consideration.

Mounting type Rated current/A Power Consumption/W

Withdrawable 800 80

Withdrawable 1600 300

Withdrawable 2000 400

Withdrawable 2500 500

Withdrawable 3200 620


Fixed 800 50
Fixed 1600 200
Fixed 2000 250
Fixed 2500 300
Fixed 3200 430

A32 Bus bar recommendation

Vertical Horizontal
In
Qty Size(in) Size(mm) Qty Size(in) Size(mm)

800A 1 1/4×3 6.35×76.2 1 1/4×3 6.35×76.2

1600A 2 1/4×3 6.35×76.2 2 1/4×3 6.35×76.2

2000A 2 1/4×4 6.35×101.6 3 1/4×3 6.35×76.2

2500A 3 1/4×4 6.35×101.6 5 1/4×3 6.35×76.2

3200A 4 1/4×4 6.35×101.6

Recommended tighting torque is 40-50 N.m.

Note: These tables should be used as a general guideline only, the solution used should take into consideration the varieties of switchgear types and conditions.

User Manual 06 User Manual 07


11

1 1

er Circ uit Breaker


r
A32 Pow200 cuit Breake
A3
A32H 2 Power Cir
3DV3
6 200
A32H3DV3
+AX12ND6
6
+UVT12NA
+AX12ND6
+UVT12NA
+XF12NA
+SHT12NA
+XF12NA
+MD12NA
+SHT12NA
+MD12NA
+SU30NHA
+SU30NHA
ard:
Conform stand C37.13
/ANS I standard:
orm
UL 1066
Conf
2 No.31 I C37.13
File E502732

UL 1066/ANS 1
CSA C22. File E502732
No.3
CSA C22.2
4 5 6 7 9 8
7 8 9 1 2 3
1 2 3 4 5 6
5 6 7 9 td
3 4Co.,L
8
8 9 1 2 i)
4 5 6 7ngha
trics 1 2 3 (sha
NOARK Elec i) Co.,Ltd
trics (shangha
NOARK Elec

1PCS
1PCS

A32
A32 Power
PowerCircuit
CircuitBreaker
Breaker
A32H3DV3200
A32H3DV3200
+AX12ND66
+AX12ND66
+UVT12NA
+UVT12NA
+XF12NA
+XF12NA
+SHT12NA
+SHT12NA
+MD12NA
+MD12NA
+SU30NHA
+SU30NHA
Conform standard:
Conform
UL standard:
1066/ANSI C37.13
CSA C22.2 No.31C37.13
UL 1066/ANSI
CSA C22.2 No.31 File E502732

File E502732

1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 9 8
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 9 8
NOARK Electrics (shanghai) Co.,Ltd
NOARK Electrics (shanghai) Co.,Ltd

User Manual 08 User Manual 09


3
installation bolt:Hex Cap Screws: 7/16 in x 2 in
4
Nameplate example

in/mm

17
0.67(17)
LOW VOLTAGE AC POWER CIRCUIT BREAKER
UL 1066/ANSI C37.13/CSA C22.2 No.31
Frame Size:3200A Frequency:50/60Hz
Rated Continuous Current: Poles:

Rated Maximum Voltage(V) 254 508 635

Rated Short Circuit Current(kA)

Short-Time Withstand Current


(kA,0.5s)

Cat.
MFG.Date:
Serial No. :
E510966
Instruction Manual: MADE IN CHINA

3
Hex Cap Screws : 7/16 in x 2
4 in

5. Press and hold pull out button


Withdrawable 6. Pull out the main breaker
Connected

Test

Disconnected

Rotate handle indicator


to disconnect position

7. Pull out the main breaker to maximum extent

User Manual 10 User Manual 11


Unpacking
Handling
Handling
unit : lb/kg
unit : lb/kg

800A/1600A 2000A/2500A 3200A


800A/1600A 2000A/2500A 3200A

net weight 123/56 net weight 133/60 net weight 147/67


power circuit breaker net weight 123/56 power circuit breaker net weight 133/60 power circuit breaker net weight 147/67
power circuit breaker gross weight 163/74 power circuit breaker gross weight 176/80 power circuit breaker gross weight 191/87
gross weight 163/74 gross weight 176/80 gross weight 191/87
net weight 117/53 net weight 126/57 net weight 141/64
non-automatic switch net weight 117/53 non-automatic switch net weight 126/57 non-automatic switch net weight 141/64
non-automatic switch gross weight 156/71 non-automatic switch gross weight 170/77 non-automatic switch gross weight 184/84
gross weight 156/71 gross weight 170/77 gross weight 184/84

800A/1600A 2000A/2500A

net weight 215/97 net weight 245/111 net weight 264/120


power circuit breaker net weight 215/97 power circuit breaker net weight 245/111 power circuit breaker net weight 264/120
power circuit breaker gross weight 257/117 power circuit breaker gross weight 289/131 power circuit breaker gross weight 308/140
gross weight 257/117 gross weight 289/131 gross weight 308/140
net weight 208/95 net weight 239/208 net weight 258/117
non-automatic switch net weight 208/95 non-automatic switch net weight 239/208 non-automatic switch net weight 258/117
non-automatic switch gross weight 250/114 non-automatic switch gross weight 282/128 non-automatic switch gross weight 301/137
net weight
gross weight 123/56
250/114 net weight
gross weight 133/60
282/128 gross weight 301/137
power circuit breaker power circuit breaker
gross weight 163/74 gross weight 176/80
net weight 117/53 net weight 126/57
non-automatic switch non-automatic switch
gross weight 156/71 gross weight 170/77

net weight 153/70 net weight 166/75 net weight 185/84


power circuit breaker net weight 153/70 power circuit breaker net weight 166/75 power circuit breaker net weight 185/84
power circuit breaker gross weight 192/87 power circuit breaker gross weight 205/93 power circuit breaker gross weight 224/102
gross weight 192/87 gross weight 205/93 gross weight 224/102
net weight 147/67 net weight 159/72 net weight 179/81
non-automatic switch net weight 147/67 non-automatic switch net weight 159/72 non-automatic switch net weight 179/81
non-automatic switch gross weight 185/84 non-automatic switch gross weight 198/90 non-automatic switch gross weight 217/99
gross weight 185/84 gross weight 198/90 gross weight 217/99

net weight 260/118 net weight 309/140 net weight 331/150


power circuit breaker net weight 260/118 power circuit breaker net weight 309/140 power circuit breaker net weight 331/150
power circuit breaker gross weight 311/141 power circuit breaker gross weight 361/164 power circuit breaker gross weight 383/174
gross weight 311/141 gross weight 361/164 gross weight 383/174
net weight 253/115 net weight 300/136 net weight 324/147
non-automatic switch net weight 253/115 non-automatic switch net weight 300/136 non-automatic switch net weight 324/147
non-automatic switch gross weight 304/138 non-automatic switch gross weight 352/160 non-automatic switch gross weight 377/171
gross weight 304/138 gross weight 352/160 gross weight 377/171

User Manual 12 User Manual 13


Handling

User Manual 14 User Manual 15


框架断路器 框架断路器
安装尺寸 安装尺寸

Fixed type Fixed type


800A/1600A 3P
固定式 800A/1600A 3P 垂直安装
800A/1600A
固定式 4P 4P 垂直安装
800A/1600A
Vertical installation Vertical installation

in/mm in/mm
in/mm in/mm

6.06(154) 6.06(154) 6.06(154) 6.06(154)

9(228.5)

9(228.5)
5.08(129) 5.08(129)
5.08(129) 5.08(129)

6.44(163.5)
6.44(163.5)
F 8.46(215) 8.46(215) F 12.99(330) 8.46(215)
3.17(80.5) 3.17(80.5)
3.58(91) 8.64(219.5) 3.58(91) 8.64(219.5)

7.95(202) 7.95(202) 12.48(317) 7.95(202)


14.61(371)
14.61(371)
12.91(328)
12.91(328)

0.47(12)
0.47(12)

12.24(311)
10.55(268)
12.24(311)
10.55(268)

5.91(150)
5.91(150)
Datum X
Datum X

8× 0.24 (6)
8× 0.24 (6)
Datum Y
Datum Y

3.17(80.5)
3.17(80.5)
Max overlap 2.36(60)
Max overlap 2.36(60)
0.98(25)
0.98(25)

3.46(88)
4.53(115) 4.53(115)
3.46(88)

4.53(115) 4.53(115) 4.53(115)


0.59(15)
0.59(15)

5.24(133)
5.24(133)

16× 0.51 13
12× 0.51 13

1.77(45)
F

0.88(21.5)
1.77(45)

0.63(16)
0.88(21.5)
0.63(16)

10.06(255.5)
10.06(255.5)

18 19
18 19

User Manual 16 User Manual 17


框架断路器 框架断路器
安装尺寸 安装尺寸

Fixed type Fixed type


800A/1600A
固定式 3P 3P 水平安装
800A/1600A 800A/1600A 4P 4P 水平安装
固定式 800A/1600A
Horizontal installation Horizontal installation

in/mm in/mm
in/mm
in/mm

6.06(154) 6.06(154) 6.06(154) 6.06(154)

9(228.5)
9(228.5)

5.08(129)
5.08(129)

5.08(129)

6.44(163.5)
5.08(129)

6.44(163.5)
F 12.99(330) 8.46(215)
F 8.46(215) 8.46(215)
3.17(80.5)
3.17(80.5)
3.58(91) 8.64(219.5)
3.58(91) 8.64(219.5)

14.61(371) 12.48(317) 7.95(202)


14.61(371) 7.95(202) 7.95(202)
12.91(328)
12.91(328)

0.47(12)
0.47(12)

10.55(268)
12.24(311)
12.24(311)

10.55(268)

5.91(150)
5.91(150)
Datum X
Datum X

8× 0.24 (6)
8× 0.24 (6)
F
F Datum Y
Datum Y

3.17(80.5)
3.17(80.5)
Max overlap 2.36(60)
Max overlap 2.36(60)

0.59(15)
4.53(115) 4.53(115) 4.53(115)
0.59(15)

4.53(115) 4.53(115) 3.46(88) 1.77(45)


16× 0.51 13
3.46(88) 1.77(45) 0.88(21.5)
12× 0.51 13

5.24(133)
0.88(21.5)
5.24(133)

0.94(25)
0.94(25)

2.36(60)
F 10.06(255.5)
2.36(60)

10.06(255.5)

20 20 21 21

User Manual 18 User Manual 19


框架断路器 框架断路器
安装尺寸 安装尺寸

Fixed type Fixed type


2000A/2500A
固定式 3P 3P 垂直安装
2000A/2500A 2000A/2500A 4P
固定式 2000A/2500A 4P 垂直安装
Vertical installation Vertical installation
in/mm in/mm
in/mm in/mm

6.06(154) 6.06(154) 6.06(154) 6.06(154)

9(228.5)

9(228.5)
5.08(129) 5.08(129)

5.08(129) 5.08(129)
6.44(163.5)

6.44(163.5)
F 8.46(215) 8.46(215) F 12.99(330) 8.46(215)
3.17(80.5) 3.17(80.5)
3.58(91) 8.64(219.5) 3.58(91) 8.64(219.5)

7.95(202) 7.95(202) 12.48(317) 7.95(202)


14.61(371) 14.61(371)
12.91(328) 12.91(328)

0.47(12)

0.47(12)
5.91(150)
10.55(268)
12.24(311)

5.91(150)
10.55(268)
12.24(311)
Datum X Datum X

8× 0.24 (6) 8× 0.24 (6)

3.17(80.5)
Datum Y

3.17(80.5)
Datum Y

4.53(115) 4.53(115)
4.53(115) 4.53(115) 4.53(115)
0.79(20) Max overlap 3.31(84)
0.79(20) Max overlap 3.31(84)
3.46(88)

3.46(88)
5.24(133)

5.24(133)
24× 0.51 13
32×0.51 13
1.77(45)

1.77(45)
0.88(21.5)

0.88(21.5)
0.63(16)

0.63(16)
0.69(17.5) 0.69(17.5)
9.53(242) 1.77(45) 9.53(242) 1.77(45)

22 23
22 23

User Manual 20 User Manual 21


框架断路器 框架断路器
安装尺寸 安装尺寸

Fixed type Fixed type


2000A/2500A 3P 3P 水平安装
固定式 2000A/2500A 2000A/2500A 4P
固定式 2000A/2500A 4P 水平安装
Horizontal installation Horizontal installation
in/mm in/mm
in/mm in/mm
6.06(154) 6.06(154) 6.06(154) 6.06(154)

9(228.5)
9(228.5)

5.08(129)
5.08(129)

5.08(129)

6.44(163.5)
5.08(129)

6.44(163.5)
F 12.99(330) 8.46(215)
F 8.46(215) 8.46(215) 3.17(80.5)
3.17(80.5)
3.58(91) 8.64(219.5)
3.58(91) 8.64(219.5)

12.48(317) 7.95(202)
7.95(202) 7.95(202) 14.61(371)

14.61(371) 12.91(328)

0.47(12)
12.91(328)

0.47(12)

10.55(268)

5.91(150)
12.24(311)
10.55(268)
12.24(311)

5.91(150)
Datum X

Datum X

8× 0.24 (6) F

F Datum Y

3.17(80.5)
8× 0.24 (6)

Datum Y

3.17(80.5)
Max overlap 3.31(84)

4.53(115) 4.53(115) 4.53(115)

0.79(20)

0.69(17.5)
Max overlap 3.31(84)
1.77(45)
3.46(88)
4.53(115) 4.53(115) 24× 0.51 13 0.88(21.5)
0.79(20)

0.69(17.5)
1.77(45)
3.46(88)

5.24(133)
24× 0.51 13 0.88(21.5)

1.77(45)
5.24(133)

1.77(45)

2.36(60)
F
2.36(60)

9.53(242) 1.77(45)
F

9.53(242) 1.77(45)

24 24 25 25

User Manual 22 User Manual 23


框架断路器
框架断路器
安装尺寸
安装尺寸
Fixed type Fixed type
3200A 3P 3200A 4P
固定式
Vertical 3200A
installation 3P 垂直安装 Vertical installation

固定式 3200A 4P 垂直安装


in/mm
in/mm in/mm
in/mm

6.06(154) 6.06(154)

6.06(154) 6.06(154)

9.00(228.5)

9.00(228.5)
5.08(129)

5.08(129) 5.08(129)
5.08(129)
6.44(163.5)

6.44(163.5)
C F 13.03(331) 8.50(216)
3.17(80.5) 8.50(216) 8.50(216)
F
3.17(80.5)
M 3.58(91) 8.64(219.5) C

7.99(203) 7.99(203) 3.58(91) 8.64(219.5)


Y M

12.52(318) 7.99(203)
CM
14.61(371) Y

MY
12.91(328) CM
14.61(371)

0.47(12)
CY MY
12.91(328)

0.47(12)
CMY CY
10.55(268)
12.24(311)

10.55(268)
12.24(311)
K CMY

5.91(150)

5.91(150)
Datum X
K Datum X

8× 0.24 (6) 8× 0.24 (6)


Datum Y F Datum Y F

3.17(80.5)
3.17(80.5)
4.53(115) 4.53(115)
1.04(26.4) 4.53(115) 4.53(115) Max overlap 3.46(88)
Max overlap 3.46(88)
0.25(6.4) 0.33(8.5) 0.33(8.5) 3.35(85) 4.53(115) 4.53(115) 4.53(115)
1.04(26.4) 4.53(115) 4.53(115) 4.53(115)

3.35(85)
0.25(6.4) 0.33(8.5) 0.33(8.5)
6.02(153)

6.02(153)
64× 0.51 13
48× 0.51 13

1.77(45)
1.77(45)

0.79(20)
0.30(7.5)
0.79(20)
0.30(7.5)

F
F
0.79(20)

0.79(20) 11.30(287) 1.77(45)

11.30(287) 1.77(45)

26

27

User Manual 24 User Manual 25


框架断路器
框架断路器
安装尺寸
安装尺寸
Withdrawable type Withdrawable type
800A/1600A
抽屉式 3P 3P 垂直安装
800A/1600A 800A/1600A 4P
Vertical installation 抽屉式installation
Vertical 800A/1600A 4P 垂直安装
in/mm
in/mm in/mmin/mm

6.40(162.5) 6.40(162.5) 10.93(277.5) 6.40(162.5)

0.67(17)
0.67(17)
0.43 11 0.43 11

6.89(175)
F

6.89(175)
F 0.43(11)
0.43(11)

3.86(98)
3.86(98)
F
F 4.37(111)
4.37(111)
(Connection position)
(Connection position)
6.14(156) 12.38(314.5)
6.14(156) 12.38(314.5)
(Disconnection position)
(Disconnection position)

14.61(371)
14.61(371) 6.06(154) 6.06(154)
6.06(154) 6.06(154) 12.91(328)
8× 0.24 (6)
12.91(328) 8× 0.24 (6)

5.79(147) 6.10(155)

9.07(230.5)
5.79(147) 6.10(155)

10.55(268)
9.07(230.5)

14.88(378)

5.09(129)
10.55(268)
14.88(378)

1.85(47)
5.09(129)
Circuit breaker
1.85(47)

Circuit breaker installation board


installation board

5.09(129)

6.89(157)

7.85(199.5)
7.64(194)
5.09(129)

6.89(157)

0.85(21.5)
7.85(199.5)
7.64(194)
Datum Y
0.85(21.5)

Datum Y panel perforating size


panel perforating size
13.13(333.5) 8.6(218.5)

8.6(218.5) 8.6(218.5)

4.53(115) 4.53(115) 4.53(115) Max overlap 3.54(90)


4.53(115) 4.53(115) 0.47(12)
Max overlap 3.54(90)
0.47(12)

3.46(88)
3.46(88)

5.59(142)
5.59(142)

1.77(45)
0.85(21.5)
1.77(45)

2.28(58)
32× 0.51 13
0.85(21.5)

24× 0.51 13
2.28(58)

F 0.89(22.5)

13.94(354) 1.77(45)
0.89(22.5)

13.94(354) 1.77(45)

28 28 29 29

User Manual 26 User Manual 27


框架断路器 框架断路器
安装尺寸 安装尺寸

Withdrawable type Withdrawable type


800A/1600A
抽屉式 3P 3P 水平安装
800A/1600A 800A/1600A 4P 4P 水平安装
抽屉式 800A/1600A
Horizontal installation Horizontal installation
in/mm in/mm
in/mm in/mm

6.40(162.5) 6.40(162.5)
10.93(277.5) 6.40(162.5)

0.67(17)

0.67(17)
0.43 11 0.43 11

6.89(175)

6.89(175)
F F
0.43(11) 0.43(11)

3.86(98)
3.86(98)
F
F 4.37(111)
4.37(111)
(Connection position)
(Connection position)
6.14(156) 12.38(314.5)
6.14(156) 12.38(314.5)
(Disconnection position)
(Disconnection position)

6.06(154) 6.06(154) 14.61(371)


14.61(371) 6.06(154) 6.06(154)
12.91(328)
12.91(328) 8× 0.24 (6)
8× 0.24 (6)

5.79(147) 6.10(155)
9.07(230.5)
5.79(147) 6.10(155)

9.07(230.5)
10.55(268)
10.55(268)

5.09(129)

14.88(378)
14.88(378)

5.09(129)
1.85(47)
1.85(47)

Circuit breaker
Circuit breaker installation board
installation board

5.09(129)

6.89(157)

7.85(199.5)

5.09(129)
7.64(194)

6.89(157)

7.85(199.5)
7.64(194)
0.85(21.5)
0.85(21.5)

Datum Y
Datum Y
panel perforating size
panel perforating size
8.6(218.5) 8.6(218.5)
13.13(333.5) 8.6(218.5)

4.53(115) 4.53(115) 4.53(115)

0.89(22.5)
0.89(22.5)

4.53(115) 4.53(115)
1.77(45) 3.46(88) 1.77(45)
3.46(88)
32× 0.51 13 0.85(21.5)
24× 0.51 13 0.85(21.5)
Max overlap 3.54(90)
Max overlap 3.54(90)

0.47(12)
1.77(45)
1.77(45)

0.47(12)

5.59(142)
5.59(142)

4.61(117)
F
13.94(354) 1.77(45)
4.61(117)

F
13.94(354) 1.77(45)

30 31
30 31

User Manual 28 User Manual 29


框架断路器 框架断路器
安装尺寸 安装尺寸

Withdrawable type Withdrawable type


2000A/2500A
抽屉式 3P 3P 垂直安装
2000A/2500A 2000A/2500A 4P
Vertical installation 抽屉式 2000A/2500A 4P 垂直安装
Vertical installation
in/mm
in/mm
in/mm in/mm

6.40(162.5) 6.40(162.5)
10.93(277.5) 6.40(162.5)

0.67(17)

0.67(17)
0.43 11
0.43 11

6.89(175)
F
0.43(11)

6.89(175)
F
0.43(11)

3.86(98)
3.86(98)
F F
4.37(111) 4.37(111)
(Connection position) (Connection position)
6.14(156) 12.38(314.5) 6.14(156) 12.38(314.5)
(Disconnection position) (Disconnection position)

14.61(371) 14.61(371)
6.06(154) 6.06(154) 6.06(154) 6.06(154)
12.91(328) 12.91(328)
8× 0.24 (6) 8× 0.24 (6)

5.79(147) 6.10(155)
5.79(147) 6.10(155)

9.07(230.5)
9.07(230.5)

10.55(268)
10.55(268)

14.88(378)

5.09(129)
5.09(129)
14.88(378)

1.85(47)
1.85(47)

Circuit breaker
Circuit breaker installation board
installation board

5.09(129)

6.89(157)
5.09(129)

7.85(199.5)
6.89(157)

7.64(194)
7.85(199.5)
7.64(194)

0.85(21.5)
0.85(21.5)

Datum Y
Datum Y
panel perforating size
panel perforating size
13.13(333.5) 8.6(218.5)
8.6(218.5) 8.6(218.5)

4.53(115) 4.53(115) 4.53(115)


0.25(6.5)
1.2(30.5)
4.53(115) 4.53(115)
Max overlap 3.54(90)
0.25(6.5)
1.2(30.5) Max overlap 3.54(90)

3.46(88)
3.46(88)

5.59(142)
5.59(142)

1.77(45)
0.85(21.5)
1.77(45)

64× 0.51 13

2.28(58)
F
0.85(21.5)

48× 0.51 13 0.89(22.5)


2.28(58)

F
13.94(354) 1.77(45)
0.89(22.5)

13.94(354) 1.77(45)

32 33
32 33

User Manual 30 User Manual 31


框架断路器 框架断路器
安装尺寸 安装尺寸

Withdrawable type Withdrawable type


2000A/2500A 3P
抽屉式 2000A/2500A 3P 水平安装
2000A/2500A
抽屉式 4P 4P 水平安装
2000A/2500A
Horizontal installation Horizontal installation

in/mm in/mm
in/mm in/mm

6.40(162.5) 6.40(162.5) 10.93(277.5) 6.40(162.5)

0.67(17)

0.67(17)
0.43 11
0.43 11

6.89(175)
F
0.43(11)

6.89(175)
F
0.43(11)

3.86(98)
F 3.86(98)
4.37(111)
4.37(111) F
6.14(156) 12.38(314.5)
6.14(156) 12.38(314.5)

14.61(371)
14.61(371)
12.91(328) 8× 0.24 (6) 6.06(154) 6.06(154)
12.91(328) 6.06(154) 6.06(154)
8× 0.24 (6)
5.79(147) 6.10(155)

5.79(147) 6.10(155)
10.55(268)

9.07(230.5)
14.88(378)

10.55(268)

9.07(230.5)
1.85(47)

14.88(378)
5.09(129)
Circuit breaker

1.85(47)

5.09(129)
installation board Circuit breaker
installation board

5.09(129)

6.89(157)

5.09(129)
0.85(21.5)

7.85(199.5)

6.89(157)
7.64(194)

7.85(199.5)
7.64(194)
0.85(21.5)
Datum Y
panel perforating size Datum Y
panel perforating size

8.6(218.5) 8.6(218.5)
13.13(333.5) 8.6(218.5)

4.53(115) 4.53(115) 4.53(115)

0.89(22.5)
4.53(115) 4.53(115)
0.89(22.5)

1.77(45) 3.46(88) 1.77(45)


3.46(88)
48× 0.51 13 0.85(21.5) 64× 0.51 13 0.85(21.5)

Max overlap 3.54(90)

Max overlap 3.54(90)

1.77(45)
0.25(6.5)
1.77(45)

1.2(30.5)

0.25(6.5)
1.2(30.5)
5.59(142)

5.59(142)
4.61(117)

F
13.94(354) 1.77(45)

4.61(117)
F
13.94(354) 1.77(45)

34 35
34 35

User Manual 32 User Manual 33


框架断路器
框架断路器
安装尺寸
安装尺寸
Withdrawable type Withdrawable type
3200A 3P 3200A 4P
Vertical installation
抽屉式 3200A 4P 垂直安装
Vertical insatallation
抽屉式 3200A 3P 垂直安装
in/mm
in/mm in/mm in/mm

6.40(162.5) 6.40(162.5) 10.93(277.5) 6.40(162.5)


0.43 11 0.43 11

0.67(17)
0.67(17)
F F

6.89(175)
0.43(11)

6.89(175)
0.43(11)

3.86(98)

4.25(108) F
3.86(98) (Connection position)
4.25(108)
F 6.02(153) 12.38(314.5)
(Connection position) (Disconnection position)
C 6.02(153) 12.38(314.5)
(Disconnection position) 14.61(371) 6.06(154) 6.06(154)
M
6.06(154) 6.06(154)
12.91(328)
14.61(371) 8× 0.24 (6)
Y
12.91(328)

5.79(147) 6.10(155)
8× 0.24 (6)

9.23(234.5)
9.04(229.5)
CM

10.55(268)

5.08(129)
14.88(378)
5.79(147) 6.10(155)

5.08(129)

1.85(47)
10.55(268)

MY
Circuit breaker
14.88(378)

installation board
1.85(47)

CY

5.08(129)
Circuit breaker

6.22(158)
5.08(129)

7.89(200.5)
7.68(195)
6.22(158)
installation board

7.89(200.5)
7.68(195)
CMY

0.85(21.5)
K Datum Y
0.85(21.5)

panel perforating size

Datum Y 13.09(332.5) 8.56(217.5)


8.56(217.5) 8.56(217.5) 4.35(115) 4.35(115) 4.35(115)
panel perforating size
1.04(26.4) 4.35(115) 4.35(115) 4.35(115)
4.35(115) 4.35(115) 0.25(6.4) 0.59(150) 0.59(150)
1.04(26.4) 4.35(115) 4.35(115) Max overlap 3.27(83)
0.25(6.4) 0.59(15) 0.59(15) Max overlap 3.27(83)

3.94(100)
3.94(100)

5.98(152)
5.98(152)

2.36(60)
0.79(20)
2.36(60)

96× 0.51 13

1.85(47)
0.79(20)

F
1.85(47)

0.79(20)
72× 0.51 13
F
0.79(20)
16.28(413.5) 1.57(40)

16.28(413.5) 1.57(40)

36

37

User Manual 34 User Manual 35


Terminal Adjustment Terminal Adjustment
Terminals are adjustable in field

Breaker with single terminal Allen wrench Limit clamp


Horizontal terminals Mixed terminals

①Remove and rotate ②Install the terminal and lock

the terminals by 90 degrees the screws with tightening

torque (15~17) N.m

Mixed terminals Vertical terminals

Breaker with double terminals


①Remove and rotate the ②Install the one of the terminal and lock
Horizontal terminals Mixed terminals terminals by 90 degrees the screws with tightening torque (15~17) N.m

Mixed terminals Vertical terminals


③Use the limit clamp to fix and install
another terminal, lock the screws
with tightening torque (15~17) N.m

Note: 3200A only provided with vertical type

User Manual 36 User Manual 37


Terminal Adiustment Neutral Current Transformer
Adjsut terminals clearance A32 Neutral Current Transformer

4and 6MM Allen wrench Dimensions


In(mm)
②Remove the bus bar screws
①Remove the inner heat sink
No need to remove the external heat sink 0.25in(6.4mm) 0.39in(10mm)

④Finished ③Remove the bus bar in sequence

⑤Mounting limit clamp ⑥Install the bus bar and lock the screws with
tightening torque (15~17)N.m

Note:

1. The bar code of Neutral Current Transformer must be the same as that of the circuit breaker and is not interchangeable;
2. Connect the conductor of Neutral Current Transformer to 28#, 29# terminals.

③Install the bus bar in sequence ⑦Install heat sink

User Manual 38 User Manual 39


ELM10消弧维护开关

Neutral Current Transformer ELM103 Install


A32 Neutral Current Transformer
Size (Note:(mm)
Geometric Dimensions Dimension’s unit is mm)
0 Safety Warning:
1)Only professional technicians are allowed for installation and maintennance.
40~50N·m Front View Side View
2)Installation in any damp ,condensed-phase environment with inflamable and explosive
gas is forbidden。
3)When the product is being installed or maintained ,the power must be switched off.
4)You are prohibited from touching the living part when the product is operating.

1 Application
15~17N·m
ELM10 is used to reduce arc hazards and protect personal safety during product mainte-
nance. It should be used together with power circuit breaker which has ARMs protection
function.

Back View Assembly Chart


Main circuit feed direction
2 Specifications

Table 1 Key technical parameter


Main circuit feed

Ambient temp(℃) -20℃~+70℃

Hot and humid Relative humidity should not exceed 50% at +40℃;up to 90% at +20℃;
atmospheric conditions
Upper supply

Pollution class Class 3

Istallation category Ⅱ Mounting Hole


Main circuit feed direction

Rated voltage Ue(V) AC480V/DC24

Rated frequency (Hz) 50/60

Enclosure protection class IP40

Life cycle(times) 1500


Main circuit feed

Lower supply

User Manual 40 User Manual 41


100 Ii=2500A
Model Description Maintain (2.0 x In) No (2.0 x In) (4.0 x In)
50 Measure ARMS
ELM10 Energy-Limiting Maintenance Switch (ELM Switch) 0 Record signal

LSC10 4 Selection
Lockable switch cover 0A Se�ng Maintain
Maintain Maintain
N A B C ARMS
Note:LSC10 is optional unit. Note whether to purchase LSC10. Table 2 7). To turn off ARMs mode,150 System set
the operation as follow:(Note: Prohibit
OFFto turn off ARMs
signal mode,
On On
when ELMs in “ON”state) 100 Protectset Ii=2500A
Ii=2500A Ii=5000A
Model Description Maintain (2.0 x In) No (4.0 x In)
ELM10 ELM10 50 Measure ARMS
(2.0 x In)
ELM10 Energy-Limiting Maintenance Switch (ELM Switch) 0A Se�ng 0 System Record
set DI/DO DI1
signal
5 Debug LSC10 Lockable switch cover
N A B C
System set Clock Set DO1 Func Set
150
Protectset Gauge Set DO2 ARMS
1). ELM10 module needs external power supply to work normally; 100 7). To turnTest/Lock
off ARMs mode, the operation as follow:(Note: Prohibit to turn off ARMs mode,
Note:LSC10 is optional unit. Note whether to purchase LSC10. Maintain DO3 State:1
2). ELM10 module has two power input interface unit. Terminal 1 and 2 are connected to 50 when ELMsCom in “ON”state)
Measure set DO4
AC85-528V or DC110-600V,terminal 5 and 6 are connected to DC24V. Choose one type N.C
0 Record DI/DO DI1
power supply input;
0A Se�ng System set DI/DO DI1
3). Connect signal output terminal 3 and terminal 4 of ELM10 module to terminal 20 and
5 Debug of air circuit breaker respectively;
terminal 21 of secondary disconnector
N A B C
System set Clock Set DO1 Func Set
150
4). After ELM10 is powered on, the power indicator(red) is on. By default, the SWITCH is Protectset Gauge Set DO2 ARMS
1). ELM10 module needs external power supply to work normally; DI1 100 DI1
in OFF position, when the SWITCH is rotated to the ON position, the blue indicator is on and Maintain Test/Lock DO3 State:1
2). ELM10 module has two power input interface unit. Terminal 1 and 2 are connected Func Setto 50 Func Set
ARMs function is opened to connect electrical trip unit. The default protection setting value is ARMS signal Measure No Com
ARMS set
signal DO4
AC85-528V or DC110-600V,terminal 5 and 6 are connected to DC24V. Choose oneARMS type N.C
State 10 OFF DI/DO DI DI1
Changed
2In. To change the protection setting, please adjust it on trip unit. Record
power supply input; State:1 State:1
5). Before ELM10 is connected to trip unit,
3). Connect open
signal the DI1
output function
terminal of trip
3 and unit and
terminal 4 ofset to
ELM10 module to terminal N.C20 and N.C
ARMs mode. The operationterminal
process21 asof
follow:
secondary disconnector of air circuit breaker respectively;
4). After ELM10 is powered on, the power indicator(red) is on. By default, the SWITCH is DI1 DI1
in OFF position, when the SWITCH is rotated to the ON position, the blue indicator is on and
Se�ng set to connectDI/DO Func Set Func Set
0A ARMs functionSystem
is opened electrical trip unit. The
DI1 default protection setting value is ARMS signal No ARMS signal
ARMS OFF
N A B C 2In. To change
System set theSet
Clock DO1 please adjust itFunc
protection setting, Set unit.
on trip 6 ENVIRONMENTAL PROTECTION State 1 DI Changed
150 State:1 State:1
Protectset
5). Before ELM10 to trip unit, open theARMS
is connectedDO2
Gauge Set DI1 function of trip unit and set to
100 In order to protect environment,
N.C when the product or its parts are scrapped, please
N.C properly
MaintainARMs mode.Test/Lock DO3 as follow:
The operation process State:1
50
dispose of them as industrial waste. Or to the recycling and treatment station according to
Measure Com set DO4 N.C
the relevant provisions of the region for classification disassembly、 recycling etc.
0 Record DI/DO DI1

0A Se�ng System set DI/DO DI1


N A B C System set Clock Set DO1 Func Set 6 ENVIRONMENTAL PROTECTION
150 NOARK Electrics (Shanghai) Co.,
6). When ARMs mode is opened, the default protection
Protectset setting value is 2In.
Gauge Set The settingDO2 ARMS
100 Ltd. In order to protect environment, when the product or its parts are scrapped, please properly
multiple can be selected by up and down keys to adjust the protection
Maintain setting parameters.
Test/Lock DO3 State:1
Add: 3857 Sixian Road, Songjiang
dispose of them as industrial waste. Or to the recycling and treatment station according to
ARMs function of trip unit is controlled
50 by the ELM10
Measuremodule,to be turned
Com seton or off,the DO4 N.C
District , Shanghai
325603,P.R.China the relevant provisions of the region for classification disassembly、 recycling etc.
interface of trip unit changes blue
0 from green when ARMs
Record function turned
DI/DO on. The operation
DI1
E-mail:
process as follow: Website:

NOARK Electrics (Shanghai) Co.,


0A Se�ng6). When ARMs mode is opened, the default protection setting value is 2In. The setting
Maintain
Maintain Maintain Ltd.
N A B C System set
multiple can be selectedARMS by up and down keys to adjust the protection setting parameters. Add: 3857 Sixian Road, Songjiang
OFF signal
150 On by the ELM10Onmodule,to be turned on or off,the
ProtectsetARMs function of trip unit is controlled
Ii=2500A District , Shanghai
Ii=5000A
100
Maintain interface of (2.0
trip xunit
In) changes blue Ii=2500A
from green when ARMs function turned on. The operation 325603,P.R.China
No (2.0 x In) (4.0 x In) E-mail:
50 Measure process as follow: ARMS Website:
0 Record signal

7). To turn off ARMs mode, the operation as follow:(Note: Prohibit to turn off ARMs mode,
when ELMs in “ON”state)

0A Se�ng System set DI/DO DI1


N A B C
System set Clock Set DO1 Func Set
150
Protectset Gauge Set DO2 ARMS
100
Maintain Test/Lock DO3 State:1
cted to User Manual 42
50 User Manual 43
Measure Com set DO4
type N.C
0 Record DI/DO DI1
Accessories
Accessories Accessories
Accessories
Undervoltage release/UVT Auxiliary contact/AX
Undervoltage release/UVT
Undervoltage release/UVT

Accessories
Undervoltage release/UVT Theundervoltage
The undervoltagerelease releaseis is
anan optional
optional device
device on on
bothboth manually
manually andand electrically
electrically operated
operated air
circuit Rated Current /
Theswitch
undervoltage release Itisopens an optional device on both manually andfalls
electrically operated circuit
breakers.disconnectors.
It opens the breaker when theitsswitch
supplywhen its falls
voltage supply voltage
to 30–60% to 30–60%
of rated voltage. of rated
If the voltage.
release Voltage /V
A
breakers.
If not It opensisthe
the energized
release breaker when its supply voltage falls to 30–60% of rated voltage. If the release
is tonot
85% energized to 85%
of its supply of itsthe
voltage, supply voltage,
circuit breakerthe switch
cannot bebreaker cannot be or
closed electrically closed
manually.
is not energized
electrically or to 85% of its supply voltage, the circuit breaker cannot be closed electrically or manually.
manually. 240 5
Voltage
AC /V Rated Current /A
Voltage240
/V 480
Rated 2
Current /A
The undervoltage release is an optional device on both manually and electrically operated circuit AC Voltage /V Rated 5Current /A
240
480
110
25 5 0.25
breakers. It opens therelease
Undervoltage
Undervoltage breaker when
releaseratings: its supply voltage falls to 30–60% of rated voltage. If the release
ratings: ACDC 240
is Undervoltage release
not energized to 85% of itsratings:
supply voltage, the circuit breaker cannot be closed electrically or manually. AC 480
110 220
0.252 0.25
DC 480
110 2
0.25
Operational
Operational Inrush/
In rush / DC 220 0.25
Operational
voltage
voltage Dropout
Dropout In rush /continuous
continuous 110
220 0.25
0.25
Control
Control voltage
rangrang
e e Dropout
voltage
voltage continuous
power power Operating
Opening
DC
Control rang
voltagesrelease ratings:
voltage e85–110%
85–110% voltage
30–60%
30–60% power consumption
consumptio n Opening
time (ms)
time (ms)
220 0.25
Undervoltage
voltage 85–110% 30–60% consumptio n time (ms)
24 Vdc Vdc
24-30 20–26 Vdc
20–33 7–147–14
Vdc Vdc 250 W/4.5 W W 7070
24 Vdc 20–26 Vdc Vdc 7–14 Vdc 250 W/4.5250WW/4.5 70
Operational
41–53
In rush / The auxiliary contact remotely monitors ON/OFF position of power circuit breaker or
48 Vdc Vac/Vdc
48-60 41–66Vdc Dropout14– 14–
29 Vdc 275 W/4.5 W 70
48 Vdc voltage
41–53 Vdc Vac/Vdc voltage
14– 29 Vdc29 Vdc continuous 275WW/4.5
275 W/4.5 W 70 70
Non-automatic Switch from remote place.
Control rang e power Opening
110-130
voltage110-130Vac/Vdc
Vac/Vdc 85–110%94–143 Vac/Vdc
94–143 Vac/Vdc 30–60% 33–78Vac/ Vdc
33–78Vac/ 275 W/4.5 W (ms) 70
110-130 Vac/Vdc 94–143 Vac/Vdc 33–78Vac/ Vdc Vdcconsumptio n 275
275 W/4.5 WW/4.5
time W 70 70 Contact configuration:
24 Vdc200-240Vac/
200-240Vac/Vdc 170–264V
Vdc 20–26 Vdc ac/Vdc
170–264V 7–14 Vdc60–144
ac/Vdc Vac/Vac/
60–144 Vdc250 W W/4.5W
VdcW/4.5 275 70
275 W/4.5W 70 70 44: 4NO and 4NC;66: 6NO and 6NC;
200-240Vac/ Vdc 170–264V ac/Vdc 60–144 Vac/ Vdc 275 W/4.5W 70
48 Vdc380–415 Vac
380–415
380–415 Vac Vac
323– 457 Vac
41–53 Vdc
323– 323– 457 Vac
457 Vac
114–249 Vac 275 W/4.5 450
14– 29 Vdc
114–249
114–249 Vac Vac
W W/4.5W70
450 W/4.5W
450 W/4.5W 70
70
70
44C: 4NO or 4NC;66C: 6NO or 6NC.
110-130 Vac/Vdc 94–143 Vac/Vdc 33–78Vac/ Vdc 275 W/4.5 W 70
Shunt trip release/SHT
Shunt release/SHT 200-240Vac/ Vdc 170–264V ac/Vdc 60–144 Vac/ Vdc 275 W/4.5W 70 Motor operator
Shunt trip release/SHT
380–415 Vac 323– 457 Vac 114–249 Vac 450 W/4.5W 70

Shunt trip release/SHT

The shunt trip isisan


anoptional device on
oncircuit breakers.It opens theopens
circuitthe
breaker
TheThe shunt
shunt triptrip optional
is an optional device
device air switch
on circuit disconnectors.It
breakers.It opens the circuit switch breaker
breaker
instantaneously
instantaneously when
when itsitscoil
coilis isenergized
energizedby a voltage input.
instantaneously when its coil is energized by aby a voltage
voltage input.
input.
The shunt trip is an optional device on circuit breakers.It opens the circuit breaker
instantaneously when its coil is energized by a voltage input.

Shunt
Shunt trip ratings:
Shunt triptrip ratings:
ratings:
Operational Irush/
Operational
Operational
voltage Irush/ Inrush/
continuous
Shunt trip ratings:
Control voltage
voltage
rang e continuous
continuous
power Opening
Control
Control
voltage rang rang
e e
70–110% power power n
consumptio Opening
timeOperating
(ms)
voltages
voltage 70–110%
70–110% consumption
consumptio n time (ms)
time (ms)
Operational Irush/
24-30 Vdc voltage17– 33 Vdc continuous250 W/4.5 W 35
Control VdcVdc
24-30
24-30 rang 17–
e 33 Vdc
17– 33 Vdc power 250 W/4.5 W
250 W/4.5 WOpening 35 35
The electric motor charges the closing spring of mechanism when the circuit breaker is
48-60 V dc
voltage 70–110% 34–66 V dc consumptio275n W/4.5 W time (ms) 35
48-60 V dcVac/Vdc
48-60 34–66 V dc Vac/Vdc
34–66 275 W/4.5 W
275 W/4.5 W 35 35 closed.
24-30110-130
Vdc Vac/Vdc 77–143Vac/Vdc
17– 33 Vdc W W/4.5 W
250 W/4.5275 35 35
110-130 Vac/Vdc
110-130 Vac/Vdc 77–143Vac/Vdc
77–143Vac/Vdc 275 W/4.5 W
275 W/4.5 W 35 35 Factory installed only.
48-60 208-240Vac/
V dc Vdc 34–66 V146–264V
dc ac/Vdc 275 W/4.5275
W W/4.5W 35 35
208-240Vac/ Vdc Vdc
20 8-240 Vac/ 146–264V ac/Vdc
146–264V ac/Vdc 275 W/4.5W
275 W/4.5W 35 35
Mechanical charging handle can be used when maintaining or without power supply.
110-130 Vac/Vdc 77–143Vac/Vdc 275 W/4.5 W 35 Equipped with a limit switch contact which signals that spring is charged.
380-415Vac 266-458.5Vac 275W/4.5W 35
Closing release/XF 208-240Vac/ Vdc 146–264V ac/Vdc 275 W/4.5W 35
Closing release/XF
Closing release/XF Miss insertion prevent device

Closing release/XF

The closing release is an optional device. It remotely closes the circuit breaker
TheThe
closing release is anisoptional device. It remotely closes the circuit breaker
when closing
the coil release
is energized anby
optional device.
a voltage input.It remotely closes the air switch disconnector breaker
when therelease
coil is energized by a voltage input. closes the circuit breaker
when
The closing the coilisisanenergized by a voltage
optional device. input.
It remotely
when the coil is energized by a voltage input.

Closing release ratings:


Closing release ratings:
Closing release ratings:
Closing release ratings: Operational Inrush/
Operational
voltage Inrush/
continuous
Control Operational
voltage
rang e Inrush/
continuous
power Opening
Control Operational
rangvoltage
e Inrush/ power continuous Opening
voltage voltage85–110% continuous consumptio n time (ms)
Control
voltage
Control rang e
rang e85–110% power n
power consumptio Operating
Opening time (ms)
voltagevoltages
24-30 Vdc 85–110% 85–110%
20– 33 Vdc consumptio 250nconsumption
W/4.5 W time (ms) time (ms)
35
24-30 Vdc 20– 33 Vdc 250 W/4.5 W 35
Vdc VVdc
24-30
24-3048-60 dc 41–6633
20– 33 Vdc20– Vdc
V dc 250 W/4.5275 250 W/4.5
W W/4.5 W W 35 35 35
48-60 V dc 41–66 V dc 275 W/4.5 W 35
V48-60
48-60110-130
dc V Vac/Vdc
dc dc41–66 V dc
41–66 V94–143Vac/Vdc W 275
275 W/4.5 275 W/4.5
W/4.5 W W 35 35 35 to
110-130 Vac/Vdc 94–143Vac/Vdc 275 W/4.5 W 35 to of main breaker does
When main breaker is inserted into the cassette, if the rating
110-130110-130
Vac/VdcVac/Vdc
208-240Vac/
208-240Vac/ Vdc
Vdc 94–143Vac/Vdc
94–143Vac/Vdc
177–264V ac/Vdc
177–264V ac/Vdc
275 W/4.5275W 275 W/4.5 W 35
W/4.5W
275 W/4.5W 35
35 35 to
not match the cassette, it will mechanically prevent main breaker to be inserted in the
208-240Vac/ Vdc
208-240Vac/ Vdc 177–264V177–264V
ac/Vdc ac/Vdc 275 W/4.5W 275 W/4.5W 35 35 cassette.
The installation method is variable according to ratings.

User Manual 24
User
UserManual
Manual 24
24
User Manual 44 User Manual 45
Accessories
Accessories Accessories
Safety shutter
Safety shutter OFF position keylock/KLK

Accessories
Safety shutter

It is Itthe
is the automatic
automatic safety
safety devicetotoprotect
device protectthe
the connectors
connectors ofofmain
maincircuits by by
circuits cutting off dangerous
cutting off Suitable for A32 Power circuit breaker and ASD32 No-automatic switch
contactcontact
dagerous from outside
from while
outsidethewhile
breaker
theisbreaker
draw out.
is When
draw the
out.main
Whenbreaker is drawn
the main in, the
breaker is safety Block a breaker in OFF position to ensure the breaker can not be closed
drawn shutter is safety
in, the automatically
shutter open.
is automatically open. One circuit breaker is provided with one lock and one key
OnlyOnly available
available for withdrawable
for withdrawable circuit
circuit breaker
breaker & non-automatic
& non-automatic switch.
switch. Two circuit breakers are provided with two locks and one key
Three circuit breakers are provided with three locks and two keys

Safety
Safety shutter
shutter lock lock Pushbutton lock device/VBP

It is the automatic safety device to protect the connectors of main circuits by cutting off dangerous
contact from outside while the breaker is draw out. When the main breaker is drawn in, the safety
shutter is automatically open.
Only available for withdrawable circuit breaker & non-automatic switch.

Safety shutter lock

When Whthe
en tmain
he mabreaker
in breakeis r isat
at disconnected
disconnected po position,
sition, loclock
k the the
safesafety
ty shuttshutter to provent
er toprevent main The cover prevents the access to control push button of the breaker
mainbreaker
breaker pushed
pushed in.in. Factory instolled only
OnlyOnly
available
availablefor withdrawable
for withdrawable circuit breaker
circuit breaker& non-automatic
& non-automatic switch.
switch. Scope of delivery: Lockable cover (lock with key is not a part of delivery)
LockLock
is not provided.
is not provided.
WDiameter
e mainof
brethe
hen thDiameter erlock
akof the should
lock
is at d be
isconshould
necte 0.12in
be
d po n, loto
sitio0.12inck t0.22in.
hto
e s0.22in.
afety shutter toprevent main
breaker pushed in.
Only available for withdrawable circuit breaker & non-automatic switch.
Mechanical interlocks
Mechanical withwith
interlocks cables
cables Doorframes
Lock is not provided.
Diameter of the lock should be 0.12in to 0.22in.

Mechanical interlocks with cables 78in/2m(max)


78in/2m(max)

78in/2m(max)
Circuit Circuit
diagram On/Off On/Off
diagram state state

Circuit diagram On/Off state A B A B


A B 0 0
0 0
0 0
1 0
A B 1 0
A B
1 0 A B
0 1
0 1 0 1

For mutual interlocking of 2 or 3 (in preparation) breakers


Mechanical interlock with cable In the scope of delivery for each PCB
For mutual interlocking of distance
2 or 3 (in preparation)
positionsbreakers
ForCable length
mutual for maximum
interlocking 2 orof3and
ofbreaker mounting
(inASD32
preparation) of interlocks 78in(2m)
breakers Degree of protection IP40
Mechanical
Suitable interlock
for A32 Power with cable
circuit No-automatic switch
Mechanical
CableScope
length
interlock
of delivery:
for maximum
with cable
2 interlocksdistance
and 2 cablesof(2mounting
breakers version), 3 interlocks
positions and 6 cables 78in(2m)
of interlocks (3 breakers version) Can be ordered separately as a spare part
Cablefor
Suitable length
A32 for maximum
Power circuit distance of mounting
breaker and positions of interlocks
ASD32 No-automatic switch 78in(2m)
Suitable
Scope for A322Power
of delivery: circuit
interlocks andbreaker and(2
2 cables ASD32 No-automatic
breakers version), switch
3 interlocks and 6 cables (3 breakerss version)
Scope of delivery: 2 interlocks and 2 cables (2 breakers version), 3 interlocks and 6 cables (3 breakers version)
User Manual 26

User Manual 46 User Manual 47


User Manual 26
Accessories Accessories
Position indicator/EF
External current transformer for Neutral

External current transformer for neutral conductor.


An external transformer for N-pole protection of three-pole circuit breakers in four-
Indicate position of the breaker - connected, testing, disconnected
wire network, installed on the neutral conductor, the current transformer enable
For withdrawable type devices only
measurement and protection of the neutral conductor.
3 CO contacts, one contact for each breaker position
● External neutral protection for three pole breaker only.
Connected to secondary terminals #58, 59, 60 (Connected), #61, 62, 63 (Test), #64, 65,
66 (Disconnected)
Factory installed only - in the scope of delivery there are additional secondary terminals Energy-limiting maintenance switch
#58-66
Phase barriers

ELM10 is used to mitigate arc hazards and protect personal safety during product
maintenance. It should be used in coordination with Power Circuit Breakers with ARMs
protection function.

Ambient temp(℃) -20℃~ +70℃


Relative humidity can be up to 90% at +20℃
Atmospheric conditions of humidity and heat
Improve insulation level between main terminals and should not exceed 50% at +40℃
Delivered as set (2pcs for 3P version, 3 pcs for 4P version) Pollution class Class 3
Istallation category Ⅱ
Rated voltage Ue(V) AC480V/DC24
Rated frequency (Hz) 50/60
Enclosure protection class IP40
Electrical/mechanical endurance(times) 1500

Lockable switch cover for ELM10 switch

LSC10 is lockable switch cover for ELM10 switch with a 7mm locking hole, it is an
optional unit, please comment if is required when purchasing.

User Manual 48 User Manual 49


Control circuit
Control circuitwiring
wiring Control circuit
Control circuit wiring
wiring
Secondary circuit wiring
A32 Power circuit breaker control circuit reference wiring diagram(4 NO and 4 NC & 6 NO and 6NC auxiliary ) Secondary circuit wiring
A32 Power circuit breaker control circuit reference wiring diagram(4 NO and 4 NC & 6 NO and 6NC auxiliary ) A32 Power
A32 Power circuit
circuit breaker
breaker control
control circuit
circuit reference
reference wiring
wiring diagram(4
diagram(4 groups
groups && 6groups
6groups auxiliary
auxiliary ))
e e
Ready to Spring Connecting Disconnecting
Fault close contact Opening Closing Ready to
charge Closing Opening positon Test positon positon Spring Connecting Disconnecting
indication indication Fault close contact Opening Closing
N indication indication indication Auiliary contact - for user indication indication indication charge Closing Opening positon Test positon positon
N indication indication indication indication indication Auiliary contact - for user indication indication indication

SB1 SB2 SB3 HL2 HL3 HL4 HL5 HL6 HL7


HL1 HL8 ELM10 NCT12N SB1 SB2 SB3 HL2 HL3 HL4 HL5 HL6 HL7
HL1 HL8 ELM10 NCT12N
AX1 AX2 AX3 AX4 AX5 AX6

AX1 AX2 AX3 AX4 AX5 AX6


4 5 6 8 15 16 17 18 19 20 22 24 26 28 32 34 36 37 39 40 42 44 46 48 50 52 54 16 18 20 22 58 61 64
FU
XT 4 5 6 8 15 16 17 18 19 20 22 24 26 28 32 34 36 37 39 40 42 43 45 46 48 49 51 52 54 55 13 58 61 64
FU
XT
QF MD
SHT XF UVT
SAL Smart Uint Control power QF
SHT XF UVT
MD

TA
1 2 SA SAL Smart Uint Control power

1 2 SA
XT TA
1 2 3 7 10 11 12 21 23 25 27 29 31 33 35 38 41 43 45 47 49 51 53 55 15 17 19 21 59 62 65 FU
XT
1 2 3 7 10 11 12 21 23 25 27 29 31 33 35 38 41 44 47 50 53 56 59 62 65 FU

A+ B- Shield ground
QF - circuit breaker SA - position switch
Smart Uint power Modbus interface when control voltage is DC,please identify positive and negative poles TA - current transformer SAL - micro switch
A+ B- Shield ground
No wiring if communication XT - terminal FU - fuse QF - circuit breaker SA - position switch
function is not available TA - current transformer SAL - micro switch
Smart Uint power Modbus interface when control voltage is DC,please identify positive and negative poles
When H-type controller, 6 NO and 6NC auxiliary contacts are selected at the same time, XT - terminal FU - fuse
No wiring if communication
please refer to additional secondary circuit wiring diagram.
function is not available

Power input SHT shunt release


1#, 2#: auxiliary power input (direct input DC24V/AC120V/AC240V). 31#, 32#: SHT shunt release working power input, if DC working
voltage is used, 31# is positive pole, 32# is negative pole. SB1 Power input SHT shunt release
Fault trip auxiliary signal opening button should be provided by user itself. 1#, 2#: auxiliary power input (direct input DC24V/AC120V/AC240V). 31#, 32#: SHT shunt release working power input, if DC working
3#, 4#, 5#: fault trip signal output XF shunt release voltage is used, 31# is positive pole, 32# is negative pole. SB1
Auxiliary signal contact capacity: AC380V, 2A; DC250V, 0.3A; 33#, 34#: XF closing coil working power input, if DC working voltage Fault trip auxiliary signal opening button should be provided by user itself.
Fault signal indicator HL1 should be provided by user itself. is used, 33# is positive pole, 34# is negative pole. SB2 closing button 3#, 4#, 5#: fault trip signal output
Ready to close contact indication (optional) should be provided by user itself.
XF shunt release
Auxiliary signal contact capacity: AC380V, 2A; DC250V, 0.3A;
6#,7#,8#: ready to close contact indication; 33#, 34#: XF closing coil working power input, if DC working voltage
UVT undervoltage relasse (optional) Fault signal indicator HL1 should be provided by user itself.
HL8 signal indicator should be provided by user itself. is used, 33# is positive pole, 34# is negative pole. SB2 closing button
35#, 36#: UVT undervoltage release working power input; Ready to close contact indication (optional) should be provided by user itself.
Communication output - (with H type smart unit) SB3 emergency disconnecting button should be provided by user 6#,7#,8#: ready to close contact indication;
itself. UVT undervoltage relasse (optional)
10#, 11#: communication interface output, where 10# is A+, 11# is B-; HL8 signal indicator should be provided by user itself.
Undervoltage release is within special order range, wiring are not 35#, 36#: UVT undervoltage release working power input;
12#: communication shielded ground wire.
provided for regular supply. Communication output - (with H type smart uint) SB3 emergency disconnecting button should be provided by user
Programmable signal output interface - (optional) 10#, 11#: communication interface output, where 10# is A+, 11# is B-; itself.
MD spring charge motor working power
15#, 16#, 17#, 18#: Programmable output interface; 37#, 38#, 39#: MD spring charge motor working power input; 12#: communication shielded ground wire. Undervoltage release is within special order range, wiring are not
19#: common terminal; HL2 spring chargr indicator should be provided by user itself. provided for regular supply.
If need this function, please contace NOARK sales. Programmable signal output interface - (optional)
AX1 - AX6 auxiliary contacts MD spring charge motor working power
15#, 16#, 17#, 18#: Programmable output interface;
40# - 55# (AX1 - AX4): 4 groups of auxiliary contacts for regular supply; 37#, 38#, 39#: MD spring charge motor working power input;
Programmable signal input interface - (with H type smart unit) 19#: common terminal;
15# - 22# (AX5 - AX6): add 2 groups of auxiliary contacts to form HL2 spring chargr indicator should be provided by user itself.
20#, 21#: Programmable input interface DI1; If need this function, please contace NOARK sales.
specially ordered 6 groups of auxiliary contacts, no wirings for regular AX1 - AX6 auxiliary contacts
When ELM10 is slected, connect signal output terminal 3 and terminal suuply;
4 of ELM10 module to terminal 20 and terminal 21 of control circuit of Programmable signal input interface - (with H type smart unit) 40# - 51# (AX1 - AX4): 4 groups of auxiliary contacts for regular supply;
HL3, HL4 status indicators should be provided by user itself.
power circuit breaker respectively. 20#, 21#: Programmable input interface DI1; 52# - 56# (AX5 - AX6): add 2 groups of auxiliary contacts to form
22#, 23#: Programmable input interface DI2; Withdrawable circuit breker 3-position indicator (optional) When ELM10 is slected, connect signal output terminal 3 and terminal specially ordered 6 groups of auxiliary contacts, no wirings for regular
DI input contact capacity: DC24V. 58#, 59#: connecting posation indicator; 4 of ELM10 module to terminal 20 and terminal 21 of control circuit of suuply;
When H-type controller, 6 NO and 6NC auxiliary contacts are 61#, 62#: test posation indicator; power circuit breaker respectively. HL3, HL4 status indicators should be provided by user itself.
selected at the same time, please refer to additional secondary 64#, 65#: disconnecting position indicator; 22#, 23#: Programmable input interface DI2;
HL5, HL6, HL7 signal indicator should be provided by user itself; Withdrawable circuit breker 3-position indicator (optional)
circuit wiring diagram. DI input contact capacity: DC24V.
this function is only avaiable for specially ordered withdrawable circuit 58#, 59#: connecting posation indicator;
breakers, no wiring for regular supply. 61#, 62#: test posation indicator;
Voltage display signal input - (with H type smart unit) Voltage display signal input - (with H type smart unit) 64#, 65#: disconnecting position indicator;
24#, 25#, 26#, 27#: A, B, C, N phase voltage input terminals respectively. 24#, 25#, 26#, 27#: A, B, C, N phase voltage input terminals respectiv HL5, HL6, HL7 signal indicator should be provided by user itself;
this function is only avaiable for specially ordered withdrawable circuit
NCT12N - (optional) NCT12N - (optional) breakers, no wiring for regular supply.
28#, 29#: External current transformer for neutral conductor. 28#, 29#: External current transformer for neutral conductor.

User Manual 31

User Manual 50 UserManual


User Manual 31
51
Control circuit wiring Control circuit
circuit wiring
wiring
Control circuit wiring Control
Secondary circuit wiring Secondary circuit wiring
ASD32 Non-automatic switch control circuit referance wiring diagram(4 NO and 4 NC & 6 NO and 6NC auxiliary ) ASD32 Non-automatic
Non-automatic switch
switch contaol
contaol circuit
circuit reference
reference wiring
wiring diagram(4
diagram(4 groups
groups && 6groups
6groupsauxiliary
auxiliary))
ASD32 Non-automatic switch control circuit referance wiring diagram(4 NO and 4 NC & 6 NO and 6NC auxiliary ) ASD32

e
Ready to Spring Connecting Disconnecting
close contact Opening Closing Ready to
charge Closing Opening positon Test positon positon Spring Connecting Disconnecting
indication close contact Opening Closing
N indication indication indication Auiliary contact - for user indication indication indication charge Closing Opening positon Test positon positon
N indication indication indication indication Auiliary contact - for user indication indication indication

SB1 SB2 SB3 HL2 HL3 HL4 HL5 HL6 HL7


SB1 SB2 SB3 HL2 HL3 HL4 HL5 HL6 HL7
HL8
HL8
AX1 AX2 AX3 AX4 AX5 AX6
AX1 AX2 AX3 AX4 AX5 AX6
6 8 32 34 36 37 39 40 42 44 46 48 50 52 54 16 18 20 22 58 61 64
FU
6 8 32 34 36 37 39 40 42 43 45 46 48 49 51 52 54 55 13 58 61 64
XT FU
XT

QF MD
SHT XF UVT
QF MD
Control power SHT XF UVT
Control power
SA
TA SA
TA

7 31 33 35 38 41 43 45 47 49 51 53 55 15 17 19 21 59 62 65 FU
XT
7 31 33 35 38 41 44 47 50 53 56 59 62 65 FU

QF - circuit breaker SA - position switch


when control voltage is DC,please identify positive and negative poles TA - current transformer SAL - micro switch QF - circuit breaker SA - position switch
XT - terminal FU - fuse when control voltage is DC,please identify positive and negative poles TA - current transformer SAL - micro switch
XT - terminal FU - fuse

Ready to close contact indication (optional)


6#,7#,8#: ready to close contact indication; Ready to close contact indication (optional)
HL8 signal indicator should be provided by user itself. 6#,7#,8#: ready to close contact indication;
HL8 signal indicator should be provided by user itself.
SHT shunt release
31#, 32#: SHT shunt release working power input, if DC working SHT shunt release
voltage is used, 31# is positive pole, 32# is negative pole. SB1 31#, 32#: SHT shunt release working power input, if DC working
opening button should be provided by user itself. voltage is used, 31# is positive pole, 32# is negative pole. SB1
opening button should be provided by user itself.
XF shunt release
33#, 34#: XF closing coil working power input, if DC working voltage
XF shunt release
is used, 33# is positive pole, 34# is negative pole. SB2 closing button
33#, 34#: XF closing coil working power input, if DC working voltage
should be provided by user itself.
is used, 33# is positive pole, 34# is negative pole. SB2 closing button
UVT undervoltage relasse (optional) should be provided by user itself.
35#, 36#: UVT undervoltage release working power input;
UVT undervoltage relasse (optional)
SB3 emergency disconnecting button should be provided by user
35#, 36#: UVT undervoltage release working power input;
itself.
SB3 emergency disconnecting button should be provided by user
Undervoltage release is within special order range, wiring are not
itself.
provided for regular supply.
Undervoltage release is within special order range, wiring are not
MD spring charge motor working power provided for regular supply.
37#, 38#, 39#: MD spring charge motor working power input;
MD spring charge motor working power
HL2 spring chargr indicator should be provided by user itself.
37#, 38#, 39#: MD spring charge motor working power input;
AX1 - AX6 auxiliary contacts HL2 spring chargr indicator should be provided by user itself.
40# - 55# (AX1 - AX4): 4 groups of auxiliary contacts for regular supply;
AX1 - AX6 auxiliary contacts
15# - 20# (AX5 - AX6): add 2 groups of auxiliary contacts to form
40# - 51# (AX1 - AX4): 4 groups of auxiliary contacts for regular supply;
specially ordered 6 groups of auxiliary contacts, no wirings for regular
52# - 56# (AX5 - AX6): add 2 groups of auxiliary contacts to form
suuply;
specially ordered 6 groups of auxiliary contacts, no wirings for regular
HL3, HL4 status indicators should be provided by user itself.
suuply;
Withdrawable circuit breker 3-position indicator (optional) HL3, HL4 status indicators should be provided by user itself.
58#, 59#: connecting posation indicator;
Withdrawable circuit breker 3-position indicator (optional)
61#, 62#: test posation indicator;
58#, 59#: connecting posation indicator;
64#, 65#: disconnecting position indicator;
61#, 62#: test posation indicator;
HL5, HL6, HL7 signal indicator should be provided by user itself;
64#, 65#: disconnecting position indicator;
this function is only avaiable for specially ordered withdrawable switchs,
HL5, HL6, HL7 signal indicator should be provided by user itself;
no wiring for regular supply.
this function is only avaiable for specially ordered withdrawable circuit
breakers, no wiring for regular supply.

User Manual 31
User Manual 52 UserManual
User Manual 31
53
Profile of SU Profile of SU

Overview All power circuit breakers are equipped with a


replaceable smart unit. The smart unit is specially
Smart Unit 2.0
LI Protection designed to protect power systems and loads. It is
applicable to 50/60Hz power grids and mainly used
for power distribution and feeder protection, to
protect lines and power supplies from overload,

Smart Unit short circuit, ground-fault, current imbalance,


over-frequency, under-frequency, reverse power
and other faults. Due to the load monitoring,
demand protection and zone-selective interlocking,
the power grid can work reasonably. The smart unit
can also be used to measure the current, voltage,
power, frequency, electric energy, demand, harmon-
ics and other parameters of grid nodes, and record
Smart Unit 3.0
LSI Protection and maintenance parameters such as the fault,
alarm, operation, maximum current history and
switch contact wear. When the power grid is subject
C

to communication networking, the controller can


M

be used as a remote terminal of the power automa-


Y

tion network for remote metering, signaling, con-


CM

trol, regulation etc. In addition, the controller sup-


MY

ports multiple protocols to meet various network-


CY

ing requirements.
CMY

Smart Unit 4.0 Naming of Smart Unit


LSIG Protection

3 . 0 A
a b c
Table of Models
Protection type Measurement type
a c
2: LI protection Basic type M
3: LSI protection Ammeter type A
4: LSIG protection Harmonics type H
Note: M type is LED display; A and H types are
LCD display.

Table of Models Design version


b
M A H
Distinguish the design version of the smart unit. “0” means the
2.0N first version.
3.0N
4.0N

User Manual 54 User Manual 55


Profile of SU Profile of SU

Appearance Appearance

Appearance Indicators Description of Rating plug


The Rating plug module is used to indicate the rated current of the circuit breaker in operation.
Indicatiors If the rating plug module needs to be replaced, first power off the controller, then take out the original rating plug module
1 Ig indicator: It is ON in case of tripping due to ground-fault. by a flat-blade screwdriver and install the required rating plug module.
2 Ir indicator: It is flashing in case of long time overload protec- Note: The rating of replaced plug-in module should not exceed the specified frame size rating in factory and not less than
tion and normally ON after Long time delay tripping. It will return
the required minimum value of frame size rating.
to the normal state after receiving the reset command.
3 Isd indicator: It is ON in case of Short time delay trip.
4 Ii indicator: It is ON in case of instantaneous tripping of the
short circuit. USB port
5 Running indicator: It is flashing during normal running. In case of no power supply, the controller can be powered on through the 5V USB port, to view its internal information and
6 A and H model: LCD, three-color backlight, green in normal run- test its tripping function.
ning, yellow in alarm and red in case of tripping due to fault cur-
rent.
Battery features
M model: LED digital tube display.
1. In case of no power supply, you can view the internal information of the controller by installing batteries.
Buttons 2. When batteries have been installed but there is no auxiliary power supply or rapid-saturable power supply, the main chip
7 ESC: Exit the current menu and enter the previous menu, or of the controller will be in the sleep state. Press“ESC”to activate the main chip, and view the internal records and parameters
C
cancel the current parameter settings. of the controller.
M
8 Down: move down or decrease the setting value (“-”);
3. In the absence of the auxiliary power supply, the fault indicator will be normally ON after the circuit breaker trips due to
Y 9 Up: move up or increase the setting value (“+”).
any fault, to facilitate troubleshooting by maintenance personnel.
CM 1600
10 OK: Enter the sub-menu of the selected box or enable one box
to change the values. Note: Battery model: ER14250; battery voltage: 3.6V, non-rechargeable. The normal operation of the controller is not affected
MY
Tsd by the use of batteries.
CY
Adjustment Interface
CMY 11 Long time delay current setting Ir
K
12 Long time delay trip time tr
Tg
13 Short time delay current Isd
14 Short time delay trip time setting tsd Reset button
15 Instantaneous current setting Ii
16 Ground fault current setting Ig Fault indicator
17 Ground fault tripping time setting Tg
18 Testing button: Tripping testing button
Reset after trip
19 USB port
20 Rating plug When the circuit breaker trips due to any fault, the correspond-
21 Transparent cover lock hook ing indicator will be ON, the LCD will turn red, and the trip inter-
22 Battery location face will be shown on the LED display. First press the“Reset”
button (see the left figure) and then“ESC”to reset the control-
ler. The default interface of the controller will appear.

3.0 4.0
Reset after alarm
1600 1600 When the circuit breaker sends an alarm, the LCD will turn

Tsd
yellow, and the LED ALM indicator will be ON. In this case, alarm
record need to be check. After the alarm is cleared, the control-
ler can return to the normal state.

User Manual 56 User Manual 57


Function Description Profile of SU
The smart unit is used for power distribution protection. It can be configured as basic type, Amme-
ter type and harmonics controllers.
Knob Setting Instructions
Function Model M (Basic type) A (Ammeter type) H (Harmonic type)
Open the standard transparent cover and carry out
Protection Long time protection
function the necessary settings of the controller. The knob is
Overload pre-alarm
used mainly to set protection parameters: long-time
Short time protection
d e l a y, s h o r t- t i m e d e l a y, i n s t a n t a n e o u s , a n d
Instantaneous protection
ground-fault values. Under normal circumstances,
Neutral protection
the knob settings can meet the system require-
Ground-fault protection 4.0 4.0 4.0
ments. Fine-tuning is not necessary for the function
Current unbalance protection
parameters.
MCR and HSISC protection
Voltage unbalance protection
Overvoltage protection
Undervoltage protection Open the standard transparent Set the knobs with a
Over-frequency protection cover with a flat-blade screw- flat-blade screwdriver
driver
Under-frequency protection
Phase sequence protection Long time delay setting Take In=1600A as an example
Reverse active power protection
C
Demand value protection
In=1600A
Harmonics protection
Ir=0.7xIn=1120A
M

Thermal memory
Tr=2s(@6Ir)
Y

CM Measurement Current measurement


function
MY Voltage measurement
Long time delay
CY Frequency measurement
Short time delay setting Take In=1600A as an example
CMY Power measurement

K
Power factor measurement
Tsd
Electric energy measurement
In=1600A
Demand value measurement
Isd=4 xIr=4480A
Harmonic measurement
Tsd=0.4S
Test function
Record of operations Note: “X” of the Tsd setting knob: Disable the shor t-delay protection.
Short time delay Tsd setting panel: OFF: definite time setting area; ON: inverse time
Maintenance Trip records setting area
function Alarm records
Instantaneous parameter setting Take In=1600A as an example
Position change records
Contact wear records
Load monitoring
In=1600A
Zone Selective Interlocking
Ii=15xIn=24000A
Other RS485 communication function
functions
Digital input/output DI/DO
Real time clock Note: X=off
Instantaneous
LED display
Ground-fault protection time setting Take In=1600A as an example
Tri-color LCD display
HMI LED status indication
Tg
Button operation In=1600A
Knob setting Ig=880A
USB test port Tg=0.4S
Note: Please Contact Noark if customers use functions like Load monitor, Zone-Selection Interlocking and digital input/out-
Note: “X” of the Tg setting knob: Disable the ground protection.
put DI/DO. ground Tg setting panel: OFF: definite time setting area; ON: inverse time
setting area

User Manual 58 User Manual 59


Profile of SU Main Menus

Button Operating Instructions The smart unit is configured with one default inter- Default interface after Starup.
face and four main menus.
Buttons can be used to set other functions, such as overvoltage, The default interface displays the continuously
undervoltage, voltage unbalance, Over-frequency, Under-fre- Display the current value of each
measured phase currents: Ia, Ib, Ic, and In.
quency, reverse active Power and harmonic protection, load phase in the default interface.
Main menu of system setting
monitoring, etc. Refer to relevant chapters for specific details. Press or to switch the current
Main menu of protection setting
values of the phase A, B and C.
Main menu of measurement
Press“OK”once to enter the“Setting”interface and menus Main menu of record
Press in the default interface
(e.g.“System Setting”and“Protect Set”). Note: The basic type controller uses LED display menu.
In the“Setting”interface, set system parameters by pressing to enter the”Setting” interface.
the“ ”and“ ”buttons.

Fine-tune parameters or check the mea- “Setting”main menu


sured values via buttons

C
Setting
Example: Current unbalance adjustment Press or to adjust the menu
System set
M

to be entered and to enter each


Protectset
Y

sub-menu.
CM
Open the initial interface. Measure
Press to return to the default
MY
Record
Press to enter the“Setting”interface. interface.
CY

Press or to the“Protect Set”interface, and then press into“Protect Set”interface,


CMY

Press or to the “I Protect”interface, and then press to open the“I Protect”interface.


K

Press and to the“I Unbalance”interface, and then press to open the“I Unbalance”interface.

Press to make the menu box thicker, and and to select“Close”,“Alarm”and“Trip”.Then

press and to set and save the values.

“System Setting” “Protection Setting” “Measurement” “Record”main menu


main menu main menu main menu

System Set ProtectSet Measure Record


Setting Protect set I.Protect I.U.protect Clock Set I.Protect Current I Alarming
System set I.protect L.protect Trip Gauge Set L.monitor Voltage V Opr. Times
Protect set L.monitor S.protect Start Value Test/Lock V.protect Freque.F Con. Wear
Measure V.protect I.protect 60% com set Power P Pos.Log
Record Others G.protect 5.0S
DI/DO Energy E Trip Log
I.U.protect Language Harmonic H Alarm Log
FactorySet

User Manual 60 User Manual 61


Menu Menu
The menu consists of four parts: System Setting menu, Protection Setting menu, Measurement menu and Record menu.
Level 1 Level 2 Level 3 Level 4 Level 5
Level 1 Level 2 Level 3 Level 4 Level 5
Protect set Others UF.protect Off
System set Clock Set Date and time setting
Underfrequency protection Alarm: (start value, time) &(return value, time) setting
Gauge Set LineinType Top-Fed
Trip: start value & time setting
Bottom-Fed
OF.protect Off
Demand time Demand time adjustment
Overfrequency protection Alarm: (start value, time) & (return value, time) setting
Test/Lock Test Trip Protection tripping test ( G.protect、ActionTime) LSI
Trip: start value & time setting
RemoteLock Lock/unlock
RP.protect Off
com set ComAddress 1-247
Reverse power protection Alarm: (start value, time) & (return value, time) setting
Baudrate 9600,19200
Trip: start value & time setting
Parity None,Odd,Even
PS.protect Off
DI/DO Func Set General DO/DI function selection
Phase sequence protection Alarm: Start value setting
Run Mode DO: NO/NC voltage level;
Trip: start value setting
NO/NC pulse; pulse time
Measure Current I Ins.Value Ia, Ib, Ic, In Display the current
State Display DI/DO status(0/1)
Instantaneous value Maximum Display the maximum value
Language Chinese / English
Unbalance rate Display the unbalance rate
FactorySet Ensure Reset to factory setting
I Heat Ca. Display thermal capacity
Protect set I. Protect L.protect Display Ir and Tr. The cooling time and curve type are adjustable.
Peak Coef. Display the crest coefficient of Ia, Ib, Ic and In
Overload protection
I.dmd Display the required values of Ia, Ib, Ic and In
S.protect Definite/inverse time, Isd, Tsd
Voltage V Ins.Value Display the Uab, Ubc, Uca, Uan, Ubn and Ucn
Time-delayed overcurrent protection
C
Average Display the average value of U
I.protect Ii
M Unbal.Rate Display the unbalance rate of U
Instantaneous overcurrent protection
Y Phase Seq. Display the phase sequence
G.protect Definite/inverse time, Ig, Tg
Peak Coef. Display the crest coefficient
CM
Groundingprotection
Freque.F Display frequency
MY
I.U.protect Off
Power P P, Q, S Instantaneous value
CY Current Alarm: (start value, time) & (return value, time) setting
demand Val
unbalance protection Trip: start value & time setting
CMY
demand value
N.protect OFF,50%,100%
K PF PF=0.00
Neutral protection
Energy E Tot.energy Display E.P E.Q E.S
Demand Set Off
Total energy reset(+/-)
Alarm: (start value, time) & (return value, time) setting
In.energy Display E.P E.Q
Trip: start value & time setting
Input energy Reset(+/-)
I.harmonic Off
Out energy Display E.P E.Q
Current harmonic Alarm: (start value, time) & (return value, time) setting
Output energy Reset(+/-)
Trip: start value & time setting
Harmonic H Fun.Wave Current I Display the fundamental-harmonic current
G.alarm Off
Fundamental Wave Voltage U Display the fundamental-harmonic voltage
Grounding Alarm Alarm: (start value, time) & (return value, time) setting
ITHD I(%)
L.Monitor Off
UTHD U(%)
Load monitoring LD.shed.I (Load shedding value 1, time) & (Load shedding value 2, time)
FFT I、U
Load Shedding I
Record Alarming Display the current alarm type CT Break,magn Break,O-L alarm,Action rejection
LD.shed.II (Start value, time) & (return value, time) setting
Opr.Times Display the number of operations
LoadShedding II
Con.Wear Display contact wear status
V.protect UV.protect. Off
Pos.Log Display 10 Position change records
Undervoltage protection Alarm: (start value, time) & (return value, time) setting
Trip Log Display 10 trip records
Trip: start value & time setting
Alarm Log Display 10 alarm records CT Break,magn Break,O-L alarm,Action rejection
OV.protect Off
Note: The actual menu may change according to the functions selected by the user.
Overvoltage protection Alarm: (start value, time) & (return value, time) setting
Trip: start value & time setting

V.U Off

Voltage unbalance Alarm: (start value, time) & (return value, time) setting
Trip: start value & time setting

V.harmonic Off

Voltage harmonic Alarm: (start value, time) & (return value, time) setting
Trip: start value & time setting

User Manual 62 User Manual 63


Symbol and Description of M Type Control unit
Overview of Functions
The LED of the control unit is a customized module. The symbols are described in the following
table for the convenience of users. Operating Instructions for M Type Control Unit Interface
No. Symbol Description The M type control unit includes the following interfaces: default interface, setting interface, view interface, and trip interface.
1 Lg L1 L2 L3 LN Ground-fault, A, B, C and N phases Default interface is measurement status, all fault indicators are OFF, and the current of each phase is displayed cyclically.
2 IR= Tr= Current and time setting of long-time delay
Example of parameter setting: Press “OK” in the default interface to enter the menu setting interface F0 of the controller. Press “OK”
3 Isd= tsd= Current and time setting of short-time delay
to enter the parameter setting or view interface. Continue to press “OK” to enable the parameter setting interface, “SET” symbol will
4 Ig= tg= Ground-fault current and time setting appear in the lower right corner of the interface, where the parameters can be set by pressing “UP” and “DOWN” in this interface.
5 Ii= Instantaneous current setting After setting the parameters, press “OK” to save them and “ESC” to the default interface.
6 Reverse time

7 F0 Neutral protection setting

8 F1 Current unbalance protection setting

9 F2 Thermal memory setting

10 F3 trip simulation setting

11 F4 Communication setting

12 F5 Trip record view

13 F6 Alarm record view

14 F7 Position change record view

C
15 F8 View of LSIG setting

M
16 U. Current unbalance

Y
17 3PHS Test setting of LSI current protection

CM
18 Vector and ground-fault protection test setting

MY
19 Test confirmation status

CY
20 gdr Modbus-RUT address setting Main function menus and settings of the M type control unit :

CMY
21 A.- Modbus-RUT address selection F0: Neutral protection setting: 50%, 100%, OFF.

K
22 bPS means Modbus-RUT baud rate setting F1: Current unbalance setting: ON (OFF), current unbalance rate setting, delay time setting.

23 TRIP Trip status F2: Thermal memory setting: ON (OFF), thermal memory recovery time setting.

24 RUN Running status F3: Test function setting: LSI protection test, ground-fault protection test.
F4: Communication setting: communication address (1-247), baud rate (9600, 19200).
25 SET Normally ON: setting status
F5: Trip record view: Take the instantaneous trip for example. Press “OK” in the default interface, select the F5 menu by pressing “UP”
26 ALM Alarm status
and “DOWN” , and then press “OK” to enter the trip record view interface. Select the serial number (e.g. 01) of record, and press
27 NULL No information
“OK” . The instantaneous trip current interface will appear. The trip time interface can be viewed by pressing “UP” and “DOWN” .
28 OPEN Open

29 CLSE Closed

30 E1 Magnetic break

31 E2 CT break

32 E3 Action rejection

33 LSIG curve. The full display means normal operation. In case of fault tripping, the corresponding segment will flash.

34 "ESC" button identification

35 "Down" button identification


F6: Alarm records include the magnetic break alarm, CT break alarm and overload alarm. E1 represents the magnetic break, and
E2 represents CT break alarm.E3 represents action reject.
36 "Up" button identification F7: Position change records include opening, closing and trip event records.
F8: View menu for LSIG protection setting, used to view the existing knob settings.
37 "OK" button identification Note: Long-time delay OFF setting: Set the Tr to 30S and enter the menu F8. Adjust Tr to the OFF status to disable long-time
delay.

User Manual 64 User Manual 65


Appendix
Tripping cur ve

Selective protection L S I

CM

MY

CY

CMY Ground protection cur ve


K

User Manual 66
C

CM

MY

CY

CMY

http://na.noark-electric.com

ZA32202209UL

User Manual 34