B. Construction: Casing shall be made of high-quality ABS providing long lasting shock-
proof and robust construction. The unit finishing shall be in white RAL 9010 and are
UV resistant. Aesthetic front flat cover for modern interior design and easily removed
for cleaning.
C. Impellor: Axial type with low noise and high efficiency aerodynamic properties.
D. Motor: Single phase induction motors with integral thermal protection, mounted on
high quality ball bearings. Suitable for continuous and intermittent running.
E. Performance: Fans shall be tested to either latest European (EN) or AMCA (US)
standards, to ensure accurate and up to date information on electrical safety, per-
formance and noise level.
A. Sound-Power Level Ratings: Comply with AMCA 301, "Methods for Calculating Fan
Sound Ratings from Laboratory Test Data." Factory test fans according to
AMCA 300, "Reverberant Room Method for Sound Testing of Fans." Label fans with
the AMCA-Certified Ratings Seal.
B. Fan Performance Ratings: Establish flow rate, pressure, power, air density, speed of
rotation, and efficiency by factory tests and ratings according to AMCA 210,
"Laboratory Methods of Testing Fans for Rating."
PART 3 - EXECUTION
3.01 INSTALLATION
A. Do not operate fans for any purpose until ductwork is clean, filters are in place,
bearings lubricated, and fan has been test run under observation.
C. Install flexible connections specified in Section 23 3343 between fan inlet and
discharge ductwork. Ensure metal bands of connectors are parallel with minimum on
inch (25mm) flex between ductwork and fan while running. Flexible connections shall
not be used for fans used for smoke exhaust applications.
H. For all fans (normal/smoke vent fans) provide fan starter switch in the space served
by the fan and location of starter switch to be as indicated on shop drawing or as
approved. Make necessary interconnections with light switch