General Data

Relay terminal that corresponds to winding 1 S


Relay terminal that corresponds to winding 2 T
NFREQ 60
PHROT ABC
INOM (5A or 1A, determined by part number) 5

Winding S Data Winding T Data


TAPS 3.49 TAPT 4.63
TSCTC 0 TTCTC 1

Differential Data
U87P 8
O87P 0.3
SLP1 25
SLP2 65
DIOPR 1.2
DIRTR 1.2

O87P test
IRTmin IRTtest IRTmax
0.42 0.6 1.04

|IAS|=|IBS|=|ICS| ∠IAS° ∠IBS° ∠ICS° |IAT|=|IBT|=|ICT|


Start 1.05 30 270 150 1.39
Expected Pickup 1.05 30 270 150 1.39
Stop 1.05 30 270 150 1.39

U87P test
IRTmin IRTtest IRTmax
8.50 9 N/A

|IAS|=|IBS|=|ICS| ∠IAS° ∠IBS° ∠ICS° |IAT|=|IBT|=|ICT|


Start 15.71 30 270 150 20.84
Expected Pickup 15.71 30 270 150 20.84
Stop 15.71 30 270 150 20.84

SLP1 test
IRTmin IRTtest IRTmax
1.20 3 32.00

|IAS|=|IBS|=|ICS| ∠IAS° ∠IBS° ∠ICS° |IAT|=|IBT|=|ICT|


Start 5.24 30 270 150 6.95
Expected Pickup 5.24 30 270 150 6.95
Stop 5.24 30 270 150 6.95

SLP2 tests
IRTmin IRTtest IRTmax
0.61 3 12.31

|IAS|=|IBS|=|ICS| ∠IAS° ∠IBS° ∠ICS° |IAT|=|IBT|=|ICT|


HSM state 2.09 30 270 150 2.78
Restraint state 5.24 30 270 150 6.95
Operate state 5.24 30 270 150 6.95
∠IAT° ∠IBT° ∠ICT°
216 96 336
240 120 0
268 148 28

∠IAT° ∠IBT° ∠ICT°


293 173 53
305 185 65
322 202 82

∠IAT° ∠IBT° ∠ICT°


201 81 321
209 89 329
217 97 337

∠IAT° ∠IBT° ∠ICT°


180 60 300
245 125 5
282 162 42
Version Date
0 10/29/2019
1 9/21/2021
1 9/21/2021

1 9/21/2021
Description of changes
Initial version.
Added this version history tab so changes can be tracked and identified for version control.

Added labels for every cell so cells can be referred to by name. All cells that require user input begin with
"UI_". To navigate to a cell with a particular name, use the keyboard shortcut Ctrl+G, and double-click on
the variable name.
Updated the following calculations to ensure high-security mode is activated for the SLP2 tests:
SLP2_HSM_Mag_W1 and SLP2_HSM_Mag_W2.