NORTH ARROW KEY PLAN

B
A01 A02 A03 A04 A05 A06 A07 A08 A09 A10 A11 A12 A13 A14 A15 A16 A C
4750 8500 8500 8500 8500 8500 8500 8500 8500 6000 6000 6000 6000 8500 8500 3 1
ZONE-
3
1
1 ZONE- 3
3 4 2 7
4 ZONE
1 ZONE- 2 4 - 1
4 2 9 ZONE
3
2 1 3 1 4 -
3 2 12
1 ZONE- 1 4
3 ZONE-
28 3
FCU B1-NW-LL6 N 1
ZONE
- 2
5 4 4
2
ZONE
10
- 1
3
4 ZONE
4 -
BOU 3086 2
2
1
3 1 2 13
4
ZONE- 3
Air Flow 334 L\s w 3 ZONE-
4 1
1 ZONE- 4 2 6 2 11 4 ZON 3
QIBLA
BE
257.37° ARING
3
2 14 E-
2 4
B
E A C
C03
1500

FCU B1-NW-CPMF-04 2016 S

75
BOU 2875
C04 Air Flow 279 L\s
UP
NOTES:
FCU B1-NW-CPEF 9

1453

1471
350x300 SAD 300x300 SCD 3422 1. ALL DIMENSIONS ARE IN MILLI METER(mm) AND ALL INVERT LEVELS ARE IN MILLI
DN BOU 3035
334.0 L/sUP 2NOS. 167.0 L/s UP METER(mm) UNLESS NOTED OTHERWISE.

254
7000

B.O.D 3052 1543 EACH Air Flow 520 L\s


2. ALL LEVELS ARE INDICATED FROM FINISHED FLOOR LEVEL(FFL).
UP
1057 VCD

3600
250x200 SAD UP 3. ACOUSTIC LINEAR WILL BE INSTALLED UPTO 3M FROM FCU UNIT.
UP
UP
167.0 L/s

LED
2487

1355
320 250x200 SAD 1182 B.O.D 3102 UP
C05 167.0 L/s
B.O.D 3102

45
1680
FCU B1-NW-CPMF 3 LED
FCU BOU 2635
B1-SW-C1-1
3275 Air Flow 279 L\s
BOU 2954
8500

Air Flow 520 L\s

02 RM01-DWG-0260-AC-01-103-01 C04 BASEMENT 1 HVAC ZONE - 1


C07

MATCHLINE FOR CONTINUATION REFER TO RM01-DRG-3000-ME-ACD-B1-02-100


1500

01 RM01-DWG-0260-A-01-103-01 C04 GENERAL ARRANGEMENT BASEMENT 01 PARTIAL FLOOR PLAN 1/14

FCU B1-SW-C1-1 S.NO DRAWING NO. REV. DRAWING TITLE


C08 852 BOU 2954
FOR ENLARGED PLAN(SCALE - 1:100) REFERENCE CONTRACT DRAWINGS
Air Flow 520 L\s
FFL+6.600 WITH DIMENSIONS REFER DRAWING : FFL+6.600 FOR ENLARGED PLAN(SCALE - 1:100)
7000

RM01-DRG-3000-ME-ACD-B1-01-101 WITH DIMENSIONS REFER DRAWING :


4868

SSL+6.600 SSL+6.600
SHEET : 1 OF 4 RM01-DRG-3000-ME-ACD-B1-01-103
UP SHEET : 3 OF 4
DN
00 26-02-2019 ISSUED FOR APPROVAL SHYAM
C09
1500

REV. DATE DECEPTION DRAWN BY


DN
PROJECT NAME
C10
FCU B1-SW-C1-1
1690
BOU 2954
7000

FFL+6.675
Air Flow 520 L\s
SSL+6.600
3385

UP AREA - REEM ISLAND -ABU DHABI / SECTOR - RR1 / PLOT - C5


REFER RFI - RFI-01284-CLOSED-1225
CLIENT
C11
1500

C12 FCU B1-SW-C1-1


2954
6000

BOU PROJECT MANAGER


UP FFL+6.600
1635 Air Flow 520 L\s FFL+6.600 FFL+6.600
SSL+6.600
3642

SSL+6.600 SSL+6.600
C13
1000

DN TO B2
TECHNICAL ARCHITECT

C14 FOR ENLARGED PLAN(SCALE - 1:100)


FOR ENLARGED PLAN(SCALE - 1:100) WITH DIMENSIONS REFER DRAWING :
5000

WITH DIMENSIONS REFER DRAWING : STAFF RM01-DRG-3000-ME-ACD-B1-01-104


RM01-DRG-3000-ME-ACD-B1-01-102 SHEET : 4 OF 4
SHEET : 2 OF 4 ENTRY
UP
C15
FCU B1-SW-C1-1
DESIGN ARCHITECT
3500

1485 BOU 2975


1317

Air Flow 520 L\s


C16

WMC
2500

UP COST CONSULTANT , QUANTITY SURVEYING


C17
FAITHFUL & GOULD
STRUCTURE, CIVIL & MEP ENGINEERING,IT,AV,TELECOM
6000

WME
INFRA STRUCTURE CONSULTANCY
MATCHLINE FOR CONTINUATION REFER TO RM01-DRG-3000-ME-ACD-B1-04-100 ARUP
C18
TRAFFIC & PARKING CONSULTANCY
INFRACAD
BASEMENT 1 AIR CONDITIONING DUCTING LAYOUT - ZONE 1 SUSTAINABILITY & ESTIDAMA, WASTE MANAGEMENT
HOARE LEA
Scale:- 1 : 200 ENVIRONMENTAL MANAGEMENT DESIGN, FIRE,LIFE & SAFETY
RAMBOLL
LANDSCAPE & IRRIGATION
CRACKNELL
INTERIOR DESIGN
INTERCON
SECURITY
GOOD HARBOUR
SIGNAGE & WAYFINDING
BRIMAXX & DEZIGNTECHNIC
SPECIALIST LIGHTING VERTICAL TRANSPORATION
ABBREVIATIONS
CD+M COOPER & WILCOCK
SAD SUPPLY AIR DUCT BOU BOTTOM OF UNIT
FACADE DESIGN & ENGINEERING FOOD & BEVERAGE CONSULTANT
RAD RETURN AIR DUCT BOD BOTTOM OF DUCT
FINISH FLOOR MEINHARDT FUTURE FOOD
SAG SUPPLY AIR GRILLE T THERMOSTAT
CONCRETE SLAB WIND TUNNEL STUDIES INDEPENDENT COMMISSIONING AGENT
ANCHOR BOLT
RAG RETURN AIR GRILLE ATT ATTENUATOR
BMT FLUID AESG
SCD SUPPLY CEILING DIFFUSER FD FIRE DAMPER MAIN CONTRACTOR:-
SLAB SLAB
RCD RETURN CEILING DIFFUSER VCD VOLUME CONTROL DAMPER
ITINERA/GHANTOOT (IGJV)
LOCK NUT W/WASHER SLD SUPPLY SLOT DIFFUSER MD MOTORISED DAMPER
DUCT P.O.BOX.34869, ABU DHABI, U.A.E.
GI THREADED ROD RLD RETURN SLOT DIFFUSER AD ACCESS DOOR Muroor Road_Al Hamed Tower-
SPACING OF SUPORTS Office-1 2nd Floor.
SPECIFIED DUCT SIZE (LOW PRSSURE) FCU FAN COIL UNIT L/s LITRE PER SECOND
MAX DUCT SIZE HANGER BEARING MAX 3MM GASKET
(LONGER SIDE) MEMBER ANGLE SPACING OF DUCT THERMAL INSULATION AHU AIR HANDLING UNIT UP UP
ROD DIA (MM) SUB CONTRACTOR:-
HANGER
UP TO 300MM 8 25x25x3MM 3000MM MS CHANNEL / ANGLE VAV VARIABLE AIR VOLUME DN DOWN Drake & Scull International L.L.C.
301MM - 600MM 8 25x25x3MM 2400MM (HOT DIP GALVANISED)
CAV CONSTANT AIR VOLUME T/A TO ABOVE P.O.Box 44325 Tel : +971 2 6225005

601MM - 1000MM 10 32x32x3MM 2400MM LEGENDS Abu Dhabi U.A.E Fax : +971 2 6226008
FCU FAN COIL UNIT F/A FROM ABOVE
1001MM - 1500MM 10 40x40x3MM 2400MM
DUCT SUPPORTS DETAILS AHU AIR HANDLING UNIT T/B TO BELOW DRAWING TITLE:-
1501MM - 1800MM 10 40x40x6MM 1800MM SUPPLY AIR DUCT
1801MM - 2400MM 10 50x50x6MM 1800MM FAHU FRESH AIR HANDLING UNIT F/B FROM BELOW RETURN AIR DUCT
BASEMENT 1 AIR CONDITIONING DUCTING
LAYOUT - ZONE 1
SHEET-A1 DRAWN BY CHKD BY APPD.BY SCALE DATE
ZONE 1 SHYAM KRISHNA AHMED 1:200 26-02-2019
REF.DRG NO: RM01-DWG-0260-AC-01-103-01
REVISION
DRG NO:- RM01-DRG-3000-ME-ACD-B1-01-100
00