External walls, roof insulation and glass performance should meet the
requirements of SBC 602, SBC 1101 & SBC 1102 requirements and
should be as follows:
b. Roof: U = 0.202W/m². K, max value
c. Wall: U = 0.342W/m². K, max value
d. Floors: U= 0.496 W/m². K, max value
e. Doors: U= 2.839 W/m². K, max value
f. Glass specifications
1) Heat transfer coefficient value U = 2.668 W/m². K, max value
2) SHGC = 0.25
E. Acoustic
1. The noise level within the following space shall not exceed the indicated
numbers:
a. Living Rooms 30 NC/NR
b. Bedrooms 30 NC/NR
c. Corridors 30 NC/NR
d. Kitchens 35 NC/NR
e. Bathrooms 35 NC/NR
f. Utility Rooms 35 NC/NR
Source: ASHRAE
F. Air Filtration
1. Mildew proof, removable and washable anti-microbial filter.
G. Face Velocity
1. Air velocity for Fan Coil Units (FCU) shall not to exceed 2.5 m/s (500 fpm).
A. The air-conditioning requirements for the residential buildings shall be met by direct
expansion (DX), variable refrigerant flow (VRF) split type system (Heat Pump). The
inverter motor driven units incorporating both decorative (wall mounted) & cassette
type indoor units with associated roof mounted condensing unit shall be furnished with
the following components:
1. Fan(s): Direct-driven, double width fan wheel shall have forward curved blades.
2. Motor(s): Inverter type. Comply with requirements in Division 23 Section