Professional Documents
Culture Documents
Manual de Usuario APC MGE Galaxy 5000 (36 Páginas)
Manual de Usuario APC MGE Galaxy 5000 (36 Páginas)
IsolateSingleUPS
ToisolatetheUPSfromtheelectricalpowersourceandsupplytheloaddirectlybythenormalorbypass
ACsource,followtheinstructionsbelow:
1.Pressabuttontoexitsleepmode.
2.ShutdowntheUPSbypressingtheOFFbutton
(A)for3seconds.
TheloadisnolongerprotectedbytheUPS.
3.SetbypassswitchQ3BP(D)toON.
4.SetoutputswitchQ5N(E)toOFF.
5.Setthebatterycircuitbreakeroftheauxiliary
cabinetstoOFF.
6.SettheinputswitchQ1(B)toOFF.
7.SettheswitchQ4S(C)toOFF.
8.WaituntilthedisplayandLEDsgooff.
TheloadisnolongerprotectedbytheUPS,but
continuestobesuppliedwithACpower.UPS
maintenanceorservicingcannowbecarried
out.
WARNING:Powerispresenton
thepowerconnectionterminals.
990-5219-001 MGEGalaxy500040-130kV A480V 15