4. Cones: Provide each fan with inlet and discharge cones.

Provide the dis-


charge cone with vanes space and contoured for maximum efficiency.
5. Motors:
a. For fans with motors inside casing, extend motor electrical leads outside
fan housing with liquid tight flexible conduit and terminate in outside junc-
tion box.
b. Provide fans with motors outside casing with a V-belt drive of ample ca-
pacity. Provide adjustable ratio type sheaves sized to give the required
fan speed with motor sheave at about the middle of its range of adjust-
ment. Provide at least two (2) belts; and drive capable of carrying the en-
tire load with an additional 50% safety factor. Provide belt guards with
opening for RPM readings for all sheaves and belts. Submit drive data for
approval. Fan fans with motors 50 HP and over supply fixed ration
sheaves in lieu of the variable type.
6. For fans used for smoke ventilation, prove direct driven fans designed to with-
stand hot smoke temperature up to 400C for 2 hours. Where direct driven
fans are indicated for smoke duty provide motor having class H insulation.
These motors shall be provided with variable frequency drives as per equip-
ment schedules.
7. Accessories:
a. Provide additional adjustable or fixed sheaves, at no additional cost, if re-
quired for balancing.
b. Provide all motors with a means of external lubrication, such that the fans
do not require disassembly for lubrication.
c. Provide belt drive fans with drive and belt guards.
8. Comply with Local Civil Defense and NFPA regulations.
9. Provide one spare motor for each motor size and provide one belt/ bearing for
each fan.

2.08 WINDOW / WALL MOUNTED FANS

A. Description: Factory-fabricated, assembled, tested and finished, suitable for window


or wall mounting, with low noise and high efficiency impellor. Fans consisting of
housing, fan, shaft, bearings, motor and disconnect switch, drive assembly and
support structure.

B. Construction: Casing shall be made of high-quality ABS providing long lasting shock-
proof and robust construction. The unit finishing shall be in white RAL 9010 and are
UV resistant. Aesthetic front flat cover for modern interior design and easily removed
for cleaning.

C. Impellor: Axial type with low noise and high efficiency aerodynamic properties.

D. Motor: Single phase induction motors with integral thermal protection, mounted on
high quality ball bearings. Suitable for continuous and intermittent running.

E. Performance: Fans shall be tested to either latest European (EN) or AMCA (US)
standards, to ensure accurate and up to date information on electrical safety, per-
formance and noise level.

F. Accessories: Fans shall be complete with the following accessories:

KEO/21-4033-0000 23 3413 / 10 Axial Hvac Fans


Roshn Single Family Standard Product
Central Region Prototype Library - KSA
1. Integral back-draught shutter to prevent air flowing back into the room when
the fan is off.
2. Window or wall mounted installation kit.
3. Safety finger guard.

G. Designed and manufactured in accordance with EN 60335-2-80 (Low Voltage Di-


rective) and the EMC Directive (Electromagnetic Compatibility) or equivalent. Fan
shall be supplied with CE or UL mark.

H. Fan shall be operated via a separate local ON/OFF isolator switch.

2.09 SOURCE QUALITY CONTROL

A. Sound-Power Level Ratings: Comply with AMCA 301, "Methods for Calculating Fan
Sound Ratings from Laboratory Test Data." Factory test fans according to
AMCA 300, "Reverberant Room Method for Sound Testing of Fans." Label fans with
the AMCA-Certified Ratings Seal.

B. Fan Performance Ratings: Establish flow rate, pressure, power, air density, speed of
rotation, and efficiency by factory tests and ratings according to AMCA 210,
"Laboratory Methods of Testing Fans for Rating."

PART 3 - EXECUTION

3.01 INSTALLATION

A. Do not operate fans for any purpose until ductwork is clean, filters are in place,
bearings lubricated, and fan has been test run under observation.

B. Install fans with vibration isolation mountings as specified in section 23 0548.

C. Install flexible connections specified in Section 23 3343 between fan inlet and
discharge ductwork. Ensure metal bands of connectors are parallel with minimum on
inch (25mm) flex between ductwork and fan while running. Flexible connections shall
not be used for fans used for smoke exhaust applications.

D. Provide fixed sheaves required for final air balance.

E. Provide safety screen where inlet or outlet is exposed.

F. Pipe scroll drains to nearest floor drain.

G. Provide back draft dampers on discharge of exhaust fans and as indicated.

H. For all fans (normal/smoke vent fans) provide fan starter switch in the space served
by the fan and location of starter switch to be as indicated on shop drawing or as
approved. Make necessary interconnections with light switch

I. Install axial fans level and plumb.

J. Install units with clearances for service and maintenance.

KEO/21-4033-0000 23 3413 / 11 Axial Hvac Fans