Ce 531xx
Ce 531xx
CE-531XX
CE H05VV5-F(0.5∼2.5Ý) A05VV5-F(4∼95Ý)
UL AWM 2587(0.5∼6Ý)
CCC 227 IEC 75(RVVY)(0.5∼2.5Ý)
4
Features
Cable carrier Oil resistance
resistance 3 ■ Global-standard cables designed to CE&CCC (equal to or less
than 2.5Ý) &UL・cUL (equal to or less than 6Ý) & <PS>E (0.75-
2
4Ý) &GOST-R
1 ■ Oil resistance/Heat resistance (105℃)/Flextiblity, allowing use in
0 mobile cable connection
left/right
bending Noise ■ Fine conductor
resistance resistance
Application
45°left/right vibration ■ Internal/external cable connection to electrical equipment
resistance Twist resistance ■ Cable connection under oil environment
※The cable is subject to limitation of applicable sizes for each relevant standard. For
Technical Data details, refer to“Applicable Range”for each standard in [Technical Data] given below.
Electrical Characteristics
Nominal Cross-Sectional Number of Cores Allowable Current(A)
Item
Area(Ý)(AWG) 2∼31 2 3 4 5 6 7 8 10 12 15 21 25 31
0.5 (20) 39.0 10 9 8 7 7 7 7 6 6 5 5 5 4
0.75(19) 26.0 13 11 10 9 9 9 8 8 7 7 6 6 5
1 (18) 19.5 15 13 12 11 11 10 10 9 9 8 7 7 6
1.5 (16) 13.3 20 17 15 14 14 13 13 12 11 10 9 9 8
2.5 (14) 7.98 27 23 21 20 19 18 18 16 15 14 13 12 11
4 (12) 4.95 36 31 28 26 25 24
Conductor Resistance 6 (10) 3.30 47 40 36 34 32 31
(20℃)
Ω/Ü or below 10 1.91 67 57 51 48 45 43
16 1.21 89 76 68
●Allowable Current (A) for the cable is based on calculation under aerial one-cable installation at ambient temperature
25 0.780 118 101 91
of 30℃, not representing a guaranteed value.
35 0.554 145 123 111 Allowable current for the cable at ambient temperature above 30℃ is to be determined by multiplying the current
50 0.386 181 153 138 value by the appropriate current reduction factor specified in the following table for the ambient temperature.
●The Allowable current values are those calculated by JCS197, but not guaranteed.
70 0.272 225 191 172
95
0.5(20)∼1.5(16)
0.206
50
267 226 203 ( For details on Allowable current of the cable when used in Europe, refer to the applicable standard
− IEC60364-5 (Electrical installation of building − Part 5: Selection and erection of electrical
equipment − Section 523: Current-carrying capacities in wiring system).
)
JCS197… Japanese Electric Wire and Cable Makers’Association’
s Standard“Allowable Current for Cabtyre Cable”
Insulation Resistance 2.5(14)∼4(12) 40
(20℃) ■ Current Reduction Factor Table
MΩÜ or above 6(10)∼10 30
16∼95 20 Ambient Temperature(℃) 30 35 40 45 50 55 60 65
Current Reduction Factor 1.00 0.94 0.87 0.79 0.71 0.61 0.5 0.35
85
Core Identification
Core identification system
Identification by
2cores − Identified by numbering in white color on black insulator surface
Number
3cores or more − Identified by numbering in white color on black insulator surface + green/yellow
(for Standard)
●Green/yellow: Yellow straight lines on green (in green/yellow color ratio of 60/40)
Cable Construction
Item Configuration
Conductor Soft annealed stranded copper
Insulator Heat resistant PVC
CE-531XX
Conductor stranding Circular
Core wrapping tape Tape wrap around cores if their number and size are 5 or above and 6Ý or above, respectively
Sheath Oil resistant/heat resistant PVC (light gray)
KURAMO E162205-K AWM 2587 Ⅰ/Ⅱ A/B 90C 600V VW-1 FT1
VCTF <PS>E JET タイネツ 300V GOST-R LF
2
2.5 (98/0.18) 9.5 10.5 11.5 12.5 14.0 15.5 17.0 18.5 18.5 19.0 21.0 21.5 25.5 27.5 29.0
※ ※ ※ ※ ※ ※ ※ ※ ※
<14> 140 180 225 265 300 360 405 500 530 570 750 750 1000 1200 1450
4 (75/0.26) 11.0 11.5 13.0 14.5 16.0 17.5
※ ※ ※ ※
UL AWM
70 (19/23/0.45) ※ ※
2100 2700 3600 Upper: Standard cable outside diameter(Approx.Ù)
41.0 42.5 47.0 Lower: Approximate weight(è/Ü)
95 (19/31/0.45) ※ ※ ※
2500 3550 4650 ※ indicates specifications for custom order production.
GOST-R
86