0 Panel Direccionable - Edwards VM-1R - Datasheet
0 Panel Direccionable - Edwards VM-1R - Datasheet
VM Series
Life Safety
Control System
S3000
7165-1657:
309
APPROVED
17
Power Alarm
2
16
Audio that speaks for itself Test Supervisory
15 Ground
Fault
Trouble
3
4 5 6
storage. An optional paging control center
GHI JKL MNO
Alarm
11 Silence
Details 6
7 PQRS 8 TUV 9 WXYZ
includes a high quality paging microphone An optional paging microphone 10 Reset Drill
0
Clear-cut remote annunciation 8 Details button Displays additional information on the selected event.
Up to 30 R-Series LCD, LED annuncia-
Activates audible alarm signals and, if configured, visible
tors and driver interface cards may be 9 Drill button alarm signals.
configured for each control panel on The LED indicates that Drill operation is active.
the VM Series network. Compatible 10
Reset button/ Resets the fire alarm system.
annunciators include a range of LED LED The LED indicates the panel is resetting.
and LCD models that provide zone or Alarm Silence Silences alarm signals.
11
button/LED The LED indicates that Alarm Silence is active.
point annunciation, as well as common Up to 30 R-Series annunciators
may be configured for each ACK/Panel Silences the panel buzzer and acknowledges all new
control capabilities. VM Series also sup- panel on the VM Series network. 12 Silence events.
ports graphic annunciation with optional button/LED The LED indicates that Panel Silence is active.
graphic snnunciator interface modules. Each interface provides Service
13 Indicates a detector needs servicing
common control, indicators, and 32 LEDS. Expansion units pro- Detector LED
vide 48 led outputs. Flashing indicates new monitor events.
14 Monitor LED On: Indicates all monitor events have been
acknowledged.
Power that goes the distance
Ground Fault
Kidde’s patented Voltage Boost™ technology delivers constant 15
LED
Indicates a system ground fault.
22.5 Vdc on NAC and AUX circuits – even at low battery power. 16 Test LED Indicates system components are being tested.
This means lighter gauge cable can be used for equivalent distanc-
On indicates the panel is using primary power.
es compared with conventional power supplies, or longer wire runs 17 Power LED Off iIndicates the panel (or another panel on the network)
on the same gauge cable. Either way, this breakthrough technology is using battery power.
saves time and equipment costs, making VM Series not only a high- Displays system status, event messages, reports, and
18 LCD
performance solution — but a cost-effective one as well. operator menus.
Class A Wiring
VM-CPU
B
+
B
-
S
H
A
+
A
-
SP
MW
B
+
B
-
24+ C
TB1/TB2
KR
LOOP1 LOOP1 1 LOOP1 AUX
Class B Wiring
VM-CPU
B B S A A SP B B 24+ C
+ - H + - MW
KR
+ - TB1/TB2
LOOP1 LOOP1 1 LOOP1 AUX
Normal/ Active/
Supervised Supervised
VM-CPU
TB5
S M BUS BUS
Signal Silence
X X Drill
Aux. Power:
Ethernet
24 VDC, RS-232 wiring
Interface
1.0 A total
Supervised Printer, RS-232 wiring Unsupervised Printer, RS-232 wiring
AUDIO AUDIO R C A B AUDIO AUDIO R C A B
VM-CPU
Central Station VM-CPU
TB5 RX TX
Common RX
DTR Common
Ethernet
Common relays
1
4
2
5
3 6
EOLR
N C N N C N N N C N
EOLR EOLR
C O O A C O C
TROUBLE ALARM SUP
VM-CPU TB4
Programming VM-CPU TB4
VM-LCD user Mounting frame PS10-4B Power Supply Board provides the required power
interface
and related supervision functions for the control panel as well as filtered,
Filler plates regulated power. It also provides 24 VDC for operating ancillary equipment.
Voltage 93 to 264 VAC, 50/60 Hz
Current Power supply current is included in the
Dimensions total current shown under VM1 above.
The backbox is designed for semiflush or surface mounting. Con- Current at 120 V, 50/60 Hz 3 A max.
duit and nail knockouts, keyhole style mounting holes, and wide Current at 240 V, 50/60 Hz 1.5 A max.
wiring troughs facilitate efficiency during installation. Power output
UL 24 VDC at 10 A [Note 1]
2.2 2.1
(5.5) (5.3)
2.0
(5.1)
ULC 24 VDC at 9.0 A [Note 1]
7.9 5.4
in (cm) (20.1) (13.7) Brownout level 93 VAC at 50/60 Hz
Rechargeable battery circuit
3.2 (8.1)
3.5(8.9) Voltage 24 VDC
3.5 (8.9) Top view
Charging current 1.5 or 3 A, selectable
21.7
3.2
(55.2) Charging capacity 65 Ah max.
(8.2) 19.0
(48.3) Type Sealed lead acid only
Battery operating voltage 20.4 V min.
5.1 5.1
(12.9) (12.9)
Notification appliance/Auxiliary power circuits
1.9 (4.9) Quantity 4
8.1
2.0 (5.1) Circuit designation
(20.5) 2.0 (5.1 NAC Class B (Style Y]
2.2 (5.5) AUX Class B
Output voltage
NAC 24 VDC
35.5 10.8
(27.5) AUX 24 VDC
(90.1)
14.1
(35.9)
Output current, NAC
Regulated 3.0 A max. per circuit
3.3 (8.4)
6.0 A total, shared
Special application 3.0 A max. per circuit
9.0 A total, shared
8.2 8.2 Output current, AUX 6.0 A total, shared
(20.7)
EOLR 15 kΩ (UL P/N EOL-15, ULC P/N EOL-P1)
Wire size 18 - 12 AWG (0.75 - 2.50 mm²) [Note 2]
Side view Side view Ground fault impedance 10 kΩ
Operating environment
Bottom view
Temperature 32 to 120°F (0 to 49°C)
Relative humidity 0 to 93% noncondensing
Note: Add 0.25 in (0.64 cm). to height and width dimensions to allow for knockouts Note 1: Internal and NAC/AUX outputs
when framing in the backbox for semiflush mounting. Note 2: Mains wiring is typically 18 to 12 AWG (0.75 mm² to 2.50 mm²