Professional Documents
Culture Documents
Book About Motors
Book About Motors
Book About Motors
UNDERSTANDING
ELECTRICAL AND
MOTOR CONTROLS
L.A. Bryan
E.A. Bryan
ISBN 0-944107-07-9
Rev. 02-07.15.95
Due to the nature of this publication and because of the different applications of motors and electrical control circuits, the readers or users and
those responsible for applying the information herein contained must satisfy themselves as to the acceptability of each application and the use
of equipment therein mentioned. In no event shall the publisher and others involved in this publication be liable for direct, indirect or conse-
quential damages resulting from the use of any technique or equipment herein mentioned.
The illustrations, charts, and examples in this book are intended solely to illustrate the methods used in each application example. The
publisher and others involved in this publication cannot assume responsibility or liability for actual use based on the illustrative uses and
applications.
No patent liability is assumed with respect to use of information, circuits, illustrations, equipment, or software described in this text.
OVERVIEW
OBJECTIVES
INTRODUCTION NOTES
NOTES
A while ago we mentioned that all the original
sources for generating power, such as nuclear,
water, coal, and others are used to produce
mechanical movement which, in turn, is used
to drive a turbine. This turbine is connected to
an alternator, or generator, which is actually
the one which translates the mechanical move-
ments into electrical energy.
POWER GENERATION
CONDUCTOR
This conductor, which moves, is formed by
CURRENT
groups of wires rotating around the north and
south poles of a permanent magnet. The cur-
DIRECTION OF
LOAD
rent which is generated through the group of MAGNETIC FIELD
NORTH TO SOUTH
rotating wires is simply AC.
Figure 4.
Current
As the current is generated (Figure 5), it also Electrical Degrees
follows the same pattern as in the mechanical 0˚ 90˚ 180˚ 270˚ 360˚
rotation, except that here the degrees created
by the two poles, the north and the south, are
called electrical degrees and alternates be- 180˚
tween positive and negative, therefore the
name alternating current.
Figure 6.
If this rotating coil, let’s call it alternator, is ro- RPMs =60 Hertz
tated 3600 times per minute, or at 3600 RPMs, 60
we would get 60 revolutions per second or 60
hertz (Figure 6), which is our normal every-
day electricity. In other parts of the world, the
number of cycles per second that this alterna-
tor rotates is 50, which means 50 Hertz. Figure 7.
Figure 8.
Now, if we add another set of poles (Figure 8),
another north and south poles to our existing
N1 MAGNETIC
alternator, we’ll find that a mechanical rotation FIELD
of 360 degrees, or one mechanical cycle, will
produce not one but two electrical cycles, each S1
S2
one of 360 degrees for a total of 720 electrical
degrees. This simply means that 180 mechani-
cal degrees will give us 360 electrical degrees N1 N2
Figure 11.
○ ○ ○ ○ ○ ○ ○
are negative and vice versa. In fact, if we add +2
the positive and negative values for each of 0
the curves, we would get a value of zero. For ○ ○ ○
-2
instance, at the dotted line, the value of A is 4
-4
while the value of B and C are each minus 2,
which, when added, will give us zero.
Figure 21.
This neutral point can also be seen in another
graphical form called vectors (Figure 21). In
here, each of the coils is represented by a line,
again separated by 120 degrees. The central 0
point will be zero.
AO
If we connect the neutral to ground, then we
would have a neutral grounded which is cus-
tomary (Figure 23).
N
Figure 24.
Large power distribution systems are designed
using three-phase systems for use with bal- AO
anced loads across each of the phases as close
as possible so that the current that flows
through the neutral wire, or the so called un- N
balanced current, is kept to a minimum.
Figure 26.
Phase To Neutral Voltage
120 VOLTS
In a three-phase Wye system, the voltage gen-
erated at each of the three coils is equal (Fig-
ure 26). That is, if the voltage from Phase A to 120 VOLTS 120 VOLTS
A
Well, we know that each voltage A, B and C to
Figure 29.
neutral is 120 volts. To find the voltage between
A and B (Figure 29) is done by simple Trigo-
120
nometry. Although it is not our intention of go- VOLTS
ing into too much explanation of it, let’s just go
over it and take it even if we don’t quite remem-
ber Trigonometry.
DELTA SYSTEM N N
OB
The delta system is created by the way the wires
OC
of coils are connected in the generator. The end
wire of one coil is connected to the beginning Figure 35.
of another and what we get is a triangular
shaped system called delta and is represented
by the symbol shown in Figure 35.
0V
48
equal to 480 volts and a line current of 173
48
VL = VP = 480V
10
0V
0A
0A
amps or 1.73 times the phase current of 100
10
IP
amps.
100A
480V IL = 1.73 x IP
POWER DISTRIBUTION
= 1.73 x 100 = 173 A
Transformers GENERATING
PLANT
SECONDARY
If the primary has more windings than the sec-
PRIMARY AC
ondary, the output voltage will be stepped down OUTPUT
(Figure 43). Conversely, if the primary has fewer
windings than the secondary, the voltage at the
output will be higher and therefore the voltage
will be stepped up (Figure 44).
Figure 43.
STEPPED DOWN
The amount of power, measured in volt am- PRIMARY SECONDARY
peres or VAs, is the same for both the primary WINDINGS WINDINGS
and the secondary. This VA power is calculated
by multiplying the voltage times the current. So
if we have 480 volts with 10 amps in the pri- Figure 44.
mary in a stepdown transformer with a ratio of STEPPED UP
2 to 1, we will get 240 volts in the secondary
PRIMARY SECONDARY
with 20 amps. In this case, the VA power will be
WINDINGS WINDINGS
the same for both the primary and the second- Figure 45.
ary at 4,800 VA or 4.8 KVA. The KVA nomen-
STEP UP
clature indicates that the VAs are times 1,000.
In a stepdown transformer the current in the AC AC
INPUT OUTPUT
PRIMARY SECONDARY
secondary is increased while, in a step up trans- 120 VOLTS 240 VOLTS
10 AMPS 5 AMPS
former, the current is decreased.
include the Wye to Wye or Wye to delta, etc. MCC1 MCC2 HVAC LIGHTING 2
transformer configuration.
Figure 52.
Figure 54.
phase of the transformer. This figure also rep- A A
resents a Wye to Wye transformer connection
for each of the transformer's coils. 480 V 120V
N
The switchboard takes the large amount of FEEDER BUS LIGHT DUTY
HEAVY CAPACITY
power coming in what’s known as a heavy ca- SMALL
CAPACITY
pacity feeder bus and reroutes all the power in
light duty conduits and wires and small capac-
ity busways throughout the plant (Figure 60).
Figure 63.
These panel boards provide the last centrally
located protection for the power run to the loads MAIN
and control circuitry. SWITCHBOARD MOTOR CONTROL
CENTER
MAIN S
CH
SWIT
MAIN
Figure 63 (cont.)
Figure 65.
Each branch circuit is used for the final propa-
gation of power. For instance (see Figure 65), PANEL BOARD
from the panel board to the kitchen, to the bed-
room, or to the basement. Each branch circuit
is controlled by a protecting device.
TO TO
KITCHEN BEDROOM
Busways
TO
A while ago we mentioned that from the BASEMENT
switchgear we transport the power to other Figure 66.
CH
SWIT
There are two primary methods of distributing MAIN
SWITC
H
MAIN
CH
SWIT
power from busways. The first one is using MAIN
NOTES
The feeder busway delivers the power directly
into the loads. The plug-in busways allow loads
to be connected to a panel module which can
be plugged in the busway close to the location
of the final power consuming load.
125/250V C73.49
If you become familiar with these standard rep- 20A 14-20
125/250V C73.50
resentations, you’ll be able to tell what kind of
30A 14-30
voltage, phase and current are available at any 125/250V C73.16
particular plug.
NOTES
duits, switch gear enclosures, etc. should be
connected to ground to limit the voltage be-
tween metal parts and earth to a safe level. The
ground bus should contain an approved ground-
ing conductor and fittings which must be prop-
erly connected to an electrode embedded in
the earth to provide a good ground.
CURRENT FLOW
needs. LOAD
REVIEW QUESTIONS
a– Reduced
b– Stepped up
c– Stepped down
d– None of the above
a– 50 Hz
b– 60 Hz
c– 36 Hz
d– 120 Hz
a– 120
b– 180
c– 90
d– 0
a– Wye
b– L1, L2, L3
c– Delta
d– 3 Phases
e– Double coils
a– The same
b– Twice the amount
c– Never the same
d– Very different
a– Neutral
b– Phase
c– 208
d– 1.73
a– Different
b– The same
c– Not connected
d– More
b– Step down
c– 1:2 :
d– 2:1
STEP DOWN
20.- The current in a stepped down transformer
AC AC
is ______ while the voltage is ______. INPUT OUTPUT
PRIMARY SECONDARY
240 VOLTS 120 VOLTS
5 AMPS 10 AMPS
a– Reduced
b– Increased
:
c– The same
d– Not altered
Figure 4.
21.- Connect the secondary of the transformer
A
shown in Figure 4 so that it is in a wye-to- B
C
wye configuration with a neutral wire in N
H2 H1 H2 H1 H2 H1
the secondary.
X2 X1 X2 X1 X2 X1
22.- True/False The two most common types
of Busways are feeder and plug-ins.
a– Conversion
b– DC resolve
c– Rectification
d– Transformation
Industrial Text & Video Company 1-800-752-8398 www.industrialtext.com 34
Chapter 1—Plant Power Distribution
a– Cathode
b– Gate
c– Anode
d– Electrode
a– Phaser
b– Bridge rectifier
c– Full wave rectification
d– Voltage correction
ANSWERS
1.- b– Stepped up
2.- True
4.- b– 60 Hz
5.- a– 120
6.- a– Wye
c– Delta A1
7.-
120 VOLTS 120 VOLTS
A2 B2
C2
B1
C1
Wye Delta
A1
11.-
PHASE
TO
NEUTRAL PHASE
TO
C2 A2 PHASE
N
B2
B1
C1
14.- b– Phase-to-phase
d– 1.73
a– Phase-to-neutral
15.- True
AC AC AC AC
INPUT OUTPUT INPUT OUTPUT
PRIMARY SECONDARY PRIMARY SECONDARY
120 VOLTS 240 VOLTS 240 VOLTS 120 VOLTS
10 AMPS 5 AMPS 5 AMPS 10 AMPS
20.- b– Increased
a– Reduced
A
21.- B
C
N
X2 C X1 X2 B X1 X2 A X1
120V 120V 120V
N
L3
L2
L1
22.- True
23.- b– Rectification
24.- a– Cathode
c– Anode
TO
CIRCUIT TO
L2
RETURN
TO
L1
120 VAC
Chapter 2—Static/Manual Control Switches
OVERVIEW
This chapter, presents the first of three chap-
ters dedicated to field control devices. Chapter
two, covers static switches which include:
• Switches
• Push Buttons
• Switches
• Pilot Lights
• Drum switches
INTRODUCTION NOTES
This chapter describes many of the control
switches and pilot devices used to control plant
equipment. Without a good understanding of
each device’s function and the terms and sym-
bols representing it, a thorough understanding
of motor control would not be possible.
Figure 1.
Switches TO POWER
The poles indicate the number of source wires THROW: Positions the Switch Can
the switch can control, whereas the throw indi- Be Thrown In or Put In
cates the possible positions the switch can be
thrown in or put in to make a connection (Fig-
ure 3). NOTES
Figure 5.
S
In fact, this is the regular everyday wall switch
we have at home. The one that turns the light
of a room on and off. When the switch closes, Figure 6.
L1 L2
contact is made and current flows through the
switch from the pole to the throw side.
Figure 9.
Figure 18.
If a switch breaks in two points (bottom of Fig-
ure 18), then it is called a double break contact SPST
switch. The single break and double break type
SINGLE
of contacts also apply to all the switches that BREAK
we have talked about. Note that, where before
we used to use the sort of swing side of the
switch, there is now the additional break. DOUBLE
BREAK
Industrial Text & Video Company 1-800-752-8398 www.industrialtext.com 46
Push Buttons
Chapter 2—Static/Manual Control Switches
WIRE
CONNECTIONS
Likewise, if a normally closed push button (Fig-
ure 19 bottom) is pressed, the normally closed
contacts will open and close again when re-
leased.
On the back side, it has the contact blocks which Courtesy of Allen-Bradley
can be formed by one or more blocks which
Figure 28.
are activated mechanically by the operator but-
ton. These contacts, as we know, come in nor-
mally open or normally closed sets.
button has not been pressed and we place one Figure 32.
0
To measure for continuity, we place each side
of the meter in the contact connections
(Figure 33). Here we should read infinity resis-
tance, indicating an open. When the push but- Figure 34.
Selector Switches
MOTOR
When the switch is moved to the run or on po-
M
sition, power is connected to the circuit and the
circuit can operate normally. In this case, the OFF RUN
Figure 42.
The HAND nomenclature implies operation by
L1 L2
hand or manual. In the example shown in Fig- OFF RUN MIX
ure 42, when the selector is to the left, the top HAND AUTO MOTOR
LINE 4
A wrongly documented diagram like the one
depicted in Figure 47 will make troubleshoot-
ing a circuit rather difficult because you would
Figure 48.
not know which one is the correct one provid-
ing continuity in line 1 or in line 2. POS
1 2 3
CONTACTS
The selector switch table representation (see
POS A B C D
Figure 48) also provides the same information A
as in the case of the X markings. In position 1, 1
The is the symbol used for a full voltage pilot Figure 50.
light, or indicator lamp is shown in Figure 49. If
there is letter indication inside the circle repre-
sentation of the lamp, it defines the color of the
lens in the lamp.
C for Clear
Figure 51.
R for Red L2
SYSTEM READY
G for Green
A for Amber G
B for Blue, and
O for Opal or White SYSTEM ON
R
Red pilot lights are often used to indicate that a
motor is running, or to indicate that a machine NOTES
is operational and caution exists.
Drum Switch
drum switches are not normally considered pi- Figure 57. CAM TYPE
lot devices because they can handle loads
larger than 10 to 15 amps, they can be used in
conjunction with motor star ters and/or FIXED
contactors and would then be considered pilot CONTACTS ROTATING
CAMS
devices.
Figure 59.
field converted–that is changed in the field by
maintenance or installation personnel–to give
even more flexibility.
L1 T1
A typical application for a drum switch would
L2 T2
be to reverse the direction of a three phase M
motor (Figure 59). When the motor has the three L3 T3
L2 3 4 T2
You troubleshoot drum switches in the same M
manner of other switches. You need to test the L3 5 6 T3
contacts for closures and continuity if there is
L1 T3
a malfunction in its operation. L2 T2
DRUM SWITCH L3 T1
REVERSE
The test in continuity in its contacts should fol-
low the chart table for the reverse and forward
Industrial Text & Video Company 1-800-752-8398 www.industrialtext.com 61
Chapter 2—Static/Manual Control Switches
L2 3 4 T2
By placing the meter, set for an Ohms reading M
L3 5 6 T3
and with the power off, you would test the ter-
METER
minal leads from the power source section to
each of the motor lead connections (Figure 66). L1 T1 0
L2 T2
When performing a continuity test, it is better if L3 T3
you disconnect the leads from the motor to
avoid possible readings of resistance, due to
the motor windings which could backfeed into
the meter.
REVIEW QUESTIONS
1.- Ladder diagrams are also known as
______.
a– Line Diagrams
b– Elementary Diagrams
c– Both a and b
d– None of the above
a– Breaks
b– Poles
c– Assemblies
d– Throws
e– Current conductors
a– Break
b– Pole
c– Throw
d– Assembly
a– Single-pole single-throw
b– Double-pole single-throw
c– None of the above.
Industrial Text & Video Company 1-800-752-8398 www.industrialtext.com
TWO TWO 63
SINGLE POLES WIRE CIR
DESTINA
Chapter 2—Static/Manual Control Switches
Figure 2.
6.- Explain the circuit of Figure 2.
L1 L2
a– Double break
b– Center off
c– Double center
d– All of the above. Figure 3
a– Contacts
b– Circuits
c– Off positions
d– On positions
a– Normally open
b– Different
c– Uncomplicated
d– Normally closed
a– Hand M
b– Off
c– Auto
d– Switch
e– All of the above
a– Test TO
CIRCUIT TO L2
COMMON
b– Bulb TO
POWER
c– Connect
d– Replace
a– Same manufacturer
b– Different make
c– The same rating
d– None of the above
a– Are
b– Larger
c– Are Not
c– Smaller
Figure 6
a– L1 and L2
b– Any two
c– Swapped
d– Controlled L1 T1
L2 T2
21.- In Figure 6, fill in the connections for for- M
ward, off, and reverse positions. L3 T3
a– Cam
b– Segmented
c– Combination
d– Stationary
ANSWERS
1.- c– Both a and b
2.- True
3.- a– Breaks
b– Poles
d– Throws
4.- b– Pole
c– Throw
light will turn off. The same circuit opera- SPDT-1 SPDT-2
tion occurs when SPDT-2 is switched first. LIGHT
This circuit (with this SPDT switches) is
the same in operation to the circuit we
have at home, where a light can be turned
on and off from two switch locations
8.- a– Contacts
11.- a– One
c– Three
f– Off
12.- a– Hand
13.- True
14.- a– Test
15.- True
18.- True.
19.- a– Are
b– Larger
21.-
HANDLE END
L2 T2 L2 T2 1 2 1 2 1 2
M M
L3 T3 L3 T3 3 4 3 4 3 4
5 6 5 6 5 6
FORWARD REVERSE
22.- a– Cam
b– Segmented
23.- False.
24.- False
MODULE
CHAPTER 3 3
FLOW
Industrial Text & Video Company 1-800-752-8398 www.industrialtext.com 70
Chapter 3—Sensing and Timing Switches
OVERVIEW
OBJECTIVES
INTRODUCTION Figure 1.
UPPER
In this third chapter we are going to cover an- LIMIT
other important and very frequently used group SWITCH
DRILL
of pilot devices which we are classifying as
sensing and timing switches. We’ll begin with MOVEMENT
sensing switches which, as the name implies,
provide information to a circuit by sensing a LOWER
LIMIT
physical condition. So let’s start by first look- SWITCH
ing at limit switches.
LIMIT SWITCHES
WORKPIECE
Limit switches are one of the most common
and widely used pilot devices in industrial
motor control applications. Their primary ob-
jective is to convert mechanical motion into an
electrical signal. For example, they are used NOTES
in applications to limit the travel of a moving
part, such as in a drill-to-depth machine where
the work piece will be drilled until the limit
switch is reached (see Figure 1). Other appli-
cations may include the detection of parts in a
conveyor or counting parts in a line. The appli-
cations of this pilot device are innumerable.
NORMALLY CLOSED
NORMALLY CLOSED-
HELD OPEN
Figure 9
The normally open–held closed switch (see NORMALLY OPEN - HELD CLOSED
Figure 9) indicates that an external force is
normally activating the switch without any ma-
chine motion or, in other words, the force is al-
-External Force Activates the Switch
ways present, just as if a normally open push
button switch were always pushed. When the
external force of the switch is removed, the
switch contacts will open. This would occur if Figure 10.
NORMALLY CLOSED - HELD OPEN
the motion had caused the forcing part away
from the switch, thus removing the external
force.
-External Force Keeps Contacts Open
Likewise, the normally closed–held open limit
switch (see Figure 10) operates in the same
manner. The normally closed contacts are held Figure 11A. Figure 11B.
Travel Action
the contacts will close. This distance, from rest Figure 13C. Figure 13D.
to the start of tripping, is the pre-travel distance TOTAL
TRAVEL
OVER
or sometimes called the trip travel. TRAVEL
When the part clears the limit switch, the ac- Figure 14.
NOTES
Installation and Adjustment of
Limit Switches
PRESSURE SWITCHES
Pressure Differential
Figure 23.
The switch mechanism is designed so that it
will not activate the switch contacts on and off
at the same pressure (see Figure 23). In other
words, if a switch is set to turn on at 100 psi, it
will not turn off when it returns to 100 psi, but
instead it will turn off at 90 psi, giving a pres-
PRESSURE
sure differential of 10 psi (see Figure 24). This FLUID PRESSURE INCREASE
Figure 27.
If your application calls for a low pressure con-
trol, like in the previous case of our compres-
sor that we wanted on when the pressure
dropped to 70 psi, you need to test the switch
by increasing the pressure to a value larger than
the target-on pressure plus the differential (see
Figure 27). In this case to a pressure greater
than 100 psi’s, so let’s take 125 psi and start PRESSURE
INDICATOR
lowering the pressure, while adjusting the PRESSURE SOURCE
GAUGE
switch, until it reaches 70 psi which is when the
contacts should close. Then you proceed to in-
crease the pressure and adjust the differential
until it gets to the cut-off point; in our compres-
Figure 28.
sor example 100 psi.
Figure 29.
During the installation, you must make sure that Figure 36.
the paddle section of the switch is placed in
the proper direction of flow, since they are de-
signed to detect flow in only one direction; oth-
erwise, the switch could be damaged.
0
After installing the switch with power removed, Ω
The most common float switches provide an Figure 43. Figure 44.
COUNTER
(see Figure 43). Some of these switches may WEIGHT
Figure 50.
TEMPERATURE SWITCH
TEMPERATURE SWITCHES
NORMALLY
OPEN
TEMP TEMP
One of the most important details to keep in SWITCH SWITCH
mind during the installation of a temperature
switch is to place the sensor close to the heat
HEAT
source where it can monitor the temperature SOURCE
and also where it will not be damaged by ex-
cessive heat. This information is generally pro-
vided by the manufacturer, along with other CAPILLARY
placement recommendations. BULB
the load side, having one of the meter probes Figure 61.
L1 TS PL L2
in the common L2 line (see Figure 61).
FOOT SWITCHES
Figure 62. FOOT SWITCH
A foot switch, as the name implies, is activated
FTS
NORMALLY
by the operator stepping onto the switch as- OPEN
sembly. This switch operation is similar to a push
button except that the foot is used. FTS
NORMALLY
CLOSED
The foot switch is represented by the symbol
shown in Figure 62, for the normally open and Figure 63.
normally closed configurations. When operated,
the normally open contacts of the switch will L1 L2
close and will open again when the foot is re-
PL
leased from the switch (see Figure 63). FTS
PROXIMITY SWITCHES
PHOTOELECTRIC SWITCHES
PES
Photoelectric switches are represented by the
NORMALLY CLOSED
symbols shown in Figure 75, for a normally
open and a normally closed type switch.
Figure 76.
Nowadays, there are two basic kinds of photo-
EMITTER RECEIVER
electric switches which are the modulated light
source and the fiber optic type. Both of these
offer three basic design types which are the
through-beam or direct scan, the retroflective L1 PES L2
NOTES
Again, we’ll see a lot more on this application
later on.
There are two types of timers—one called ON- Figure 90. TIMER SYMBOL
delay and the other one OFF-delay. The ON- TR
delay timer, as its name implies, has its con-
tacts react after the timer has been turned on,
while in the OFF-delay timer, its contacts react Timers Have Time Delayed Contacts
NORMALLY
A timer is represented by the symbol, shown in CLOSED
input of the timer goes down to off. We’ll touch Figure 94B. ON OFF
more on these representations in a second.
OFF
reset as soon as power is removed from the
TR ON
timer’s input (see Figure 99).
OFF
delay (see Figure 100). Before the input to the TIMER INPUT
OFF
timer is on, the normally closed contacts of the DELAY
ON
The OFF-delay timer contacts operate similarly
OFF
to the ON-delay, except that the timed contacts
will open or close after the timer’s input goes
from on to off (see Figure 103). If the input to Figure 104. TIMER INPUT
Figure 114.
In the circuit of Figure 111, you would have the
coding shown in Figure 114 where the pilot light L1 L2
load is controlled by the ON-delay timer. The TR
LS
light is off during reset when the timer is not
on, and will continue off during the ON-delay
TR PL
timing. Once the delay has elapsed or timed
out, the light will be on.
O O X O O X
Types Of Timers
Figure 117.
All of these timers operate in a very similar TIMER
1 CLUTCH 2 LIGHT
manner when it comes to timing operation. How-
ever, the synchronous motor timer, which is M
10 11 A
widely used, has two instantaneous contacts 9
C 12
and two delay contacts (see Figure 117). The 8 4 3
6 5
7
clutch controls the two instantaneous contacts
INSTANTANEOUS DELAY
while the motor controls the two-delay contacts. CONTACTS CONTACTS
M
11
The number one and eleven terminals in the A
12
diagram are jumped together in the field to pro- 9
10
C 4 3
vide power to the motor once the timer is turned 5
8
6
on (see Figure 118). This can be seen in the 7
nected to the loads, in this case lights. You may FIELD JUMPER
1 2
times out, it disconnects itself from timing and 11 A
M
12
PL1
contact connection 11-12 goes to 11 A, and 4- 3 O O X
4
5
5 go to 4-3. These two are the delay contacts. PL2
X X O
tacts are not used in place of the delay con- FIELD JUMPER
tacts and vice versa (see Figure 123).
Figure 123.
The same applies to the type of timer being L1 L2
used, whether it is an ON-delay or an OFF-de- LS TR
ing diagrams. C
M
4
9 3
10 2
If the timers have already been in operation,
11 1
and for some reason fail, check first for broken 12 A
NO1 3 7 -
Counters are used in numerous industrial ap-
8
plications to count parts being made, parts +
2
1
Figure 129.
The solid state counter functions in a very simi-
SOLID STATE COUNTER
lar manner as the electromechanical with the
INHIBIT INPUT
only difference being that it may have an addi- 2
COUNT
tional input to the counter (see Figure 129). This 5
input is usually called inhibit. The inhibit input, ENABLE C B
A
when on, makes the counter ignore the count
7 4
input signal or bypass those counts (reference
1
Figure 130). When the up or down-counts are
9 6
obtained, then the count contacts will open or
3
close.
INHIBIT
OUTPUT
REVIEW QUESTIONS
a– External sensor
b– Actuator Figure 1
c– Electrical Contacts
d– Spring
a– Normally closed
b– Normally open
c– Normally open– held closed
d– Normally closed– held open
a– Rest
b– Pre-travel (trip travel)
c– Over-travel
d– Differential travel (reset travel)
TOTAL
8.- Pressure switches open or close their con- OVER
TRAVEL
TRAVEL
tacts in reaction to pressure, and can have
as measurement method(s) ______.
a– Diaphragms
b– Bourdon tubes
c– Bellows
d– Pistons RESET
POSITION
DIFFERENTIAL
(RESET)
e– All of the above TRAVEL
a– Pressure connection
b– Test to set pressure
c– Check of the switch
d– Actual field wiring Figure 3
a– N.O. FLS
b– N.C.
c– Not applicable
d– Not applicable
a– After
b– Before
c– Turbulence
d– Blockage
a– Sealed
b– Inductive
c– Capacitive
d– Detecting
a– Radio frequency
b– Voltage
c– Current
d– Detection field
a– Sealed
b– Inductive
c– Capacitive
d– Detecting
a– Normally closed–Off-delay
b– Normally open–On-delay
c– Normally open–Off-delay
d– Normally closed–On delay
ANSWERS
1.- b– Actuator
c– Electrical Contacts
2.-
3.- True
4.- False. They come with both normally open
and normally closed contacts.
5.- False
6.- c– Normally open—held closed
7.- TRIP
TRIP TRAVEL
Rest POSITION OVER
TRAVEL
TOTAL RESET
DIFFERENTIAL
TRAVEL POSITION
(RESET)
TRAVEL
9.- False
10.- b– Test to set pressure
d– Actual field wiring
11.-
a– N.O. (Normally Open) FLS
12.- b– Before
c– Turbulence
13.- True
16.- b– Inductive
c– Capacitive
18.- b– Inductive
c– Capacitive
19.- True
22.-
L1 REV L2
REV
FWD
FWD
FULL REV ZERO FULL FWD
SPEED SPEED SPEED
REV FWD
CONTACTS
CLOSE
1 CONTACTS
CLOSE
2
ON ON
OFF OFF
23.- b– On delay
c– Off delay
a
25.- b– Normally open time delay
a– Normally closed time delay
d– Reset to on
L1 L2 L3
CON
AUX
H
H 480
VOLTS
H
Chapter 4—Electromagnetic Control Switches
OVERVIEW
OBJECTIVES
INTRODUCTION Figure 1.
ELECTROMAGNETIC
In this chapter we are going to cover electro- DEVICES
magnetic switches and their uses and opera-
tions in motor control circuits. We’ll also cover E/M LOADS
protective type switches used, as their name
implies, to protect electrical circuits and the ma-
chinery controlled by these circuits. So let’s start
by defining these control elements. Figure 2.
CONTACTS
MOVABLE
CONTROL RELAYS CONTACTS
COIL
Control relays, or simply relays, are magneti-
ARMATURE
cally operated switching devices used for a wide
MAGNET
range of control applications. A relay consists
of an electromagnet (Figure 2), or the so-called
coil, which moves an armature to open or close Figure 4.
CR1
contacts to open. Relays and their normally Figure 5.
RELAY
open and closed contacts are shown in Figure 5.
CR1-1
A relay may have several normally open and
N.O.
normally closed sets of contacts available, all
CR1-2
controlled by the same coil (see Figure 6). N.C.
25 amps.
Latch/Unlatch Relays
Figure 8.
Another widely-used relay is the latch/unlatch LATCH / UNLATCH
type, is illustrated in Figure 8. This relay differs CRL
ure 11).
LS CR
As we know, control relays must receive power
in order to actuate their contacts. If power is
CR PL
not present, the contacts will not open or close.
So the first thing to check is to make sure that
the proper voltage is getting to the relay (see
Figure 12). By proper, we mean the voltage at
which the relay coil is rated; in this example,
120 volts AC. You can measure with a voltme- NOTES
ter between L1 and L2 to insure that the source
voltage is present. If the voltage is less than
120 volts, the relay may not be able to pick up
and operate the contacts. In fact, if the voltage
fluctuates, being at 120 sometimes and drop-
ping at others, it will result in an intermittent
problem. This could happen if the transformer
does not have the proper KVA rating, as we’ll
see in Chapter 7.
If you suspect that the relay is bad, you could Figure 13.
MAGNETIC CONTACTORS
Figure 14.
the switching of lighting systems, heaters, trans-
former loads (which are inductive), and other
capacitive loads (see Figure 14).
CONTROL COIL
VOLTAGE
ARMATURE
Magnetic contactors are available for single- INPUT
MAGNET
phase and three-phase AC voltages as well as
for DC voltages (see Figure 16). Contactors for
Figure 16. Figure 17.
each of these three categories are rated ac-
cording to NEMA to specify the size of the load AC/DC MAG
CONTACTOR
NEMA SIZES
they can handle safely by each contact in the CONTACTORS
Figure 20. L1
fore providing power to its load. For example, L2
L3
in a three-phase, three-pole contactor (see Fig-
CONTROL
ure 20), connected to a three-phase heater, will 120 V
Figure 25.
L1 L1 L2 L3 L2
Even though AC and DC contactors operate in
a similar manner, there are some differences CON
Figure 26. + -
having only one pole (see Figure 26). In three-
phase circuits. it is necessary to switch all three
lines, thus requiring three poles (see Figure 27).
The magnetic or coil assembly of a DC CON C
contactor is made of solid steel instead of lami-
nated steel, as in the case of the AC contactor,
the reason being that DC current only flows in
one direction continuously and doesn’t create ONE POLE SWITCH
Eddie current problems.The other major differ-
ences are the electrical and mechanical require-
ments to suppress the “arcing” created during Figure 27.
L1 L2 L3
the opening and closing of the contacts. We’ll
touch on this subject next.
Figure 30.
Suppression of DC arcing is harder to elimi-
SUPPRESSION OF DC
nate because the DC supply continuously pro- ARCING IS HARDER
vides flow of current in one direction instead of
fluctuating (see Figure 30). like AC does, be-
CONSTANT
tween positive and negative (see Figure 31). CURRENT
The DC arc will last until the two contacts are FLOW
arc chute where it is enlarged and extinguished Figure 35. MOVEMENT DUE TO
MAGNETIC FIELD
Figure 48.
In the ladder circuit (see Figure 48), the motor
starter will be on if the limit switch closes. Note L1 L2
that the normally open auxiliary contacts close
M OL
and turn the pilot light on. The power contacts LS
will close, providing power to the motor as soon
as the starter coil is energized. If the motor pulls
too much current, the overload relays will trip M PL
and open the normally closed overload contacts
which, in turn, disconnect the motor from the
circuit. Later, we’ll see this overload operation
in more detail.
Figure 49.
There are several types of magnetic motor start- L1 L2 L3
M
Reversing starters are available for applications
which require reversal of motor rotation, that
is, forward and reverse. You can recall when
we were talking about plugging switches, that NOTES
we can reverse the direction of a 3-phase mo-
tor by simply switching two of its lines. The re-
versing starter provides the hardware to imple-
ment this reversal. This starter is composed of
two contactor sections with their respective
auxiliary contacts. These sections are used to
switch the phases to the motor. The starter also
provides the overload protection for the motor.
(see Figure 51). These speeds are low and high. Figure 51.
Reduced voltage starters are available to con-
trol and allow a motor to start at a lower speed L1 L2 L3
Figure 52.
The wiring connections made during installa-
tion of a motor starter must follow the manu-
• MAKE SURE THAT THE
facturers wiring diagram specifications. As we
PROPER VOLTAGE PHASES
know, ladder diagram descriptions will serve
ARE CONNECTED
little purpose, if any, during the wiring and in-
stallation of a motor starter. Many times, espe- • AN UNPREDICTED REVERSAL
cially applications requiring multiple motors to OF PHASE CAN CAUSE
control a line, all starters are housed in motor SERIOUS DAMAGE AND/OR
control centers where they are easily accessed INJURY
and available for troubleshooting.
CURRENT
keeps the plunger in the center, is called the
sealed-in or holding current.
HOLDING
1 AMP
As an electrician or technician, you will be called
VOLTAGE
upon to replace or troubleshoot control com-
ponents which may have a solenoid incorpo- TIME
Figure 61.
This solenoid may have a spring retention which
causes the plunger to close against the seat of REPRESENTATION
the valve preventing fluid from passing. When
power is applied, the plunger will be pulled back
and the valve would open. This valve is called
a one-way valve because the flow of fluid is only
SOLENOID VALVE
in one direction. There is one inlet and one out-
let, and fluid goes from the inlet to the outlet.
way or as a three-way.
Figure 67.
As a two-way valve (see Figure 66), the pres-
sured air is supplied to the inlet port (port 1) and
goes to the air system through port 2, while the
other 3 ports are plugged. When the solenoid is 4 2
AIR
Suppose now that we wanted to use this valve
4 2
as a three-way, in an application which uses
an air cylinder whose piston is used to push a
bad part off a conveyor, and that the cylinder is
5 1 3
returned back to its off position by a spring (Fig- P
Figure 74.
If you suspect a problem with a solenoid valve, L1 L2
you should try to feel or hear the “click” associ- SOL
ated with the plunger movement as the sole-
noid is energized and de-energized. The fluid
flow should also be changing direction. To check
for voltage to a valve, you can use a voltmeter
to see if proper power is getting to the solenoid
(see Figure 74). If there is power (Figure 75)
and the valve doesn’t change in spite of receiv-
ing the right voltage, it could be that the valve
is corroded and requires replacement or per-
haps that the fluid pressure is too much for the Figure 75.
Fuses
MOTOR
Under normal operation, the fuse conduces STARTER
current simply by acting as a conductor (see
10 HP
Figure 81). If an overload occurs and persists
for a short interval, the temperature created by
the overcurrent reaches a level which melts the
link and a gap is formed, thus breaking the cir- Figure 81.
cuit.
Figure 86.
Fuse Curves
6
As you’ll see later in Chapter 6, when we talk
CURRENT
about the National Electric Code, non-time de-
3 300%
lay and dual-element, time-delay fuses are
rated, under normal conditions, in the range of
300 and 175 percent of the full load current of
motors. This gives, for example, a non-delay
TIME
time fuse only three times its rating to allow for
the start of a motor (see Figure 86). And we
know that a motor may take at least six times Figure 87.
the full load current when it is first started. The
reason is that fuses do not open instantly at a 100,000
CURRENT IN AMPERES
current just above the fuse rating.
10,000
3,000
As the graph in Figure 87 describes a single- 1,000
500 TIME-DELAY
element and dual-element, time-delay fuses,
100
NON-TIME DELAY
rated at 100 amps, it will take 10 seconds for
.2
the time-delay to open at a current of 500 amps, 10
.01 .1 1 10 100 1,000
whereas it will take 2 tenths of a second for the TIME IN SECONDS
Figure 88.
horsepower, 200-volt motor (see Figure 88).
STARTER
SWITCH
This motor has a full load amperage rating of F
CURRENT
90 amps fuse does not provide protection for
the motor under overload (shown in dotted line
FUSE
in the motor curve of Figure 89). Therefore, it OVERLOAD
MOTOR CONDITION
would require overload protection at the starter.
TIME
If we want to use a dual-element, time-delay
fuse to protect the motor from overload, as well
Figure 90.
as the circuit from short circuits, we would se-
STARTER
SWITCH
lect, according to Article 430-32 of the code, a F
DAMAGE CURVE
protect it from overload conditions. In fact, if TIME
100% DELAY
motor overload relays are used in the motor OVERLOAD CURVE
HEATER CURVE
control circuit, the dual-element fuses will serve TIME
as running motor backup protection in case the
overload relays are the wrong size or fail to
Figure 91.
operate. The graph illustrated in Figure 90 STARTER
SWITCH F
shows the motor damage curve and the pro-
tecting curve provided by the motor overload 100A
M
90A
heaters. The dual element curve is shown as NON-TIME PROTECTION
DELAY
backup protection. Additionally, the disconnect SWITCH STARTER
F
switch used in the dual-element circuit will be
M
of smaller current-carrying capacity than the 60A
40A
one in the 90-amp circuit, therefore reducing TIME DELAY PROTECTION
BACK-UP
space and money (see Figure 91). Remember, PROTECTION
Fuse Types
DISCONNECTED
Circuit Breakers
CB
TO TO
LOAD LOAD
The bimetal breaker responds in an inverse time LINE LINE
250%
while the other one represents the magnetic THERMAL
Figure 99. L1
OVERLOADS
L2
L3
As we have mentioned before, motors are re-
THERMAL-MAGNETIC
quired to have protection against overload situ- CIRCUIT BREAKER
CURRENT
MOTOR
stopping rotation because of a jamming condi- PROTECTION
CURVE
tion in the line. When overloading occurs in a
motor, it will produce overheating, resulting in
TIME
a deterioration of its insulation, and cause dam-
age to the motor. A motor can also overheat if it
is started and stopped too frequently.
Figure 101.
OVERLOAD
To meet the protection requirements of a mo- SYMBOL
tor, overload relays provide: 1—a time delay to
allow the harmless temporary overcurrent dur-
ing start up; 2— tripping capability of the motor
circuit once a dangerous level of overcurrent OL
has been detected for a period of time and 3—
they provide a means for resetting the circuit.
Figure 102.
HEATER
• MEASURE HEAT
The assembly of the overload relay is formed GENERATED BY
by the heater coil, also called overload heater OL
CONTACTS
CURRENT
RESET
OPERATER
After the bimetal has cooled off from the heat DEFLECTION
WITH TEMP.
created by the current, it may return to its origi- INCREASE
% of Trip Current
curves of heater elements are specified at an
ambient temperature of 40 degrees Celsius to
correspond with the temperature at which most
motors are specified for ambient conditions.
Underwriters Laboratory requires, at a tempera-
ture of 40 degrees, that an overload relay trip
in 4 hours of operation at 100% the trip cur-
rent, in 8 minutes at 200%, and in 30 seconds
at 600% (see Figure 113). Figure 114.
Just make sure that the heater you are refer- Figure 115.
TOTAL HEAT REQUIRED TO TRIP OVERLOAD RELAY
encing to the table has the proper current for it,
whether it is already calculated at 125% the HEAT GENERATED
HEAT BY MOTOR CURRENT HEAT
full load current or if it is calculated without the GENERATED GENERATED
BY MOTOR BY MOTOR
125% required by the code. CURRENT CURRENT
AMBIENT
Effects of Ambient Temperature HEAT
AMBIENT
HEAT
Thermal overloads are sensitive, as we have A B C
AMBIENT
HEAT
mentioned, to heat and they do get affected by
the ambient temperature. For example, if the
total heat required by the overload relay to trip Figure 116. LOAD
HEATER TERMINALS
is represented as in Figure 115 (left), and the
ambient temperature creates part of the heat,
BIMETAL
then the rest of the heat is left for overcurrents
due to an overload. If the motor draws the full
load current for a long period, the overload re-
lay will trip. Now, if the ambient heat is as shown
in the middle of Figure 115, then the overload Compensating Bimetal Strip
will trip at less overcurrent, creating a nuisance LOAD
Figure 117.
tripping. Conversely, if the ambient heat is as HEATER TERMINALS
1.3
Bimetal overloads may provide a compensat- 1.2
ing bimetal strip which is added to the assem- 1.1
bly (see Figure 116). This compensating strip 1.0
allows the relay to adjust (Figure 117) for
0.9
changes in ambient temperature “at the loca-
0.8
tion” of the overload assembly, which is usually
0.7
close to the motor starter.
0.6
REVIEW QUESTIONS
a– Motor starters
b– Relay
c– Solenoid
d– Dual-element fuse
a– Opposite
b– Latch/Unlatch
c– Two-way
d– Same
a– Less
b– More
a– Manual
b– Cadmium oxide
c– Magnetic
d– Anti-arcing
a– Contactors
b– Starters
a– Two-speed starter
b– Full-voltage starter
c– Reduced-voltage starter
d– Multi-channel voltage starter
a–
b–
c–
d–
a– Single element
b– Dual element
c– Two-way
d– Full-load amperage
a– A solenoid
b– A circuit breaker
c– A current-carrying capacity switch
d– A thermal overload
a– Bimetal or thermal
b– Class R rejection clips
c– Magnetic
d– Static
a– A motor
b– A circuit
c– A branch circuit
d– A complete busway
ANSWERS
1.- True
2.- b– Relay
3.- b– Latch/Unlatch
d– same
4.- True
7.- True
8.- b– More
9.- a– Manual
c– Magnetic
10.- b– Starters
12.- c–
15.- True
18.- True
21.- True
22.- a– A motor
23.- True
MODULE
CHAPTER 5 5
L1 L2 L3
OVERVIEW
OBJECTIVES
NOTES
INTRODUCTION
SOLENOID VALVE
trical industry there is an established set of sym-
bols universally known and rules on how these
ladder circuits must be laid out.
Figure 5.
LADDER DIAGRAMS
L1 L2
PICTORIAL REPRESENTATION
In previous chapters, when we explained each
of the components used for control, we de-
scribed the symbols that were used for their
representation in control circuits—in other
words, in ladder diagrams (see Figure 4).
PUSH BUTTON PB1 PILOT LIGHT PL1
Figure 6.
In fact, continuity is said to exist if there is a L1 L2
POWER CONTINUITY
power path from left to right (see Figure 6).
POWER PATH
We know that it would be very difficult to repre-
sent all the control devices in a pictorial man-
ner, and that is why we use their appropriate
symbols in an electrical ladder diagram.
Figure 12.
and L2 which is required to properly operate.
LOADS CONNECTED TO L2
If we place a voltmeter across each of the loads,
L1 L2
we would read 120 volts AC. S1 SOL1
Loads Connected to L2
PB1 CR1
As can be seen so far, all the loads, such as
control relays, pilot lights and solenoids are
connected to L2, completing the circuit from L1
through the control and switching devices such
as limit switches, push buttons and relay con- Figure 13.
tacts (see Figure 12). The reason why loads
LOADS CONNECTED TO L2
are connected to L2, and not as illustrated in
L1 L2
Figure 13, is because we always want to switch SOL1 S1
the power or hot lead to the loads for safety
reasons, as opposed to switching the return line
as described in Figure 12. In Figure 13, the so-
lenoid is always powered, waiting for a switch
connection to the return L2 line.
One small exception to the rule, that the loads Figure 14.
S1
To get a better idea, let’s look at a simple, single-
phase manual starter with overloads. In the one-
phase motor starter shown in Figure 15, we can
see that the pilot devices are connected to the Figure 16.
L1 L2
Control Devices Between L1 and Loads PB1
PL
PB3 TMR1
PS1
activation of the load or control devices is 3
TMR1
achieved. For instance, either of the two push 4
10 SEC
FS1
buttons in Figure 21 will turn the light on when 5
TS1 SOL1
3
a load. Note that lines three and four have the PB3 TMR1
PS1
4
same load, and two different line numbers are TMR1 10 SEC
5
assigned because there are two complete paths FS1
TS1 SOL1
to the timer, from L1 to L2. An independent line 6
CR1
number will also be assigned to a set of con- 7
CR2-1 LS2
13 M
Figure 26.
For instance, a float switch (Figure 26) which is
activated automatically when water reaches a
desired level can be considered an automatic
control. TANK
OF
FLOAT WATER
Regardless of whether these signals are SWITCH
manual or automatic, they do not operate as
an output load, thus they perform no work. They
simply provide information—input information
to be used to make a decision on the behavior
of an output control. Figure 27.
Logic Section
LOGIC SECTION
• DECISION L1 L2
The logic section of a circuit is considered as MAKER
INPUT LOGIC OUTPUT
the decision maker where, depending upon how • OUTPUT
we want an output to take place, the wiring or WIRING
interconnections of the input signals will be
performed. We’ll cover in detail this area in a
little while (see Figure 27).
Figure 28.
M
Logic, as used in control circuits, can be de-
fined as the necessary arrangements of input
signal conditions that need to take place to
cause a control output. This arrangement is
implemented by the interconnecting wires of
the circuit (see Figure 31).
Figure 32.
It is obviously apparent that the organization L1 L2
and documentation of the control circuit will DEVICES
define how complicated it will be for someone
else to figure out what you have done. LOGIC OUTPUT
AND
Figure 36.
OR
L1 L2
The OR logic function describes the result of DEVICES
an output if at least one of its input signal con-
LOGIC OUTPUT
ditions provide a path from L1 to the load to L2 OR
(see Figure 36).
2
Most control circuits will be a combination of
AND logic with OR logic to control an output. 3
Logic as shown in Figure 39, which in this case
drives a pump’s motor starter, is created ac- 4
cording to the need that you have or better said
yet, according to the necessary conditions that
must be present to activate the pump motor. Figure 39.
vated. Notice that the logic simply follows what Figure 40.
CR1
NOT
LS1
The NOT function is used a lot in control cir-
cuits because a lot of devices we use, we want
in the normally closed position (see Figure 46).
Figure 47.
For instance, all stop push buttons are normally
closed. So that, if someone pushes it, it will
break or stop power continuity to the circuit.
power to the rest of the circuit (see Figure 52). Figure 53.
If the door is closed, the switch will be pushed,
L1 DOOR PANEL L2
opening the switch contacts; thus CR1 will de- LIGHT
SWITCH
energize and its contacts CR1-1 will remain
1
closed, providing L1 power. If the door opens,
there is power to CR1 and the normally closed CR1
2
contacts will now open disrupting power.
OFF T/S CR2
3
But what if your boss asks you what happens if
someone needs to troubleshoot the circuit with
4 CR1-1 CR2-1
the door open and needs the power?
TO REST OF CIRCUIT
If the door opens, we need to bypass the power
that has been cut off by the contacts of the con-
trol relay CR1 (see Figure 53). This can be done NOTES
by placing another set of contacts in parallel to
CR1-1. By creating a signal (line 3 in Figure
51) that says we want to troubleshoot the sys-
tem, even though the door is open, we can
control these contacts. If we add another con-
trol relay CR2 and we label the parallel con-
tacts CR2-1, we can create the bypass and
control it with a signal from a selector switch
inside the panel which creates the signal
troubleshoot. If the selector switch is in the
troubleshoot position, the relay CR2 will ener-
gize and the contacts CR2-1 will close, thus
passing L1 power to the rest of the circuit. If
the troubleshoot switch is not selected, CR2
will be de-energized and the CR2-1 contacts
will open.
next example.
ever the motor is turned on. If the motor is off, Figure 59.
L1 L2
then the light will also be off (see Figure 59).
START STOP STOP
M1 OL
PB1 PB2 PB3
You may encounter or have to modify many
motor control circuits in the plant to include
several start or stop circuits, the so called mul- M1 PL
2 3
tiple start/stop (see Figure 60). This simply
AUX
means that you can start or stop a particular
motor from different locations. When any start
push button is pressed, the starter will be en- Figure 60.
ergized, seal the circuit, and turn the motor on. L1 L2
PB1 OL
If you want, you may have motor indicator lights PB5 PB6 PB7 PB8 M1
1
routed to where each start/stop circuit is physi- PB2
PL1
cally located so that any operator may know if 2
PB3
the motor is on. 3 PL2
PB4
PL3
4
To review some of these circuits, let’s take an
M1
PL4
example of a motor control circuit which our 5
boss tells us needs to be modified (see Figure
61).
Figure 61.
L1 L2
START 1
In the circuit of Figure 61, we have two inde- STOP 1
M1 OL
PB1 PB2
pendent motor starters being controlled by two 1
Figure 62.
We can easily accomplish this by knowing that, L1 L2
STOP 1 START 1
at the point with the shaded area in Figure 62, PB1 PB2
M1 OL
1
the circuit provides information with memory
M1
that M1 is running so, if we connect our first 2
INTERLOCKING CIRCUITS
R1
4
NOTES
When no push button has been pressed, both
of the auxiliary contacts, R2 and F2 will re-
main in its normal state, which is normally
closed. If the operator pushes the forward push
button, there will be power continuity from L1
to the forward starter, its sealing contacts F1
will seal around the forward push button and
the auxiliary normally closed F2 contacts in
line 3 will open because the starter coil is en-
ergized. These F2 contacts, now opened, will
block any reverse push button activation of the
reverse starter.
BYPASS
CR2-2
We can solve this problem by adding some in-
terlocking and using a two-position selector
CR1-1 CR2-1
switch that has a spring return so that it acts BYPASS
as a momentary switch which goes back to off
after being turned to troubleshoot.
NOTES
The modified circuit shown in Figure 73 will pre-
vent the bypass power from remaining on once
the door has been closed; when the door opens,
the contacts CR1-2 close to allow for bypass
power to occur. Once the selector switch is mo-
mentarily put in troubleshoot, CR2 will turn on
and seal the selector switch with contacts CR2-
2 and provide bypass power. If the door is
closed, the contacts CR1-2 reset the bypass
coil and the bypass power.
CR2
open in line 5 and one normally closed in line 6 (9)
CR1
TMR2
7 (9)
7. This representation shows the electrician or 8
CR3
TMR2 PS2 CR1 CR2
SOL3
technician that this limit switch has an action 9
Level
ure 80). It would not be logical to have one set 7 FS5 CR2 SOL2
Open
10 PL1 Ready
4
LAYOUT AND CONNECTION DIAGRAMS Level
SOL1
FS4 CR2 CR3
5 Open
PL2
The layout and connection diagram provides 6 #1
7
going to L1 and L2, we’ll assign a block to each 8
9 SPARE
with several terminals with label one and two 10 TMR
11
as shown in Figure 85.
Figure 86.
The rest of the wiring connections will be as- L1 L2
signed as we go through each circuit (see Fig- PB2
PB1 CR1
1 3 4 2
ure 86). That is, one side of PB1 will be wired
to terminal 3, which also connects the sealing
PL1
contacts CR1-1 and PB2. The other side of PB2 CR1-1
2
will go to terminal 4, which connects to the other
side of CR1-1 and to one side of CR1 and to CR1-1 CR2
1 5 LS1 6 2
one side of PL1. The other sides of the coil CR1
and the light PL1 are connected to terminal 2. PL2
2
CR2-1
The rest of the control circuits would follow in
the same manner. CR2-2
1 TMR1
7 2
PB1 PB2
SOL1
9,2 LS1
TO 1, 3 TO 3, 4 TO 5, 6
This chapter covered some important control
circuit topics that will certainly help you to not PL1 PL2 PL3
4,2 6,2 9,2 TO 8, 9
only understand control circuit ladder diagrams, LS2
REVIEW QUESTIONS
a- Wiring diagrams
b- Ladder diagrams
c- Layout diagrams
d- Busway diagrams
a- Output section
b- Logic section
c- Interface section
d- Input section
a- Input section
b- Output section
c- Logic section
d- Interface section
a- NOT
b- OR
c- AND
d- NOR
a- AND
b- NOT
c- OR
a- AND PB2
b- NOT
c- OR
a- Series
b- Parallel
M1
2 3
AUX
a- Circuit actuation
b- Circuit interlocking
c- Circuit completion
d- Circuit modulation
a- Mechanical
b- Push button
c- Sequential
d- Auxiliary or control relay contact
Figure 3
17.- The Figure 3 is an example of ______ in-
L1 L2
FWD
terlock which protects two circuits from F OL
ST0P REV
being on at the same time. 1
F
2
a- Mechanical
b- Push button R
3
c- Sequential
R
d- Control relay contact 4
a- Ladder diagram
b- Layout diagram
c- Auxiliary control diagram
d- Busway diagram
L1 L2
FWD
25.- True/False. The cross-referencing of me- ST0P F OL
chanically linked devices with the dash line
method is only useful if the contact ele- F
ANSWERS
1.- True
3.- True
5.- True
10.- c- AND
11.- NOT
12.- c– OR
13.- b- Parallel
16.- a- Mechanical
b- Push button
d– Auxiliary or control relay contact
18.- True
22.- True
25.- True
FUSE =
200A + 40A =
240A REQUIRED
300% x 40 = 300% x 65 =
120A 195A
USE 125 A FUSE USE 200 A FUSE
CODE J
30 HP 50 HP
FLA = 40A
M1 M2 FLA = 65A
Chapter 6—Introduction to AC and DC Motors and Motor Control Circuits
OVERVIEW
OBJECTIVES
INTRODUCTION NOTES
In Chapter 6, we’ll explore some important
details that deal with motor controls. We’ll start
with a general review of Article 430 of the
National Electric Code and then we’ll progress
into some important information needed for the
specification and implementation of motor con-
trol circuits.
Figure 1.
430 - 1
adhere to any other local and state electrical
General Part A
code regulations in addition to the ones pre- Requirements for over 600 volts, nominal Part J
Protection of live parts all voltages Part K
sented by the NEC. Grounding Part L
Tables Part M
To Supply
Motor Feeder Part B
It is not our objective here to go into extreme Sec. 430-23 and 430-24
430-25 and 430-26
detail on the code, but to give you an overview
Motor Feeder Part E
of Article 430 and also to give you an inside look Short-Circuit and Part E
Ground-Fault Protection
at how you can better understand it and get
information from it. Motor Disconnecting
Means
Part H
Motor Branch-Circuit
Article 430 starts with a section named 430-1 Short-Circuit and
Ground-Fault Protection Part D
which is titled Motor feeders and branch cir- Motor Circuit Conductor Part B
the motor (see Figure 2). Article 430 simply BRANCH CIRCUIT
CONDUCTORS
Figure 6.
All manufacturers of electrical motors are re-
BRYAN MOTOR CONTROLS
quired to provide a motor nameplate on each AC MOTOR
motor they supply (Figure 6). These name FRAME TYPE INS CLASS I.D. NO
182T P B P18G11D CY
plates provide all the motor data pertinent to
H.P. RPM VOLTS AMPS HZ S.F.
that motor’s operational characteristics. The
7.5 1740 230/460 22/11 60 1.15
nameplate contains information about the mo- DESIGN: B CODE: J PHASE: 3
tor design, motor type, the type of frame, the 4 5 6 4 5 6
the RPMs or revolutions per minute, the num- AMB: 40˚C DUTY: CONT.
1 2 3 1 2 3
NOTES
To understand it better, let us go over the motor
nameplate for the motor shown in Figure 6 and
get all the characteristics and specs on it.
tor or SF of 1.15. The service factor is a mea- H.P. RPM VOLTS AMPS HZ S.F.
sure of the motor overload capacity that was 7.5 1740 230/460 22/11 60 1.15
DESIGN: B CODE: J PHASE: 3
designed into the motor. A service factor of 1.15 4 5 6 4 5 6
tells us that this motor can deliver 15% more of DRIVE END BEARING 30BCOZXPP3M 7 8 9 7 8 9
OPP. END BEARING 25BCOZXPP3M
the rated horsepower as noted in the name- 1 2 3 1 2 3
AMB: 40˚C DUTY: CONT.
plate, without damage to the motor from over-
LOW V HIGH V
heating. So this motor could deliver up to 8.63
horsepower if overloaded. This allows you to
safely use this motor in an application which
NOTES
may require, let’s say, 8 horsepower.
nent specifications for its control circuit. Table 430-150. Full-Load Current*
Three-Phase Alternating-Current Motors
Induction Type Synchronous Type
Squirrel-Cage and Wound-Rotor †Unity Power Factor
MOTOR CIRCUIT SIZING Amperes Amperes
HP 115V 230V 460V 575V 2300V 230V 460V 575V 2300V
1/ 2 4 2 1 .8
What we’re going to be concerned with, accord- 3/ 4 5.6 2.8 1.4 1.1
1 7.2 3.6 1.8 1.4
ing to the diagram in Figure 10 which relates to 1 1/ 2 10.4 5.2 2.6 2.1
2 13.6 6.8 3.4 2.7
Article 430, will be the conductors going to the 3 9.6 4.8 3.9
motor full load current rating. In this case, the Table 310-16. Allowable Ampacities of Insulated Conductors
Rated 0-2000 Volts, 60˚ to 90˚C
value is 22 amps from the table times 1.25 Not More Than Three Conductors in Raceway or Cable or Earth
(Directly Buried), Based on Ambient Temperature of 30˚C (86˚F)
which tells us that our branch circuit conductor Size Temperature Rating of Conductor, See Table 310-13 Size
Figure 13.
Table 430-152. Maximum Rating or Setting of Motor Branch-Circuit
we need to rate it at 175% of the full load current Short-Circuit and Ground-Fault Protective Devices
of 22 amps or 1.75 times 22 which gives us 38.5 Percent of Full-Load Current
Dual
amps. Element Instan-
Nontime (Time- taneous *Inverse
Delay Delay) Trip Time
Type of Motor Fuse Fuse Breaker Breaker
This calculation implies that we need a 38.5 Single-phase, all types
No code letter..................... 300 175 700 250
amps fuse. According to table 240-6 of the code All AC single-phase and
polyphase squirrel-cage and
(Figure 14), which deals with standard sizes synchronous motors† with
full-voltage, resistor or reactor
starting:
and ratings of fuses and circuit breakers, we No code letter..................... 300 175 700 250
Code letter F to V................
find that there is no 38.5 amp fuse. However, Code letter B to E................
300
250
175
175
700
700
250
200
Code letter A....................... 150 150 700 150
Article 430-52 provides Exception #1 (Figure All AC squirrel-cage and
synchronous motors† with
15), which states that if we can’t find the exact Autotransformer starting:
Not more than 30 Amps
fuse, the next standard size should be used; in No code letter..................... 250 175 700 200
More than 30 Amps
this case, 40 amps. With a 40-amp fuse, the No code letter..................... 200 175 700 200
Code letter F to V................ 250 175 700 200
motor branch circuit and the 10-gauge RUW Code letter B to E................
Code letter A.......................
200 175 700 200
150 150 700 150
conductor will be protected. Note that this pro- High-reactance squirrel-cage
Not more than 30 Amps
No code letter.....................
tection is against short circuit and ground faults, More than 30 Amps
250 175 700 250
No code letter.....................
not to protect against motor overloads. Wound-rotor–
200 175 700 200
No code letter..................... 150 150 700 150
Direct-current (constant voltage)
Not more than 50 hp
Motor Overload Protection No code letter..................... 150 150 250 150
More than 50 hp
No code letter..................... 150 150 175 150
Article 430-32a, part one, states that this motor For explanation of Code Letter Marking, see Table 430-7(b).
For certain exceptions to the values specified, see Sections 430-52
shall be protected by an overload device de- through 430-54.
*The values given in the last column also cover the ratings of nonadjustable
inverse time types of circuit breakers that may be modified as in Section 430-52.
signed to trip at no more than 125% of the motor †Synchronous motors of the low-torque, low-speed type (usually 450 rpm or
lower), such as are used to drive reciprocating compressors, pumps, etc.
name plate full current, namely in this case, that start unloaded, do not require a fuse rating or circuit-breaker setting in
excess of 200 percent of full-load current.
1.25 times 22 or 27.5 amps. Note that this Reprinted with permission of NFPA
overload protection is designed to protect the
Figure 14.
motor, not to protect the circuit against ground Table 240-6
faults or short circuits, that’s the function of the STANDARD AMPERE RATINGS
fuse or breaker.
The standard ampere rating for fuses and
inverse time circuit breakers shall be
considered 15, 20, 25, 30, 35, 40, 45, 50, 60,
It is also important that, when you get the full 70, 80, 90, 100, 110, 125, 150, 175, 200, 225,
250, 300, 350, 400, 450, 500, 600, 700, 800,
load current of the motor, you get it from the 1000, 1200, 1600, 2000, 2500, 3000, 4000,
5000, and 6000.
nameplate and not from the NEC tables, since
Reprinted with permission of NFPA
this number may differ and, if this is the case,
Figure 15.
the one from the nameplate is the one to use. ARTICLE 430-52
• Manual
Figure 17.
• Magnetic
Figure 18.
600 VOLTS MAXIMUM
Maximum Horsepower Maximum
Rating 2 Horsepower
NEMA Contin-
Size uous Full load current must not Rating For
Amp- exceed the "continuous Plugging
Rating Ampere Rating" Service 1
Figure 21.
If more than one branch circuit is connected to
a feeder (see Figure 21), you should pay atten-
tion to the size of the feeder conductor and also FEEDER
to the protection against ground fault and short
BRANCH
circuit at the feeder. CIRCUITS
START
Safer Control Circuits—Control Power STOP OL
M
MOTOR
STARTER
In all the control circuits we have seen so far, M1
L1
These control transformers eliminate the need L2
480V M
of bringing an additional power source to the L3
control circuit (Figure 31). By adding the control
L2
transformer, we also eliminate the need of a 120V L1
separate disconnect means. Note that, in the
diagram (Figure 32), the transformer’s primary
connections are made “after” the disconnect M
means in the power circuit. Disconnecting the
motor control circuit will also disconnect the
motor load.
L1
M
gized, the motor load contacts close which, in
turn, start the motor.
Figure 41.
Finally, below the heaters, you’ll find the termi- L1 L2 L3
2
Most of the time, you will find starters that come
with some pre-wired control circuit connections
which are done at the time of manufacturing
T1 T2 T3
(Figure 41). These include one side of the
Figure 42.
starter coil to terminal 3 of the auxiliary contact.
L1 L2
This connection will also be represented in the
wiring diagram (Figure 42).
START
STOP OL
2 3
2 3
If we added a pilot light in the ladder diagram
(see Figure 46) to indicate a “motor on” condi-
tion, we would include it in the wiring diagram
(see Figure 47) coming from a this point in the
push button terminal or the point at the terminal Figure 47.
NOTES
pecially when you are troubleshooting a system
and find these circuits described somewhere in
the wiring or ladder diagrams. So let’s take a
look at these circuits.
Two-Wire Control
M
Three-Wire Control
2 3
The three-wire control circuit (Figure 52), as its
name implies, uses three wires to connect to
the coil of the motor starter. In fact, the extra
wire is the one that connects the auxiliary con-
tacts which seal the start push button, as can be Figure 53.
seen in the wiring diagram of Figure 53. This is THREE POWER
actually the circuit which we first discussed in WIRES
L1 L2 L3
Chapter 5 as having the function of adding
memory to a circuit. Start
Stop
3
In Figure 53, we can see the three wires that go
2
to the starter. Three-wire control does provide
both low voltage release and low voltage pro- OL
tection. If the control power is lost, the starter T1 T2 T3
Figure 54.
turn on the motor unless the operator again START
presses the start push button; so this circuit is
2
providing the low voltage protection by not
allowing the motor to turn back on automatically 3
without operator intervention. 1
STOP
The three-wire circuit can also be visualized in
PUSH BUTTON
the standard push button station (Figure 54) STATION
used for three wire control where there are
three terminals for the three wires. Terminal Figure 55.
THREE POWER
one goes to L1 and terminals 2 and 3 go to the WIRES
L1 L2 L3
auxiliary set of contacts in the starter. This
START
typical push button station, as we know, would
be represented in a wiring diagram as shown in 3
Figure 55. Note that the two push buttons are 2
STOP
surrounded by a dotted line to signify a three-
wire control push button station. OL
T1 T2 T3
2 3
AC Motors
Figure 61.
also represented by the Wye and Delta configu-
rations (Figure 61). They perform the inverse WYE PHASE
A
function of an alternator or generator system. L1 T1 PHASE
L2 T2 B
L3 T3 PHASE
The 3-phase induction motor (Figure 62) is C
primarily composed of these three basic parts: MOTOR STARTER
PHASE
• Stator DELTA A
L1 T1
• Rotor PHASE
L2 T2 B
• End Plates Brackets L3 T3
PHASE
C
MOTOR STARTER
The stator is the stationary part of the motor
and, therefore its name, and consists of several
Figure 62.
parts, including the frame type, according to
NEMA standards. The stators consists of a
group of individual coil windings (Figure 63)
where the rotor will rotate once the voltage is
applied. These windings will be connected to
the motor starter terminals.
T9 T8
The squirrel-cage, wye wound, dual voltage T6 T5
motor has 9 terminal leads from the end of its T3 T2
HIGH VOLTAGE
coils for field connections (Figure 64). These
terminals are numbered clockwise, starting at Figure 65.
WYE CONNECTION
one, two, three, and so on. The terminal con- T1
T6 T7
nine-lead delta motor configuration also repre-
sents the terminal in number order in a clock-
wise direction, starting at T1, T2, and so on to T3 T8 T5 T2
HIGH VOLTAGE
T9. For a full voltage configuration, we would
connect the terminals shown in Figure 67, where Figure 68.
the T1, T2 and T3 terminals are connected to DELTA CONNECTION
T1
the motor starter’s T1, T2 and T3 connections.
T9 T4
For a low-voltage configuration (Figure 68), we T6 T7
LOW
would connect terminals 1, 6 and 7 together; 2, VOLTAGE
1-Phase Motors
MOVE FORWARD
Single-phase motors (see Figure 70) are used MOVE REVERSE
most frequently in applications requiring a frac-
tional horsepower motor or in applications where
there is a need for a motor and there is no three- Figure 70.
phase power available. 1O MOTOR
T1
The start winding may also show four terminals,
of which 6 and 7 are connected together and5 T2
T6
START
1O RUN T7
and 8 go to power. Terminals 5 and 8 of the start POWER T3
T8
black, respectively.
DUAL 120/240 VOLTAGE
T8
Others are the capacitor type motors.
DUAL 120/240 VOLTAGE
• Capacitor Start
• Permanent Split Capacitor CAPACITOR START
• Capacitor Start-Capacitor Run
Figure 78.
The capacitor start motor (Figure 77) has a C
DC Motors
• Armature
• Motor Frame
• End Plates or Brackets
• Shunt DC Motor
SERIES DC MOTOR
• DC Compound Motor
armature winding. The wires coming from the Figure 81. SERIES FIELD
series field are labeled S1 and S2 and the
armatures are labeled A1 and A2. The electrical S2 S1
+ A2
representation of this motor is given by the
DC
circuit shown in Figure 81, where the series field POWER
ARMATURE
POWER FACTOR + -
If there is no phase angle (Figure 92), the power POWER = 1.73 X VP-P X I X Cos PA
=
in a 3 phase will be 1.73 times the voltage times 0°
the current times the value of the cosine of the = 1.73 X VP-P X I X Cos 0°
phase angle difference which will be the cosine
= 1.73 X VP-P X I X 1
of zero degrees which is one, therefore making
= 1.73 X VP-P X I
the true power be the same as the apparent
TRUE POWER = APPARENT POWER
power. To see this more clearly, let’s take an
example. Figure 93.
PF CALCULATION
Let’s take a 460-volts (Figure 93), 3-phase, 20 • 460 V MOTOR
horsepower motor which draws 21 amps at full • 3O
• 20 HP
load and we’re told that there is a 30-degree
• 21 FLA
phase angle due to inductance. The power
• 30˚ PA
(Figure 94) will be 1.73 times 460 times 21
times the cosine of 30 degrees which is 0.866
Figure 94.
for a total of 14, 472 watts or 14.47 kilowatts. T POWER =1.73 x 460 x 21 x Cos 30˚
This is the true power for the motor. =1.73 x 460 x 21 x 0.886
=14,472 WATTS =14.47 KW
The apparent power will be 1.73 times 460 A POWER =1.73 x 460 x 21
times 21 for a total of 16,711 Volts Amperes or =16,711 VA =16.71 KVA
16.71 KVA.
Figure 95. TRUE POWER (KW)
The ratio between these two gives us 0.866 or PF =
APPARENT POWER (KVA)
86.6% (Figure 95), which is the power factor.
This number is actually the cosine of the phase 14.47
= = 0.866 OR 86.6%
angle, which is the power factor. 16.71
!
=
Cos 30˚
If we measured with a watt meter in front of the
% POWER FACTOR
80
16.7. Power companies do not like plants that
70
run at below a 90% power factor so they charge
60
a premium rate for the power they deliver to 50
your equipment. 40
30
20
This example demonstrates a power factor
10
problem which is very common in AC squirrel- 0
25 50 75 100
cage induction motors and is the biggest cause % LOAD
of power factor problems. In fact, as the load of
the motor decreases (Figure 96), its power
factor decreases tremendously, so sizing the Figure 97. POWER TERMINALS
L1
In this chapter, we have covered some impor-
tant introductory topics on motor controls and L2
M
the precautions you must take in following the L3
proper National Electrical Code rules. In chap-
ters 8 and 9, we’ll cover in detail more on DC
and AC motor control circuits.
REVIEW QUESTIONS
c– The nameplate
d– The rating and code
a– Overcurrent capacity
b– Slip
c– Service factor
d– Service power
a– Magnetic
b– Centrifugal
c– Manual
d– Isolated
a– Magnetic
b– Centrifugal
c– Manual
d– Isolated
a– 100%
b– 150%
c– 125%
d– 115%
a– Ladder
b– Wiring
c– Power
d– Plant
Figure 2
16.- In Figure 2 , the normally closed contacts
L1 L2 L3
are ______.
a– Control contacts
b– Overload contacts 3
c– Interlocking contacts
2
d– Power contacts
T1 T2 T3
a – Between 1-20 HP
b – Less than 3 HP
c – Up to 50 HP
d – Up to 10 HP
a– Stator
b– Cage
c– Rotor
d– End plates
21.- Identify each of the two diagrams in Figure Figure 3 WYE CONNECTION
T1
3 as a high voltage or low voltage connec-
tion a– T4
T7
a – Start winding T4
b – Run winding b– T7
T9 T8
T6 T5
T3 T2
LOW VOLTAGE
a – 50%
b – 35%
c – 75%
d – 90%
a– Shunt
b– Compound
c– Series
ANSWERS
1.- True
6.- True
9.- True
10.- a– Magnetic
c– Manual
11.- a– Magnetic
12.- c– 125%
13.- True
14.- True
15.- b– Wiring
17.- True
20.- a– Stator
c– Rotor
d– End plates
a– T4 b– T4
T7 T7
23.- c– 75%
24.- c– Series
25.- True
OVERVIEW
In this seventh chapter, you are presented with
the important topic of preventive maintenance
and electrical troubleshooting.
OBJECTIVES
INTRODUCTION
PREVENTIVE MAINTENANCE
...Preventing Something
Preventive maintenance consists of inspecting, From Happening
cleaning, replacing and in some cases moni- MAINTENANCE:
toring components before they fail or break ...Maintaining in
down. The successful operation of a plant re- Working Order
quires minimizing the time a machine is down
and avoiding something we can really measure,
dollars lost to the company.
• Inspection of components
• Cleaning
• Lubrication
• Adjusting and tightening
Inspection
NOTES
ning with power applied, where you can, for
example, hear noise or feel overheating from
motors. Under the static mode, the machinery
does not have power applied and is the perfect
time to look for loose parts, location of dirt ac-
cumulation and any other signs of abnormali-
ties. Inspection should be the first thing to do in
a preventive maintenance program and its im-
portance cannot be overemphasized.
Cleaning
Lubricating Equipment
NOTES
Adjusting and Tightening
Figure 4.
This means that we can prevent or minimize
potential problems in electrical control systems WORD
before they occur and get the useful life of
equipment to be maximized. You don’t want ei-
ther to overdo it because this will keep the STICK TO YOUR P.M.
PREVENTATIVE
Figure 5.
Engineering Preventive Maintenance
Into Control Systems
• Phase imbalances
• Phase loss
• Phase reversals
Phase Imbalance
L3
This phase imbalance could easily happen
when we are going through an expansion and N
L3
Phase Loss N
Phase Reversal
Figure 17.
There are two ways to try to find a problem
(see Figure 17); one is by a “shotgun” method
in which we hope to hit it by luck or by guess-
SELECTIVE
ing or we can go through a selective and ratio- SHOT-GUN APPROACH
nal process following an approach program. To MAYBE IT'S... LET'S START
??? AT THE MAIN
speed up the finding of the problem we can I GUESS IT'S... POWER INPUT
?? FIRST...
define three major areas for focusing our
troubleshooting attack:
The next step to check is the status of the fuse Figure 20.
L2 F2
sure that it is being passed to the system. Break- FUSE
VOLTS AC
present, F2 will be good. To test for F1 (Figure
22), we would place one side of the voltmeter
PANEL
on L2 or L3, and the other one on the load side
of F1. Again, if a reading is present, then the
fuse is OK. If no voltage is present, then the
fuse is blown or bad. Don’t forget to check all of Figure 22.
POWER CHECK
them because there could be more than one
L1 F1
FUSE
fuse blown.
L2 FUSE
F2
L3 F3
You can also check fuses in a static mode with- FUSE
cuit and not have power for example in Line 3 Figure 24.
of Figure 24. If a motor were being driven, a L1
single-phasing problem could be occurring; L2
we’ll see this later.
M
L3
NOTES
Another way of engineering an indication of
fuse status is by using a overcurrent protection
chapter (such as the Bussman Optima). If a
line fuse is blown, its indicating light will be on.
If a fuse needs replacing, you can simply re-
move it by pulling the front case and replacing
the fuse.
Figure 37. L1 L2 L3
set it for an ohms resistance or continuity read- PB4
OL
Our problem lies around the shaded area of
Figure 38; any of these wires or connections Motor
PB4
points right after PB4, the screw connection
3
from PB3 of the auxilary contacts and right af- 2
the system.
Motor
• Loose connections
• Faulty contacts
• Mechanical problems
Figure 45.
instance, overloads. The best solution to this
ACTUATOR
potential problem is to make sure that all com-
ponents are tightly connected when the pre-
ventive maintenance is scheduled.
FUSE
Jumper Method
3 3
2 2
Similarly, we also check the other stop push STOP STOP
2 2
button (stop 2) for power continuity as shown
T1 T2 T3 T1 T2 T3
in Figure 54. If there is no power and the coil is START 1 START 1
Motor Motor
not on, then there could be a problem with this STOP 1 STOP 1
3 3
2 2
L1 L2 L3
L1 L2
If there is power from the jumper at the second START 1
START 2
STOP 1 STOP 2 OL 3
START 2
STOP
the start push buttons (Figure 59). If we place 2
M
the jumper at the highlighted points in Figure 2 3 START 1
T1 T2 T3
Motor
Figure 61.
the problem lies between the terminal point at
the start PB and the coil. L1 L2 L3
START 2
3
If the jumper turns the coil on, then we place it
2
at the other end of the start 1 PB and press the
STOP
push button to see if the start push button is 2
to check the other side of the start push button Figure 69.
by pressing the start and reading voltage in our
voltmeter (Figure 69).
L1 L2
START 1
If there is no voltage, there is a problem with STOP 1 STOP 2 OL
the start1 PB. The same test is performed with M
START 2
the other start 2 push button. No need to check
the auxiliary contacts because the problem is
not with sealing, rather, it’s with getting the 2
M
3
method.
NOTES
In this next section of the program, we’re going
to look at the causes that make a motor fail so
that we are constantly aware of them, espe-
cially when troubleshooting the motors and
their power circuits, as explained in Chapters 8
and 9.
Symptoms
NOTES
Why Motors Fail
• Excessive loads
• Excessive duty cycle
• High or low line voltages
• Imbalanced voltages Figure 72.
EXCESSIVE LOAD
• Single phasing
• High ambient temperature
• Lack of proper motor ventilation
M
Excessive Load
M
M
Excessive Duty Cycle
NOTES
High or Low Line Voltage
Imbalanced Voltage
Single Phasing
Figure2
REVIEW QUESTIONS
a– Calendar schedule
b– Equipment running hours
c– Specific details
d– Equipment breakdown
a– Single phasing L2
b– Phase imbalance
L3
c– Phase reversal
d– Phase monitoring N
a– 10%
b– 15%
c– 20%
d– 15%-20%
L2 F2
side of the fuse, we would know that the FUSE
fuse is OK if ______. L3 F3
FUSE
VOLTS AC
a– Shotgun
b– Contact pressure
c– Silver plate
d– Cross firing
a– 15%
b– 12% to 15%
Ω
c– 10% READ
OHMS
d– 20%
a– An increase
b– A decrease
a– The coil.
b– The wiring between the coil and the
start push button.
c– The overloads.
d– The wiring between the coil and over-
loads.
STOP
2
25.- In Figure 8, if the auxiliary contacts are sus-
pected to be bad (not sealing), where would T1 T2 T3
START 1
you put the jumper to check if the auxiliary
Motor
contacts are indeed bad once a start push STOP 1
button is pressed?
ANSWERS
1.- True
4.- True
5.- False
6.- a– 10%
9.- True
12.- b– Start
13.- True
18.- c– 10%
19.- a– An increase
b– A decrease
22.- True
SHUNT
F F
+ -
Chapter 8—Understanding & Troubleshooting DC Motor Controls
OVERVIEW
In this eighth chapter, you are presented with
the necessary information to understand and
apply DC motors and their control circuits.
OBJECTIVES
INTRODUCTION
In this eighth chapter of the program we’re
going to go over DC motors, how they operate, Figure 1.
and the methods used to start them. We’ll also
SERIES
look at the different circuits used to accelerate
and decelerate the speed of the motor. At the S S
end of the chapter, we’ll conclude with the A
troubleshooting of the different kinds of DC
motors. So let’s start by looking at the basic
operation of a DC motor.
+ -
DC MOTOR COMPONENTS AND
SHUNT
OPERATION
F F
In chapter 6 we introduced DC motors and said A
that they are composed of three basic sections
which are the frame, the armature, and the end
plates or brackets. Now we are going to see
them in just a little more detail. + -
COMPOUND
We know that the main stationary electrical
component of a DC motor is the frame to which
the main field assembly is attached. This field F S S F
A
assembly is composed of the so-called poles
which are formed of stamped laminations se-
curely bolted to the frame.
+ -
These field poles are wound with wire to form
the field coils. These coils are the ones that form
the fields represented in the series DC motor, Figure 2.
the shunt DC motor and in the compound DC
STATIONARY
motor (see Figure 1). Note that in the diagram
of Figure 2, the field windings are shown sta-
tionary. A
+
The field poles, attached to the frame, are -
accompanied by interpoles which are posi-
tioned between the field poles and are made up SERIES
• Full-voltage starting
• Reduced-voltage starting
Full-Voltage Starts
Figure 14.
Reduced-Voltage Starts
Figure 15.
ARM
Reversing With A Drum Switch
motor.
SERIES
During the forward cycle of the motor, the
current through the armature as indicated by
Reverse + –
the bold lines in Figure 22, and during the
reverse cycle, it goes the opposite way (Figure
Figure 24. DC SHUNT MOTOR
23). The drum switch connections for the rever- REVERSAL
sal of the shunt DC motor and compound DC
motor are shown in (Figure 24).
SHUNT ARM
Reversing with Manual/Magnetic Starters
+ –
tional normally closed contacts from the for- Figure 30. FWD
STOP R OL
SPEED
rated torque for a short period of time, whereas VDC A F
+
the full voltage across the armature (Figure 44), Figure 44.
VFIELD VARM A
you could increase the speed of the motor
above the base speed. BASE –
SPEED +
VFIELD F
VARM
In smaller motors, the acceleration can be ac-
–
complished in two steps (Figure 45) by having VOLTAGE
one set of contacts removed after the start,
F
while larger motors will have a smoother start Figure 45.
SCR Operation M1
R R R
APPLIED VOLTAGE
+ –
An SCR, also referred to as thyristor, is repre-
sented by the symbol shown in Figure 47. It is Figure 47. Figure 48.
formed by three elements which are the anode, SCR SCR DIODE
CATHODE CATHODE
the cathode and the gate. As you can see in
GATE
GATE
Figure 48, it is very similar to the diode we
discussed in Chapter 1, which is used to rectify
AC voltage into DC voltage. ANODE ANODE
THROUGH GATE
the gates. The gate essentially works as a • GATE ACTS AS A
SWITCH
switch which allows current passing from the
Cathode to the Anode to turn on and off (Figure
50). This control allows the SCR to turn on at
Figure 50.
any point in the half cycle rectification from full
to partial conduction of voltage. The firing circuit
controls the amount of voltage conduction of L
GATE O
the SCR by controlling the gate. V FIRING A
CONTROL D
SCOPE
vided by an electronic control board which Figure 55 TO
FIRING
controls the firing of the SCRs. CONTROL DC
MOTOR
L1
A1
If a problem is suspected with the drive, in this L2
L3 A
case one which uses a so-called 6 pulse bridge
A2
(Figure 55), the first thing to do is to check for
proper operation of the SCRs, making sure they
are firing and providing power to the motor. To
do this, you can place an oscilloscope across Figure 56. OSCILLOSCOPE
the A1 and A2 terminals of the motor or from the
terminal coming from the power bridge. You
should observe the type of curve shown in
VDC
Figure 56, where all six SCR curves should be
present within a 16.66 millisecond range which
equates to one pulse for each SCR on each half
cycle of the three phases (Figure 57). Make
TIME BASE 16.66 msec
sure the scope is set for at least a 16.66 millisec-
ond scale.
Figure 57.PHASE
• Plugging circuits
• Regenerative braking
• Electromechanical brakes.
Figure 62
START
When start is pushed (reference Figure 64), the STOP R
F
motor will start in the forward direction and the F
plugging switch’s forward contacts will close FWD
CLOSE DC MOTOR
and set up the reverse motor to wait for the SPEED
R O F
normally closed forward interlock to be back to
its normal state. This will occur as soon as we Figure 64.
press the stop pushbutton which will reset the + R –
forward starter coil. At this time, the reverse F
OL
R
starter will be energized because there is con- F
tinuity from L1. This continuity is provided by the START
STOP R
plugging switch forward contact which is still
F
closed by the centrifugal force due to the rota- F
F
stop is pressed, the reverse will not be allowed
until the forward rotation slows enough to close R
Regenerative Braking
TROUBLESHOOTING DC MOTORS
If there is no voltage at the terminals and there Figure 74A Figure 74B
+ –
is power to the starter coil (Figure 74) points 1 A A + –
A A
and 2), then check the voltage with a voltmeter B B
+ 1 2 B B
set to a DC reading at a terminal point before the POWER
–
C C + 1 2
POWER C C
power contacts (Point A). If there is no power, –
+ –
you need to reset them and make note that
something in the system has caused them to
trip and you need to investigate it.
Figure 75
OPEN
If there is voltage at the motor terminals (Figure
75), but the motor is not operating, we can
+
assume that the motor has an open in its S
winding or between the brushes and the com- VDC
mutator in the armature. To proceed, you should A
–
disconnect the power to the motor and discon-
Figure 76 DISCONNECT
nect the series field and armature to test for an S A
open condition (Figure 76). S2 S1 A2 A1
ROTATE
By placing the meter (Figure 77), with the selec-
ARMATURE
tion for ohms to read resistance, across the S1
+ –
and S2 terminals of the field, we could test to
see if an open is present. If the ohmmeter Ω
+ –
To test the armature, we place the ohmmeter
between terminals A1 and A2. If the reading
Figure 78.
shows a resistance in ohms, there is continuity.
You should now start rotating the armature
shaft slightly so you can detect possible bad
spots where the commutator may have an open
or the brushes may not be properly seated
(Figures 78 and 79).
S A
You can also inspect to see if the field and
S2 S1 A2 A1
armature windings are loose or damaged. And
check the shaft bearings to make sure they are
lubricated and not damaged. If not properly
lubricated, the bearing could be seizing on the
shaft and create friction which develops heat + –
and reduces its capability to pull the load.
Figure 81.
Once you’ve had the motor replaced or re- F
paired, it is important that you monitor again the
current and heat once the motor is reinstalled A
again.
• MOTOR NOT RUNNING
Troubleshooting a Shunt Motor PROBLEMS WITH
–SUPPLY VOLTAGE
–POWER CIRCUIT
The shunt motor also exhibits similar problems • MOTOR RUNS
as the series DC motor (Figure 81). The two –BUT OVERHEATS
main problems occur when the motor is not
running in which case it could be the supply Figure 82.
voltage or its power circuit. If the motor is + –
running, overheating can be exhibited by the MOTOR
motor, thus indicating a potential problem. DOES NOT
START
NO SOUND
If the motor does not start and does not make
any sound (Figure 82), it is most likely due to a
problem with the voltage being supplied to its
DCV
terminals. Check for a voltage and troubleshoot
the power circuit in the same fashion used for SHUNT
MOTOR
+ –
the series DC motor power circuit.
SHUNT
To test the field winding (Figure 84), you must MOTOR
+ –
remove the shunt connection from the arma-
ture. Otherwise, you won’t be able to detect an
open in the field winding because the armature Figure 84.
is connected in parallel and you could read
continuity in the armature. Make sure that you F2 F1
REVIEW QUESTIONS
a– Starter
b– Armature
c– End plates or brackets
d– Frame
Figure 1
2.- Match the appropriate motor shown in Fig-
ure 1 with their appropiate representation.
S S
a– Series
A
b– Shunt
c– Compound
a– End plates
F F
b– Stator
A
c– Armature
d– Frame
a– Armature F S S F
b– Commutator A
c– End plates
d– Interpoles
+ -
5.- True/False. The brushes are small blocks
of special carbon that function as the inter-
face between the external power source
and the commutator.
a– Full-voltage
b– Rapid
c– Reduced-voltage
d– Slow
a– Compound
b– Shunt
c– Series
a– Rheostat
b– Open voltage
c– Closed voltage
d– Solid state speed control.
a– Cathode GATE
b– Anode
c– Gate
ANODE
13.- In Figure 3, when troubleshooting the
SCR’s circuit, if you see all six pulses will
mean that ______. Figure 3
SCOPE
TO
FIRING
a– One SCR is not working CONTROL DC
MOTOR
b– All SCRs are working L1
A1
c– The motor is OK L2
A
d– Frequency is OK L3
A2
a– Rheostat
b– Full bridge
c– Tachogenerator
d– Stepper
a– Plugging circuit
b– Electromechanical brakes
c– Contact pressure
d– Regenerative braking
a– Braking switch
b– Plugging switch
c– Forward/reverse open switch FWD
R
a– Plugging circuit
b– Regenerative braking
c– Forward/reverse open loop
d– Forward/reverse safety switch Figure 6
+ –
Figure 7
20.- Which one of the following equations de- + –
scribes the estimated braking torque?
______.
START
HP x 5252 STOP M OL SOL
a– Torque= BRAKE
RPM
RPM x 5252 M
b– Torque=
Break Factor
DC
c– Torque=HP x 5252 x RPM MOTOR
ANSWERS
1.- b– Armature
c– End plates or brackets
d– Frame
2. Series
S S
A
+ -
Shunt
F F
A
+ -
Compound
F S S F
A
+ -
3.- c– Armature
4.- b– Commutator
5.- True
6.- a– Full-voltage
c– Reduced-voltage
8.- True
9.- c– Series
10.- a– Rheostat
d– Solid state speed control
11.- True
12.- SCR
CATHODE
GATE
ANODE
14.- c– Tachogenerator
16.- Figure
17.- True
19.- True
HP x 5252
20.- a– Torque=
RPM
21.- True
22.- True
24.- True
25.- True
M2
T7
T4, T5, T6
M1 T2 T3
L2
M2 INTERNAL
T8 T9
M1
L3
M2
Chapter 9—Understanding & Troubleshooting AC Motor Controls
OVERVIEW
OBJECTIVES
INTRODUCTION NOTES
the number of poles that form the stator and 60Hz x 120
=
2
the frequency of the AC voltage coming into
the motor (see Figure 1). The operating speed, = 3600 RPMs
Figure 2.
POLES SPEED
called synchronous speed, is equal to the fre-
2 3600
quency of the voltage times a constant of 120
4 1800
divided by the number of poles of the motor. 6 1200
The result of this synchronous speed is given 8 900
in RPMs. So, for a 60 HZ frequency, a two-pole 10 720
motor will operate at 3600 RPMs, a four-pole 12 600
at 1800 RPMs, and so on (see Figure 2). 14 514
16 450
This formula indicates that the only parameters
Figure 3.
that can be changed in order to vary the syn-
FREQ x 120
SPEED =
chronous speed of the motor are the frequency # OF POLES
of the voltage or the number of poles in the
stator field (see Figure 3). Figure 4.
Figure 7.
The initial current pulled by a motor when it is LOCKED-ROTOR AMPERAGE
(LRA)
first started is called the locked-motor amper-
age or LRA. It is so-called because this is the
CURRENT
required current that moves through the stator
FULL LOAD AMPERAGE
to start to move the rotor when it is at rest or (FLA)
TORQUE
is about 6 to 10 times that of the full load cur-
rent. The rotor of an induction motor will de-
velop full or maximum torque when the speed
has reached between 70 to 80% of synchro-
nous speed (see Figure 8). SPEED 80% 100%
RUN START
Single-phase motors, as mentioned before,
come in different types, such as the split-phase
• Capacitor-Start
• Permanent Split Capacitor
• Capacitor-Start Capacitor-Run
• Across-the-line or full-voltage
• Reduced-voltage
Figure 11.
Across-The-Line Start
Reduced–Voltage Starts
CURRENT
•Primary Resistor CLOSED
•Auto transformer
•Wye-Delta 100%
CURRENT
OPEN
tages and disadvantages. All of these methods,
except the wye-delta, provide closed transition,
100%
which means that power to the motor is not in-
terrupted (see Figure 14). The wye-delta start SPEED
M
Primary Resistor R
M
S1
500
motor circuit. The resistors are removed by the
CURRENT %
% 400
65% 65%
bypass start contacts S1 after a time delay. 300
200
42%
100
0 20 40 60 80 100
The primary resistor provides at start about 65% VOLTAGE TORQUE INRUSH
CURRENT SYNCHRONOUS SPEED %
M
18), full voltage is applied from the power con- TR
TR S1
tacts at the starter and voltage is created at the
Figure 19.
resistors, thus reducing the amount of voltage S1 S2 S3
transformer can be tapped at 80, 65 or 50% of Figure 23. TAPPED TAPPED TAPPED
% AT 80% AT 65% AT 50%
the line voltage. This reduced voltage is the one 64% 64%
passed on to the motor terminals. The au- 42% 42%
65%
50%
At 80% voltage (see Figure 23), this method
gives 64% of inrush current and 64% of normal
torque. At 65% voltage, the current and torque
are both at 42% while, if tapped at 50% volt- Figure 25. L1
age, the current and torque will be lowered to
T1
25%.
When start is pushed, the timer TR1 starts tim- Figure 28.
ing and its instantaneous contacts seal the cir- L1 START L2
STOP TR1 OL
cuit; the starting contactor S1 is energized be-
cause there is continuity and all the three power TR1
contacts associated with S1, which are con- TR1 S1 M1
TR1
nected to the autotransformer, close (see Fig-
ure 28 and 29). M1 TR1 S1
WYE DELTA
These windings are internally connected and MOTOR MOTOR
the T1, T2 and T3 terminal wires are brought
Figure 33. T6
out of the motor for connection to the motor T1
WYE-DELTA MOTOR
cian to wire the motor in a wye configuration or
a delta configuration. Figure 34. Figure 35.
T6 T6
T1 T1
L1 L1
TORQUE INRUSH
CURRENT
Figure 38.
We can recall these wye and delta voltages WYE DELTA
and current relationship from Chapter 1 when VL=VP x 1.73 VL=VP
we discussed the wye and delta power distri- IL=IP IL=Ip x 1.73
bution (see Figure 38).
Figure 39. Figure 40.
T2 T2
L2 L2
the inrush current (see Figures 39 and 40). This T5
T3
T5
T3
L3 L3
is simply done by interlocking the power circuit WYE CONNECTION DELTA CONNECTION
L2 and L3.
Figure 43. L1 L2 L3
Part Winding
Figure 46. TRANSITION
600%
T4, T5, T6
The circuit used to control these starts is rather
M1 T2 T3
L2
simple (see Figure 48). Once the start is M2 INTERNAL
T8 T9
pushed, the M1 contactor closes and places L3 M1
M2
the line voltage across one of the two identical
coils. Once the time delay occurs, the other coil
Figure 48. L1 L2
is brought on line by the turning on of contactor
START
OL
M2. M1 acts as the starting contactor while M2 STOP M1
Figure 49.
As you can see in Figure 49, the voltage is not M1
L1 T1
reduced in this starting method. However, the M2
inrush current is reduced to about 65% and the T7
CT
Figure 53.
RECTIFIED
drive, where SCRs are also utilized (see Fig- VOLTAGE
START
The solid state reduced-voltage starter (Figure STOP CR
Figure 58.
Reversing 1Ø Motors
L1
Reversing With A Drum Switch
Figure 60. L2
In Chapter 2, we covered the operation of drum
switches which have six standard terminal con-
nections (see Figure 58) and, as we know, the REV R S
Figure 63. L1 L2
REV
As seen in the wiring diagram shown in Figure R
L1 1 2 T1
Reversing With A Drum Switch
L2 3 4 T2
M
L3 5 6 T3
As we have stated several times, the reversal
of a 3-phase motor can be accomplished by DRUM SWITCH
switching any two of the three phases (see Fig-
Figure 68.
ure 65 and 66). In Chapter 2 we explained how
a drum switch was used to reverse the direc- L1 1 2 T1
Figure 69.
reverse, L1 goes to T3 and L3 goes to T1; L2
still goes to T2 (see Figure69).
L1 1 2 T1
DECELERATION OF AC MOTORS
Figure 73.
Electric Braking
Figure 75.
Electric braking provides an excellent way to L1
ON
the off-delay elapses (Figure 79), the normally- TIMER
OFF
opened timed open contacts of the timer will ON
TIMER OFF
reset back to their original open state, thus re- CONTACTS OFF
DELAY
Figure 80).
T1
T3
Multispeed Motors
T3 T7 T2 T13 T17 T12
SPEED L1 L2 L3 OPEN
We know that, by removing poles from the mo- LOW T1 T2 T3, T7 ALL OTHERS
tor, we would increase the speed of the motor; HIGH T11 T12 T13, T17 ALL OTHERS
Figure 85.
T2 T2
T5 T6 T5 T6 T5 T6
T2
T2
T4 T4 T2 T14 T12
T6
Figure 85 cont...
T5 T7 T2 T6 T15 T17 T12 T16 T5 T7 T2 T6 T15 T17 T12 T16 T5 T2 T6 T15 T12 T16
SPEED L1 L2 L3 OPEN TOGETHER SPEED L1 L2 L3 OPEN TOGETHER SPEED L1 L2 L3 OPEN TOGETHER
LOW T1 T2 T3 ALL OTHERS T4,T5,T6,T7 LOW T1 T2 T3 ALL OTHERS T4,T5,T6,T7 LOW T1 T2 T3 ALL OTHERS –––––
2ND T6 T4 T5,T7 ALL OTHERS ––––– 2ND T11 T12 T13 ALL OTHERS T14,T15,T16,T17 2ND T6 T4 T5 ALL OTHERS T1,T2,T3,T7
3RD T11 T12 T13 ALL OTHERS T14,T15,T16,T17 3RD T6 T4 T5,T7 ALL OTHERS ––––– 3RD T11 T12 T13,T17 ALL OTHERS –––––
HIGH T16 T14 T15,T17 ALL OTHERS ––––– HIGH T16 T14 T15,T17 ALL OTHERS ––––– HIGH T16 T14 T15 ALL OTHERS T11,T12,T13,T17
and the variable torque also has the horse- Figure 86. T4
L1 L2 L3
Multispeed motors provide the necessary wir- Figure 87.
ing to allow for proper connection of the poles LO LO LO HI HI HI
T4
in the control circuit and in the power circuit T1 T2 T3 T6 T4 T5
T3 T1
(see Figure 87). So that the motor is not run at
T5 T2 T6
low and high speed at the same time. These
circuits may look similar to the forward/reverse Figure 88. L1 L2
LOW
controls we’ve talked about earlier (see Figure STOP H LOW OL
88). L
HIGH
L HIGH
For example, the circuit shown in Figure 88 al-
H
lows the operator to start the motor at either of
the two speeds, but he must stop the motor
Figure 89. L1 L2
before changing speed. We can easily modify LOW
STOP HIGH H LOW OL
this circuit so that the operator could change
L
the speed from low to high without stopping
(see Figure 89). L HIGH
LOW
STOP LOW OL
at a low speed and then be allowed to acceler- HIGH H
ate to the high speed when required (see Fig- CR1-1 L HIGH
L
TR1 TR1
in Figure 91, utilize a timer on-delay to bring
HIGH
CR1
the motor to high speed once the low speed
L HIGH
pushbutton has been pressed. This circuit gives CR1-3 TR1
H
Bear in mind that the speed of these motors
could have been controlled automatically by
LOW HIGH
pilot devices. For example (see Figure 92), if SPEED SPEED
PILOT PILOT
the selector switch is in AUTO, the pilot devices DEVICE DEVICE
TROUBLESHOOTING AC MOTORS
Figure 104.
NOTES
age, then the overloads are OK. If any of these
voltage readings that were used to check the
overloads is not correct, you need to remove
power and check the overload heaters for an
open condition which can prevent it from con-
ducing current to the motor.
T2
an infinity resistance measurement, the coil is
open and needs to be removed and repaired
(see Figure 114). For a dual voltage delta mo- Figure 114. Figure 115.
tor (Figure 115), you have to test the three cir- T1 COIL T1
CIRCUIT
1
cuits that form the delta voltage. For instance, INFINITY
RESISTANCE
T9 T4
MEANS OPEN
you would put the meter leads between T4 and COIL
COIL T6 T7
CIRCUIT
T1 and see if there is continuity, and between 2
T8 T5
T3
T2
T1 and T9 to check also for continuity (see Fig- T2 T3 COIL
CIRCUIT
3
ure 116). The same applies to other circuits. If
it is a single-voltage delta motor, you will sim-
ply measure from T1 to T2 and T1 to T3 and T2 Figure 117.
Figure 116.
to T3 for continuity (see Figure 117).
T1 T1
T9 T8
T6 T5 T9 T8
T6 T5
If the motor is a single-voltage wye, then the COIL
CIRCUIT
3
COIL
CIRCUIT
T3 T2 4 T3 T2
measurement of continuity will be done be-
tween T1 and T2, T2 and T3 and T1 and T3
(see Figure 120). This method can also be used Figure120. Figure 121.
Ω
the delta or wye motor to a ground; for example, Ω
M
When testing the start winding for continuity, if
the motor is a single-phase capacitor motor,
you will need to use a jumper and jump or by-
pass the capacitor so that a continuity test can
be made (Figure 124). If there is an open, you
should first check the centrifugal switch for an
Figure 124.
open or malfunction. You need to measure with JUMPER
a meter across the switch for continuity. If the M T5
L1
switch is good, then the open would be in the
winding; if the switch is not good, you need to T1
replace it and test the winding again to ensure R S
proper rewiring and that the winding itself does T4
M
not also have an open. L2
T8
Remove the load from the shaft and start the Figure 125.
motor. If the shaft does not rotate, then you
need to check the bearings. If the shaft rotates
T1
when started, you need to check the load’s
bearings and make sure that the load capacity
is not being exceed for the motor. T2
loose coil in the motor, or if the load is too large Figure 128.
L1
for the motor application. If the field wiring for T1
together.
Figure 129.
If a single-phase motor develops a heat prob-
lem after a start, you should check to see that
the centrifugal switch is disengaging the start
winding once the motor speed has reached VOLTAGE R S
75% of full speed. If the start winding is not
taken out , it will create heat (see Figure 129).
REVIEW QUESTIONS
a– Value
b– Frequency
c– Poles
d– Brushes
a– Locked-motor amperage
b– Full load amperage
a– Start
b– Centrifugal
c– Stationary
d– Run
synchronous speed.
a– Auto transformer
b– Part winding
c– Wye-delta
d– Power start
e– Primary resistor
f– Solid state
a– Parallel
b– Series
c– Primary resistor
d– Auto transformer
b– Part winding
c– Primary resistor
REV
16.- True/False. In Figure 3, if the motor is run- R
a– Increase
b– Decrease
c– Less
d– More
LOW
STOP HIGH H LOW OL
20.- The so-called ______ is just the right L
amount of torque to cause movement of a
CR1-1 L HIGH
load.
H
L CR1
a– Main disconnect
b– Starter
c– Main branch circuit
d– Motor
a– Run winding
b– Start winding
c– Overload winding
d– Centrifugal winding
ANSWERS
1.- True
2.- c– Poles
b– Frequency
Frequency x 120
3.- c– Operating Speed=
Number of Poles
4.- True
6.- a– Start
d– Run
7.-
SPEED
8.- False
9.- True
14.- True
15.- True
17.- a– Increase
c– Less
18.- True
19.- True
21.- b– Starter
d– Motor
23.- True
25.- True
L1 L2 L1 L2
PB1 PL1
10 11 20
10 20
20 100
LS1
11
20 101
Chapter 10—Use, Application & Troubleshooting of Programmable Logic Controllers
OVERVIEW
In this tenth chapter of the program, you will be
presented with an introduction to programmable
controllers, or PLCs, and how this control equip-
ment is used in industry to implement electri-
cal and motor control circuits.
OBJECTIVES
• Define scan.
INTRODUCTION NOTES
Figure 4.
The operation of a PLC is rather simple. It first
reads the input status of the control devices con- LS
CPU M
nected to its input interfaces; then provides the
input status information to the CPU, which ex- PB
SOL
ecutes the control instructions similar to an elec-
trical ladder diagram and then outputs the re-
sult status to the output interfaces (see Figure LS PL1
4). The process of reading the inputs, execut-
ing the control program and updating or writing
the information to the outputs is called scan-
ning or simply the scan (see Figure 5). A PLC
Figure 5.
can perform a scan in a matter of milliseconds
or one thousandths of a second. This scan is READING INPUTS
composed of two actual scans which are the I/
O scan and the program scan (see Figure 6),
EXECUTING THE
and can be graphically represented as illus-
CONTROL PROGRAM
trated in Figure 7, where the inputs are read,
the program is executed, and the outputs are
updated according to the control program. UPDATING OUTPUTS
PLC Classification
SCAN
PLCs are available in many sizes to accommo-
Figure 6.
date different applications. The sizes of PLCs
are generally dictated by the number of field TOTAL = I/O + PROGRAM
devices that can be connected to its input and SCAN SCAN SCAN
output system in a particular application.
Figure 14.
Binary Concepts
BINARY CONCEPT
Programmable controllers, just like any com-
puter, can only understand ones and zeros,
• PLCs UNDERSTAND 1's AND 0's
therefore the mane binary for two numbers, one
and zero. One for a condition that shows it is • 1 = CONDITION IS PRESENT
present, such as a light on, and a zero for a • 0 = CONDITION NOT PRESENT
condition not present, like the light being off
(see Figure 14). In fact, when we look at per-
sonal computers or copiers, we generally see Figure 15.
a one or a zero to illustrate the on or off status TO A PLC:
in the switch. Without much thinking, we place
the switch to the one to turn it on and to the 1 = VOLTAGE
(ACTIVATED, HIGH, CLOSED)
zero to turn it off.
0 = NO VOLTAGE
To a PLC, a one represents a voltage and a (DEACTIVATED, LOW, OPEN)
LS2
I/O Addressing and Structure LS1 01 02
Figure 22.
that location for use by the control program. If I/O Image Table
16 TERMINALS
the switch is open, a zero is stored. It is useful
that you know how and where the devices are 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
or off.
02
32
OUTPUTS
The same applies for output devices(reference
03
Figure 21). Each location will represent the sta-
tus of a device after the control program is ex-
ecuted. If a location, let’s say 0506 has a one Figure 23.
Figure 29.
8 bit locations of the outputs. The input devices
0
connected to the input module will be known 1
by the addresses 00 through 07, while the out- 2
3 INPUT
puts will be known by addresses 10 octal to 17
octal (see Figure 29). You could mix and match
4 MODULE
5
the addresses as you wish when placing the I/ 6
7
O modules. It is, however, not only customary
0
but highly recommended that you group the
1
inputs and outputs together for installation and 2
troubleshooting purposes (see Figure 30). That OUTPUT 3
4
is why most of the time you would see all in- MODULE 5
puts and outputs close together in their enclo- 6
sures and, therefore, in their image tables. 7
I/O SYSTEM
In micro and most small PLCs, the input and Figure 30.
OUTPUT OUTPUT 3
Let’s now take a look at the input and output
modules available in PLCs. There are two pri-
mary classifications of the input and output
modules which are designed to interface with Figure 31.
SIGNAL
inputs and outputs and their programming.
necting the field wires to the input terminal. Most Figure 37.
Figure 40.
The output module will have LED status indi-
cators which will be on when the output mod- FILTER
ule is turned on. There may be a logic indicator FROM
LINE
to show that the information coming from the VOLTAGE
processor is available at the module (see Fig- RS
ure 39). Note that, if the module has its power MOV
LED on, it doesn’t necessarily mean that the CS
output is automatically on. It means that the
output is switching the power to the load but, if TO
there is a malfunction in the device or if there LOAD
is a wiring problem, the output device will obvi-
ously not be on.
NOTES
Installation of Output Modules
Figure 41. L1 L2
A 120 volts AC output module is connected to L1
+
The PLC itself is also easily installed. The power
is brought in to a control transformer to bring 0
PLC INSTRUCTIONS
Examine On
Figure 50.
L1 L2
The examine on (Figure 49) is used to exam-
PB1
ine the status of the reference address for an 10
10
on condition to provide continuity through the
contact. For example, if the push button is con-
nected to an input module and the address of
the connection is 10 and you program an ex- 10
amine on instruction to represent PB1, the pro- 1
Output Coil
mally closed and the output , in this case ad- PB1 PL1
10 11 20
dress 20, is connected to a pilot light, the out- 10 20
put coil instruction will turn on whenever PB1 LS1
is pushed. As soon as it turns on, the light will 11
be lit.
L1 L2 L1 L2
Output coils may also be internal to the PLC, in
PB1 PL1
which case they do not have a reference ad- 10 11 20
dress mapped to an output module and they 10 20
are said to be internal outputs. 20 100
LS1
11
If, to the circuit shown in Figure 58, we take a
20 101
normally open contact from output 20 and ref-
erence it with the same address and make it
drive an internal output, let’s say 100, the out-
put 100 will be on whenever output 20 is on.
We could also take a normally closed reference Figure 59.
from 20 and program it to drive another inter-
nal output like 101. This output will be on when- L1 L2 L1 L2
ever coil 20 is off. If PB1 is pushed, output 20 is PB1 PL1
10 20
on and internal output 100 is also on; internal 10 L 20
output 101 will be off.
LS1 11 20
11 U
A PLC manufacturer will specify the valid ad-
dresses for internal output coils. For instance,
it may say that addresses from 100 through 137
octal can be used as internal outputs. Internals
are useful whenever interlocking is required. NOTES
Figure 65.
has not been pushed. Therefore, the proces-
sor will not provide power continuity to the nor-
L1 L2 L1 L2
mally closed instruction because this instruc-
PL1
tion examines for an off condition to provide con- PB1 10 20
tinuity and the condition is on. If PB1 is pressed, 10 20
then the status of input 10 will be off and the
normally closed referenced instruction will pro-
vide power and the light will be lit. However,
according to the hardwired control circuit, we
NOTES
don’t want this. We want the light on when PB1
is not pushed and off when pushed.
the light is off; when pushed, the light is on. Figure 66.
L1 L2
The equivalent hardwired circuit is shown in
Figure 66, where an additional control relay PB1 CR1
would be needed to implement the circuit logic.
CR1-1 PL
The same applies for a normally open device;
we can make it act in a circuit as a normally
closed (see Figure 67). Let’s take the same
case of a normally open push button in which
Figure 67.
we wanted it to act as a normally closed. The
way we would program it is by saying that we L1 L2 L1 L2
PB1 PL1
want the light on whenever PB1 is not pushed, 10 20
when this normally open device is not provid- 10 20
ing power or is off. So we program its refer-
ence address with an examine off instruction.
If PB1 is not pushed in Figure 67, the output is
on. If PB1 is pushed, the output will be off. To Figure 68.
PLC Timers
Timer Basics
dresses you can use with timers; for instance, Figure 74.
from register 1000 to 1777 octal.
TIMER ON DELAY
The preset register holds the number of ticks TON 100
A
you want the timer to time to, while the accu-
mulated register holds the timing ticks that are
PR: Reg 1000=50
elapsing while the timer is enabled. When the
AR: Reg 1001=xx
accumulated and preset are equal, the timer TB: 0.1 sec
will execute its output, depending on the type
of timer you select. 100 20
is shown in Figure 75. When the timer is en- TIMER OFF DELAY
abled or on, it starts timing and when the delay
is achieved, the output will turn on. If at any A TOF 100
time the input to the timer goes off, the timer
output will also turn off, thus resetting the timer. PR: Reg 1000=50
AR: Reg 1001=xx
The OFF-delay energized timer, shown in Fig- TB: 0.1 sec
ure 76, is a modification of the previous one. 20
100
This timer will start timing if its control input is
off and turn its output on after the delay. The
output will be off or reset when the timer’s in-
Figure 77.
1
put is back to on. For example, if A remains Timer's Control Input 0
closed, the timer’s input will be on and not tim-
ing. Once A opens, the input to the timer will be Timer's Output 1
OFF-Delay Energize 0
off and start timing. After a 5 seconds delay, its
output will turn on. The timing diagram of the
timer OFF-delay is as illustrated in Figure 77.
Delay
Special Timer Example Cases
Figure 78.
PLC timers do not have instantaneous contacts L1
TMR1
L2
FS1 PS1
which can be used for interlocking (see Figure
78). All the timer contacts available in a PLC 10 SEC
TMR1-1
are of time-delay action. If we want to imple-
ment the circuit shown in Figure 78 in a PLC, TMR1-2
SOL
Figure 81. L1 L2
TMR1
FS1 PS1
internal outputs from 100 to 177 and registers
10 SEC
are available from preset and accumulated val- TMR1-1
DSCHG
We know that there are not instantaneous con- PS1
21
01
tacts from timers so the original hardwired cir-
cuit shown in Figure 78 cannot be implemented
in a PLC directly. If we did, the float switch will
Figure 83.
never be sealed before the timer times out as L1 L2 L1 L2
we can see in the PLC program of Figure 83. If SOL
FS1 FS1 PS1 TON
FS1 is on and PS1 is on, the timer starts to 00 20
START
START
sealed with the contacts from output 20. If the 20
01
start push button is pressed, output 20 will turn
on, seal the stop push button and turn the mo-
tor on through the starter. If the stop push but- Figure 92.
L1
ton is pressed, the motor will be turned off.
L2
M
In a PLC wiring diagram, the PLC will be con-
L3
nected to power L1 and L2 (see Figure 92).
The field inputs will be connected to L1 on one
side and to the module on the other. The com-
mon or return connection from the input mod-
ule will go to L2. The outputs module will re- L1 PLC L2
Figure 96.
Reversing Motor Control (FWD/REV)
L1 L2
FWD
STOP R2 OL
to the forward coil and then to L2; while the Figure 99.
L1 L2 L3
STOP 00 01 22 20 OL
00
The first rung will have the wired normally 20 F
FWD 02
closed stop push button programmed as an ex- 20
21 FWD ON
01
amine on instruction in series with an examine 21
F1
on forward push button address 01 (see Fig- 02 00 03 20
22
22 R
ure 100). The forward push button will be sealed REV
04
with the forward auxiliary contacts address 02. 03 22
23 REV ON
23
Then we’ll program the interlock of the reverse R1
04
normally closed using the reverse coil address
22. We could also have used the address 04
since it, too, belongs to the reverse coils’ auxil- NOTES
iary contacts. This logic will be driving the for-
ward starter coil with address 20. To program
the forward light indicator, we don’t need to redo
all the logic. We know that, when output 20 is
on, the light should be on. Therefore, we sim-
ply program a normally open contact from out-
put 20 to drive the pilot light output 21.
NOTES
lock which prevents the reverse starter from
being on at the same time as the forward starter.
This contact address could be the address 02
of the forward auxiliary contacts or the address
of the forward coil which is 20. In this case, we’ll
use address 20. The reverse indication pilot light
circuit, similar to the one in the forward circuit,
will be driven by output 22, the reverse starter’s
coil. If the starter is on, the light will be on.
Figure 103.
output control. Then you can have the field de-
vice manually activated or closed; for instance,
L1
INPUT L2
PLC MONITOR
have the limit switch close (Figure 103). When
the switch is closed, you should see the power 10
LS1
status indicator in the module turn on. This pro-
vides continuity to the module and the proces-
sor should read its on status. If the indicator C
turns on, it means that wiring is not the cause LS1 STATUS = 1
of the problem.
PLCs, where the processor reads the inputs POWER ISOLATION LOGIC
and executes the program but does not acti-
vate the power switching the outputs. In this Input
Signal
mode, you could use the programming device
Noise Threshold
Bridge
and see the status of a 1 or a 0 of the image Rectifier
and
Debounce
Level ISOLATOR Logic
Detection
Filter
table or see the contact reference instruction
To
become highlighted when it is closed. If you see Processor
supplied to the field device and the module are Figure 105.
not at the right level.
L1 120 VAC L2
While closing the field device, measure the volt-
age to the input module (see Figure 105). If LS1
the signal is a 120 volts AC, the meter should
read that level. If the voltage is present, then
the input module is faulty because it is not rec-
ognizing the signal. If the voltage is below 10% C
to 15% of the voltage, there could be a prob-
lem in the source voltage to the limit switch be-
cause the module is not recognizing the signal
as a valid signal. If no voltage is present, then
there is a problem with the wiring or in the field
device. Make sure you check the wiring con- NOTES
nection to the module to ensure that the wire is
secured at the terminal or terminal blocks, if
used.
Figure 106.
At the output module, insure that the source
power for switching the output is at the correct L1 L2
OUTPUT
level (see Figure 107). In a 120 volts AC, this
SOL
value should be within 10% of the rated value.
Check for a blown fuse if incorporated in the
output module (see Figure 108). If a fuse keeps
blowing, check its rated value and the output
device to see if it is pulling too much current. C
REVIEW QUESTIONS
a– Availability
b– Convenience
c– One Figure 2
d– Two
TERMINAL
INPUT
e– Zero ADDRESS
WORD
ADDRESSES
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
a– BInary Term
b– BInary digiT
c– BIdirectional digiT
d– BInary TesT
a– Coil
b– Fuse
c– Resistor
d– LED indicator
a– CPU
b– Output memory
c– Output module itself
d– Supply Voltage
a– Contacts
b– Coils
c– Terminals
d– Contactors
ANSWERS
1.-
PROCESS
OR
MACHINE
MEASURE CONTROL
PROGRAMMABLE
PROGRAMMABLE
CONTROLLER
CONTROLLER
2.- True
3.- Figure
4.- b– Convenience
c– One
e– Zero
8.- True
9.- b– Fuse
10.- True
11.- ___
b Normally Closed a– Examine ON
a Normally Open
___ b– Examine OFF
12.- False. They come in both, normally closed
and normally open
14.- True
16.- True
PL1 is ON OFF