1.

MCCB Test:
1.1. Name Plate Details
Feeder Short circuit current Frequency Adjustable O/L
Make Type Nominal Current(A) Sl.No
Ref rating(kA) (Hz) Setting
Q2.14 TERASAKI H125 63 85 50 HZ - 23M12A
1.2. Test Procedure

➢ Before commencing of test, ensure that the all the safety measures complied.
➢ Ensure that MCCB is isolate from supply.
➢ Metering CT secondary terminal kept short.
➢ Do the tests set up.
➢ Switch On the current injection kit, Increase the Current gradually up to 2 times of set current of MCCB.
➢ Note down the Current and Operating time readings.
➢ Follow the above procedure for all other MCCB’s.
(1) Long time Inverse : Ir=x In (2). Short Circuit : Isd=x In ( 3). Instantaneous : *Ir (4). Earth Fault : Ig=%In

NOTE : Above Settings Not Applicable for this MCCB Except Instantaneous trip.

1.3. Thermal Release:

Injected current = 2*Set Expected time Operating time


Phase Set Current (A)
Current (A) (sec) measured at seconds
R 63 126 60-270 264.5
Y 63 126 60-270 215.76
B 63 126 60-270 232.93
Criteria: As per the Tripping Characteristics

1.4. Instantaneous Trip:

Set Trip Injected current = Expected time Operating time measured.


Phase
Setting (Ii) Set Current *Trip Setting*1.2 (sec) at milliseconds
R 12 950 Immediate 53
Y 12 950 Immediate 86
B 12 950 Immediate 60
Criteria: Immediate

MCCB Found Healthy : OK


Auxiliary Contact Fount Healthy : OK

1.5 Test Instruments Used:

S.No Description Make Equipment S.No Calibration date Calibration due date
1 CPC-100 OMICRON 02.07.2023 02.07.2024

2 CP-CB2(Booster) OMICRON 29.03.2023 29.03.2024

3 MULTIMETER FLUKE 115 13.02.2023 13.02.2024

L&T

Signature Signature

Name SIRAJ AB Name


Date 28.10.2023 Date 28.10.2023