GENERAL NOTES AND SPECIFICATIONS:


230V, 3-PH, 50-60kHZ
1. ALL WORKS HEREIN SHALL COMPLY WITH THE LATEST PROVISIONS OF THE LATEST
EDITION OF THE PHILIPPINE AND NATIONAL ELECTRIC CODES WITH THE RULES AND LEGEND:
REGULATIONS OF THE NATIONAL AND LOCAL AUTHORITIES CONCERNED IN THE
LF-1 15W LED PINLIGHT (DAYLIGHT)
ENFORCEMENT OF ELECTRICAL LAWS AND ORDINANCES AND WITH THE RULES AND
REGULATIONS OF THE POWER PROVIDER CONCERNED. LF-2 9W LED PINLIGHT (DAYLIGHT)
2. ALL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF THE DULY PP 200AT 3P
QUALIFIED AND COMPETENT ELECTRICAL ENGINEER. CO CONVENIENCE OUTLET 3-38.0 SQ.MM. THHN + 1-14.0
SQ.MM. THHNN GROUND IN
3. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL BE NEW AND APPROVED TYPE FOR

FCO
40MM IMC PIPE 125AT 3P 60AT 3P
FCO FLOOR MOUNTED OUTLET MACHINE PANEL 1 2 R.O.
THE LOCATION AND PURPOSES. 30AT 2P 30AT 2P
4. THE SERVICE ENTRANCE SHALL BE 3 PHASE, 3 WIRES + Ground, 230Vac, 60Hz.

SPO
SPO SPECIAL PURPOSE OUTLET ACU SPLIT TYPE 2.5 HP 3 4 ACU SPLIT TYPE 2.5 HP
30AT 2P 30AT 2P
( IN COMPLIANCE TO THE POWER UTILITIES REQUIREMENTS AND STANDARDS) ACU SPLIT TYPE 2.5 HP 5 6 ACU SPLIT TYPE 2.5 HP

5. WHENEVER REQUIRED AND NECESSARY, PROPER SIZES AND DIMENSIONS OF PULL BOXES ACU ACU AIR CONDITIONING UNIT MP ACU SPLIT TYPE 2.5 HP 7
30AT 2P 30AT 2P
ACU SPLIT TYPE 2.5 HP
125AT 3P 8
SHALL BE PROVIDED AND INSTALLED AT CONVENIENT AND STRATEGIC LOCATIONS. EXHAUST FAN 30AT 2P 30AT 2P
EF ACU SPLIT TYPE 1.0 HP 9 10 ACU SPLIT TYPE 1.0 HP
6. ALL PANEL BOARDS SHALL BE BREAKER TYPE ENCLOSED IN A METAL CABINET. ALL MAIN 20AT 2P 20AT 2P 30AT 2P 30AT 2P

AND POWER PANEL SHALL BE BOLT-ON-TYPE, SAME FOR LIGHTING PANEL. MACHINE 1 1 2 MACHINE 2 ACU SPLIT TYPE 1.0 HP 11 12 ACU SPLIT TYPE 1.0 HP
EXIT EXIT SIGN 20AT 2P 20AT 2P 30AT 2P 30AT 2P
7. ALL CONVENIENCE OUTLETS, THREE PRONG (PARALLEL SLOT WITH GROUNDING TYPE) MACHINE 3 3 4 MACHINE 4 ACU SPLIT TYPE 1.0 HP 13
20AT 2P 20AT 2P
14 ACU SPLIT TYPE 1.0 HP
20AT 2P 20AT 2P
AND LIGHTING SWITCHES SHALL BE RATED 15A, 250V, AND 10A, 250V, RESPECTIVELY AS EL EMERGENCY LIGHT MACHINE 5 MACHINE 6 15 16
5 6 REPROCESSING AND BICARB MIXER CONVENIENCE OUTLET
20AT 2P 20AT 2P
MANUFACTURED BY "PANASONIC" OR APPROVED EQUAL. TV OUTLET MACHINE 7 7
20AT 2P 20AT 2P
8 MACHINE 8 CONVENIENCE OUTLET 17 18 CONVENIENCE OUTLET
TV 20AT 2P 20AT 2P
20AT 2P 20AT 2P
8. ALL OUTLETS ABOVE THE LAVATORY AND KITCHEN SINK, BATH TUBS, WATER HEATERS, MACHINE 9 9 10 MACHINE 10 CONVENIENCE OUTLET 19 20 CONVENIENCE OUTLET
WASHING MACHINE, DRYERS, AND WEATHER PROOF OUTLETS SHOULD HAVE GROUND CIRCUIT HOMERUN 20AT 2P 20AT 2P 20AT 2P 20AT 2P
MACHINE 11 11 12 MACHINE 12 C.O. FOR TV, EXIT SIGN & EMERGENCY LIGHTS 21 22 C.O. FOR TV, EXIT SIGN & EMERGENCY LIGHTS
FAULT CIRCUIT INTERRUPTOR (GFCI). 20AT 2P 20AT 2P 20AT 2P 20AT 2P

9. THE MINMUM SIZE FOR THE WIRES SHALL BE 3.5 SQ. MM. IN THE TYPE OF THHN COPPER MACHINE 13 13 14 MACHINE 14 LIGHTING OUTLET 23 24 LIGHTING OUTLET
20AT 2P 20AT 2P 20AT 2P 20AT 2P
AND 15MM DIA., FOR CONDUITS. (REFER TO LOAD SCHEDULE FOR OTHER WIRE SIZES, MACHINE 15 15 16 MACHINE 16 LIGHTING OUTLET 25 26 SIGNAGE
20AT 2P 20AT 2P 20AT 2P 20AT 2P
TYPES OF INSULATION AND RACEWAYS SIZES). NO BRANCH CIRCUIT CONDUCTOR SHALL MACHINE 17 17 18 MACHINE 18 SPARE 25 26 SPARE
20AT 2P 20AT 2P
HAVE A LOAD MORE THAN 80% OF ITS RATING. MACHINE 19 19 20 MACHINE 20
GROUND BUS
10. FOR EACH SPARE BRANCH CIRCUIT IN THE PANEL BOARD, PROVIDE ONE 15MMØ EMPTY GROUND BUS
CONDUIT CONNECTED TO A OCTAGONAL BOX ABOVE THE CEILING.
11. ALL FEEDERS AND BRANCH CIRCUIT SHALL BE INSTALLED AS INDICATED ON PLAN,
INDIVIDUAL CIRCUIT HOMERUNS TO PANEL BOARD SHALL NOT BE COMBINED IN THE
SAME RACEWAY UNLESS OTHERWISE INDICATED ON THE PLAN.
12. THE CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF SERVICE ENTRANCE FOR
CONNECTION TO THE POWER SUPPLY AND ALSO THE ACTUAL LOCATION OF
TELEPHONE SERVICE REQUIREMENT FOR THE CONNECTION TO THE MAIN TELEPHONE
CABINET.
13. THE METHOD OF WIRING SHALL BE AS FOLOWS:
A. POWER SERVICE ENTRANCE: IMC/RSC
B. LIGHTING AND CONVENIENCE OUTLETS: EMT/IMC/RSC
C. AIR-CONDITIONING UNIT: EMT/IMC/RSC
4 SCHEDULE OF LOADS
14. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: E1
A. LIGHTING SWITCHES 1400MM ABOVE FINISH FLOOR LINE
B. CONVENIENCE OUTLETS 300MM ABOVE FINISH FLOOR LINE (FROM
CENTER OF THE PLATE) OR AS
SPECIFIED BY DESIGNER IN THE PLAN
C. PANEL BOARDS 1800MM ABOVE FINISH FLOOR LINE TO THE TOP OF PANEL BOARD
D. COUNTER TOP OUTLETS 300MM ABOVE FINISH LINE OF COUNTER TOP
E. SPECIAL OUTLETS AS DIRECTED BY THE ARCHITECT
15. ALL MOUNTING HEIGHTS ARE SUBJECT TO ARCHITECT'S APPROVAL PRIOR TO
INSTALLATION,
16. ALL METAL HOUSING OF LIGHTING FIXTURES, BOXES, CONDUITS, PANEL BOARDS SHALL
BE PROPERLY CONNECTED TO THE GROUNDING SYSTEM OF THE BUILDING.
17. UPON COMPLETION OF ELECTRICAL CONSTRUCTION WORK, THE FOLLOWING TESTS
SHALL BE PERFORMED BY THE CONTRACTOR INCLUSIVE OF THE INSTALLATION TO
BE REPORTED IN DETAILS ON FORMS APPROVED BY THE OWNERS REPRESENTATIVE.
18. THE FOLLOWING TESTS SHALL BE AS FOLLOWS:
A. INSULATION RESISTANCE TEST, 600VDC
B. GROUNDING RESISTANCE TEST
C. OPERATIONAL TEST
D. SYSTEM TEST AN ACCEPTANCE
19. ALL CONVENIENCE OUTLETS AND SWITCHES ARE PROPERLY TAG.
20. WORKSMANSHIP: THE WORK THROUGHOUT SHALL BE EXECUTED IN THE MOST AND
THOROUGH MANNER KNOWN TO TRADE AND TO THE SATISFACTION OF THE ARCHITECT
AND ENGINEER.
21. ANY MODIFICATION TO THE ELECTRICAL PLAN IS TO BE COORDINATED AND APPROVED
TO A DULY LICENSED ELECTRICAL PRACTITIONER.

RA 9266 ARTICLE IV, SEC. 33 AND


PROFESSIONAL ELECTRICAL ENGINEER: PROJECT TITLE: OWNER: REVISION: P.D. NO. 49 " PROTECTION OF INTELLECTUAL SHEET CONTENT: SHEET NO. :
PROPERTY "

1 OWNERSHIP OF PLANS, SPECIFICATIONS AND OTHER

LIFESTREAM DIALYSIS CENTER 2


CONTRACT DOCUMENTS

E-1
Drawings and specifications and other contract documents
duly signed, stamped or sealed, as instruments of service, are AS SHOWN
3 the intellectual property and documents of the architect,
whether the object for which they are made is executed or
PTR: PRC: not. It shall be unlawful for any person to duplicate or to make
4 copies of said documents for use in the repetition of and for
DATE: VALIDITY: other projects or building, whether executed partly or in
whole, without the written consent of architect or author of
PLACE: TIN: LOCATION: 5 said documents.
FIRE EXIT FIRE EXIT

SPO
ACU

SPO

SPO

SPO

SPO

SPO

SPO
HAND
SPO
BICARB
WASH
MIXER
REPROCESSING
ROOM 15 16 17 18 19 20 15 16 17 18 19 20
ACU

ACU

DIALYZER RACK DIALYZER RACK

LINEN CABINET

LINEN CABINET
ACU
STORAGE 14 13 12 11 10 9 14 13 12 11 10 9
ROOM

SPO

SPO

SPO

SPO

SPO

SPO
HAND HAND
WASH WASH

SPO

SPO

SPO

SPO

SPO

SPO
R.O. ROOM
AREA = 12.48 SQ. M
SLIDING 3 4 5 6 7 8 3 4 5 6 7 8
DOOR

ACU

2 1 2 1
NURSE

FCO
STAFF
STATION
PANTRY
ACU

FCO
SPO

SPO
ACU
ENTRANCE

STAFF
C.R.
C.R. INFORMATION AREA

ACU
DOCTOR'S OFFICE BUSINESS AREA
ACU
ACU
WAITING AREA

ACU

ACU

MAIN ENTRANCE

1 MACHINE & ACU POWER LAYOUT 2 POWER LAYOUT


E2 SCALE: 1:100 E2 SCALE: 1:100

RA 9266 ARTICLE IV, SEC. 33 AND


PROFESSIONAL ELECTRICAL ENGINEER: PROJECT TITLE: OWNER: REVISION: P.D. NO. 49 " PROTECTION OF INTELLECTUAL SHEET CONTENT: SHEET NO. :
PROPERTY "

1 OWNERSHIP OF PLANS, SPECIFICATIONS AND OTHER

LIFESTREAM DIALYSIS CENTER 2


CONTRACT DOCUMENTS

E-2
Drawings and specifications and other contract documents
duly signed, stamped or sealed, as instruments of service, are AS SHOWN
3 the intellectual property and documents of the architect,
whether the object for which they are made is executed or
PTR: PRC: not. It shall be unlawful for any person to duplicate or to make
4 copies of said documents for use in the repetition of and for
DATE: VALIDITY: other projects or building, whether executed partly or in
whole, without the written consent of architect or author of
PLACE: TIN: LOCATION: 5 said documents.
Sa

FIRE EXIT
t u FIRE EXIT
HAND
WASH
Su p
m m m m m m m
t t St

DIALYZER RACK

LINEN CABINET
s s

m m m m m m

s s Ss
p

HAND n
WASH
r r

p
n n n n n n
Sr SLIDING
DOOR
r r

q q o o
n n n n n
Sq
NURSE
p STATION
q q
HAND
WASH o o
Sp SmnoENTRANCE

l Sij Sab Scd e


c c c b b Sef
k f f
j

Skl i
Sh Sg d

h h h g g g
Sv v
d b b v

a a a

a a

MAIN ENTRANCE

1 LIGHTING LAYOUT 2 TV, EMERGENCY LIGHTS & EXIT SIGN LAYOUT


E3 SCALE: 1:100 SCALE: 1:100
E3

RA 9266 ARTICLE IV, SEC. 33 AND


PROFESSIONAL ELECTRICAL ENGINEER: PROJECT TITLE: OWNER: REVISION: P.D. NO. 49 " PROTECTION OF INTELLECTUAL SHEET CONTENT: SHEET NO. :
PROPERTY "

1 OWNERSHIP OF PLANS, SPECIFICATIONS AND OTHER

LIFESTREAM DIALYSIS CENTER 2


CONTRACT DOCUMENTS

E-3
Drawings and specifications and other contract documents
duly signed, stamped or sealed, as instruments of service, are AS SHOWN
3 the intellectual property and documents of the architect,
whether the object for which they are made is executed or
PTR: PRC: not. It shall be unlawful for any person to duplicate or to make
4 copies of said documents for use in the repetition of and for
DATE: VALIDITY: other projects or building, whether executed partly or in
whole, without the written consent of architect or author of
PLACE: TIN: LOCATION: 5 said documents.