Professional Documents
Culture Documents
41-133 2F
41-133 2F
41-133 2F
41-133.2F
Type IRQ Directional Overcurrent
Negative Sequence Relay
Figure 1. Type IRQ Relay without Case (Rear View) *Figure 2. Type IRQ Relay without Case (Front View)
Type IRQ Directional Overcurrent 41-133.2F
Negative Sequence Relay
Figure 3 .Time Overcurrent Unit (Front View). 1)Tap Block, 2) Time Dial, 3) Control Spring Assembly, 4) Disc, 5) Stationary
Contact Assembly, 6) Magnetic Plugs, 7) Permanent Magnet
The electromagnet has two series-connected polariz- the underside of the bridge and is attached to the
ing coils mounted diametrically opposite one another; moving contact arm by a spiral spring. The spring
two series-connected operating coils mounted dia- adjuster is also held in place by a spring type clamp.
metrically opposite one another; two magnetic
adjusting plugs; upper and lower adjusting plug clips, With the contacts closed, the electrical connection is
and two locating pins. The locating pins are used to
made through the stationary contact housing clamp,
accurately position the lower pin bearing, which is
to the moving contact, through the spiral spring out to
mounted on the frame, with respect to the upper pin
bearing, which is threaded into the bridge. The elec- the spring adjuster clamp.
tromagnet is secured to the frame by four mounting
screws. 2.2. Negative Sequence Filter
The moving element assembly consists of a spiral The current and voltage filters consist of reactors and
spring, contact carrying member, and an aluminum resistors connected together as shown in the internal
cylinder assembled to a moulded hub which holds schematic (Figure 4).
the shaft. The shaft has removable top and bottom
jewel bearings. The shaft rides between the bottom 2.3. Time-Overcurrent Unit (CO)
pin bearing and the upper pin bearing with the cylin-
The electromagnets for the types IRQ-5, IRQ-6, IRQ-
der rotating in an air gap formed by the electromag-
net and the magnetic core. 7, IRQ-8 and IRQ-9 relays have a main tapped coil
located on the center leg of an “E” type laminated
The bridge is secured to the electromagnet and structure that produces a flux which divides and
frame by two mounting screws. In addition to holding
returns through the outer legs. A shading coil causes
the upper pin bearing, the bridge is used for mount-
ing the adjustable stationary contact housing. The the flux through the left leg to lag the main pole flux.
stationary contact housing is held in position by a The out-of-phase fluxes thus produced in the air gap
spring type clamp. The spring adjuster is located on cause a contact closing torque.
3
41-133.2F Type IRQ Directional Overcurrent
Negative Sequence Relay
*Sub 4 Sub 1
185A096 184A996
Figure 4. Internal Schematic of the IRQ Relay Figure 5 .Sensitivity Curve of the Directional Unit (D)
The electromagnet for the type IRQ-2 and IRQ-11 2.5. Instantaneous Overcurrent Unit (I)
relays has a main coil consisting of a tapped primary The instantaneous overcurrent unit consists of an
winding and a secondary winding. Two identical coils induction cylinder type unit and a transformer. The
on the outer legs of the lamination structure are con- induction cylinder unit is similar in construction to the
nected to the main coil secondary in a manner so directional unit. The time phase relationship of the
that the combination of all the fluxes produced by the two air gap fluxes necessary for the development of
electromagnet result in out-of-phase fluxes in the air torque is achieved by means of a capacitor con-
gap. The out-of-phase air gap fluxes produced cause nected in series with one pair of pole windings.
a contact closing torque. The normally-closed contact of the directional unit is
connected across one pair of pole windings of the
2.4. Auxiliary Switch (CS-1 or TR-1) instantaneous overcurrent unit as shown in the inter-
nal schematics. This arrangement short-circuits the
The CS-1 switch is a small solenoid type dc switch. A
operating current around the pole windings, prevent-
cylindrical plunger, with a silver disc mounted on its
ing the instantaneous overcurrent unit from develop-
lower end, moves in the core of the solenoid. As the ing torque. If the directional unit should pick up for a
plunger travels upward, the disc bridges the silver fault, this short circuit is removed. allowing the
stationary contacts. The TR-1 is a telephone type instantaneous overcurrent contact to commence
relay. A tapped resistor is used to enable one to use closing almost simultaneously with the directional
the auxiliary switch on a 24, 48, 125 or 250 volt dc contact for high speed operation.
system connected per Figure 14. The operation of
The transformer is one of the saturating type for limit-
the CS-1 or TR-1 switch is controlled by the direc-
ing the energy to the instantaneous overcurrent unit
tional unit (D) which in turn directionally controls the at higher values of fault current and to reduce ct bur-
time-overcurrent unit (CO). When sufficient power den. The primary winding is tapped and these taps
flows in the tripping direction, the aux switch oper- are brought out to a tap block for ease in changing
ates and bridges the lag coil of the time-overcurrent the pickup of the instantaneous overcurrent unit. The
unit (CO) permitting this unit to operate. use of a tapped transformer provides approximately
4
Type IRQ Directional Overcurrent 41-133.2F
Negative Sequence Relay
Sub 1 Sub 2
184A995 292B934
Figure 6 .Time Curve of the Directional Unit (D) Figure 7. Diagram of Test Connections of the Circuit
Closing Time Overcurrent Unit of the IRQ Relay
the same energy level at a given multiple of pickup relays are designated by specific numbers as indi-
current for any setting, resulting in a single time cated in the following chart (e.g., IRQ-8).
curve throughout the range of the relay.
Also during this operation two fingers on the arma- Range Taps
ture deflect a spring located on the front of the
.5 - 2.5 0.5 0.6 0.8 1.0 1.5 2.0 2.5
switch, which allows the operation indicator target to
2-6 2 2.5 3 3.5 4 5 6
drop. 4 - 12 4 5 6 7 8 10 12
5
41-133.2F Type IRQ Directional Overcurrent
Negative Sequence Relay
* Sub 3
290B264
Figure 8. Test Diagram for Calibration of the Negative Sequence Current Filter in the IRQ Relay
The time vs., current characteristics for the direc- The auxiliary switch operating time is approximately
tional unit is shown in Figure 6. 5 milliseconds.
6
Type IRQ Directional Overcurrent 41-133.2F
Negative Sequence Relay
Sub 4
290B560
Figure 9 .In Service Test Procedure for Verifying Proper External Connections
Where CT Neutral is Formed Within the Relay.
7
41-133.2F Type IRQ Directional Overcurrent
Negative Sequence Relay
*Sub 4
290B559
Figure 1 0 .In Service Test Procedure for Verifying Power External Connections
Where CT Neutral is Formed Externally.
8
Type IRQ Directional Overcurrent 41-133.2F
Negative Sequence Relay
*Sub 6
290B551
9
41-133.2F Type IRQ Directional Overcurrent
Negative Sequence Relay
1 2
I A2 = --- ( 0 + a l – al )
3
l
I A2 = ------- ∠– 90°
3
10
Type IRQ Directional Overcurrent 41-133.2F
Negative Sequence Relay
Sub 1
184A946
6.4.3. Time Curve The pickup of the overcurrent unit can be checked by
Table 1 shows the time curve calibration points for inserting the tap screw in the desired tap hole and
the various types of relays. With the time dial set to applying rated tap value current. The contact should
the indicated position apply the current specified by close within ±5% of the tap value current.
Table 1 (e.g., for the IRQ-2, 3 and 20 times tap value 6.6. Indicating Contactor Switches
current), and measure the operating time of the relay. (ICS/I and ICS/T)
The operating times should equal those of Table 1
a. Close the contacts of the CO and pass sufficient
plus or minus 5 percent.
dc current through the trip circuit to close the
For Type IRQ-11 relay only, the 1.30 times tap value contacts of (ICS/T). This value of current should
operating time from the number 6 time dial position is not be greater than the particular (ICS/T) tap set-
54.9 ±5% seconds. It is important that the 1.30 times ting being used. The operation indicator target
tap value current be maintained accurately. The should drop freely, bringing the letter “T” into
maintaining of this current accurately is necessary view.
because of the steepness of the slope of the time- b. Close the contacts of the instantaneous overcur-
curve characteristics (Fig. 21). A 1% variation in the rent (I) and the directional (D) units. Pass suffi-
1.30 times tap value current (including measuring cient dc current through the trip circuit to close
instrument deviation) will change the nominal operat- the contacts of (ICS/I). This value of current
ing time by approximately 4%. should not be greater than the particular (ICS/I)
tap setting being used. The operation indicator
6.5. Instantaneous Overcurrent Unit (I)
target should drop freely, bringing the letter “I”
6.5.1. Contact Gap into view
The gap between the stationary and moving contacts c. The contact gap should be approximately .047”
with the relay in the de-energized position should be between the bridging moving contact and the
approximately.020”. adjustable stationary contacts. The bridging
moving contact should touch both stationary
6.5.2. Minimum Trip Current
contacts simultaneously.
The normally closed contact of the directional unit
should be blocked open when checking the pickup of 6.7. Routine Maintenance
the overcurrent unit. All relays should be inspected periodically and the
11
41-133.2F Type IRQ Directional Overcurrent
Negative Sequence Relay
time of operation should be checked at least once 6.10. Negative Sequence Current Filter
every year or at such other time intervals as may be Refer to Fig. 8 for positive sequence calibration.
dictated by experience to be suitable to the particular
application. a. Connect relay terminals 7 and 9 together.
Remove lead to lower right hand terminal of
If an additional time check is desired, pass second- mutual reactor (right side view) to disconnect the
ary current through the relay and check the time of direction unit.
operation. It is preferable to make this at several
b. Pass 10 amperes in terminal 6 and out terminal
times pick-up current at an expected operating point
8.
for the particular application. For th e.5 to 2.5 ampere
range IRQ-5 and IRQ-6 induction unit use the alter- c. With a 0-15 volts, high resistance voltmeter,
native test circuit in Figure 7 as these relays are measure and record voltage between terminals
affected by a distorted wave form. With this connec- 6 and the lower right hand terminal of mutual
tion the 25/5 ampere current transformers should be reactor. This voltage should be between 1.85
worked well below the knee of the saturation (i.e., and 1.95 volts.
use 10L50 or better). d. Now measure the voltage from terminal 6 to ter-
minal 7. Adjust the top filter resistor tap until this
All contacts should be periodically cleaned. A contact
voltage is 1.73 times the reading of part C.
burnisher #182A836H01 is recommended for this
Refer to Fig. 8 for neutral tap calibration
purpose. The use of abrasive material for cleaning
contacts is not recommended, because of the danger Using the test connections as shown and a low range
of embedding small particles in the face of the soft voltmeter connected between terminal 6 and 7,
silver and thus impairing the contact. adjust the middle filter resistor tap connection until
the measured voltage is zero. Reconnect lead to
6.8. Calibration
mutual reactor at end of this test.
Use the following procedure for calibrating the relay if
6.11. Directional Unit (D)
the relay has been taken apart for repairs or the
adjustments have been disturbed. This procedure a. The upper bearing screw should be screwed
should not be used unless it is apparent that the relay down until there is approximately .025” clear-
is not in proper working order. (See “Acceptance ance between it and the top of the shaft bearing.
Check”). The upper pin bearing should then be securely
locked in position with the lock nut.
6.9. Negative Sequence Voltage Filter b. Contact gap adjustment for the directional unit is
a. Apply 120 volts balanced 3 phase voltage 60 made with the moving contact in the reset posi-
Hertz to terminals 14, 15, and 16 of the relay, tion, i.e., against the right side of the bridge.
making sure that phase A, B, and C of the Advance the right hand stationary contact until
applied voltage is connected to terminals 14, 15, the contacts just close. Then advance the sta-
and 16 respectively. tionary contact and additional one-half turn.
b. Using a calibrated high resistance voltmeter, Now move in the left hand stationary contact
measure the voltage between the tap on the until it just touches the moving contact. Then
auto-transformer (middle terminal, lower-right back off the stationary contact 3/4 of one turn for
hand reactor, rear view of Figure 1 and the tap a contact gap of .020” to .024”. The clamp hold-
on the adjustable 2” resistor on the upper right ing the stationary contact housing need not be
hand corner of Figure 2. If the voltage is high (40 loosened for the adjustment since the clamp uti-
to 50 volts) the filter is probably improperly con- lizes a spring-type action in holding the station-
nected, the voltage will be low. Using a low ary contact in position.
range (approximately 5 volts) move the adjust- c. The sensitivity adjustment is made by varying
able tap until the voltage reads a minimum. This the tension of the spiral spring attached to the
value should be less than 1.5 volts. moving element assembly. The spring is
12
Type IRQ Directional Overcurrent 41-133.2F
Negative Sequence Relay
adjusted by placing a screwdriver or similar tool unit. Recheck on balanced, 3 phase, 120V posi-
into one of the notches located on the periphery tive sequence voltage. Relay must not operate.
of the spring adjuster and rotating it. The spring
adjuster is located on the underside of the bridge 6.12. Instantaneous Overcurrent Unit (1)
and is held in place by a spring type clamp that
does not have to be loosened prior to making the a. The upper pin bearing should be screwed down
necessary adjustments. until there is approximately .025” clearance
between it and the top of shaft bearing. The
The spring is to be adjusted such that the con- upper pin bearing should then be securely
tacts will close when the relay is energized 0.57 locked in position with the lock nut. The lower
volts and 6.93 amps at 188° (current leading bearing position is fixed and cannot be adjusted.
voltage), considering the relay connected to the
test circuit in Figure 12. b. The contact gap adjustment for the overcurrent
d. The magnetic plugs are used to reverse any unit is made with the moving contact in the reset
unwanted spurious torques that may be present position, i.e., against the right side of the bridge.
when the relay is energized on current alone. Move in the left hand stationary contact until it
just touches the moving contact then back off the
The reversing of the spurious torques is accom-
stationary contact 2/3 of one turn for a gap of
plished by using the adjusting plugs in the follow-
approximately .020”. The clamp holding the sta-
ing manner:
tionary contact housing need not be loosened for
1) Connect the relay voltage circuit terminals the adjustment since the clamp utilizes a spring-
(phase A, B, and C) together. type action in holding the stationary contact in
2) Apply 80 amperes single-phase current position.
(momentarily) in phase B terminal and out
c. The sensitivity adjustment is made by varying
phase C terminal.
the tension of the spiral spring attached to the
Plug adjustment is then made per Table 2 such that moving element assembly. The spring is
any contact closing spurious torques are reversed. adjusted by placing a screwdriver or similar tool
The plugs are held in position by upper and lower into one of the notches located on the periphery
plug clips. These clips need not be disturbed in any
of the spring adjuster and rotating it. The spring
manner when making the necessary adjustment.
adjuster is located on the underside of the bridge
The magnetic plug adjustment may be utilized to and is held in place by a spring-type clamp that
positively close the contacts on current alone. This does not have to be loosened prior to making the
may be desired on some installations in order to necessary adjustments.
insure that the relay will always trip the breaker on
Before applying current, block open the normally-
zero potential.
closed contact of the directional unit. Insert the tap
e. The core adjustment is made as follows: screw in the minimum value tap setting and adjust
Relay must not trip with 120 Vφ-φ Positive the spring such that the contacts will close as indi-
Sequency voltage only applied to terminals 14, cated by a neon lamp in the contact circuit when
15, and 16 must not trip when terminals 14 and energized with the required current. The pick up of
15 are reversed. the overcurrent unit with the tap screw in any other
tap should be within ±5% of tap value.
If trip is observed for either condition, proceed as
follows: If adjustment of pickup current in between tap set-
With balance 120V, 3 phase 60 Hz voltage tings is desired, insert the tap screw in the next low-
applied to terminals 14, 15 and 16 adjust core est tap setting and adjust the spring as described. It
until the contact arm just restrains. The core can should be noted that this adjustment results in a
be adjusted by the use of an insulated screw- slightly different time characteristic curve and bur-
driver in the slots at the bottom of the cylinder den.
13
41-133.2F Type IRQ Directional Overcurrent
Negative Sequence Relay
14
Type IRQ Directional Overcurrent 41-133.2F
Negative Sequence Relay
bringing the letter “T” into view. the play in the assembly is taken up, and where the
moving core just separates from the stationary core
b. Close the contacts of the CO and the directional
unit and pass sufficient dc current through the screw. Back off the core screw approximately one
trip circuit to close the contacts of the (ICS/T). turn and lock in place. This prevents the moving core
This value of current should not be greater than from striking and sticking to the stationary core
the particular (ICS/T) tap setting being used. The because of residual magnetism. Adjust the contact
operation indicator target should drop freely clearance for 3/64” by means of the two small nut(s)
bringing the letter “T” into view. on either side of the Micarta disc.
c. Close contacts of instantaneous overcurrent unit
The TR-1 unit does not require adjustments.
(I) and directional unit (D). Pass sufficient dc cur-
rent through the trip circuit to close contacts of
Connect lead (A) to proper terminal per Figure 14.
the (ICS/I). This value of current should not be
Block directional unit (D) contacts close and energize
greater than the particular (ICS/I) tap setting
trip circuit with rated voltage. Contacts of auxiliary
being used. The operation indicator target
switch (CS-1 or TR-1) should make as indicated by a
should drop freely bringing the letter “I” into view.
neon lamp in the contact circuit.
6.15. Auxiliary Switch (CS-1 or TR-1)
Adjust the stationary core of the CS-1 switch for a 7.0 RENEWAL PARTS
clearance between the stationary core and the mov-
ing core when the switch is picked up. This can be Repair work can be done most satisfactorily at the
done by turning the relay upside-down. Then screw factory. However, interchangeable parts can be fur-
the core screw up until the moving core starts rotat- nished to the customers who are equipped for doing
ing. Now back off the core screw until the moving repair work. When ordering parts, always give the
core stops rotating. This indicates the points when complete nameplate data.
Table 1:
TIME CURVE CALIBRATION DATA - 60 HERTZ
PERMANENT MAGNET ADJUSTMENT ELECTROMAGNET PLUGS
CURRENT CURRENT
TIME TIME OPERATING OPERATING
(MULTIPLES (MULTIPLES
OVERCURRENT UNIT DIAL TIME TIME
OF TAP OF TAP
TYPE POSITION SECONDS SECONDS
VALUE) VALUE)
IRQ-2 6 3 0.57 20 0.22
IRQ-5 6 2 37.80 10 14.30
IRQ-6 6 2 2.46 20 1.19
IRQ-7 6 2 4.27 20 1.11
IRQ-8 6 2 13.35 20 1.11
IRQ-9 6 2 8.87 20 0.65
IRQ-11 6 2 11.27 20 0.24
15
41-133.2F Type IRQ Directional Overcurrent
Negative Sequence Relay
Table II:
DIRECTIONAL UNIT CALIBRATION ‡
RELAYING RATING CURRENT AMPERES BOTH PUGS IN CONDITION ADJUSTMENT
Spurious Torque in Contact Closing Right (Front View) Plug Screwed Out
All Ranges 80
Direction (Left Front View) Until Spurious Torque is Reversed.
‡ Short circuit the voltage polarizing circuit at the relay terminals before making the above adjustment.
ENERGY REQUIREMENTS
IRQ-2 TIME OVERCURRENT UNITS
VOLT AMPERES **
ONE AT 20
SECOND AT AT 3 TIMES AT 10 TIMES TIMES TAP
AMPERE CONTINUOUS RAT- RATING * POWER FAC- TAP VALUE TAP VAlUE TAP VALUE VALUE
RANGE TAP ING (AMPERES) (AMPERES) TOR ANGL EØ CURRENT CURRENT CURRENT CURRENT
0.5 0.91 28 58 4.8 39.6 256 790
0.6 0.96 28 57 4.9 39.8 270 851
0.8 1.18 28 53 5.0 42.7 308 1024
0.5/2.5 1.0 1.37 28 50 5.3 45.4 348 1220
1.5 1.95 28 40 6.2 54.4 435 1740
2.0 2.24 28 36 7.2 65.4 580 2280
2.5 2.50 28 29 7.9 73.6 700 2850
2.0 3.1 110 59 5.04 38.7 262 800
2.5 4.0 110 55 5.13 39.8 280 920
3.0 4.4 110 51 5.37 42.8 312 1008
2/6 3.5 4.8 110 47 5.53 44.2 329 1129
4.0 5.2 110 45 5.72 46.0 360 1216
5.0 5.6 110 41 5.90 50.3 420 1500
6.0 6.0 110 37 6.54 54.9 474 1800
4.0 7.3 230 65 4.92 39.1 268 848
5.0 8.0 230 50 5.20 42.0 305 1020
6.0 8.8 230 47 5.34 44.1 330 1128
4/12 7.0 9.6 230 46 5.53 45.8 364 1260
8.0 10.4 230 43 5.86 49.9 400 1408
10.0 11.2 230 37 6.6 55.5 470 1720
12.0 12.0 230 34 7.00 62.3 528 2064
* Thermal capacities for short times other than one second may be calculate on the basis of time being inversely proportional to the square of the current.
Ø Degrees current lags voltage at tap value current.
** Voltages taken with Rectox type voltmeter.
16
Type IRQ Directional Overcurrent 41-133.2F
Negative Sequence Relay
ENERGY REQUIREMENTS
IR Q -5 , I R Q- 6, TI M E OV E R CU R RE N T UN I TS
ENERGY REQUIREMENTS
I RQ -7 , T IM E O V E RC U RR E N T UN I TS
VOLT AMPERES **
ONE
CONTINUOUS POWER AT 3 TIMES
AMPERE SECOND AT AT 10 TIMES AT 20 TIMES
TAP RATING FACTOR TAP 19
RANGE RATING * TAP VALUE TAP VALUE TAP VALUE
(AMPERES) ANGLE Ø
(AMPERES) CURRENT CURRENT CURRENT
CURRENT
E N E R GY RE Q UI R E M E N TS
I RQ -8 , I RQ -9 , T I M E O V E RCURR E N T UN IT S
VOLT AMPERES **
ONE
CONTINUOUS SECOND POWER AT AT 3 TIMES AT 10 TIMES AT 20 TIMES
AMPERE RATING RATING * FACTOR TAP VALUE TAP value TAP VALUE TAP VALUE
RANGE TAP (AMPERES) (AMPERES) ANGLE Ø CURRENT CURRENT CURRENT CURRENT
E N E R GY RE Q UI R E M E N TS
I RQ -1 1, TI M E OV E R CU R RE N T U NI TS
VOLT AMPERES **
ONE
CONTINUOUS SECOND POWER AT AT 3 TIMES AT 10 TIMES AT 20 TIMES
AMPERE RATING RATING * FACTOR TAP VALUE TAP VALUE TAP VALUE TAP VALUE
RANGE TAP (AMPERES) (AMPERES) ANGLE Ø CURRENT CURRENT CURRENT CURRENT
The current burden of the relay with positive sequence currents applied (no output current to the directional unit) is as follows:
The current burden of the relay with Zero sequence currents applied is as follows:
The voltage burden of the relay with positive sequence voltage applied (no output voltage to the directional unit) is as follows:
Burden values on three star connected potential transformers. Values at the star Voltage of 66.4 volts (115 volts delta):
A 115 0 26.8 90° Lag
Burden values on three delta connected potential transformers. Values at 115 volts:
CA 115 15.4 31.0 60°
19
41-133.2F Type IRQ Directional Overcurrent
Negative Sequence Relay
E NE RG Y RE Q UI RE M E NT S
INSTANTANEOUS OVERCURRENT UNIT OPERATING CURRENT CIRCUIT - 60 HERTZ
AMPERE VA AT TAP VA AT 5
TAP P.F. ANGLE Ø P.F. ANGEL Ø
RANGE VALUE †† AMPS ††
.5 .37 39 24 46
.75 .38 36 13 37
1 .39 35 8.5 34
.5-2
1.25 .41 34 6.0 32
1.5 .43 32 4.6 31
2 .45 30 2.9 28
1 .41 36 9.0 36
1.5 .44 32 5.0 32
2 .47 30 3.0 29
1-4
2.5 .50 28 2.1 27
3 .53 26 1.5 26
4 .59 24 0.93 24
2 1.1 49 6.5 48
3 1.2 43 3.3 42
4 1.3 38 2.1 37
2-8
5 1.4 35 1.4 35
6 1.5 33 1.1 33
8 1.8 29 0.7 29
4 1.5 51 2.4 51
6 1.7 45 1.2 45
8 1.8 40 0.7 40
4.16
9 1.9 38 0.6 38
12 2.2 34 0.37 34
16 2.5 30 0.24 31
10 1.7 28 0.43 28
15 2.4 21 0.27 21
20 3.1 16 0.20 17
10-40
24 3.6 15 0.15 15
30 4.2 12 0.11 13
40 4.9 11 0.08 12
20 6.6 31 0.40 31
30 9.3 24 0.25 24
40 12 20 0.18 20
20-80
48 13.5 18 0.14 18
60 15.9 16 0.10 16
80 19.2 15 0.07 15
.5-2 5 100
1-4 8 140
2-8 8 140
4-16 10 200
10-40 10 200
20-80 10 200
* Thermal capacities for short times other than one second may be calculate on the basis of time being inversely proportional to the square of the current.
Ø Degrees current lags voltage at tap value current.
** Voltages taken with Rectox type voltmeter.
20
Type IRQ Directional Overcurrent 41-133.2F
Negative Sequence Relay
Sub 3
418244
Figure 15.Typical Time Curve of the Time Overcurrent Unit of the Short Time (2) Relay
21
41-133.2F Type IRQ Directional Overcurrent
Negative Sequence Relay
Sub 2
418245
Figure 16.Typical Time Curve of the Time Overcurrent Unit of the Long Time (5) Relay
22
Type IRQ Directional Overcurrent 41-133.2F
Negative Sequence Relay
Sub 2
418246
Figure 17.Typical Time Curve of the Time Overcurrent Unit of the Definite Time (6) Relay
23
41-133.2F Type IRQ Directional Overcurrent
Negative Sequence Relay
Sub 2
418247
Figure 18.Typical Time Curve of the Time Overcurrent Unit of the Moderately Inverse (7) Relay
24
Type IRQ Directional Overcurrent 41-133.2F
Negative Sequence Relay
Sub 2
418248
Figure 19.Typical Time Curve of the Time Overcurrent Unit of the Inverse (8) Relay
25
41-133.2F Type IRQ Directional Overcurrent
Negative Sequence Relay
Sub 2
418249
Figure 20.Typical Time Curve of the Time Overcurrent Unit of the Very Inverse (9) Relay
26
Type IRQ Directional Overcurrent 41-133.2F
Negative Sequence Relay
Sub 2
288B655
Figure 21.Typical Time Curve of the Time Overcurrent Unit of the Extremely Inverse (11) Relay
27