ALL ELECTRICAL WORKS AND INSTALLATION HEREIN SHALL BE DONE


GENERAL NOTES: IN ACCORDANCE WITH THE PROVISION OF THE LATEST APPROVED
EDITION OF THE PHILIPPINE ELECTRICAL CODE, WITH THE RULES AND
1. ALL ELECTRICAL WORKS SHALL CONFORM TO THE LATEST EDITION REGULATIONS OF THE NATIONAL AND LOCAL AUTHORITIES CONCERNED
OF PHILIPPINE ELECTRICAL CODE, TO THE RULES AND REGULATIONS IN THE ENFORCEMENT OF ELECTRICAL LAWS AND ORDINANCES AND
OF LOCAL AND NATIONAL AUTHORITIES CONCERNED AND THE REQTS. WITH THE RULES AND REGULATION OF THE UTILITY COOPERATIVE
OF LOCAL UTILITY COMPANIES. CONCERNED.
2. WIRING METHODS SHALL BE AS FOLLOWS 15. POWER SEVICE TO THE BUILDING SHALL BE 230V, 1 PHASE, 3WIRE ,
60 HERTZ SYSTEM.
a. MAIN SERVICE ENTRANCE . . . . . . . . RIGID STEEL
b. RACEWAYS EMBEDED IN CONCRETE POLYVINYL 16. WIRING METHOD SHALL BE AS INDICATED IN THE SPECIFICATION.
WALL AND FLOORING . . . . . . . . CHLORIDE (PVC) 17. UNLESS OTHERWISE SPECIFIED IN THE PLAN, MINIMUM SIZE OF WIRES
c. RACEWAYS NOT EMBEDED IN ELECTRICAL METALLIC AND CONDUITS TO BE USED SHALL BE #3.5MM THWN AND 13MM
CONCRETE . . . . . . . . TUBING (EMT) NOMINAL DIAMETER RESPECTIVELY. WIRES SHALL BE INSULATED
3. SERVICE VOLTAGE ENTERING THE STRUCTURE SHALL BE 230 VOLTS FOR RATING SUITED FOR THE EQUIPMENT SERVED.
SINGLE PHASE TWO WIRE SYSTEM. 18. GENERAL USE RECEPTACLES SHALL BE RATED 10 AMPERES, 2
POLE, 250 VOLTS, GROUNDING TYPE WITH PARALLEL SLOTS,
4. MINIMUM SIZE OF WIRE AND OF CODUIT SHALL BE 2.0 mm SPECIAL PURPOSE IUTLET SHALL BE OF THE TYPE AND RATING
(#14 AWG) AND 15mm (1/ 2") NOMINAL DIAMETER RESPECTIVELY, SUITED FOR THE EQUIPMENT SERVED.
UNLESS OTHERWISE SPECIFIED ON PLANS. 19. ALL ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER
5. NO BRANCH CIRCUIT WIRING IN LIGHTING AND POWER SHALL HAVE APPURTENANCES FOR THE ENTIRE INSTALLATION SHALL BE OF THE
A LOAD MORE THAN 80 % OF IT'S RATING. APPROVED TYPE FOR BOTH LOCATION AND PURPOSE INTENDED.
20. ALL ELECTRICAL EQUIPMENT SHALL BE PROPERLY GROUNDED IN
ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE
ACCORDANCE WITH THE REQUIREMENT OF THE LATEST EDITION OF
APPROPRIATE FOR BOTH LOCATION AND INTENDED USE. THE PHILIPPINE ELECTRICAL CODE.
7. UNLESS OTHERWISE SPECIFIED PULLBOXES OR JUNCTION BOXES 21. ALL MATERIAL TO BE USED SHALL BE NEW AND OF THE APPROVED
TYPE FOR BOTH LOCATION AND PURPOSE INTENDED.
SHALL BE PROVIDED WHENEVER REQUIRED AND NECESSARY, 22. OUTLET BOXES SHALL BE FABRICATED FROM 1.5 mm THICK
ALTHOUGH SUCH BOXES ARE NOT INDICATED ON PLANS.
8. FOR EACH SPARE CKT. IN PANEL BOARD, PROVIDE AN EMPTY CONDUIT
20mm (3/ 4") DIAMETER TERMINATING TO A COVERED SQUARE BOX. A. LIGHT CONTROL SWITCHES 1.40M ABOVE FLOOR FINISH
9. ALL LOADS SHALL BE PROPERLY AND ADEQUATELY GROUNDED. B. CONVENIENCE OUTLETS 0.30 M ABOVE FLOOR FINISH
C. TABLE HEIGHT OUTLETS 0.15 M ABOVE COUNTER
10. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL BE BRAND NEW D. A.C.U. OUTLETS .50 M ABOVE FLOOR FINISH
AND OF APPROVED TYPE AS LOCATION AND PURPOSE.
E. ELECTRICAL RANGE OUTLETS 0.60 M ABOVE FLOOR FINISH
ALL INSTALLATIONS AND WIRINGS SHALL BE CONCEALED FROM VIEW F. CLOTHES DRIER OUTLETS 0.60 M ABOVE FLOOR FINISH
AND SHALL BE ENCASED IN POLYVINYL CHLORIDE (PVC) CONDUITS OR G. SPECIAL PURPOSE OUTLETS AS REQUIRED BY EQUIPMENT
ELECTRICAL METALLIC TUBING (EMT) OR RIGIDSTEEL CONDUITS (RSC). SERVED
H. KWHR. METER 1.90M ABOVE FLOOR FINISH
12. ALL JUNCTION BOXES, DISCONNECTS, ETC. SHALL BE INSTALLED I. PANEL BOARDS 1.40M ABOVE FLOOR FINISH
SO AS NOT TO INTERFERE WITH EQUIPMENT PLACEMENTS. @ CENTER UNLESS OTHERWISE
13. ALL 20-AMPERES CIRCUIT HOMERUN TO PANEL BOARD MORE REQUIRED BY FIELD CONDITIONS
THAN 30 METERS IN LENGTH SHALL BE 5.5mm
ULESS OTHERWISE SPECIFIED ON PLANS.