Professional Documents
Culture Documents
ECOMax HE Manual New
ECOMax HE Manual New
ECOMax-HE®
Automatic Tube Cleaning System
Table of Contents
Introduction ................................................................................................................................. 3
About Us ...................................................................................................................................................................................... 3
Inspection of System .................................................................................................................................................................... 4
Installation Note .......................................................................................................................................................................... 4
Handling of System ...................................................................................................................................................................... 4
P&I Diagram of System ............................................................................................................... 5
Part List....................................................................................................................................... 9
Description of System Components .......................................................................................... 13
1. Ball Trap (A) ...................................................................................................................................................................... 13
2. Ball Collector (B) ............................................................................................................................................................... 13
3. Booster Pumps (C) ............................................................................................................................................................ 13
4. Control Panel (D) .............................................................................................................................................................. 13
5. Control Valves (E) ............................................................................................................................................................. 13
6. Manual Valves (F) ............................................................................................................................................................. 13
7. Manual Valve (H) .............................................................................................................................................................. 13
8. Manual Valves (I) .............................................................................................................................................................. 13
9. Check Valves (G) ............................................................................................................................................................... 14
10. Pressure Gauges (J) .......................................................................................................................................................... 14
11. Balls .................................................................................................................................................................................. 14
Sponge Balls Disposal Procedure ............................................................................................. 14
Installation of Unit ..................................................................................................................... 15
Commissioning Procedure ........................................................................................................ 17
Pre-Commissioning Checks ........................................................................................................................................................ 17
Shutdown ................................................................................................................................................................................... 18
System Maintenance................................................................................................................. 19
Preventive Maintenance Schedule ............................................................................................................................................ 19
Daily Check-up ........................................................................................................................................................................... 19
Weekly Check-up ....................................................................................................................................................................... 20
Monthly Check-up ...................................................................................................................................................................... 20
Quarterly Check-up .................................................................................................................................................................... 20
Yearly Maintenance ................................................................................................................................................................... 20
Annexure A: Components of ECOMax-HE® ............................................................................. 22
Annexure B: HMI Screens Description ...................................................................................... 23
Annexure C: Wiring Diagram..................................................................................................... 30
Annexure D: Trouble Shooting .................................................................................................. 34
Ball Replacement Procedure..................................................................................................... 37
About Us
ECOMAX SOLUTIONS PVT LTD is a leading company having its headquarters in Pune, INDIA engaged in
manufacturing of ECOMax-HE® Automatic Tube Cleaning System, ECOMax-CT® Electrolytic CT Water
Treatment System for Cooling Towers and ECOMax-CH® Electrolytic Chilled Water Treatment System.
ECOMAX is committed to offer clean technology based innovative solutions which result in substantial
Energy Saving and Water Saving for its clients. It promotes the technologies which are sustainable and
have positive impact on environment resulting into substantial energy and water savings.
ECOMAX was started in April 2014 as ECO GREEN SYSTEMS LLP. Since then it has grown in India & Overseas
market with Hundreds of satisfied customers.
ECOMAX has partnered with Strategic Partners from USA having deep industrial experience across the
globe and with this partnership ECOMAX plan to expand its markets in other geographies across the globe.
System Description
ECOMax-HE® patent pending system uses sponge balls to keep heat exchanger tubes clean. The sponge
balls are injected almost simultaneously at the heat exchanger tube sheet with the help of injection pump
thereby giving effective spread to the sponge balls in various tubes, the sponge balls would pass through
the tubes and clean the fouling /scales/deposits inside the tubes. Once the sponge balls come out of the
heat exchanger tubes they are collected at ball trap, they are sent back to the ball collector with the help
of collection pump. The entire process is a batch operation automatically controlled by PLC and occurs 2-
3 times in an hour. These pumps run hardly for few seconds for injection and collection of sponge balls.
ECOMax-HE® is maintenance free and designed to have long life & trouble free operation.
Inspection of System
Check all items carefully against the Delivery Challan. Inspect all components for damage upon arrival.
Check the unit nameplate after unloading.
Installation Note
Installation is to be performed by qualified personnel who are familiar with local codes, factory standards,
factory safety norms and regulations.
Handling of System
Avoid rough handling of the system. The system should be moved from the base to avoid any damage
during the handling. Carefully lift the system and put it at the specified location.
2 Ball Collector 01 B
Manual Valves ½” 04 H
Booster Pumps 02 C
Control Valves 02 E
Pressure Gauges 02 I
4 Other Accessories
Rubber Bush 04
Mesh Component 01 J
2 Ball Collector 02 B
Manual Valves ½” 06 H
Booster Pumps 02 C
Control Valves 04 E
Pressure Gauges 02 I
4 Other Accessories
Rubber Bush 04
Mesh Component 01 J
2 Ball Collector 03 B
Manual Valves ½” 08 H
Booster Pumps 02 C
Control Valves 06 E
Pressure Gauges 02 I
4 Other Accessories
Rubber Bush 04
Mesh Component 01 J
2 Ball Collector 04 B
Manual Valves ½” 10 H
Booster Pumps 02 C
Control Valves 08 E
Pressure Gauges 02 I
4 Other Accessories
Rubber Bush 04
Mesh Component 01 J
11. Balls
The Sponge Rubber Balls are the key elements of the system and are responsible for cleaning the
tubes. The number of balls & diameter are decided depending on the heat exchanger/condenser
specifications. They are housed in the Ball Collector.
ECOMax-HE ATCS comes to you packed in two wooden boxes. The first step begins with unpacking. Un-
pack Box no. 1 and take out the items like Skid, Ball Collector and Fittings Box. Now un-pack Box no. 2 and
take out the Ball Trap & Ball collector stand. Unpack the fittings box and take out the valves & fittings like
swing check valves, manual ball valves and rubber bush.
1. Skid Positioning:
Once the un-packing is done, first fix the location of the Skid at a convenient location. In case of Single
Chiller system, the skid should be placed near the condenser inlet/outlet nozzle. In case of Multiple
Chillers, the skid position should be near the central chiller so that piping connections are minimized.
The skid should be positioned in such a way that the HMI on control panel should be easily accessible
to the operating personnel. Fix the rubber bushes at four corners of the skid.
Commissioning Procedure
Pre-Commissioning Checks
1. Check the electric power supply and ensure that the control panel is charged with 3-phase, 415
VAC electric power supply
2. Check all the valves & fittings for leakage & correct if necessary
3. Inspect all water piping for flow direction and correct connections
4. Inspect the check valve on injection pipe and collection pipe for correct direction
5. Check the control valves operation for opening & closing.
X
3. Open all the 1½”/2” & 1”/ 1½” Manual ball valves installed on the interconnected piping.
4. Ensure that the pump MPCBs and 230 VAC MCB are ON before starting the power supply to the
control panel
5. Switch ON the supply to the control panel and set all the timing such as Injection and Collection
time, Time between the cycle & Ball Circulation time as per ECOMax-HE® guidelines
6. Perform manual operation of the cycle to check if the balls are injected and collected properly
7. Perform automatic operation and adjust the timing for the smooth operation of system
8. Put all the required number of balls into the Ball Collector necessary for routine operation as
specified by ECOMax-HE® at the time of commissioning
9. Perform 3-4 automatic operation
Shutdown
Before shutting down the system make sure that the balls are in the Ball Collector and none of the two
(Injection or collection) cycle are in operation if yes then let the operation get completed and then switch
OFF the power supply to the control panel with the help of switch located on the control panel.
General
- Check Injection & Collection cycle operation once X
- Check quantity of balls from site glass provided on the ball collector X
- Check ECOMax-HE® is running on that chiller whose interlock is active X
- Check operation of Injection & Collection control valve X
- Clean Ball Collector for any dirt X
- Check for leakage X
- Visually inspect system for any loose or damaged component X
- Clean sight glass from inside & outside for clear vision X
- Check for normal operation of system X
Electrical
- Check interlock terminals for tightness, tighten if necessary X
- Check terminals for tightness, tighten if necessary X
- Clean control panel from inside & outside X
Components
- Clean Ball Trap screen if necessary X
Note:
1. Weekly operations include all daily operations.
2. Monthly operations include all weekly operations.
3. Quarterly operations include all Monthly operations
4. Annual operations include all weekly, monthly and quarterly operations.
Daily Check-up
1. Look through the Ball Collector’s sight glass, verify it has required number of sponge balls
2. Wait for the injection cycle to start
3. Once injection cycle starts verify that balls are injected and released into the heat
Exchanger/condenser
4. Wait till the end of the operation
5. Visually confirm that the balls have returned to the Ball Collector
If the sponge balls have returned, the system is functioning properly
Monthly Check-up
1. Physically check the balls quantity & condition of the balls
2. If ball quantity & condition is Okay, continue with the same balls
3. If ball quantity is less & add the balls to make up the quantity
4. If the balls are hard or worn out change the complete ball quantity
Quarterly Check-up
1. Compulsorily replace the entire quantity of the balls with new balls
Yearly Maintenance
Clean the Ball Collector and Ball Trap as per the guidelines mentioned below:
1. Shut down the system
2. Close the water connections
3. Drain the water from Ball Collector
4. Remove sight glass and clean the Ball Collector & connect it back after cleaning
5. For Ball Trap drain the condenser and ensure no water is present inside the Ball Trap
6. Open the Ball Trap from ball exit side, visually inspect the screen inside for any cleanliness
7. Clean them if necessary and put them back in position & fix all the parts to their respective
positions
Important Notes
If the number of balls returned back to the Ball Collector are less than the normal quantity,
does not indicate that system is not operating properly
If no balls are there in the Ball Collector after the complete operation of the system, refer
Trouble Shooting page for guidelines or contact Ecomax office representative
Warning:
If the chiller runs without the ECOMax-HE® for a number of days, condenser tubes will
develop a layer of scale that cannot be removed by the sponge balls. If this happens,
the heat exchanger/condenser must be opened and descaling/cleaning should be done.
The chiller should be restarted with ECOMax-HE®.
Level :- 1
Contact
Region Base location State/Cities Covered Name Designation details Email ID
Haryana, Jammu & Kashmir, Himachal
Pradesh, Punjab, Rajasthan, Uttar Pradesh,
North Delhi Bihar, Uttarakhand Abhilash Thakur Service Engineer 9595114198 abhilasht@ecomax.in
East Delhi West Bengal, Jharkhand Abhilash Thakur Service Engineer 9595114198 abhilasht@ecomax.in
Gujarat-Ahmedabad Ahmedabad, Gandhinagar, Vadodara Akshay Bharsakle Service Engineer 9881388252 guj@ecomax.in
Gujarat-Ankleshwar Madhya Pradesh, Ankleshwar, Bharuch Avinash Kokate Service Engineer 9175481233 guj1@ecomax.in
West
Maharashtra-Pune Chhattisgarh, Maharashtra Angad Deshmukh Sr. Service Engineer 8668231961 angadd@ecomax.in
Maharashtra-Pune Pune Satish Rajurkar Service Engineer 8999791245 seho1@ecomax.in
Bangalore Karnataka, Kerala, Tamilnadu Vishnu Ramachandran Service Engineer 9995341740 vishnur@ecomax.in
South
Hyderabad Telangana, Andhra Pradesh Santosh Tallikar Asst Manager 9518314029 santosht@ecomax.in
Level :- 2
Level :- 3
Ball
Ball Collecto
Trap
Skid with
Control
Panel
The Control Panel consists of a multicolor screen touch HMI which is composed of following screens:
A. Home Screen:
This screen displays the number of existing system and their status of operation. If the buttons
(1/2/3/4) turns green means the particular systems are in operation. The numbers shown are for
count down for next cycle
Also the screen has the function of manual operation of system which can be accessed by inserting
the password on same screen.
This screen shows the injection cycle operation and total time for injection of the balls in CW inlet
pipe of heat exchanger/condenser & ABCDEFGHIJ where it shows on which chiller the cycle is in
operation
This screen shows the ball circulation time and after completion immediately the collection cycles
starts & ABCDEFGHIJ where it shows on which chiller the cycle is in operation.
This screen shows the collection cycle operation and total time for collection of the balls from Ball
Trap to Ball Collector & ABCDEFGHIJ where it shows on which chiller the cycle is in operation.
C. Input Screen:
This is screen where the time for system operation & ball replacement is set. This screen is
password protected and time can be changed by authorized person only.
D. Log Screen:
This screen displays number of times the valves have operated in the said system working hours
F. Alarm Screen:
This screen displays the Model No., Serial No., Year of Manufacturing., and Date of commissioning
of the system.
This screen displays the Balls Diameter & No. of Balls required for the system.
You can give names to system 1/2/3/4 as per your chiller number so that any person can
understand on which chiller system is operational.
Sr. No. Type of Fault Additional Check How to Determine the Fault Reason Solution
1 Pumps not 1.1 Check supply to the Controller and wire connection Controller not working 1.1.1 Check & Repair/Replace the
operating between pumps if all ok still not running Controller
1.2 If supply ok controller working & still pump not Pump Problem 1.2.1 Check & Repair/Replace Pump
working Motor
Pump not giving desired 1.3 Open the air vent on pump discharge & check for Air in condenser inlet pipe 1.3.1 Open the air vent on pump
pressure airlock discharge slightly & remove the airlock &
operate the pump
1.4 Open the pump impeller & check for any dirt or Dirt or welding particle 1.4.1 Ope the pump impeller, clean it &
welding particle stuck inside stuck inside the pump then operate the pump
impeller
Pump Motor Heating Up 1.3 Please check the pump discharge pressure for Pump is running at very less 1.3.1 Throttle the valve on pump
measuring the head at which pump is operating by head discharge for additional head so that
referring the pump curve pump will operate at desired head
2 Injection Balls are in Ball Collector 2.1 Make sure all manual valves on skid, Injection & Manual Valve on Injection 2.1.1 Open all manual valves on Injection
Problem collection pipe are open and Injection Pump is line/Skid/Injection Pump line, Skid & Injection Pump suction
operating at full load & designed head by checking the suction tapping point is tapping point or clean the pump impeller
current from control panel with multimeter & observe closed or there is dirt inside for any dirt inside it
pump head from pressure gauge at pump discharge if it the pump impeller
doesn’t see 2.1.1
2.2 Again do manual operation & make sure manual Swing Type Check Valve is 2.2.1 Clean the Swing Type Check Valve
valves on skid, Injection & collection pipe are open and choked because of dirt on injection line for any dirt / replace it.
control valve on injection line is open & still balls not
injected see 2.2.1
2.3 Again do manual operation & make sure manual Injection Control Valve not 2.3.1 Check connection between control
valves on skid, Injection & collection pipe are open and opening or partially valve & control panel or repair/replace
control valve on injection line is open if it doesn’t see opening the actuator/control valve on injection
2.3.1 line
2.4 Again do manual operation and still no injection of Collection Control Valve 2.4.1 Check connection between
balls, close manual valve on collection line before opening fully or partially control valve & control panel or replace
control valve and re-operate. If balls are injected see the actuator/control valve on collection
2.4.1 line
If balls have not returned 3.4 Retry manual operation and partially open the ½” Airlock in collection pipe 3.4.1 Check for water leakage on
to Ball Collector, check valve on Ball Collector & release the air. If balls return collection pipe.
the Ball Collector if there to Ball Collector then re-operate and no ball collection
is air inside it if yes then then there is water leakage on collection pipe
see #3.4. If there is no air
in Ball Collector then see
#3.4.1
3.5 Retry manual operation, if balls still don’t return to Check the water quality 3.5.1 Replace the old balls with new balls
the Ball Collector, check the condition of balls if
they are spongy or became hard. If balls have
became hard see 3.5.1
3.7 Retry manual operation, if balls still don’t return to Due to less distance 3.7.1 Shift the Injection pump suction
the Ball Collector, check the distance between Injection between Injection Pump tapping at 2-3 meters from Ball injection
Pump suction tapping and Ball injection point on suction tapping and Ball point on condenser inlet line or weld a
condenser inlet pipe if it is less than 2 meters then see injection point balls going in reducer with mesh on the bigger of it at
3.7.1 injection pump suction pipe injection pump suction tapping.
3.8 Retry manual operation, if still balls don’t return to Wrong connections from 3.8.1 Correct the connections or again
the Ball Collector, check during collection if two control ECOMax-HE control panel upload the program for smooth
valves of collection are open at a time if yes then see to control valve or problem functioning
3.8.1 in PLC program logic
3.9 Retry manual operation, if still balls don’t return to Balls gone to panel cooling Blind the taping on condenser cover &
the Ball Collector, check if the chiller condenser has pipe heat exchanger as that is shift the panel cooling pipe at minimum
going to panel cooling heat exchanger the least resistance path distance of 1 meter from ball injection
point by taking a taping on condenser
inlet pipe
3.10 Retry manual operation, if still balls don’t return to Tubes not cleaned properly Open condenser cover from both sides,
the Ball Collector, check whether tubes are clean & or tubes are blocked either clean the condenser tubes, check the
checked properly from both sides of condenser if not from front side or backside tubes with id gauges & retry the cycle
then see 3.10.1
3.11. Retry manual operation, if still balls don’t return Condenser pump not giving Clean the strainer/Design a proper pump
to the Ball Collector, check the dP across condenser if it the desired flow because of for required flow & head/ Run the pump
is not sufficient than what is required then see 3.11.1 either strainer after pump is on full frequency to get the desired flow
chocked or pump design is
not proper to give desired
flow or pump flow is
controlled VFD by adjusting
its frequency
4 Interlock 4.1 If interlock cable is connected between Chiller panel Interlock connection is not 4.1.1 Check the interlock connection and
Problem & ECOMax-HE panel while chiller is running and still proper connect the wire between chiller panel
cycle not started see 4.1.1 potential free contact & system panel.
Re-operate to check
X
1. Shut off the power supply from the control panel.
2. Close Manual Valves located on pipelines at Injection & Collection above Ball Collector.
3. Close Manual Valves located on pump suction pipeline
1. Open the air vent valve located at the top of Ball Collector
2. Drain the water from the Ball Collector completely by opening the drain valve
3. Open the Site Glass located on the Ball Collector
4. Take out the old set of balls and compare them with new set of balls for any reduction in the diameter.
Replace the old balls having reduced diameter with new balls
5. If the quantities of balls are less, then add new balls to make-up the required number of balls.
6. Put back the Site Glass on the Ball Collector and tighten the bolts properly so that there is no leakage
7. Close the drain and air vent valves located on Ball Collector
8. Open manual valves located on pipelines at pump suction, Injection & Collection above Ball Collector.
9. Partially open-air vent valve located on Ball Collector to release air in Ball Collector and then close it.
10. Start the power supply to the control panel
11. Verify that the balls are injected into condenser
12. Observe one complete cycle of operation
13. Visually confirm that the balls have returned to Ball Collector.