Professional Documents
Culture Documents
BVH2412GB
BVH2412GB
Instruction Manual
BV-H2412 GB
PASS - Service you can rely on
Fast, comprehensive, anywhere in the world
Table of Contents
2 Safety notes................................
notes................................................................
................................................................................................
................................................................................................
..........................................................................
..........................................3
..........3
2.1 Signal Words .........................................................................................................................................4
2.1.1 Signal Words for Safety Warnings ................................................................................................4
2.1.2 Signal Words for Application Notes ..............................................................................................5
2.2 Five Safety Rules of Electrical Engineering ..........................................................................................6
2.3 Damaged / Defective Electrical Components ........................................................................................6
4 Operation................................................................
................................................................................................
................................................................................................
............................................................................
............................................13
4.1 Behavior after Connecting the Power ................................................................................................. 13
4.2 Operating and Control Access............................................................................................................ 13
4.2.1 Connecting an operating panel (VHM) with a scale controller (VCU) ........................................ 14
4.2.1.1 Connection via Ethernet Cable .................................................................................................. 14
4.2.1.2 Connection via Bluetooth ........................................................................................................... 14
4.2.1.3 Connection via RS485 ............................................................................................................... 15
4.2.2 Connecting EasyServe (PC) with the scales controller (VCU) .................................................. 15
4.2.2.1 Connection via Ethernet ............................................................................................................. 15
4.2.2.2 Connection via RS-232 .............................................................................................................. 16
4.2.2.3 Connection via WLAN ................................................................................................................ 16
4.2.2.4 Connection via Bluetooth ........................................................................................................... 16
4.2.3 Connecting the web browser with the scales controller (VCU) .................................................. 17
4.2.4 The web server in the scales controller (VCU) .......................................................................... 17
4.3 VHM operating panel .......................................................................................................................... 19
4.3.1 Display and Operation Fields ..................................................................................................... 20
4.3.1.1 Name of the Device .................................................................................................................... 20
4.3.1.2 Event messages ......................................................................................................................... 20
4.3.1.3 Selecting the operating range .................................................................................................... 20
4.3.1.4 On/Off Operation ........................................................................................................................ 21
4.3.1.5 Detail Selection .......................................................................................................................... 21
4.3.1.6 Measured Values and Graphics ................................................................................................. 21
4.3.1.7 Command and Edit Keys ........................................................................................................... 21
4.3.1.8 Symbol for Running Operation ................................................................................................... 21
4.3.2 Authorization for Control Commands ......................................................................................... 22
5 Commissioning ................................................................
................................................................................................
................................................................................................
...................................................................
...................................47
7 Parameters ................................................................
................................................................................................
................................................................................................
.........................................................................
.........................................55
7.1 Abbreviations ...................................................................................................................................... 56
7.2 Configuring the Interfaces .................................................................................................................. 56
7.3 Configuring Event Messages.............................................................................................................. 58
7.4 Parameter List .................................................................................................................................... 59
7.4.1 Parameter Overview .................................................................................................................. 59
7.4.2 Parameter Details ...................................................................................................................... 81
7.4.2.1 Parameter Block 01 - Hardware Modules .................................................................................. 81
7.4.2.2 Parameter Block 02 - Dialog Behaviour ..................................................................................... 84
7.4.2.3 Parameter Block 03 - Feeder Definition ..................................................................................... 89
7.4.2.4 Parameter Block 04 - Control Sources ...................................................................................... 92
7.4.2.5 Parameter Block 05 - Rated Data .............................................................................................. 95
7.4.2.6 Parameter Block 06 - Feeder control ......................................................................................... 97
7.4.2.7 Parameter Block 07 - Feeder Monitoring ................................................................................... 98
7.4.2.8 Parameter Block 08 - Filters..................................................................................................... 103
7.4.2.9 Parameter Block 09 - Limit Values ........................................................................................... 104
7.4.2.10 Parameter Block 10 - Calibration Data .................................................................................... 105
7.4.2.11 Parameter Block 11 - Rate controller ....................................................................................... 106
7.4.2.12 Parameter Block 12 - Analog Outputs ..................................................................................... 111
7.4.2.13 Parameter Block 13 - Digital Inputs ......................................................................................... 113
7.4.2.14 Parameter Block 14 - Digital Outputs ....................................................................................... 118
7.4.2.15 Parameter Block 15 - Batch Mode ........................................................................................... 120
7.4.2.16 Parameter Block 16 - Maintenance interval ............................................................................. 123
7.4.2.17 Parameter Block 17 - Communication EasyServe ................................................................... 124
7.4.2.18 Parameter Block 18 - Communication Fieldbus....................................................................... 125
7.4.2.19 Parameter Block 19 - Fixed mode configuration ...................................................................... 130
7.4.2.20 Parameter Block 20 - Ethernet ................................................................................................. 134
7.4.2.21 Parameter Block 21 - PLC Outputs .......................................................................................... 134
7.4.2.22 Parameter Block 22 - Bin Weigher ........................................................................................... 136
7.4.2.23 Parameter Block 23 - Bin Level Controller ............................................................................... 144
7.4.2.24 Parameter Block 24 - Second Bin Weigher ............................................................................. 152
7.4.2.25 Parameter Block 25 - Check System ....................................................................................... 158
7.4.2.26 Parameter Block 26 - Tube Control ......................................................................................... 170
7.4.2.27 Parameter Block 27 - Moisture................................................................................................. 172
7.4.2.28 Parameter Block 28 - Additional device ................................................................................... 176
7.4.2.29 Parameter Block 29 - Pressure Compensation........................................................................ 178
7.4.2.30 Parameter Block 30 - Dead Time ............................................................................................. 182
7.4.2.31 Parameter Block 31 - Process Temperature............................................................................ 184
7.4.2.32 Parameter Block 32 - Safety Functions ................................................................................... 187
7.4.2.33 Parameter Block 33 - Interlocking ............................................................................................ 193
7.4.2.34 Parameter Block 34 - FCB analog outputs .............................................................................. 196
9 Appendix ................................................................
................................................................................................
................................................................................................
..........................................................................
.......................................... 231
9.1 Setpoint and switch-on sources........................................................................................................ 231
9.2 Block diagram: measuring the flow rate ........................................................................................... 233
9.3 The flow rate regulation .................................................................................................................... 235
9.3.1 Constant controller ................................................................................................................... 235
9.3.2 Step controller .......................................................................................................................... 240
9.4 Batch Operation Control ................................................................................................................... 243
9.5 Bin weigher: Scaling and threshold value ........................................................................................ 245
9.6 Continuous bin fill level control ......................................................................................................... 246
9.7 Bin fill level regulation via feed gate ................................................................................................. 247
9.8 Details and flow chart control measurement (KME) ......................................................................... 250
9.9 Adjusting linearization ....................................................................................................................... 251
9.10 Correction with a known quantity...................................................................................................... 252
9.11 Controlling tube type check bins....................................................................................................... 253
9.12 Links in the Parameter Block 'Interlocking' ....................................................................................... 255
9.13 Using alternative signals (such as analog or fieldbus) for DMS inputs ............................................ 257
9.14 PLC Functionality (Optional)............................................................................................................. 258
9.14.1 Handling the Function Blocks................................................................................................... 259
9.14.2 Function Blocks for Binary Signals .......................................................................................... 260
9.14.3 Function Blocks for Analog Signals ......................................................................................... 261
9.15 Setting the Pressure Compensation ................................................................................................. 263
9.16 Safety Function for Feeding Hazardous Materials (Coal Dust) ........................................................ 265
9.17 Actuating Variable Safety Functions ................................................................................................ 266
9.18 Pulse Output for External Totalizing Counters ................................................................................. 267
9.19 Checking the Weight Measurement Instrumentation ....................................................................... 268
Index ................................................................
................................................................................................
................................................................................................
................................................................................
................................................ 269
The following software releases or later must be available to ensure that a DISOCONT Tersus sys-
tem will operate correctly with this software version:
▪
VHM 20170-007 → VHM operating panel
▪
VPC 20150-022 → Schenck Process EasyServe
▪
For the sake of simplicity, the DISOCONT Tersus system will also be called the weighing elec-
tronics, controller, scale or unit hereinafter.
– The BV-H2406 system manual contains information on its electronic structure.
– DISOCONT is a registered trademark of Schenck Process GmbH, Darmstadt.
▪
The Windows-based Schenck Process EasyServe program is a service tool for conveniently
handling continuous scales based on weighing electronics such as DISOCONT Tersus.
– For the sake of simplicity, this tool will also briefly be called EasyServe here.
– The BV-H2185 operating manual describes EasyServe's functionality.
2 Safety notes
To avoid personal injury and material damage, follow the safety regulations stated below.
Additionally you should also observe:
▪
Safety information given in order-specific documentation
▪
Safety information relating to mechanical components
▪
Instructions and safety instructions for parts manufactured by thrid-party suppliers or parts that are not
part of Schenck's scope of delivery.
When performing installation, commissioning and service work, observe all applicable local regulations.
Intended Use
The measuring system and connected mechanical components is intended solely for weighing tasks and
related control applications. It is not intended for any other use.
Risks
If properly installed and put into service the measuring system itself does not represent a hazard.
Hazards may arise when the system is used for control operations or for transporting weighed goods. Po-
tential sources of danger would then be add-on equipment that the material weighed is transported or me-
tered in. Residual risks may originate from the measuring system if unskilled operators improperly handle
the system.
This measuring system may be a component of a more complex system. The operating company is fully
responsible for overall plant safety.
Personnel
Preparation, assembly, commissioning, operation, maintenance and servicing may only be carried out by
qualified personnel.
All persons working on the system are required to observe the safety hints and know the parts of the tech-
nical documentation relevant to their work.
The operating company is responsible for instructing his operators to observe all regulations and instruc-
tions given.
Changing parameters
The parameters dictate how the measuring system functions. Only personnel familiar with the device's mode
of operation may alter these parameters (e.g. after training by Schenck Process). Parameters incorrectly set
may cause injuries or damage to the machine whenever a control system is connected. They can also ad-
versely affect weighing operation.
Password
Passwords safeguard the parameters against unauthorized alteration. The measuring system operating
company has to ensure safe password handling.
Design Modifications
Unauthorized modifications to the system and/or use of replacement parts not supplied by Schenck Process
voids Schenck Process's liability for any resulting damages. This especially applies to alterations which
could affect the operating safety of the system.
Replacing Components
Spare parts must meet the technical specifications indicated by Schenck Process. To ensure this require-
ment is met, only genuine Schenck Process spare parts should be used. When using other spare parts, the
warranty will be void.
In this manual the following signal words will indicate hazards that may arise when using this machine:
DANGER
This signal word indicates a danger that can immediately cause the
most severe injuries up to and including death.
Follow all instructions to prevent this from occurring.
WARNING
This signal word indicates a danger that can cause serious injuries up
to and including death.
Follow all instructions to prevent this from occurring.
CAUTION
This signal word indicates a danger that can cause slight or medium
injuries.
Follow all instructions to prevent this from occurring.
2.1.2 Signal
Signal Words for Application Notes
Signal words for information on material damages and on the optimal use of the machine
STRICTLY OBSERVE
Signal word used to identify situations in which material or environ-
mental damage could occur.
Follow all instructions to prevent this from occurring.
HINT
Signal word used to identify information on using the product eco-
nomically and at an optimal level of efficiency.
These fives safety rules must be followed in the order shown before work is begun on electrical systems.
Once the work is finished, they are to be applied in reverse order.
DANGER
Electric shock from live components.
There is a danger of life from an electric shock.
– Take all possible precautions to ensure safety before work is begun on
live components. Observe, among other things, the following:
1. Disconnect the components.
2. Secure them against inadvertent restart.
3. Ensure that the components have been de-energized.
4. Above 1 KV: earth and bypass the cables.
5. Cover or shield adjacent, live components.
DANGER
Live damaged or defective components
There is a danger of life from an electric shock.
– Always have qualified personnel ensure that the components are nei-
ther damaged nor defective.
1. Qualified personnel must immediately replace or, if possible, repair
damaged or defective electrical components.
3 General Diagram
The basic functions of the DISOCONT Tersus in combination with a feeder or measuring equipment will be
explained in this chapter.
3.1 What
What is the DISOCONT Tersus?
DISOCONT Tersus is a versatile modular electronic system for weighing and feeding technology.
Its components are:
▪
the VCU control unit ('scales controller')
▪
the VHM local operating panel
▪
Input/output expansion modules
The DISOCONT Tersus has been designed for continuous measurement and control tasks or for disconti-
nuous batching.
All weighing-related functions and process functions for measuring and feeding bulk solids are performed by
the DISOCONT Tersus system.
The DISOCONT Tersus is customizable and very flexible in terms of its physical layout and interconnection.
DISOCONT Tersus can be used in the following areas with specific software for weighing and feeding job
applications:
▪
Steel
▪
Cement production
▪
Chemical industry
▪
Foodstuffs industry
▪
Power plants
It supports the following plant systems in connection with the right mechanical equipment:
▪
Beltweighers
▪
Weighfeeders
▪
Loss-in-weight feeders
▪
Filling plants
▪
Feeders with a weighing discharge screw (MULTIFLEX)
▪
Mass flow rate measuring devices and mass flow rate feeders that operate on the basis of the Coriolis
® ®
principle (MULTICOR ) or the principle of inertia (MULTISTREAM )
The abbreviations for input and output channels for use in parameterization can be found in chapter Abbrev-
iations [➙ 56].
Y The analog output for the controller magnitude G The speed transmitter
The mass flowthrough unit consists of a measuring wheel rotating at a constant speed that is subdivided
into chambers by specially shaped guide blades.
The bulk solids are continuously conducted centrally from above onto the distributor cone of the measuring
wheel, spun outwards by the rotation and it then slides on the stator frame shell to the lower outlet opening.
The motor is mounted to rotate and transfers the torque it yields to the LC load cells through a lever. The
output tension of the load cells is proportional to the torque and is transformed into digital information with
an analog/digital converter.
The speed of the measuring wheel is recorded with the speed transmitter G and comes into the micropro-
cessor system through a frequency/digital converter. The frequency/digital and analog/digital converter are
components of the control system.
The measurement processing system calculates the quantity of material running through per unit of time
(meaning the momentary flow rate) from the torque and speed.
LC Load cell
The material moves outwards along the guide blades due to the centrifugal force Z and exercises a force C
on it that is known as the Coriolis force. That puts the motor under stress so that it has to give off greater
torque.
Ideally, each material particle impacts the measuring wheel with the mass m and an angular momentum of 0
and leaves it with an angular momentum L of
L=m*
ω * R2
where:
m = the mass of the particle
ω = the angular speed of the wheel
R = the exterior radius of the measuring wheel
The impact radius R0 and the friction between the material and guide blades have no impact.
The change in the angular momentum equals the time integral of torque. This means that
dm/dt equals the flow rate I in kg/s, from which it in turn follows that:
M=I* ω * R2
3.6 Batching
In batch mode a preset quantity of material is discharged and the feeding is subsequently switched off.
Once the batch setpoint has been reached the batch operation is complete. A subsequent start command to
the feeder will begin a new charge.
Batch filling can be carried out in all modes and variants of operation.
The general procedure for batch operation is shown in the following figure:
Fig. 3: Feeding
4 Operation
The DISOCONT Tersus and an attached weighfeeder can be operated in one of several ways:
▪
Operation under normal circumstances using one or more local VHM operating panels. The features of
the different panel versions can be found in system manual BV-H2406. The sides with the operating di-
alogs are also available via web interface for a browser .
▪
Operation using a higher-order plant control system where the control commands are either exchanged
conventionally by means of binary and analog signals or by means of a fieldbus such as PROFIBUS.
▪
Operation for service work by means of a wireless VHM operating panel.
▪
Operation for service work by EasyServe on a PC/notebook with a cable or wireless access.
▪
Local operation by means of an optional service operating level and the VLG or VMO operating units
specifically for work performed on the mechanism. The special characteristics of this operating panels
can be found in the system manual BV-H2406.
DANGER
Feeding can be started using the operating panel. This switches the
drives on, allowing bulk material to flow. Before turning it on, the op-
erator has to make sure that turning it on cannot cause any damage.
Interrupting communications when operating on a non-permanent line
(pluggable cable or radio) may cause dangerous situations. There-
fore, such methods of accessing control should be reserved for ser-
vice work only.
You have to select the Ethernet channel (Configuring the Communication Path (Com)) in the operating pan-
el configuration.
Once the first connection has been made, the operating panel searches in the network for VCU control units
and shows its findings on the Feeder operating page. A button belonging a scale that is displayed is used to
select the scale and establish the data connection.
The Bluetooth channel has to be selected (Configuring the Communication Path (Com)) in the configuration
of the operator panel.
Once the communication path has been selected, the console will search for Bluetooth adapters within
range. Other Bluetooth adapters can be found and displayed along with controllers (VCUs). The outcome is
shown on the Feeder [➙ 34] operating page.
Note: A complete search for Bluetooth adapters can take several seconds. A progress indicator is
displayed during the search. There will also be Bluetooth adapters shown to which no con-
nection can be established, either because they are not DISOCONT Tersus controllers or
they are already otherwise connected.
You can select the scale and establish a data connection by pressing the key belonging to the scale dis-
played. It may take several seconds before a connection is established. The respective status will be shown
in the header of the operating panel while a connection is being established.
Note: It can only establish a connection to one scale (assuming the scale is not simultaneously
connected to another Bluetooth adapter). It might be necessary to close the other connection
first. The operating panel will continue to attempt to establish a connection if another connec-
tion already exists.
If Bluetooth is used, the scales to whose Bluetooth adapter a connection has been established is the only
scales with which communication can be made. The Ethernet destination address may not be changed in
the VHM.
Note: The operating panel is the master on the bus. This is why only one operating panel may be
connected on the bus at any one time.
Note: Either use a non-coded socket of the VCU for this connection or a special (yellow) cable
when using the red-coded socket.
The EasyServe address must be in the same Ethernet subnetwork as the scales' address. It might be poss-
ible to adapt the address in the scanner dialog of EasyServe. A scales can also be addressed using a router
if the network has already been configured. The scale address is input manually and not via scanner dialog.
The PC must then have an IP address in the directly connected subnetwork.
The easiest way to select is with the EasyServe Connection | Ethernet (Scanner) item on the menu. This
shows all of the scales available in the network. The scales' connection parameters can be adjusted here
and a connection to the scales can be established.
If the scales are connected to a different subnet, they are selected manually using Connection|Ethernet
(Manual)' and entering the scale's IP address.
Note: A software update via RS232 interface can take as much as 20 minutes. Other functions run
slower than would be usual if the connection was made using Ethernet.
Establishing a connection:
The URL of the operator interface homepage must be entered into the browser address line. This URL is
composed of the following:
http://<address>/hmi/<display factor>.html
Example: http://192.168.240.1/hmi/start.html
NOTES:
▪
The user interface in the browser corresponds largely to the display on the VHM operating panel.
▪
The field used to select a different scales and the configuration dialogs for the VHM operating panel
itself are not available.
▪
Keyboard and mouse are used for operation so the entry keyboard is not shown on the screen.
Various data from the scales controller can be called up on the left-hand navigation bar.
Navigation entry Function
HMI Opens at a different size the same controller interface as is in the operating panel.
HMI_2x Also refer to: Connecting the web browser with the scales controller (VCU) [➙ 17]
HMI_3x
HMI_4x
Events Memory of the most recent events (such as alarms or warnings, etc.)
Parameter changes Memory of the most recent changes in parameters
Command log Logs a list of certain commands, e.g. start / stop
Totalizer hourly Table of hourly-saved totalizing integrators / counters. The values are also available
on the VHM operating panel.
The minute of saving the data is set after the full hour in P36.01.
Totalizer daily Table of daily-saved totalizing integrators / counters
The time of saving from 00:00 h is set in P36.02.
Totalizer Table of totalizing integrators / counters saved on the command
DataLogger 1 Table of the measured values recorded. The sampling interval can be set using
DataLogger 2 P36.03. The up to 10 process variables that can be recorded are selected using
P36.04 P36.13. It begins recording when activating in the Mode operating range.
Tab. 3 : Function calls on the scales controller homepage
Memory depth is approx. 1,000 entries. All entries are keyed in stating the entry time. The entries in the
tables are only up-dated when they are called up. The values can be exported into a PC file for analysis with
standard programs using select-copy-paste.
2 Field for event messages 6 Field for measured values and graphics
Notes:
▪
VHM VCU The operating panel works in the Configuration Mode as long as it is NOT in
communication with a scale. Then the [Feeder] buttons are offered in the ‘Se-
lect the Workspace’ (3) range for selecting a scale and [Con. Scale] for estab-
lishing the connection to the scale selected.
Also refer to the Operating and Control Access Chapter.
▪
The communication to a scale has to be interrupted for adjustments to the
display such as brightness and adjusting the touch-sensitive screen. You can
call up the adjustment dialogs for the operating panel with the [Sel. Scale] but-
ton.
Some functions are not available to non-privileged users. Beyond this, access to some func-
tions can be switched off per parameter.
WARNING
A start signal will actuate the motors!
There is a risk of injury to people standing within range of the motors. Bulk
material can be transported and may overwhelm downstream components.
The stop signal is not an emergency stop, but rather will stop the facility
normally.
Sources for operation under normal conditions can be set for entry at the scales operating panel during ser-
vice work. This mode is called keyboard mode. The VHM operating panel and the analog operating soft-
ware that can be started via a web browser from the scales control homepage are considered to be operat-
ing panels. In keyboard mode the service software tool 'EasyServe' can also be used to control the scales.
4.3.2.2 Restrictions for Operating Panel with Ethernet Connection and Connection Moni-
Moni-
toring
The system can be configured so that normal operation is accessible only to devices with IP addresses that
have been specified by parameters. The corresponding parameters can be found in the parameter group
'Dialog Behaviour' (P02.04 … P02.10).
Operation via 'EasyServe' is not affected by the parameter setting.
The connection to the operating devices with specified addresses can be monitored so that the scales can
be returned to a safe state in case of a malfunction.
'active' Command not restricted. The command may always be called up at the scales
operating panel.
'not active' This command is never allowed. The relevant key is not shown at the operating
panel making it impossible to execute the command.
'Password' This command is accessible only after logging on with password 1. Password 1
is variable and can be changed using P02.12.
This password is principally intended for service access. The basic system set-
tings are always made using this password.
'2nd Password' This command is accessible only after logging on with password 2. Password 2
is variable and can be changed using P02.13.
The parameters for defining access authorizations are in the group of Dialog Behaviour (P02.14 ... P02.23)
parameters. If the user has not registered with sufficient privileges for the desired function, the operating
button appears as non-active (grey) with a star in the lower right-hand corner.
The operating company is responsible for assuring that the passwords are known to those personnel only
who are to receive authorization for the respective control command. The control functions are released
once the user has logged on with the Login key and has entered the password. The Logout key should be
used to log off the privileged user from the system once work has been completed. The unit falls back by
itself into the non-privileged operating mode after the time set on the operating panel (refer to Setting the
Display [➙ 33]) .
However, the control commands can always be executed via EasyServe regardless of the
parameter setting.
Scales will be switched off. Flow rate measurement will cease after the time set in parameter P06.02 has
elapsed.
Display during stopped feed
OFF appears in the graphical display. Moving displays are turned off.
HINT
Limiting the entry
The setpoint is limited to the nominal flow rate in P03.03 in gravimetric op-
eration and to the threefold value of the nominal value in volumetric opera-
tion.
HINT
Limiting the entry
The setpoint is limited to the nominal flow rate in P03.03 in gravimetric op-
eration and to the threefold value of the nominal value in volumetric opera-
tion.
4.3.3.4
4.3.3.4 Resetting (zero setting) the totalizing counter
The DISOCONT Tersus has three totalizing counters that sum up the measured bulk material quantity.
Counters 1 and 2 can be reset. Counter 3 cannot be reset. The counters do not have any independent over-
flow.
How to reset a totalizing counter
Press the Totals button, then press the button for zero setting the desired counter and confirm the com-
mand.
HINT
Other ways to reset the counters
The system can be configured to allow the counters to be reset by means
of an electrical signal. All counters will still be able to be reset via the field-
bus interface by the main computer. All reset commands work
independently of one another.
4.3.3.5 Acknowledging
Acknowledging Event Messages
All of the important functions are monitored. An event message is generated if a malfunction occurs. This
will be displayed in the message field. The event with the highest priority will be displayed if several events
should occur.
The order of priorities is: Alarm (A), Warning 1 (W1), Warning 2 (W2).
HINT
Displaying earlier events
To display older events, open the 'Values' screen and select 'Event Log'.
Earlier events can be called up using the navigation keys in the event field.
The list of events can also be viewed via web server and can be exported
for an external evaluation.
DANGER
Event messages indicate unusual and/or dangerous states.
For reasons of safety, the causes of any malfunctions must be corrected
before an event message is acknowledged.
To acknowledge an event message press the 'Ack Event' key, available on many screens e.g. in 'HOME'.
Once acknowledged, any blinking messages will be displayed continuously. When the cause of the malfunc-
tion has been corrected the event will be cleared from the message line but can be displayed again using
'EreignisLog'.
A troubleshooting list can be found in section Event Messages.
4.3.4.1 Trend
The trend is a graphical depiction on the VHM operating panel of the course of process values over time.
HINT
It is easier with EasyServe
EasyServe allows you to adjust trend depictions much more comfortably
and to export measured data. The trend in the VHM is intended to offer
permanent and simple trend depiction.
The trend depiction, stored values from previous weighings and the configuration of the trend will be deleted
if the operating panel suffers a power failure or if it connects to a different scales.
Button Function
<< Open older values into the display window, large increments
< Open older values into the display window, small increments
> Open more recent values into the display window, small increments
>> Open more recent values into the display window, large increments
Settings Enter the configuration dialog (see below)
Z- Increase time period shown
Z+ Decrease time period shown
Tab. 5 : Control keys
The process values selected for display are shown in the left table (1). The first time it is called up the list
will be empty.
In order to configure the display of a value, click on the value in table 1 to select it. This will show the value's
reference number (ID), its thresholds and the color of the line. Touching fields (3) to (5) will open the corres-
ponding adjustment dialog box.
Button Function
Remove Delete the values selected in (1) and (2).
Back Close the configuration window and return to the trend display. Altered settings will not
be activated.
Update Activate the configuration shown for the trend depiction.
Add Open the dialog to select the value to be displayed.
Tab. 6 : Keys in the lines configuration
Click on a value in list (5) to select it. The properties of the trend line are transferred to the right-hand col-
umn, the reference number (ID) shown in field (4).
The value is transferred with the keys 'Add' or 'New' into list 1 of the values to be displayed.
You can not only see the current bin weight, but also the limits set per parameter. The parameters can be
adapted right on the screen if you register with sufficient privileges.
Parameters No. Meaning
Bin Level MAX P22.18 Upper threshold of the permissible fill level. Generates an event if exceeded.
Control Level MAX P22.13 Fill level at which the filling will be stopped.
Control Level MIN P22.12 Filling is started if the fill level falls below this threshold.
Bin Level MIN P22.15 Lower threshold of the permissible fill level. Generates an event if level falls
below this level.
Tab. 8 : Bin weigher parameters
Button Effect
Auto The filling is regulated automatically by means of the threshold values 'Control Level MIN'
and 'Control Level MAX' set.
Manual The filling of the hopper is controlled by the operator using the keys 'Start' and 'Stop'. For
reasons of safety filling is automatically stopped if the limit 'Control Level MAX' is ex-
ceeded.
Start Begin filling the hopper.
Stop End filling the hopper.
Tab. 9 : Operating keys for controlling hopper fill level
Refer to Adjustment Functions for information on adjusting the bin weigher.
NOTE: The following description applies to a visible and write unprotected parameter accessed by a user
with sufficient user privileges.
The parameter group is displayed and selected in the upper part of display area 6 (see VHM operating pan-
el [➙ 19]). Use the arrow keys to scroll through the groups. Individual parameters in a group can be se-
lected in the lower half of display area 6.
A parameter can be selected directly with the keyboard symbol.
The value of the parameter is shown in display area 7 (see VHM operating panel [➙ 19]) of the command
and edit keys.
The Edit button calls up the dialog for changing the selected parameters. The parameter's identifier will ap-
pear in the focus of the upper part of display area 6 and its current value in the lower part. Depending on the
type of parameter the arrow keys can be used either to assign a new value to the parameter or a value can
be entered for it. A changed value is written into the parameter via Store resident. An alternative is discard-
ing the change with the Exit or Back button. In the latter case the parameter value will remain unchanged.
Active parameter set Set controller behaviour Individual parameter values can be altered (see
Reading and Setting Parameters [➙ 30]).
Backup set Pre-prepared parameter set for By pressing 'Setup', right arrow and then 'Custom'
certain applications or settings you can begin a complete rewrite of the active para-
after commissioning meter set.
Factory settings Unalterable set of parameters for By pressing 'Setup', right arrow and then 'Factory'
the basic configuration you can begin a complete rewrite of the active para-
meter set.
Tab. 10 : Parameter sets: Usage and activation
WARNING
Irretrievable loss of adjusted parameters
Loading the backup parameter set or the factory settings will overwrite all of
the parameters in the active parameter set. The overwrite cannot be re-
versed. We recommend you to use EasyServe to save a copy of the cur-
rent parameter set to the PC drive before overwriting.
WARNING
Output signals are set in simulation mode. This allows externally
connected motors to start. The system will show that material is flow-
ing.
The starting motors may represent a hazard. The on signal can activate
systems upstream of the feeder whether the feeder is prepared to receive
the bulk material or not.
Button Function
Inactivity Inactivity timeout Length of time from the most recent activity until the bright- 20 min
timeout ness of the screen is automatically reduced. The screen will
return to normal brightness once the screen is touched. This
contact will not be interpreted as communication with the
scales.
Logout timeout Length of time from the most recent entry before a privileged 600 min
user is automatically logged out of the system security rea-
sons.
Working Display brightness during operation. At full brightness the display has a life expectancy of approximately
brightness 5 years. This expectancy can be increased to over 10 years by dimming the brightness a little.
Sleeping Brightness after a longer period with no activity.
brightness Note: If the display touchscreen is not to be used and the display is intended to be permanently fully
legible, the sleeping brightness can be set to the same level as the operating brightness.
Save Save the changes made. Changes are discarded without prompting if they were not saved beforehand.
Tab. 14 : Parameters for the display
URL of homepage Address of the scales' web server homepage. A web http://192.168.240.1/hmi/start.html
browser on a PC can open the scales' user interface
at this address.
Under normal circumstances the scales are selected
on the 'Feeder' page. The start address is entered
automatically.
Communication will be automatically established to
the last address entered here once power resumes
after a power failure.
Start timeout Length of time between command to connect to a 7s
scales and the start of connection. This period can
be used to access the operating panel configuration
[➙ 33].
Save Save the settings. The entries are discarded if they
are not saved before the page is left.
Tab. 16 : Setting startup routine
4.3.6.6 Configuring
Configuring the Communication Path (Com)
Select the medium of communication here. The key is accessible only to a user with privileged access
[➙ 36].
Ethernet Communication via Ethernet interface and The complete IP address of the x
the RJ45 plug. scales will be used when selected.
Bluetooth Communication via Bluetooth will be auto- All Bluetooth adapters within range
matically activated if a Bluetooth adapter is are listed in the 'Feeder' selection.
connected (wireless interface for portable Each scales must be equipped with its
devices). own adapter. Scales connected to
each other via Ethernet can commu-
nicate via Bluetooth only to the scales
to whose adapter the operating panel
has been connected.
A subordinate IP connection is estab-
lished in a separate subnetwork.
Therefore the IP subnetwork address
displayed in the VHM differs from the
scales' subnetwork address stored in
the parameter.
RS485 Communication via serial interface The last part of the scales' IP address
(1 ... 254) will be used when selected.
The IP address must therefore also
be set when using an interface of this
kind.
Tab. 17 : Alternatives
The select scales page will automatically open if the communication path is changed. The scales stores its
addresses in a parameter.
Details on possible alternative cablings of operating panel and scales are described in the system manual
BV-H2406.
In contrast to the zero setting program, the zero setting range is not monitored or limited with taring. The
tare program deletes the findings of the the zero setting program.
Condition The mass flow metering unit has to be turned off. This closes any material feeder.
Batching operation may not be active.
The measuring wheel has to be running.
To call up Call up the 'TW: Tare' calibration program
Program runtime The runtime is determined by P10.05
Display while running The remaining running time of the program in % of the value in P10.05
The tare measured in percent of the value in P05.06
Display when finished The tare deviation with reference to the previous tare of P10.02 in % of P10.02
Recently determined tare in percent of the rated load cell load (P05.06)
Parameters changed New value of tare in P10.02
when results are accepted The P10.03 parameters will be set to zero
Potential events and 'Stop !': Switch off feeding (feeder) (refer to the conditions)
messages 'Aborted !': One condition was not met during the measurement and the calibration pro-
gram was ended.
'Batch active': Reject batching for calibration (refer to the conditions)
'Measuring wheel ON': The measuring wheel has to be running since it has an impact on
tare.
Tab. 18 : The details and process of taring
4.4.2 Zero-
Zero-setting for the Coriolis flowthrough measurement
The '>0< Zero Set' program calibrates the zero point of flow rate measurement just like the 'TW: Tare' pro-
gram. However, the results is ascertained relative to the basic adjustment and cannot be accepted if the
deviation from the basic adjustment is greater than the limit adjusted in P10.04.
Condition The mass flow metering unit has to be turned off. This closes any material feeder.
Batching operation may not be active.
The measuring wheel has to be running.
To call up Call up the '>0< Zero Set' calibration program
Program runtime The runtime is determined by P10.05
Display while running '>0< active': remaining running time of the program in % of the value in P10.05
The deviation of tare from the basic adjustment in percent of the value in P05.06
Display when finished The tare deviation with reference to the previous tare of P10.02 in % of P10.02
Recently determined tare in percent of the rated load cell load (P05.06)
Parameters changed The new value of the tare correction in P10.03
when results are accepted
Potential events and 'Stop !': Switch off feeding (feeder) (refer to the conditions)
messages 'Aborted !': One condition was not met during the measurement and the calibration pro-
gram was ended.
'Batch active': Reject batching for calibration (refer to the conditions)
'Measuring wheel ON': The measuring wheel has to be running since it has an impact on
tare.
Tab. 19 : The details and process of zero setting
The second weight value is now taken and checked for plausibility.
Display when finished Set/Act shows the quotient from the change in mass entered in P22.25 and the measured
change in mass.
Parameters changed Enter in P22.24
when results are accepted P22.24new = P22.24old * 'Set/Act'
Condition The conveying element constant of the filling or emptying element entered into P23.06.
The dead time (transit time) from the conveying element to the bin into P23.07
To call up Select and start the BIN: Controller Optimization calibration program
Program runtime 10 s
NOTE: The calculated values of the parameters in P23.08 and P23.09 can be further adapted ma-
nually. The optimization program does not have any impact on the rest of the parameters of
the bin level controller (such as D portion, bypass and lift, etc.).
Display when finished Deviation in % with reference to the previous value of tare in P24.27
Tare in % of the rated load in P24.06
Parameters changed New value of tare in P24.27
when results are accepted
Potential events and 'Aborted !': The program was aborted. The parameters remain unchanged.
messages
Tab. 23 : The details and process of taring the 2nd bin weigher
The program can be used to identify shunt forces, i.e. links between the weighed and static components that
absorb forces that cannot be captured with the load cell.
The second weight value is now taken and checked for plausibility.
Display when finished Set/Act shows the quotient from the change in mass entered in P24.28 and the measured
change in mass
Parameters changed Enter in P24.26
when results are accepted P24.26 new = P24.26 old * Set/Act
Potential events and Aborted ! : The program was closed. The parameters remain unchanged.
messages
Tab. 24 : The details and process of checking the weight of the 2nd bin weigher
weight value). In the worst-case scenario, the total error ET (when determining the actual quantity) may be
calculated as:
|ET| = |E1| + |E2|
The relative error er (when determining the actual test mass Mr) can be estimated at:
er = |ET| / Mr
This error er should not be any more than 1/5 of the admissible error of continuous measurement. This
means that a minimum control quantity can be calculated if error ET is known. The random share of errors
E1 and E2 can be eliminated by carrying out the control several times while only partially correcting the fault.
The error of the continuous scale may contain constant shares, i.e. the tare error and errors dependant
upon the flow rate (the range errors). When correcting the continuous scale, the user has to decide what
type of error it is. It is necessary to distinguish the individual types of errors when operating at different flow
rates. Correct classification is less important if continuous measurement is carried out at approximately
equal flow rates. After all, it is not possible to give a general recommendation for classifying errors due to
the different bulk solids and local conditions.
DISOCONT Tersus is adapted to the technical design in a plant via P25.01 Type of Check System (select-
ing the control strategy).
You can find the parameters for adjusting the control measurement unit in the Check System block of para-
meters. There are further explanations on the process of control in the appendix [➙ 231].
Depending upon the design, the bin weight also takes in the weight of the mass flow meter and the mass
within the unit.
Normally, the bin weight no longer takes in the bulk solids on the transport distance.
The separate unit measures the bin weight and distributes the errors calculated over the continuous mea-
surements. The correction parameters of the continuous scales are correspondingly adjusted.
Preconditions:
▪
The P25.01 Type of Check System parameter have to be unequal to NO.
▪
The P25.09 Check Start Tare parameter has to be on OP to be able to start from the operating panel or
EasyServe.
Proceed to start tare correction from the VHM operating panel:
Call up the KME page starting from the main page (HOME).
Testing and additive correction of the zero point are called up with the Check Start Tare button and testing
and multiplicative correction of the measuring unit can be called up by Check Start Span.
After start, control goes through the phases shown in Details and flow chart control measurement (KME).
These phases are shown in the operating panel.
The following process quantities are displayed during the measurement until starting the next measurement:
The quantity shown Unit Description
Contin. Result Z kg The quantity of bulk solids ascertained by the continuous scale
Check Result F/Z - The quotient of the change of bin weight and the quantity ascertained by the
continuous scale
Relative Tare % The correction ascertained in tare with reference to rated load
Correction
Relative Span % The correction ascertained in calibration of span = the deviation in both mea-
Correction surements with reference to the measured value (even after completing the
control)
Check Belt Length m Only with belt-supported systems: the progress in the conveyor belt during
control
Check Meas. Time s Only with non-belt-supported systems: the duration of the measurement
Check Quantity kg Preselected quantity of bulk solids for the control (P25.12). The parameter
can be changed here directly with the privilege of changing parameters .
Check Circuits - Only with belt-supported systems: preselected belt progress for the control
(parameters)
BIN: Fill Weight kg or t Current bin weight
Note:
If P25.03 Auto Correction = YES, the continuous scale is automatically corrected if the results of control are
within the boundaries defined via P25.28 to P25.31.
If automatic correction was not selected or if the results of control are outside of the specified boundaries,
the Apply function can be used to correct the continuous scale. The Cancel function ends control without
changing continuous scale adjustment. The result is maintained to the next control.
If tare is corrected, the correction is carried out through P10.03 Tare Correction and the results of a zone
correction is calculated into P10.01 Range Correction. The correction is documented in the log files.
You can find more detailed information in the Types of control measurement [➙ 42] section and a flow chart
in the appendix.
5 Commissioning
This chapter describes commissioning the system consisting of the DISOCONT Tersus and the MULTICOR
loss-in-weight feeder.
The following sequence can be used to avoid making mistakes during commissioning.
Step Task
NOTE: If you have purchased components, please read the DISOCONT Tersus BV-H2406 system
manual where you will find information on the installation dimensions and architecture of
the DISOCONT Tersus system.
The rated load cell capacities of recording torque P05.06 LC Rated Capacity
Characteristic value of load cell sensitivity P05.05 LC Characteristic Value
Nominal feeder flow rate P03.03 Nominal Flow Rate
The nominal speed of the measuring wheel P05.03 Nominal Speed
The characteristic value of speed measurement P05.02 Pulses per Motorrevolution
The radius of the measuring wheel P05.08 Wheel Radius
The lever arm for recording torque P05.07 Lever Arm
Tab. 26 : Basic parameters
The adjustment depends on the type of conveyor element used and the matching output controller. We will
explain the basic procedure during commissioning using the example of a continually rotating feeder. The
procedure is identical for a feed gate continually controlled per the position setpoint with an external position
controller (mostly pneumatic). You can find the details in the relevant manuals of the external controller.
1 Set the flow rate regulation to volumetric operation (not synchronous volumetric) [➙ 28]
2 Select a value between 10 mA and 15 mA as a setpoint bypass P11.08 Bypass. We recommend leaving
the parameter value on factory settings.
3 Fill the bin with a sufficient quantity of bulk material. Bulk material is discharged during this calibration.
Ensure that the discharged material cannot cause malfunctions or damage in downstream processes.
4 Enter flow rate setpoint = zero [➙ 24]
Switch on feeding
5 Select the controller magnitude zero point in P11.04 and P11.06 so that the feeder just conveys no more
bulk solids.
6 Key in the flow rate setpoint between 20 % and 100 % of the nominal flow rate [➙ 24]
7 Adjust the external controller so that the measured flow rate just corresponds to the setpoint. Instructions
can be found in the manual of the external controller. If the appropriate adjustment cannot be made, there
might be reason to believe that the mechanical design of the feeder is not good.
If it is not possible to adjust the external parts, they can be adjusted with the bypass constant (P11.08).
Tab. 27 : Carrying out calibration
The control parameters in the factory settings already supply sufficiently good and stable control characte-
ristics at short running times from the feeder to the measuring point. Wherever necessary, the parameters
can be manually improved in the Rate controller block.
The new value P10.01new is calculated as follows from the prior value P10.01old from the MA counter pro-
gression of continuous measurement and the MW mass ascertained on the control scale:
P10.01new = P10.01old * MW / MA
For example:
Old value of P10.01 = 1
A material quantity of MW = 4.9 t is conveyed over a period of 15 minutes. The MA counter progression
read off the device is 5.0 t.
P10.01new = 1 * 4.9/5.0 = 0.98
The calculated value should be entered into P10.01.
The parameters for the bin's load cells should be keyed into P22.02, P22.03 and P22.04. The data apply
correspondingly if a second weighed bin is supposed to be adjusted.
The tare program [➙ 38] should be called up if the bin is empty. The fill level's display should vary by zero
after taking on the findings. As a check, it is advisable to get the bin vibrating for a brief period of time and
then check the measured weight value. The deviation from zero is a measure of the likely measuring error.
The bin weigher is now calibrated when using calibrated load cells.
▪
NOTES: If checking zero point stability has given rise to major errors, there are generally also
errors between the actual and displayed weight for bulk solids.
▪
The proportionality between the actual and displayed weight can be checked with the
calibration program CB: Weight Check and corrected [➙ 39].
▪
The rated value for the bin fill level should be set into P22.09 for theoretical considera-
tions, the data sheet or an optic check with a full bin.
▪
If the bin fill level is regulated by turning a prefeeder on and off, the P22.12 and P22.13
parameters should be adjusted for filling control.
▪
Regulation should be streamlined [➙ 39] after keying in the parameters if the fill level
is created with a prefeeder continually controlled in its flow performance.
Periodically, e.g. every 3 months Turn off bulk solids conveying and Most errors in the measuring unit can
tare [➙ 37] the measuring unit. be identified in changes in tare.
A substantial change in tare indicates
changed air currents or friction in the
measuring unit. It might make sense
to check the equipment for unaccept-
able foreign particles and material
build-up of bulk solids in the instru-
ment room.
If available: check the bin weight ac- The bin should be set vibrating for a
quisition. brief period of time. The weight values
shown before and after these vibra-
tions provide a measure for shunt
forces. This can also be checked with
an empty bin. The results of taring
[➙ 50] provide a measure of the bulk
solids remaining in the bin when emp-
tying.
Change in bulk material Adjust the external output controller You may need to adjust the rated
[➙ 48] output and possibly the fill limits for a
bin.
Periodically as per the operating in- Do the maintenance work listed in the The interval may depend on the bulk
structions of the mechanical measur- manual. solids.
ing equipment and other mechanical
parts of the unit
Tab. 28 : Suggested actions
7 Parameters
The DISOCONT Tersus is adapted to each application via parameters. No special programing knowledge is
therefore necessary.
default settings Complete parameter set Copy into the active para- Cannot be changed
Non-alterable basic set- meter set using EasyServe,
ting the software the VHM oper-
ating console [➙ 31] or a
web server
Backup set Complete parameter set Copy into the active para- Only using EasyServe in
Pre-setting for a group of meter set using EasyServe, expert mode
applications or a setting the software the VHM oper-
stored during commis- ating console [➙ 31] or a
sioning web server
Tab. 29 : Using parameter sets in the DISOCONT Tersus
Note: parameters not required for an application can be faded out or declared 'read only' using EasyServe
in expert mode. EasyServe compiles a list of visible parameters that form an integral part of the system do-
cumentation. They, together with this manual, make up the relevant documentation of the control system for
an application. The parameter list in the operating manual contains all of the parameters, regardless of their
actual use in an application.
In addition to the parameter set stored in the scales, we recommend that after commissioning you keep a
copy of the parameter set in a mass storage medium using EasyServe.
The parameters are arranged into blocks to for clarity. A parameter is uniquely identified by its block and
number within that block in the respective scales software version:
P01.03: block of parameters 1 → Parameter 3
Note: Each parameter also has a unique number (ID) with which it can be addressed over the serial inter-
face. This number can be seen as a tooltip in EasyServe when passing over the parameter and can be out-
put in the parameter printout.
Gaps can appear between block numbers and parameters within the blocks.
In rare cases, the number of a parameter may change.
Note: The procedure for resetting with the VHM operating panel all parameters to their factory defaults is
described here: Reset to Factory Settings [➙ 31]. The procedure can also be called up using EasyServe.
7.1 Abbreviations
Source Description
FB Fieldbus
OP Operating panel
DI Digital Input
DO Digital Output
AI Analog Inputs
AO Analog Outputs
LS Logical signal for using internally available signals
Event Event. The reaction to the occurrence of an event can be configured.
W1 Warning 1 (requires acknowledgement)
W2 Warning 2 (does not require acknowledgement)
ALARM Alarm (requires acknowledgement)
IGNORE Ignore: do not show any event message, but switch the corresponding contact outputs
LC Load Cell
I Flow rate
v Belt velocity
VCU VCU 20100 system unit of DISOCONT Tersus. Refer to the BV-H2406 manual for details.
VHM DISOCONT Tersus operating panel. Refer to the BV-H2406 manual for details.
VMO The machine operating console for service work. Refer to the BV-H2488 manual for details.
Tab. 30 : Abbreviations frequently used in parameters
Step Task
The source parameter defines whether a more precise signal path setting is also necessary. The linking
parameters only offer technically meaningful interfaces.
Source Unit Channel Level Purpose
n/a The internal signal is not assigned to any interface. Input signals adopt automatically a
state that does not interfere with the
program flow.
FB Fieldbus, no additional details required Controlled by signals or fieldbus
OP VHM operating panel, no additional details required Controlled by operating panel entries
v Speed, no additional details required Link with an internal signal
Tab. 32 : Signal sources and their descriptions
Low Voltage = 0 V across the Current at the input > 3 mA High resistance, relay contact open
input terminals (sensor not covered)
High Voltage > 18 VDC across Current at the input < 1 mA Low resistance, relay contact closed
the input terminals (sensor covered)
Tab. 34 : The meaning of the Level parameter segment for an internal True signal
The DI: External Event 1 signal is connected at input DI1 of VCU1. If the input is open (low), this is inter-
preted as logically True (or 1).
NOTE: An external binary output channel is set that may have been assigned to the event regard-
less of the event class.
A recently pending alarm- or warning 1-class event will be shown on the operating panel blinking and in
color. The blinking stops when acknowledged. Acknowledged event messages are cleared from the display
for currently pending events when the event is no longer pending. Each event is stored with a time-stamp in
the internal memory [➙ 29] for later analysis.
01 - Hardware Modules
Number: Name Default Customer Sys ID
P01.01 [➙ 81] Analog Channel A10 NO 5746
02 - Dialog Behaviour
Number: Name Default Customer Sys ID
P02.01 [➙ 84] Language * DEUTSCH 4224
03 - Feeder Definition
Number: Name Default Customer Sys ID
P03.01 [➙ 89] Control YES 4590
04 - Control Sources
Number: Name Default Customer Sys ID
P04.01 [➙ 92] Feeder Start * FB 4241
05 - Rated Data
Number: Name Default Customer Sys ID
P05.01 [➙ 95] Speed Measurement DI 4952
06 - Feeder control
Number: Name Default Customer Sys ID
P06.01 [➙ 97] Volumetric Start-Up 0s 4272
07 - Feeder Monitoring
Number: Name Default Customer Sys ID
P07.01 [➙ 98] Event: Stand-By W2 4289
08 - Filters
Number: Name Default Customer Sys ID
P08.01 [➙ 103] LC Filter 0.25 s 4334
09 - Limit Values
Number: Name Default Customer Sys ID
P09.01 [➙ 104] Limit: Actual Flow Rate MIN 5 % Io 4337
10 - Calibration Data
Number: Name Default Customer Sys ID
P10.01 [➙ 105] Range Correction 1 4352
11 - Rate controller
Number: Name Default Customer Sys ID
P11.01 [➙ 106] Controller Type Continuous 4701
12 - Analog Outputs
Number: Name Default Customer Sys ID
P12.01 [➙ 111] AO: Setpoint n/a 4385
13 - Digital Inputs
Number: Name Default Customer Sys ID
P13.01 [➙ 113] Event: External Event 1 * A 4417
14 - Digital Outputs
Number: Name Default Customer Sys ID
P14.01 [➙ 118] DO: Wheel Start DO 4447
15 - Batch Mode
Number: Name Default Customer Sys ID
P15.01 [➙ 120] Batch Mode NO 4448
16 - Maintenance interval
Number: Name Default Customer Sys ID
P16.01 [➙ 123] Maintenance Electric 3000 h 4465
17 - Communication EasyServe
Number: Name Default Customer Sys ID
P17.01 [➙ 124] Own Address 1 4520
18 - Communication Fieldbus
Number: Name Default Customer Sys ID
P18.01 [➙ 125] Protocol Type NO 4528
20 - Ethernet
Number: Name Default Customer Sys ID
P20.01 [➙ 134] IP Address 192.168.240.1 6235
21 - PLC Outputs
Number: Name Default Customer Sys ID
P21.01 [➙ 134] DO: PLC 1 n/a 4662
22 - Bin Weigher
Number: Name Default Customer Sys ID
P22.01 [➙ 136] Bin Weigher Active NO 4704
25 - Check System
Number: Name Default Customer Sys ID
P25.01 [➙ 158] Type of Check System NO 4861
26 - Tube Control
Number: Name Default Customer Sys ID
P26.01 [➙ 170] DI: CO-Alarm Hopper n/a 5607
27 - Moisture
Number: Name Default Customer Sys ID
P27.01 [➙ 172] Moisture Active NO 5386
28 - Additional device
Number: Name Default Customer Sys ID
P28.01 [➙ 176] Auto Zero Active NO 4675
29 - Pressure Compensation
Number: Name Default Customer Sys ID
P29.01 [➙ 178] Compensation Active NO 5479
30 - Dead Time
Number: Name Default Customer Sys ID
P30.01 [➙ 182] Dead Time Active NO 5403
31 - Process Temperature
Number: Name Default Customer Sys ID
P31.01 [➙ 184] Temperature Active NO 5512
32 - Safety Functions
Number: Name Default Customer Sys ID
P32.01 [➙ 187] Safety activation: Option code n/a 7091
33 - Interlocking
Number: Name Default Customer Sys ID
P33.01 [➙ 193] DI: Event Mechanics 1 n/a 4760
36 - Data Logging
Number: Name Default Customer Sys ID
P36.01 [➙ 202] Hourly Total Time 0 min 5743
38 - Linearization
Number: Name Default Customer Sys ID
P38.01 [➙ 206] Linearization ON NO 4577
39 - Flow Gate
Number: Name Default Customer Sys ID
P39.01 [➙ 207] S: DO Open Flow Gate n/a 4702
7.4.2.1
7.4.2.1 Parameter Block 01 - Hardware Modules
A DISOCONT Tersus system can comprise up to a maximum of 3 VCU control units, several VHM (OP)
operating panels and up to 2 motor controllers (VMO). A PC running the EasyServe program can be con-
nected for service purposes.
With the exception of EasyServe and the operating elements (VHM, OP) all of the units involved must be
signed on with the parameters in group P01.xx. Units that are not signed on cannot be used and their inputs
and outputs will not be made available by either EasyServe or the operating elements.
Furthermore, up to 2 analog input or output components (VAI or VAO) can be installed.
Caution:
For reasons of safety, it is imperative that the relevant communication error messages should register an
alarm (A) when originating from units that are actively involved in the control loop.
This event is identified when communication with the VCU input/output expansion with VIO
software and local bus address 2 is disrupted. The cables and the address setting should
be checked if an error occurs.
This event is identified when communication with the VCU input/output expansion with VIO
software and local bus address 3 is disrupted. The cables and the address setting should
be checked if an error occurs.
This event is identified when communication with the first local operating terminal VMO
201xx with local bus address 11 is disrupted. Check the cables and the address setting if
an error occurs.
This event is identified when communication with the second local operating terminal VMO
201xx with local bus address 12 is disrupted. Check the cables and the address setting if
an error occurs.
Letters and characters can be used. The name appears in the upper row of the operating
console and when searching through networks for controllers.
Remark: The characters ";" and "=" are not accepted. During the saving procedure these
characters will automatically be deleted.
Address of the first operating panel from which control commands should be given.
The value 127.0.0.1 must be entered into at least one parameter of P02.05, P02.07 or
P02.09 if a VHM is used for controlling via RS485.
Address of the second operating panel from which control commands are to be given.
The value 127.0.0.1 must be entered into at least one parameter of P02.05, P02.07 or
P02.09 if a VHM is used for controlling via RS485.
The address of the third operating element that control commands are supposed to be giv-
en from.
The value 127.0.0.1 must be entered into at least one parameter of P02.05, P02.07 or
P02.09 if a VHM is used for controlling via RS485.
This event is detected when the connection via the serial RS485 interface to a VHM operat-
ing panel is interrupted.
Steps:
- check cable connection
- check that operating console is correctly functioning
- check the operating console settings
- check the addresses of the scales at the RS485 data bus (P01.11 VHM RS485 Address)
YES: The measuring wheel is not switched off when measuring or feeding is switched off.
X hour(s): The measuring wheel is switched off X hours after switching off measuring or
feeding to reduce wear and tear and use of energy due to unnecessary constant operation.
If the impulse duration is shorter than 10 ms the impulse output is disabled. All impulses not
issued yet are cleared.
The digital input is flank-controlled, i.e., the ON signal must be removed and then reapplied
if the scale becomes inoperative because of something like an alarm.
The range and offset parameters take effect only if P04.02 Feedrate Setpoint has been set
to AI.
This parameter takes effect only if P04.02 Feedrate Setpoint has been set to AI.
No release signal from the source determined by P04.05 Source Run Enable.
If this event is pending then the downstream transport equipment is most likely not switched
on.
If the setpoint is given as per P04.02 by the operating console (P04.02 = OP) or the scales
are in keyboard mode P04.07 will have no effect, i.e. the setpoint entered at the operating
console works as entered.
Dependant upon P04.13 Difference Function, further signal processing uses the difference
from the actually measured flow rate and the already known flow rate, meaning the still
unknown flow rate. Therefore, the totalizing counters only add together the additional quan-
tity of bulk solids. The flow rate regulator might receive the additional quantity of bulk solids
as the actual input quantity so that it can be controlled through the prefeeder.
Current at the analog input for 100 % entry of the nominal flow rate in P03.03 Nominal Flow
Rate
The number of impulses of the optional tachometer (refer to P05.01 Speed Measurement)
per revolution of the drive motor of the measuring wheel.
MAC address of the Bluetooth transmitter in the rotating part of force recording.
Its address can be ascertained with a Bluetooth scanner in the PC.
The event is identified when Bluetooth communication to the rotating component of the
meter has been interrupted.
Possible causes:
- major malfunctions in the surroundings
- the loss of the voltage supply of the rotating Bluetooth transmitter
Actions:
- a brief voltage interruption of VCU and the rotating Bluetooth transmitter for initialization
- check the availability of the rotating Bluetooth transmitter with a scanner in the PC
The event defined by P06.04 Event: T_Volum. is identified once this time expires.
This event is identified if the filling time exceeds the threshold value in P06.03
T_Volumetric.
Possible cause:
- storage bin is empty
- storage bin has a blockage
- the filling gate is malfunctioning or is blocked
Scales are in standby operation, i.e. the controller magnitude to the feed drive is smaller
than the threshold value set in P07.02 Stand-By Limit Value. The feeder drive is switched
off. The 'running' state will still be displayed.
This function protects the motor from overheating at very low speeds or when idling.
Actions:
Key in the larger setpoint and check P07.02 Stand-By Limit Value.
The signals at the feeder drive's impulse speedometer input are outside of the specified
range.
Possible causes:
- there is a fault in the speed impulse sensor cable (check the shielding and the wiring)
- the sensor has been incorrectly calibrated
The load cell cable is improperly connected, not connected or has been interrupted. The
load cell may be faulty.
Measures:
- check the cabling and the load cell
- check the load cell
Note:
The power supply must be switched off and on again if the scales cannot be switched on
even after the error has been rectified.
The load acting on the load cell is greater than 110 % of the sum of the nominal loads of
the load cells.
Possible causes:
- Shunt forces or compression ratios bring about incorrect load cell loading
- incorrect cabling
- faulty load cell
The scales will not switch on automatically, regardless of the event class. The event must
first be acknowledged and the command to start given again before the scales will restart.
Simultaneously P07.08 Time Deviation functions as a time constant for the filter that con-
tains the value of the control deviation. A 'control deviation' event is also identified if the
filtered result exceeds the threshold value P07.11 Deviation abs. max..
Maximum Deviation exceeded. The actual feed rate has deviated to far from the setpoint
over too long a period of time.
Possible causes:
- material has been incorrectly handled:
- the bulk material is flowing irregularly or cannot be discharged satisfactorily
- arching in the feed hopper
- there is a backup on the discharge side
- a large quantity of material continues to trickle from the feeder
- calibration error: during initial calibration the regulator was set at such a critical value that
minor changes in the overall properties of the system lead to unreliable operation.
Also refer to: P07.11 Deviation abs. max., P07.10 Factor Deviation, P07.09 Threshold Dev-
iation, P07.08 Time Deviation
The Controller Magnitude of the feed rate regulator has reached the upper response thre-
shold. After a time message HI05 (P07.12) will be output.
1. No material is flowing or material flow is irregular.
2. The external output regulator has been incorrectly set.
Step to take: check the material discharge and the Controller Magnitude (service value Y).
At Nominal Flow Rate Y should be between about 10...14 mA.
The program and parameters memory are checked cyclically. An error has occurred during
that. The scales will no longer function correctly.
Steps to take:
- load the factory settings
- Normally the hardware has to be replaced.
One of the analog inputs has a smaller signal than the zero-point offset that was set.
A tolerance of 0.4 mA has been set to avoid constant setting and clearing of the input sig-
nal, in case this input signal should happen to be unsettled.
Note: filtering the load cell signal also effects the regulating action.
Events that can only occur with regular feed operation are only monitored 10 s after beginning feed opera-
tion.
The actual feed rate is lower than the minimum value P09.01 Limit: Actual Flow Rate MIN.
Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equipment
- feed rate setpoint too low
Actual feed rate higher than the maximum value set in P09.03 Limit: Actual Flow Rate MAX
Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equipment
- feed rate setpoint too large
This event is identified when the force on the measuring wheel exceeds the upper threshold
value.
Possible causes:
- bulk solids blocked in the area of the measuring wheel
- measuring wheel covered
Steps to be taken:
Open the MULTICOR equipment and check the measuring wheel for friction
The speed of the measuring wheel has dropped below the lower threshold value. Measur-
ing the flow rate is afflicted with major defects. The free flow of bulk solids through the unit
is obstructed.
Possible causes:
- the measuring drive is blocked by bulk solids or foreign particles
- there is a defect in the motor of the measuring drive
Actions:
- open the equipment and check the measuring wheel for friction
- check the drive train, motor and motor's drive
Continuous: A continuous controller magnitude is issued to the controller for the prefeeder.
This setting should be used for continually rotating prefeeders and position-controlled pre-
feeders with built-in position regulation.
Also refer to: P12.16 AO: Motor Speed Control
Stepping: Control commands are issued for a feed gate that is position-controlled by the
VCU.
Also refer to: P39.01 S: DO Open Flow Gate to P39.12 Position MAX Flow Gate
If transfer is made with currents of between 4 ... 20 mA, the parameter must be set to 4 mA
at least. P11.06 Controller Magnitude Offset must be set to a value equal to or greater than
P11.04 Lower Limit.
This limit depends on the size of the setpoint with inputs less than 20 mA.
Generally the same values are chosen for P11.06 Controller Magnitude Offset as for
P11.04 Lower Limit.
Optimization:
- fill the feeder hopper with bulk material
- calculate the actuating variable Y1, the value at which the discharge unit begins to work
- calculate the actuating variable Y2, the value at which reduction of the feed is suspended.
For feeders that are operated with flow rate setpoints of 0:
P11.06 Controller Magnitude Offset = Y2
All other feeders:
P11.06 Controller Magnitude Offset = Y1
Note: P11.06 Controller Magnitude Offset must be equal to or greater than P11.04 Lower
Limit.
0: the actuating variable is set to 0 when the scales are switched off.
Lower limit: the actuating variable is set to the lower limit.
NO : do not save
YES : save
YES-A : only save if the scale has not broken down due to an alarm.
Also refer to: P12.05 Flow Rate Offset, P12.06 Flow Rate Range
Possible cause: depends on the external cabling. Usually: an error in the main drive
The input is also linked to the internal interference logic (block: interlocking).
The input is also linked to the internal interference logic (block: interlocking).
The input is also linked to the internal interference logic (block: interlocking).
The input is also linked to the internal interference logic (block: interlocking).
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Caution: the level is static and may not be on permanently (otherwise continuous acknowl-
edgement).
(The DISOCONT Tersus is operated using the operating console VHM or EasyServe).
Interim values result in filtered adjustment; this should be used in particular for systems with
poor reproducibility.
The result of the event is stored in P15.04 Correction Amount.
The printout can be made only after a batch has ended automatically or manually. The
printout is stored to a file that can be read using the Web-Server.
The batch setpoint resulting for an input flow corresponding to the parameter P15.12 Batch
Setpoint Range.
For example:
P15.11 = 1000 kg
P15.12 = 20 mA
P15.13 = -20 mA
0 ... 20 mA then correspond to 500 ... 1000 kg
Possible causes:
- highly erratic material flow
- altered feeder discharge behavior
- error in weight calculation due to disturbance forces
Erroneously entered batch setpoint. The value entered is reduced to the permissible upper
limit in P15.16 Batch Setpoint Limit.
Possible causes:
- incorrect entry
- incorrect upper threshold
The sum of the times during which the mains voltage is on is greater than the time P16.01
Maintenance Electric.
A message occurs after each expired time interval. The message may indicate service work
required.
The sum of the runtimes of the conveying elements is greater than the time P16.03 Main-
tenance Feeder Run.
A message occurs after each expired time interval. The message may indicate service work
required.
All devices connected to the communicatio bus must have disjunct addresses.
Data transfer speed. This parameter is used for information only. The speed cannot be
changed.
Formats the serial data. The value is used for information only and cannot be altered.
DISOCONT Tersus: Further details on card installation can be found in the system manual
BV-H2406. Manual 'Data Communication' (BV-H2448) contains further information on the
data structures.
INTECONT Tersus: Manual 'Data Communication' (BV-H2474) contains further information
on the data structures.
NO: Modbus-TCP can be used to read but write-accesses will not be processed.
Modbus-RTU: RS232, RS422 or RS485 interface; fieldbus interface card VSS 28020 must
be installed.
Modbus-TCP: Complete communication (read/write) using Ethernet and the main VCU
RJ45 plug.
Ethernet/IP: Communication via Ethernet and the RJ45 plug on the main VCU.
The red-coded RJ45 socket X96 may not be used for communication with the host comput-
er.
A telegram from the host system will be expected within the time set if the timeout value in
P18.02 is greater than zero.
Cyclical serial communication with the higher-order plant control system has been inter-
rupted for longer than the timeout-period in P18.02.
The contents of the data have to be set on the scale and opposite point in a way that is
compatible to one another!
N = No parity
O = Odd parity
E = Even parity
The number of freely selectable measuring and status values (scales→ master) that are
queried in a telegram.
NO: No restrictions
FIRST WRITE: The subscriber that transmits the first write access gets the control rights.
The other subscribers may read only.
REMOTE IP: Control commands from the subscriber with the IP address given in P18.23
Remote IP Address FB only will be carried out.
For the available data and their Ids see the separated communication manual:
Selecting the first control command with ID 320 (decimal) in the Fieldbus telegram. It can-
not be changed in this parameter.
The following values in the telegram can be configured as per the ID list in the 'data com-
munication' manual:
DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468
Selecting the first value to be read from weighing electronics in the fieldbus telegram. The
number of the value (ID) can be found in the Data Communication manual:
DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468
IP address of the weighing electronics. If the control system is integrated into an Ethernet
network, the address must be chosen in agreement with the network administrator. In iso-
lated networks we recommend the factory setting 192.168.240.x. "x" allows for selection of
the system on the bus.
The DISOCONT Tersus allows physical output signals to be controlled directly by the control system com-
puter via fieldbus. The parameters of this group assign physical channels to the fieldbus commands.
Please also refer to: status of fieldbus protocol commands in manual 'DISOCONT Tersus Data Communica-
tion' (BV-H2448).
If FB or AI are selected the external value will be converted to a value with mV/V units that
corresponds to a measurement from a load cell. The following signal processing calculates
weight in kg from the signal in mV/V and is identical for all input types.
As there is generally always an initial load on the load cell it is usually sufficient to analyze
the signal in the direction of compression only. The YES setting is needed in rare special
cases only, e.g. if a measuring eye is used to record weight.
Bipolar measurement reduces the resolution of the measuring signal.
The load cell cable is improperly connected, not connected or has been interrupted. The
load cell may be faulty.
Steps to take :
- check the cabling and the load cell
- if the cabling is intact: replace the load cell amplifier VME in the VCU
Note:
The power supply must be switched off and on again if the scales still cannot be switched
on even after the error has been rectified.
The load cell load is greater than 110 % of the sum of the load cell nominal loads.
Possible reasons:
- force shunts or pressure ratios can reduce significantly the load on the load cell
- incorrect cabling
- faulty load cell
The output is set to 'do not fill' each time a scales alarm is triggered.
Also refer to: P22.12 Control Level MIN, P22.13 Control Level MAX
Also refer to: P22.16 Event: Bin Level MIN, P22.17 DO: Bin Level MIN
Possible cause:
- refilling working incorrectly
The output becomes active if the fill level underruns the lower threshold value. It operates
independent of the event class of the corresponding event.
Also refer to: P22.19 Event: Bin Level MAX, P22.20 DO: Bin Level MAX
Possible cause:
- refilling not switching off correctly
The output operates independently of the event class of the corresponding event.
See also:
P22.21 AO: Bin Load
P22.23 AO: Range
P22.09 Nominal Bin Load
The fill level sensor reports a too-high fill level in the hopper.
Possible causes:
- the weight of the bulk material is very low so that the weight-controlled filling is not shut-
ting off soon enough.
- the refill equipment is not closing correctly.
- the upper fill threshold level P22.13 Control Level MAX has been set too high.
An overfilled hopper can lead to inaccurate check measurements and so to false adjust-
ment of the calculation of the flow rate.
Converting the analog value into the voltage signal corresponding to a load cell:
The measured value [mV/V] = (input current – P22.30) / (P22.31 – P22.30) * P22.03
where:
P22.30 = Bin Level analog Input Offset
P22.31 = Bin Level analog Input Range
P22.03 = LC Characteristic Value
Precondition: weight measurement of the separate bin has been activated (P22.01 Bin Weigher Active =
YES).
Digital control of the separate bin filling can be found in the Bin Weigher block.
Details on the controller and the controller block diagram can be found in the appendix.
The output is set to off, the controller magnitude is set to 0 and the controller is put into the
base position with every scale alarm. The automatic check system (KME) does the regulat-
ing during its measuring phase.
An I controller results at KP = 0 that leads to a control circuit with an instable structure with
this regulation. This setting should therefore be avoided.
This value should not be greater than the D component. 0.1 ... 0.3 * P23.10 is normal.
The bypass is adjusted so that the fill level of the bin is retained (outflow = inflow) if the
controller is switched off (P23.08 P-Component KP, P23.09 I-Component TN, P23.10 D
Portion TV = 0) and the scale is switched on.
The bypass can be changed in small increments until the service value yBi oscillates
around 0, even if the controller is active.
(The designs with different signs apply correspondingly to P23.02 Filling Type = NO.)
The value set is automatically taken into account by the calibration program BIN: Controller
Optimization'.
The parameter of the continuous controller: P23.07 Dead Time TT - P23.22 Bin Setpoint
source
The parameter of the position controller: P23.24 S: P-Component - P23.40 Position MAX
Flow Gate(B)
The integral component is switched off for TN = 0 s and the controller works as a three-
point switch.
Special case: threshold = 0 %: The smallest allowed trigger threshold has an internal effect.
Also refer to: P23.32 AI: Offset (B), P23.33 AI: Range (B)
Also refer to: P23.31 AI: Position Flow Gate (B), P23.33 AI: Range (B)
Also refer to: P23.31 AI: Position Flow Gate (B), P23.32 AI: Offset (B)
Also refer to: P23.35 AO: Offset (B), P23.36 AO: Range (B)
Also refer to: P23.34 AO: Position Flow Gate (B), P23.36 AO: Range (B)
Also refer to: P23.34 AO: Position Flow Gate (B), P23.35 AO: Offset (B)
The prefeeder to the bin has exceeded its limit switch in the direction of the smallest open-
ing.
Possible causes:
- defect in the adjustment of the prefeeder control (control parameter P23.24 S: P-
Component - P23.28 S: Compensation Element)
- defect in the prefeeder's performance drive
- the prefeeder is leaky and bulk solids are flowing even when the prefeeder is closed
- the limit switch is incorrectly set
Actions:
- check the controller settings
- check the mechanical equipment of the prefeeder and limit switch
Note: The limit switch does not have any limiting impact on the controller. The controller
can go into saturation if the limit switch responds. This is why the limit position should be
clearly outside of the normal setting range.
The prefeeder to the bin has exceeded its limit switch in the direction of the largest opening.
Possible causes:
- defect in the adjustment of the prefeeder control (control parameter P23.24 S: P-
Component - P23.28 S: Compensation Element)
- defect in the prefeeder's performance drive
- the prefeeder is leaky and bulk solids are flowing even when the prefeeder is closed
- the limit switch is incorrectly set
Actions:
- check the controller settings
- check the mechanical equipment of the prefeeder and limit switch
Note: The limit switch does not have any limiting impact on the controller. The controller
can go into saturation if the limit switch responds. This is why the limit position should be
clearly outside of the normal setting range.
If FB or AI are selected, the external value will be converted to a value with an mV/V di-
mension that corresponds to a measurement from a load cell. The following signal
processing for calculating weight in kg from the signal in mV/V is identical to all input types.
As there is generally always an initial load on the load cell it is usually sufficient to analyze
the signal in the direction of compression only. The YES setting is needed in rare special
cases only, e.g. if a measuring eye is used to record weight.
Bipolar measurement reduces the resolution of the measuring signal.
The load cell cable is improperly connected, not connected or has been interrupted. The
load cell may be faulty.
Actions:
- check the cabling and the load cell
- if the cabling is intact: replace the load cell amplifier VME in the VCU
Note:
The power supply must be switched off and on again if the scales still cannot be switched
on even after the error has been rectified.
The load acting on the load cell is greater than 110 % of the sum of the nominal loads of
the load cells.
Possible causes:
- force shunts or pressure ratios can significantly reduce the load on the load cell
- incorrect cabling
- faulty load cell
The output is set to 'do not fill' each time a scales alarm is triggered.
Also refer to: P24.14 Control Level MIN, P24.15 Control Level MAX
The output becomes active if the fill level underruns the lower threshold value. It operates
independently of the event class of the corresponding event.
Also refer to: P24.18 Event: Bin Level MIN, P24.19 DO: Bin Level MIN
Possible cause:
- refilling working incorrectly
Also refer to: P24.21 Event: Bin Level MAX, P24.22 DO: Bin Level MAX
Possible cause:
- refilling not switching off correctly
The output operates independently of the event class of the corresponding event.
Also refer to: P24.23 AO: Bin Load, P24.24 AO: Offset
7.4.2.25
7.4.2.25 Parameter Block 25 - Check System
The check system controls and corrects a continuous scales using the change in bin weight; the changes in
weight result only from the bulk material passing over continuous scales. During measurement all other in-
and outflows must be stopped.
NO:
No check system
Single unit:
The continuous feeder scale and control weighing bin form a mechanical unit and are
weighed together. The continuous weighfeeder discharges from the hopper.
Separated Units:
The continuous feeder scale and control weighing bin are decoupled both mechanically and
with regards to weighing. The continuous weighfeeder discharges from the hopper.
Filling system:
The continuous weighfeeder fills the control bin during the check.
External:
The control procedure is controlled by a higher-order system. The DISOCONT Tersus only
supplies the relevant measured values.
The following parameters only are effective:
- P25.23 DO: Check Measurement Active
- P25.26 Absolute Range
- P25.27 Relative Range
The following parameter description relates primarily to the single unit and separated units
types.
Bin + Second Bin: The total of the weight of both bins is used
NO:
No automatic start
Tare:
Automatic start for controlling and correcting tare or additive effects of errors.
Span:
Automatic start for controlling and correcting the proportionality factor between the meas-
ured value and actual flow rate. Correction of multiplicatively acting effects of errors.
It starts after a pause preselected with the parameters P25.05 Cycle Time. It also makes
sense to preselect automatic correction (P25.03 Auto Correction = YES).
This event is identified if a check has been started but the plant control has not authorized
one.
Generally, no steps need to be taken. The event serves only as an indication of the missing
authorization.
Once measurement has ended the check system moves to the acknowledgement phase
and waits for the correcting command, when P25.03 Auto Correction = NO. Corrections can
also by made manually if the tolerances P25.26 Absolute Range or P25.27 Relative Range
have been exceeded. Correction is triggered by the input flank.
The check must be canceled if the measuring system is in acknowledgement phase and if
the control outcome is not to be used to correct the continuous scales.
The quantity selected should be large enough to minimize the effects of errors when deter-
mining the control quantity. By the same token the hopper should have sufficient capacity
for the control quantity.
Preconditions:
1. The storage quantity must be smaller than the max. control fill level: P25.13 < P25.16
Maximum Fill Weight.
If this condition is not met, the check will end after starting with the message CH 03 (max.
check fill level).
The measurement would cancel with the message CH 02 (min. check fill level) if the ma-
terial quantity falls below this amount.
The fill level has fallen below the threshold value in P25.14 Minimum Fill Weight during a
check. The control measurement is finished early.
Possible cause:
- bulk material density greater than specified
- unfavorable adjustment of P25.12 Check Quantity or P25.14 Minimum Fill Weight or
P25.13 Storage Quantity
The maximum fill level was exceeded during the check. The control measurement is fi-
nished early.
Possible cause:
The storage quantity (P25.13 Storage Quantity) is greater than the maximum control fill
level (P25.16 Maximum Fill Weight). The check will be canceled just after it starts. In case
of an error, check the magnitude of both parameters.
The signal is active from the start of the control until successful correction or cancellation.
The check will be canceled without a response if the conveying element On feedback is
received after starting settling time.
The control waits until conveyance into the control bin is stopped.
Possible cause:
- long time required to end filling
- incorrect control sequence for bin filling
The check procedure is in the filling phase or settling time or the fill level is still greater than
the maximum check fill level (P25.16 Maximum Fill Weight).
At the end the check system waits for a decision by the operator:
Correction will not be made automatically if the threshold would be exceeded by a check.
An event will be identified in each case.
See also:
P25.28 Event: Absolute Tare Correction Error
P25.30 Event: Absolute Span Correction Error
Correction will not be made automatically if the error overshoots the threshold. An event will
be identified in each case.
See also:
P25.29 Event: Relative Tare Correction Error
P25.31 Event: Relative Span Correction Error
The current correction would make the sum of all zero-point corrections greater than the
threshold value P25.26 Absolute Range since the last basic tare calibration. There is no
automatic correction. The operator can acknowledge the message and enter the result
manually. Monitoring and messaging occur in the acknowledgement phase. The correction
weighting factor P25.32 Correction Evaluation is not taken into account in the error analy-
sis.
Actions:
- checking the weighing station of the feeder scale
- taring the feeder scale
- checking bin weighing (the stability of the weight display when loading and unloading)
The result of the current correction deviates more greatly than the threshold value P25.27
Relative Range from that of the last measurement. There is no automatic correction. The
operator can acknowledge the message and enter the result manually. It is monitored and
reported in the acknowledgement phase. The correction weighting factor P25.32 Correction
Evaluation is not taken into account in the error analysis.
Actions:
- checking the weighing station of the feeder scale
- taring the feeder scale
- checking bin weighing (the stability of the weight display when loading and unloading)
The threshold in P25.26 Absolute Range was exceeded by the sum of all corrections for
multiplicative errors.
Bprod = (1 - B * K) * 100 %
The multiplicative error just ascertained exceeds the threshold value in P25.27 Relative
Range.
Brel = (1 - B )× 100 %
P25.32 = 1 is normally set for the first control measurement to make a basic setting. Sub-
sequent corrections, in particular when checks are automatically started, are normally car-
ried out with P25.32 < 1. This makes it possible to filter the control results and eliminate
random measuring errors in the control measurement.
Procedure: the control gate will divert the material either through the normal conveyance
path or into the control bin. The correct position of the control gate can be monitored by the
digital input 'Echo Control Gate' (P25.36 Check Gate Feedback).
Defines the input channel for the position return signal from the control gate. The return
signal is not monitored with the setting 'n/a'.
If there is no feedback from the control gate within the monitoring time (P25.37 Check Gate
Time), the 'control gate error' event is set and the KME is canceled.
Also refer to: P25.35 DO: Check Gate, P25.38 Event: Check Gate Error
Tolerated time allowed for the control gate to move between command and position return
signal.
This parameter relates only to the check by increase in weight of the bin (P25.01 Type of
Check System = Filling System).
The control gate did not reach its end position within the tolerance time.
Possible cause:
- gate has no power
- gate is stuck
If the malfunctions exceed the threshold value in P25.39, another attempt at measuring will
be started after a time defined by P25.18 Damping Time. However, if this attempt also re-
turns excessively high malfunctions, the check will be canceled, the results discarded and
an event identified (P25.40 Event: Bin Error). Disturbances are not monitored if the setting
is 0 %.
How to set:
1. set the threshold to 10,000 %
2. Monitor the service display 'KME Window' during the check procedure
and note the max. value.
3. key in approximately 3 times this value in parameter P25.39 Limit Max. Bin Error.
Large disturbances in the weight signal of the control bin were detected during the check.
The check was canceled and the result discarded. It is also canceled if the event class has
been set to IG.
Possible cause:
- force bypasses at the control bin
- pressure forces acting on the control bin
- wind forces acting on the control bin
Special conditions have to be maintained to guarantee the safety and reliability of the plant. The appendix
has a logic diagram of the control unit needed.
The event is identified when the CO sensor has noted higher values.
Possible causes:
Smolder spots or bulk solids burning en route
Actions:
Explosion and fire protection as per the plant's protection strategy
It dropped below the lower threshold value of the flow rate during a check measurement
(KME). The check was canceled.
This report only acts as a indication of the reason for cancelling the check. This check
should be repeated if the flow rate is sufficiently high.
The measuring system can correct bulk solid properties such as these. This requires that the disturbance
variable, e.g. the moisture or ash content, be measured and the result sent to the system. The measuring
system then calculates the bulk solid components relevant to the process and feeds it instead of the total
weight.
NO: No correction
YES: Weight signal is corrected
The parameters relevant to moisture correction are visible only when correction is active.
Also refer to: P27.03 AI: Moisture Measurement, P27.06 Moisture Range
Also refer to: P27.03 AI: Moisture Measurement, P27.05 Moisture Offset
Also refer to: P27.09 DO: Moisture MAX, P27.10 Event: Moisture MAX
Also refer to: P27.08 Moisture MAX, P27.10 Event: Moisture MAX
The measured value of the interference quantity (for instance, the moisture) has been ex-
ceeded. Feeding errors may arise.
Possible cause:
- extremely damp bulk material
- moisture measurement measuring error
Also refer to: P27.08 Moisture MAX, P27.09 DO: Moisture MAX
Also refer to: P27.12 AO: Flow Rate Offset, P27.13 AO: Flow Rate Range
Conditions:
- the measuring wheel is running and the prefeeder is switched off
- no set-up program active
- no parameter input active
At the end of automatic zero setting, it checks to see whether the amount of the deviation is
smaller than P28.02 to the last valid zero setting. If the value is outside of the tolerance
limit, the results are discarded; otherwise, it checks the absolute zeroing limit (P10.04 Ze-
roing Limit). The zeroing results only become effective when both conditions are met.
Otherwise, an event P28.03 Event: Tare Correction is identified.
Possible cause:
- changed air characteristics on the route
- shunt forces between the rotor and walls
Actions:
- check the force measurement
- check for friction between the measuring wheel and housing
- check flexible seals
- check the air currents
Pressure compensation does not work for the second bin weigher.
If compensation is not activated, the associated parameters will not be displayed in Easy-
Serve.
The event is identified if there is a substantial defect in the signal of the pressure sensor
and the pressure signal is read in through the VME interface.
Possible causes:
- defective sensor cable
- sensor improperly connected
This event is identified when the output signal of the pressure measuring sensor is over its
nominal value.
Possible causes:
- overload on the pressure sensor
- defective sensor
The event is identified when the output signal of the pressure measuring sensor is substan-
tially below zero.
Possible causes:
- sensor improperly connected
- unexpected pressure conditions
- defective sensor
Setting:
P29.09 = 0
Read off the service value of the pressure with atmospheric pressure on the sensor
Adjust the value read in P29.09
Finally, the service display should display the value '0' for pressure.
Setting:
- initially adjust P29.09
- note the weight m0 of the bin at the pressure = '0'
- impinge the bin with any (although constant) pressure
- read the service value of the pressure (p1)
- note the weight m1 of the bin
- adjust P29.10 = (m1 - m0) / p1
The bin weight shown should now always be m0 regardless of the pressure.
The pressure in the bin has fallen below the lower threshold.
Possible causes:
- unexpected pressure conditions
- soiled sensor
- defective sensor
The output functions independant of the selection of event class in P29.12 Event: Pressure-
MIN.
The pressure in the bin has exceeded the upper threshold value.
Possible causes:
- unexpected pressure conditions
- soiled sensor
- defective sensor
The output functions independant of the selection of event class in P29.15 Event: Pressure-
MAX.
The temperature can be read in through an analog input or a Bluetooth link on the rotating part.
AI: Using an analog signal. The signal is adapted over P31.03 Temperature Norming MIN
through P31.06 Temperature Norming Range.
n/a: The signal is read in through Bluetooth. which means that the communication has to be
activated through P05.04 LC: Load Measurement and configured through P05.09 Loading
cell BT ID1 and P05.10 Loading cell BT ID2.
The event is identified when the temperature in the meter exceeds the upper threshold
value. There is the danger of damage to the meter.
Possible cause:
- higher bulk solid temperature
- a lack of cooling
Potential actions:
- checking the bulk solids
- checking cooling
Generally, it is cooled by blowing cool air into the inside of the meter.
The event is identified when the pressure in the cooling system is too low. There is the
danger that the meter becomes too warm and suffers damage.
Potential causes:
- a loss of the compressed air supply
- the filter is blocked
Actions:
- check the cooling plant
- cleaning the filter
The safety functions reduce the range of allowed values of some parameters. They are
activated in case of the risk of serious danger resulting from a wrong parameter setting.
Typical use: Dosing of fuel. Details for the limitations are found in the appendix chapter
"Safety Function for Feeding Hazardous Materials".
The safety functions can only be activated and de-activated via codes specific for the de-
vice. These codes can only be generated by Schenck Process.
When the correct activation code is entered, the parameter shows "SAFETY SET:Enabled",
when disabled with the correct code it shows "SAFETY SET:Disabled". The setting remains
on loading of defaults and on loading of the application software. Units with activated safety
functions are of type VCU20100-S with a specific material number.
The event is identified when purge air is missing for the bearing of the measuring wheel. A
lack of purge air on the running measuring wheel causes damage in the bearing.
Possible causes:
- a lack of compressed air
- soiled filter
Steps to be taken;
check the compressed air for bearings
The event is identified when there is a lack of conveying air. There is the danger of clogging
in the route. Furthermore, it is possible that the system cannot convey the nominal flow
rate.
Possible causes:
- compressed air is missing
- the filter is blocked
Actions:
check the compressed air
YES: the keyboard setpoint is set to zero when the scales are switched off.
The ratio of the actuating variable to the feed rate setpoint of the feeder is smaller than the
threshold.
Possible reasons:
- bulk material is shooting through the discharge unit
The ratio of the actuating variable to the feed rate setpoint of the feeder is larger than the
threshold.
Possible reasons:
- the feed hopper is empty
- arching in the feed hopper
When turn-on delay is activated, the blower is initially switched on through the appropriate
output (P32.26 DO Blower) when turning it on. The pressure in the cooling system is moni-
tored (P32.23 Pressure Blower OK). The measuring wheel and then feeding is switched on
20 s after the feedback on sufficient pressure.
The pressure in the cooling system is too low. This means that the meter can overheat,
which might have the effect of igniting an explosive atmosphere.
Possible causes:
- loss of the cooling blower
- soiled filters in the cooling system
Actions:
- checking the cooling blower
- cleaning the filter
Defines the event class. The meaning of the event can be gathered from the logic diagram.
Defines the event class. The meaning of the event can be gathered from the logic diagram.
Defines the event class. The meaning of the event can be gathered from the logic diagram.
Defines the event class. The meaning of the event can be gathered from the logic diagram.
Defines the event class. The meaning of the event can be gathered from the logic diagram.
Select the process value for recording. You can find the identification number of a value in
the 'data communication' manual.
EasyServe can be used for easy configuration or the settings can be made with the help of the allocation
map in the data description of the serial interface in the operating panel.
You can find the characteristic values (ID) belonging to the process variables in the manual on data com-
munication:
DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468
Consider the location of the linearization in the signal processing (--> appendix).
Detailed calibration instructions are in the appendix.
The definition of the output channel for opening the position-controlled prefeeder. With
DISOCONT Tersus the output should be on the main VCU (local bus address 1).
The definition of the output channel for closing the position-controlled prefeeder. With
DISOCONT Tersus the output should be on the main VCU (local bus address 1).
The event is identified when the prefeeder has run past the limit switch for the minimum
position. It is used to protect the mechanical equipment.
Possible causes:
Defects in the prefeeder control unit
Actions:
Check the control unit.
The event is identified when the prefeeder has run past the limit switch for the maximum
position. It is used to protect the mechanical equipment.
Possible causes:
Defects in the prefeeder control unit
Actions:
Check the control unit.
8 Event Messages
DANGER
Events register abnormal states, e.g. malfunctions or exceeded thre-
shold values.
A running feeder can be a hazard to people or to property.
The cause of event messages must be corrected before events are ac-
knowledged!
Note:
In the following list, parameters related to the indicated event are shown in parentheses.
Measures:
- check the cabling and the load cell
- check the load cell
Note:
The power supply must be switched off and on again if the scales cannot be switch-
ed on even after the error has been rectified.
Possible causes:
- there is a fault in the speed impulse sensor cable (check the shielding and the wir-
ing)
- the sensor has been incorrectly calibrated
Steps to take :
- check the cabling and the load cell
- if the cabling is intact: replace the load cell amplifier VME in the VCU
Note:
The power supply must be switched off and on again if the scales still cannot be
switched on even after the error has been rectified.
Possible cause:
- changed air characteristics on the route
- shunt forces between the rotor and walls
Actions:
- check the force measurement
- check for friction between the measuring wheel and housing
- check flexible seals
- check the air currents
Possible causes:
- defective sensor cable
- sensor improperly connected
Actions:
- check the cabling and the load cell
- if the cabling is intact: replace the load cell amplifier VME in the VCU
Note:
The power supply must be switched off and on again if the scales still cannot be
switched on even after the error has been rectified.
Possible cause:
- bulk material density greater than specified
- unfavorable adjustment of P25.12 Check Quantity or P25.14 Minimum Fill Weight
or P25.13 Storage Quantity
Possible cause:
The storage quantity (P25.13 Storage Quantity) is greater than the maximum control
fill level (P25.16 Maximum Fill Weight). The check will be canceled just after it starts.
In case of an error, check the magnitude of both parameters.
Actions:
- checking the weighing station of the feeder scale
- taring the feeder scale
- checking bin weighing (the stability of the weight display when loading and unload-
ing)
Actions:
- checking the weighing station of the feeder scale
- taring the feeder scale
- checking bin weighing (the stability of the weight display when loading and unload-
ing)
Bprod = (1 - B * K) * 100 %
Brel = (1 - B )× 100 %
Possible cause:
- long time required to end filling
- incorrect control sequence for bin filling
Generally, no steps need to be taken. The event serves only as an indication of the
missing authorization.
The control gate did not reach its end position within the tolerance time.
Possible cause:
- gate has no power
- gate is stuck
Possible cause:
- force bypasses at the control bin
- pressure forces acting on the control bin
- wind forces acting on the control bin
Possible causes:
Smolder spots or bulk solids burning en route
Actions:
Explosion and fire protection as per the plant's protection strategy
This report only acts as a indication of the reason for cancelling the check. This
check should be repeated if the flow rate is sufficiently high.
Step to take: check the material discharge and the Controller Magnitude (service
value Y). At Nominal Flow Rate Y should be between about 10...14 mA.
Possible causes:
Defects in the prefeeder control unit
Actions:
Check the control unit.
Possible causes:
Defects in the prefeeder control unit
Actions:
Check the control unit.
Possible causes:
- the weight of the bulk material is very low so that the weight-controlled filling is not
shutting off soon enough.
- the refill equipment is not closing correctly.
- the upper fill threshold level P22.13 Control Level MAX has been set too high.
Possible causes:
- defect in the adjustment of the prefeeder control (control parameter P23.24 S: P-
Component - P23.28 S: Compensation Element)
- defect in the prefeeder's performance drive
- the prefeeder is leaky and bulk solids are flowing even when the prefeeder is closed
- the limit switch is incorrectly set
Actions:
- check the controller settings
- check the mechanical equipment of the prefeeder and limit switch
Possible causes:
- defect in the adjustment of the prefeeder control (control parameter P23.24 S: P-
Component - P23.28 S: Compensation Element)
- defect in the prefeeder's performance drive
- the prefeeder is leaky and bulk solids are flowing even when the prefeeder is closed
- the limit switch is incorrectly set
Actions:
- check the controller settings
- check the mechanical equipment of the prefeeder and limit switch
The scales will not switch on automatically, regardless of the event class. The event
must first be acknowledged and the command to start given again before the scales
will restart.
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
If this event is pending then the downstream transport equipment is most likely not
switched on.
Possible causes:
- compressed air is missing
- the filter is blocked
Actions:
check the compressed air
Possible causes:
- a lack of compressed air
- soiled filter
Steps to be taken;
check the compressed air for bearings
Possible cause:
- extremely damp bulk material
- moisture measurement measuring error
Also refer to: P27.08 Moisture MAX, P27.09 DO: Moisture MAX
Possible causes:
- highly erratic material flow
- altered feeder discharge behavior
- error in weight calculation due to disturbance forces
Possible causes:
- incorrect entry
- incorrect upper threshold
Possible cause:
- higher bulk solid temperature
- a lack of cooling
Potential actions:
- checking the bulk solids
- checking cooling
Possible causes:
- loss of the cooling blower
- soiled filters in the cooling system
Actions:
- checking the cooling blower
- cleaning the filter
Potential causes:
- a loss of the compressed air supply
- the filter is blocked
Actions:
- check the cooling plant
- cleaning the filter
Possible causes:
- Shunt forces or compression ratios bring about incorrect load cell loading
- incorrect cabling
- faulty load cell
Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
- feed rate setpoint too large
Possible causes:
- material has been incorrectly handled:
- the bulk material is flowing irregularly or cannot be discharged satisfactorily
- arching in the feed hopper
- there is a backup on the discharge side
- a large quantity of material continues to trickle from the feeder
- calibration error: during initial calibration the regulator was set at such a critical
value that minor changes in the overall properties of the system lead to unreliable
operation.
Also refer to: P07.11 Deviation abs. max., P07.10 Factor Deviation, P07.09 Thre-
shold Deviation, P07.08 Time Deviation
Possible causes:
- bulk solids blocked in the area of the measuring wheel
- measuring wheel covered
Steps to be taken:
Open the MULTICOR equipment and check the measuring wheel for friction
Possible reasons:
- force shunts or pressure ratios can reduce significantly the load on the load cell
- incorrect cabling
- faulty load cell
Possible cause:
- refilling not switching off correctly
Possible reasons:
- the feed hopper is empty
- arching in the feed hopper
Possible causes:
- overload on the pressure sensor
- defective sensor
Possible cause:
- refilling not switching off correctly
Possible causes:
- force shunts or pressure ratios can significantly reduce the load on the load cell
- incorrect cabling
- faulty load cell
Possible causes:
- unexpected pressure conditions
- soiled sensor
- defective sensor
Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
- feed rate setpoint too low
Possible causes:
- the measuring drive is blocked by bulk solids or foreign particles
- there is a defect in the motor of the measuring drive
Actions:
- open the equipment and check the measuring wheel for friction
- check the drive train, motor and motor's drive
Possible cause:
- refilling working incorrectly
Possible causes:
- sensor improperly connected
- unexpected pressure conditions
- defective sensor
Possible cause:
- refilling working incorrectly
Possible reasons:
- bulk material is shooting through the discharge unit
Possible causes:
- unexpected pressure conditions
- soiled sensor
- defective sensor
This function protects the motor from overheating at very low speeds or when idling.
Actions:
Key in the larger setpoint and check P07.02 Stand-By Limit Value.
A message occurs after each expired time interval. The message may indicate ser-
vice work required.
A message occurs after each expired time interval. The message may indicate ser-
vice work required.
Possible cause: depends on the external cabling. Usually: an error in the main drive
Possible cause:
- storage bin is empty
- storage bin has a blockage
- the filling gate is malfunctioning or is blocked
Steps to take:
- load the factory settings
- Normally the hardware has to be replaced.
Steps:
- check cable connection
- check that operating console is correctly functioning
- check the operating console settings
- check the addresses of the scales at the RS485 data bus (P01.11 VHM RS485
Address)
Possible causes:
- major malfunctions in the surroundings
- the loss of the voltage supply of the rotating Bluetooth transmitter
Actions:
- a brief voltage interruption of VCU and the rotating Bluetooth transmitter for initiali-
zation
- check the availability of the rotating Bluetooth transmitter with a scanner in the PC
9 Appendix
Details of special functions are described in this chapter.
The sources are preselected with parameters in the 'Control Sources' group.
You can use the OP Mode function to switch back and forth between the pre-selected sources and the key-
board (Keyboard Mode ON/OFF [➙ 28]).
The effective setpoint is displayed on the operating panel. The setpoint input field is only available if the
inputs from the operating panel are allowed by parameter.
A new window for entering the relative component will open when the setpoint field is touched if the relative
setpoint qualifier was pre-selected with the operating panel.
Setpoint Synchronization:
The external setpoint will be taken if the source of the setpoint is switched from an external source to the
keyboard (OP). The external source has its effect in the opposite direction.
On / Off Synchronization:
The on/off switch status is retained when switching from an external source to the keyboard (OP). The ex-
ternal source has its effect in the opposite direction.
Mains Power OFF:
The keyboard setpoints are stored.
Time Condition
1 Feeding does not begin with the on command since the all-clear signal has not been given.
2 To start, the scale requires the rising slope of a start command.
3 Feeding is started with the rising slope.
4 Flow rate control will operate in volumetric operation (also refer to: Volumetric / (Volumetric Syn-
chronous) / Gravimetric Modes of Regulator Operation [➙ 28]) during the start up time defined by T1
= P06.01.
5 Changing over in normal gravimetrically controlled feeding operation (assuming gravimetric mode
was previously selected). Control stays in volumetric mode (assuming it was previously selected by
the operator).
6 Feeding will be switched off if there is no all-clear signal (or if the switch on command was removed).
7 Flow rate recording continues over the time set by T2 = P06.02 to capture trickling bulk solids. After-
wards, the flow rate is no longer calculated; the counter stays at the level already achieved.
Tab. 38 : The states and points in time in the flow chart
Parameter Function
Fig. 16: A simplified signal flow block diagram of 'calculating the flow rate'
Description Meaning
Description Meaning
Punlin The measured flow rate (not linearized)
LIN Linearized for the flow rate
P The measured value of the flow rate for display, regulation and totalizing
Tab. 40 : Designations in the signal flow diagram
The measuring wheel exercises a force on the dynamometer (WZ) through lever H. The output tension of
the dynamometer Ua is reinforced and transformed into the unprocessed measurement value with the ana-
log-digital converter A/D .
The flow rate is inversely proportional to the speed n. Flow rate recording is turned off at speeds lower than
0.01 * P05.03.
Constant Continuous 0 (4) ... 20 mA A continuously rotating feeder such as a helix or starwheel, ...
controller The feed gate with built-in pneumatic or electric position control
The parameter has no effect in the Flow Gate block
Step control- Stepping OPEN and CLOSE The feed gate driven by a motor with position feedback
ler contacts The parameters in the Flow Gate block configure the characteris-
tics
Tab. 41 : Controller models and how they are used
Fig. 17: The 'constant controller' signal flow block diagram (simplified)
Measuring the flow rate For details see Block diagram: measuring the flow rate
[➙ 233]
Message Identifying the event and reporting the state
Q The load on the force transducer for measuring the torque
N The speed of the measuring wheel
I The actual flow rate value [kg/h]
P The flow rate setpoint [kg/h]
Xd Control deviation
P source Selector for the source of the setpoint in P04.02
Sim The switch after simulation operation
K Input via keyboard
S Received via fieldbus
A Analog value
The standard PI controller is also equipped with a setpoint bypass (P11.08). The bypass quickly carries out
setpoint jumps even if the controller is set slowly. Beyond this, the bypass allows controlled (volumetric)
operation.
To prevent overshoot, the setpoint is decoupled from the actual controller through a reconstruction of the
controlled member (P11.10 and P11.11). The controller is also equipped with controller magnitude limitation
(P11.04 and P11.05) dependant upon the setpoint. The controller is stopped and an event is identified
(message) when reaching the lower or upper controller magnitude limit.
The relationship between the controller parameters and the actuating variable is shown schematically in the
following diagram.
Parameters Effect
P06.01 The duration of volumetric start-up operation once the scales have been switched on in s
Volumetric Start-Up
P11.09 NO: The integral component is not stored when switched off
Store YES: The integral component is stored when switched off and it has an impact when start-
ing up
YES-A: The integral component is stored when switched off and it has an impact when
starting up if feeding is not switched off by an alarm.
Parameters Effect
P11.08 One value is superimposed additively on the actuating variable, proportionally to the pre-
Bypass set setpoint. This parameter gives the bypass value for the nominal setpoint.
P11.10 The filters delay the setpoint for the controller while the bypass comes to the controller
Setpoint Filter 1st Ord magnitude output without a delay.
This has the purpose of approximately adjusting the time characteristics of the controlled
P11.11 member to prevent the actual value from overshooting on setpoint jumps.
Setpoint Filter 2nd Ord
P11.15 This additional constant integral member in the control deviation branch can have the
Compensation Element following favorable effects:
Contouring errors brought about by monotonous variable malfunctions (such as control
measurement equipment)
Constant control deviations with actuators with a non-symmetric effect.
The compensation element only has an impact in gravimetric operation and P11.15 para-
meters unequal to zero. The input and output are limited to ± 5 %.
P11.16 This parameter can be used to evaluate the proportional component of the controller de-
KP Adaptation pendant upon the target flow rate.
KP control= 1 : KP is independent of the setpoint
KP control = 0 : KP decreases in proportion to the setpoint
KP control = 2 : KP increases in proportion to the setpoint.
P11.17 The upper limit for evaluating the control deviation by the setpoint as per P11.16
Setpoint Threshold
Condition Characteristics
Changing the values of the The integral component is not converted when parameters are changed, which means
parameters that there might be jumps in the controller magnitude Y. If these jumps cannot be
tolerated, there should only be major changes in the (P11.08) bypass when feeding is
switched off.
Network connection The stored values in the integral component and in the filters are set to zero.
Switch off feeding Stored components of the setpoint filter are set to zero. The value of the integral com-
ponent is determined by P11.09.
Starting up feeding The feeder is switched on when all conditions are met.
The controller magnitude is set to the value of the setpoint bypass. The rise in P11.06
and the stored I-component of the controller overlap one another consecutively as per
P11.09.
The setpoint filter starts working simultaneously from zero.
The flow rate controller works according to P06.01 in volumetric operation during the
start-up period. After the start-up period, the controller ts released and gravimetric
operation begins.
Standby The drive for protecting the motor is switched off if the internal controller magnitude
drops below the limit set in P07.02 longer than three seconds. The controller magni-
tude is set to the lower value corresponding to P11.06. It continues to report outwards
that feeding is in progress.
The controller does not function and the integral component of the flow rate controller
is deleted or retained depending on P11.09.
Measurement remains active.
It switches to normal operation if the internal controller magnitude exceeds the limits
set in P07.02.
Gravimetric operating mode The actual flow rate value is set to the effective setpoint through the material feeder.
Condition Characteristics
Volumetric operating mode Only the setpoint bypass and rise act as a controller magnitude. The feeder is con-
trolled proportional to the setpoint. The integral component of the controller is deleted
regardless of the P11.09 while the setpoint filters continue to run.
Volumetrically synchronous In contrast to volumetric operation, switching synchronously from gravimetric to volu-
operation type metric makes it possible to switch over from the gravimetric operating mode without a
bump by including the current controller output value.
Simulation The control circuit is closed internally in simulation operation. The measured values Q
and n are also simulated (Q=Qnominal, n = nominal speed).
The simulated value is shown as the flow rate. The controller magnitude Y is propor-
tional to the setpoint and is 10 mA specifying the nominal setpoint.
The operation types, switch on/off sources and setpoint sources function as usual in
simulation operation.
The task: testing the plant, especially the control processes. Learning operation.
The characteristics in the The components stored in the controller are set to zero when selectively switching off
'Prefeeder – Stop' mode the feeder just as when switching off feeding. However, totalizing continues to functi-
on.
Tab. 45 : Characteristics in special operational states
Monitoring control deviation
The control deviation is displayed and monitored in gravimetric operation only.
The display, but not the monitoring system input, is filtered by parameter P08.05.
Event message 'P07.08' will be triggered if the value of the error signal Xd exceeds the limit value S1 for a
duration defined in parameter Event: Deviation. Monitoring will restart if the error signal falls below the thre-
shold during this time.
At the same time, the control deviation value is filtered (filter time in parameter P07.08) and the filter output
is monitored. Event 'Event: Deviation' will be identified if the filter output exceeds the threshold value S2.
Threshold values S1 and S2 can be adapted to the current flow rate setpoint by means of the following for-
mulas:
S1 = P07.09 * [P07.10 + (1 - P07.10) * Flow rate setpoint / P03.03]
S2 = P07.11 * [P07.10 + (1 - P07.10) * Flow rate setpoint / P03.03]
The following diagram illustrates the relationship using with examples for threshold value S1.
Parameters Effect
Value Meaning
The EXTERNAL component is not a part of the DISOCONT Tersus. Instead, it is only a proposal for creat-
ing local switching for connecting to an FAE 8202 model power unit.
Drawing elements Meaning
The OPEN, STOP and CLOSED switch positions are only available with manual control of the feeder.
The Min and Max limit switches keep the limit positions of the feeder from being overrun.
T2 P06.02 Measuring Delay Measure Recording the actual flow rate and calculating the
totalizing counter
PR Effective flow rate setpoint Feed The switch-on command to the feeder's discharge
organ
Main_Spd The command for feeding in full feed Dbl_Spd The command for feeding in dribble feed
NOTE: The most important settings for batching are made in the Batch Mode block of parameters.
Adaptation
With adaptation, a corrective quantity K is calculated from the error quantity (batch actual weight - weight
setpoint) after each completed batch and stored in the P15.04 parameter. This automatically shifts items 3
to 5 of the diagram with the next batch.
K(new) = K(old) + P15.05 * error
K(new) = new corrective quantity
Error = actual batch weight – batch setpoint
Errors greater than the batching tolerance set by P15.14 are restricted to the set tolerance value. Shortfalls
that are smaller than the smallest display digit are not corrected.
P15.05 acts as a filter parameter to ensure that P15.04 contains a mean for the bulk material overrun with.
Threshold values
The P09.02 Event: Actual Flow Rate MIN event message is suppressed during the rundown time. This does
not apply to the digital output.
This display applies to the first bin weigher with parameters in the 'Bin Weigher' block. The values apply
correspondingly to the second bin weigher with the parameters in the Second Bin Weigher block.
The 100 % value of the control scale is the total of the nominal loads of the bins whose levels are used as a
check as per P25.02.
The normal scales applies in normal operation. The fill level is regulated by the metering hopper. In intermit-
tent operation the metering hopper is activated when the fill level F-Min is underrun and is deactivated as
soon as the F-Max level is exceeded. If the metering hopper is continuously active (P23.01 = YES), the fill
level is regulated to the fill level setpoint F-Set by means of the changes in the metering hopper flow rate.
The check measurement takes over the fill regulation when a check is started. Wherever necessary, it is
filled until there are sufficient bulk solids in the bin (fill level > C-Check + C-Min). The check starts when the
fill level falls below F-Max and is stopped when the fill level falls below C-Min.
The fill level controller only works for the first Bin Weigher, although not for any Second Bin Weigher availa-
ble.
Setup Notes
P23.12 can be determined in a stationary state once the transient oscillations have subsided. In this state,
the value is calculated as follows:
P23.12 = (yB - P23.14 ) × P03.03 / flow rate setpoint
We recommend calling up the Optimizing Hopper Fill Level Regulation [➙ 39] adjustment program for the
control parameter after entering input the P23.07 and P23.12 parameters.
Abbreviation Meaning
B-S: Xd Service value: the control deviation for the position controller
B: Position Service value: the position of the feed gate
Abbreviation Meaning
a) P The flow rate setpoint (P) with feeding systems
b) I The actual flow rate (I) with measuring systems
B: Xd Service value: the control deviation for the fill level controller
StepCTRL Step controller
PosCTRL The position controller for the feed gate
PowerCTRL The power control for the feeder
Conti_M Continuous measurement of the flow rate
MIN The limit switch of the minimum position
MAX The limit switch of the maximum position
Tab. 50 : The meaning of the abbreviations in the block diagram
Ideal: Straight course of the correlation between the measured value and actual flow rate
Real: The calculated non-linear course of the real characteristic curve
The figure shows the selected measuring points of the flow rate in the horizontal axis. The S(k) values to be
keyed into the parameters are as follows:
S(k) = I(k) / (P03.03 * P10.01) * 100 % ; k = 1, 2, 3, 4
The value S(k) can be read out during the measurement from the Unlin. Flow Rate service value. If the
measurement takes place in the operation controlled by the flow rate, I(k) corresponds to the flow rate set-
point used.
The value R(k,n+1) to be adjusted in the parameters of the vertical axis after making the measurement re-
sults from the value of the corresponding parameter R(k,n) that is active during the measurement, the value
ms of the conveyed quantity ascertained on a sufficiently precise static scale and the meter progress mc of
the Coriolis measuring unit:
R(n+1) = R(n) * ms/mc
The flow rate naturally deviates from the flow rate I(k) in the middle of the measurement at the start and end
of the measurement. To ensure that these effects have the smallest possible impact on parameter adjust-
ment, the start phase should be as brief as possible until reaching the flow rate I(k) and the take-off phase
should be as brief as possible in relation to the entire duration of the measurement. This can be supported
with a quick controller adjustment with systems controlled by flow rate. If the start- and take-off phase can-
not be selected to be brief in relation to the overall duration, all linearization points should be preset and
then checked and recalibrated. Suitable controller adjustment should guarantee a flow rate that is as con-
stant as possible during the measurement.
We recommend depicting the actual values of linearization for the plausibility control graphically.
Tab. 51 : Legend
The P04.13 parameter decides on whether the correction to the shown actual flow rate and quantity integra-
tion derived from that or/and to the input signal of the optional controller has an impact. This makes it possi-
ble to easily control the bulk solids component B even in this architecture.
Open Gate P26.03 DO: Check Valve Open the shut-off valve
A current check is interrupted if the slide is
not closed during the check.
Cancel CH P25.11 Finish Check Measurement Interrupt a control measurement
Vent P26.05 DO: Hopper Aeration Switch on the bin ventilation
Gate Open P26.07 DO Check Gate Opened Message: the slide is open
dp-Comp P26.06 DO Pressure Compen. Open the pressure equalization line
Filling P26.08 DO Check Gate Closed Message: the feed element is switched off
stopped
Tab. 52 : The meaning of the signals
Fig. 28: The logic diagram of the link between events and ready messages
Explanations:
All signal levels can be inverted by setting the associated source parameter (also refer to Configuring the
Interfaces [➙ 56]). The factory setting is given in the diagram.
▪
LOW: closed contact in standby, i.e. power is on. The contact is open if the signal is active (functions as
opener).
▪
HIGH: open contact in standby, i.e. power is not on. The contact is closed if the signal is active (func-
tions as closer).
E: event message
DI: digital input
DO: digital output
NOTE: When an input source parameter accepts the value n/a, the signal is internally assumed to
be True.
9.13 Using alternative signals (such as analog or fieldbus) for DMS inputs
It is usual for some signals to be read in through sensors with strain gauges (DMS) such as weight, force or
pressure signals. In special cases, these signals are recorded with other types of sensors or reshaped ex-
ternally so that they are available in the form of standard signals (such as 4 ... 20 mA). DISOCONT Tersus
provides the option of reading in some sources of input signals via standard signals. The standard signal is
read in through an analog VAI 20100 interface and reshaped to make it correspond to the signal of a DMS
sensor. The remaining signal processing is identical for the DMS signal and standard signal.
Some measuring signals can also be read in by fieldbus to prevent faults on the transmission path. These
are also processed like DMS signals after appropriate conversion.
Fig. 29: Alternative inputs using the example of a weight signal for an additional bin
LC DMS load cell output voltage 0 - 20 mA Input current from the external sensor
FB:kg The weight value in kg transmitted [mV/V] A signal with the dimension mV/V
from the fieldbus
Adjust Handing over the signal to the set-up LC [mV/V] The service value of the load in the dimen-
program sion mV/V
LC_0 The rated load cell load in P22.04 LC [%] The service value of the load in percent of
LC_0
V Transmission factor of the load cell in x, y Input and output values of the calculating
P22.03 blocks
Error Error signal if the physical signal is out Source Selecting the source for the signal in P22.02
of range
Corr Multiplicative correction of the trans- Tare Zero signal in P22.25 such as determined by
mission factor in P22.24 the set-up program
This figure uses recording the weight of an additional bin as an example of the form the signals of sources
other than DMS load cells are processed in. The set-up programs and service displays (including the para-
meters for tare and correcting sensitivity) remain in manual override, even though they show some values
such as for the DMS load cells. The figure applies accordingly to other signals such as force or pressure.
The corresponding parameters are in the group that also contains the parameter for selecting the signal
source.
NOTE: Please bear the fact in mind that the value resolution of a value read in through the stan-
dard signal is reduced by the resolution of the external transmitter and the VAI 20100 inter-
face assembly in relation to the input for DMS via interface VME0120 (VME0120: 24 bits
and VAI 20100: 16 bits). In addition, there can also be a temporal offset of the signal due to
scanning.
There can be additional errors in particular when forming the difference of signals (such as
differentiating) or a compensator (such as pressure compensation).
In this example, a binary input signal (for instance, an input contact of DISOCONT Tersus) is being read in
through the GP-Din 1 input block and the Delay 1 delay while an inverter is given to the And1-4 AND gate.
The other inputs are linked with the constant 1 and a Cycle 1 frequency generator. This provides the output
with a cyclical signal when the waiting period has elapsed after setting the input. The output of the AND gate
is linked to an output of the DISOCONT Tersus standard control. The physical output requires connecting
the signal with a digital output through P35.01 FCB_DO 01.
CAUTION: Creating and modifying links is reserved solely to Schenck Process person-
nel.
Configurations can be read out of and loaded into the control. They can be filed on the hard disk of PCs and
called up from there. Links have to be given a name. The empty link (as a factory default) has the name
Empty and should not be used for other links.
WARNING
Possible loss of function when exchanging the VCU.
Function blocks are not automatically stored with the parameters in
EasyServe. If a function block link is loaded, it will be necessary to store it
separately in EasyServe. If the VCU is exchanged, both the parameters
and the function block link have to be loaded separately to restore full func-
tionality. Alternatively, you can use the additionally installed tool
DISOPLAN (that contains both the parameters and the function block links)
to make a complete backup. However, this backup can then no longer be
used for setting a more recent version of the program in the scale.
It is not necessary with a system with the Empty link (refer to Cleaning the Screen and Information [➙ 36])
to reload the link after exchanging the VCU since there is no expansion to the functions from the function
blocks.
Loading the function software or loading default settings or the locking set of the parameters does not have
any impact on the function blocks loaded. In other words, any link that is already loaded is retained. Any
loaded link cannot be deleted; it can only be overwritten. If you want to make a link ineffective, it can be
overwritten with a new link that has to contain at least one block.
A loaded link does not have any effect on scales operation as long as the outputs for the link are not
coupled to the scales software with the corresponding parameters P34.01 to P35.20.
1 Binary input 20 Process variable as per the de- Connection of the function block logic
'GP-DIn' scription of the fieldbus interface to the function of the standard pro-
gram
2 Binary output 20 - Makes output signals available. Con-
'GP-Dout' nect using the parameter in the 'FCB
digital outputs' block. All outputs are
available as status information in the
fieldbus interface.
3 Clock generator 2 Period duration Signal generator for a periodic signal.
'Cycle'
4 'Bin. 0' 1 - Encoder for the binary constants 1 =
'Bin. 1' 1 True and 0 = False
5 Pulse generator 1 Time for the pulse The timer has three outputs that
'Timer' supply an pulse of 0.1 seconds dura-
tion at the time set.
6 AND 6 - AND link between two input signals
'And'
AND 4 - AND link between four input signals
'And 4'
7 OR 6 - OR link between two input signals
'Or'
OR 8 - OR link between four input signals
'Or 4'
8 Negation 10 - Inverts the signal
'Not'
9 Retardation 8 Delay time in seconds Delays the input signal by the speci-
'Delay' fied time
Tab. 53 : Blocks available for processing binary signals
1 Analog input 20 Process variable as per Input for a variable with a continuous value.
'GP-AIn' the description of the
fieldbus interface
2 Analog output 20 - Makes output signals available. Connecting via
'GP-Aout' parameters in the FCB analog outputs block. Only 5
FKB outputs can be configured to physical outputs.
All outputs are available as measured values in the
fieldbus interface.
3 Comparator 6 Upper and lower com- Supplies the 'True' value if the input signal lies out-
'Comparator' parative value side of the threshold values.
4 'Limit' 10 Upper and lower thre- Limits the input signal and becomes True when the
shold value limiter arises.
5 Multiplier 5 - Supplies the product of the input values at the out-
'Multiplier' put.
9 Counter 6 Start value Supplies the counted input impulses at the output
13 Offset 10 Dividend
'Offset' Divisor
The electronic pressure compensation compensates for the force components in the hopper weight signal
caused by pressure in the hopper. The pressure forces can be great even if the pressures are low, resulting
in significant errors in weight measurement.
Pressure compensation only affects the main bins (refer to the Bin Weigher for the appropriate parameters).
Fig. 33: The signal flow diagram for pressure compensation for the bins
The pressure in the hopper is best measured by a DMS pressure sensor for purposes of electronic compen-
sation. The input for the pressure sensor is defined by P29.02.
The parameters for the pressure sensor are entered into P29.03 and P29.04. For atmospheric pressure
(hopper open) the measured pressure will be read as a service value and entered into P29.09.
▪
Furthermore, the following parameters are restricted in their value range:
– Constant controller always active: P03.01 = YES, P11.01 = continuous
– Feeder Check FC (P32.13) always active (P32.13 = Y)
– Time Deviation (P07.08) < 30 s
– Threshold Deviation (P07.09) < 5 %
– Filter: Deviation (P08.05) < 3 s
– Volumetric Start-Up (P06.01) < 2 s
– Store (P11.09) = NO
– Speed Measurement (P05.01) = VCU1, DI6
– LC: Load Measurement (P05.04) = VCU1, LC1
WARNING
We strongly recommend that you activate the monitoring if combus-
tibles are to be conveyed, as a failed sensor (speed sensor or weight
measurement) may lead to overfilling. The control deviation monitor
must be set correctly.
An overdosage could lead to a fire or an explosion with severe conse-
quences for personnel and equipment.
Symbol Meaning
Symbol Meaning
Y[%] Actuating variable output to the discharge element in mA or % under consideration of off-
set and maximum value
P Change of the setpoint
MIN-Area A MIN event is identified if the value lies within this area
MAX-Area A MAX event is identified if the value lies within this area
OK Normal area in which no event is identified
E Change of the setpoint, related to the nominal output
FC-Deviation [%] Deviation from the optimum value of the current value in % of the tolerance effective for the
current flow rate setpoint. An event will be generated if FC-Deviation = ±100 %.
The tolerance range is increased for changes of setpoint. The tolerance values set by parameter will be
increased by the percentage rate of the change in the moments after a setpoint change.
EXAMPLE: A sudden change of setpoint of 50 % of the rated output increases directly after the change a
tolerance set by parameter from 25 % to 75 %. If the setpoint remains the same, the increase will reduce
exponentially towards zero with a set time constant of 10 s, i.e. long after the change the tolerance will have
the same effect as the setting made by parameter.
The service value FC act. Deviation shows the current deviation of the ratio between the actual value and
the ideal value as a % of the permissible tolerance Y_tol.
Values > 100 % will trigger a MAX event, values < -100 % will trigger a MIN event.
The value 'FC-Deviation' is calculated from the current actuating variable Y [%] and the flow rate setpoint
P [%] based on the current tolerance Y_tol as follows:
FC-Deviation = (Y [%] – P [%]) / Y_tol * 100 %
Y_tol is the tolerance at the operating point P [%] set by parameter and possible increaesed by a compo-
nent from setpoint changes.
The test connector is plugged into the load cell cable input on the DISOCONT Tersus instead of the load
cell cable.
Once plugged in, the raw measured value can be read off at the service values of the measuring electron-
ics. It must have the following value: raw measured value 1.5 mV/V ± 3 %.
Note: The raw measured data can be calculated according to the formula: raw measured data ~ 500 *
R2 / R1 [mV/V] if other resistance values should be used in the test connector
The measuring amplifier is working properly if the raw measuring value lies within this range.
The measured load display in kg depends on the way the scale's rated data are set.
Index
2. Password ..................................................................................................................................................................... 87
Abbreviations ................................................................................................................................................................... 56
About This Manual ............................................................................................................................................................. 1
Absolute Range.............................................................................................................................................................. 165
Accept Correction ........................................................................................................................................................... 161
Access Rights Limitation FB........................................................................................................................................... 130
Access Rights Limitation HMI........................................................................................................................................... 85
Access to Special Functions ............................................................................................................................................ 22
Accessing the Configuration............................................................................................................................................. 33
Acknowledging Event Messages...................................................................................................................................... 25
Actuating Variable Safety Functions .............................................................................................................................. 266
Adaptation Factor ........................................................................................................................................................... 121
Adaptation Time ............................................................................................................................................................. 121
Additional Bin Weighers ................................................................................................................................................... 12
additional containers ........................................................................................................................................................ 12
Additional device ............................................................................................................................................ 176, 177, 178
Address .................................................................................................................................................................. 128, 129
Adjusting linearization .................................................................................................................................................... 251
Adjusting the flow rate regulation ..................................................................................................................................... 48
AI Moisture Measurement ............................................................................................................................................. 173
AI Offset ........................................................................................................................................................................ 208
AI Offset (B) .................................................................................................................................................................. 150
AI Position Flow Gate .................................................................................................................................................... 208
AI Position Flow Gate (B) .............................................................................................................................................. 149
AI Range ....................................................................................................................................................................... 208
AI Range (B) ................................................................................................................................................................. 150
Analog Channel A10 ........................................................................................................................................................ 81
Analog Channel A11 ........................................................................................................................................................ 81
Analog Outputs .............................................................................................................................................................. 111
Analog Setpoint Relat..................................................................................................................................................... 122
AO Actual Flow Rate ..................................................................................................................................................... 111
AO Bin Load .......................................................................................................................................................... 141, 157
AO Check Measurement Result .................................................................................................................................... 168
AO Controller Magnitude Bin Level ............................................................................................................................... 144
AO Deviation ................................................................................................................................................................. 113
AO Flow Rate corrected ................................................................................................................................................ 175
AO Flow Rate Offset ..................................................................................................................................................... 175
AO Flow Rate Range .................................................................................................................................................... 175
AO Load ........................................................................................................................................................................ 112
AO Motor Speed Control ............................................................................................................................................... 113
AO Offset ...................................................................................................................................................... 141, 157, 208
AO Offset (B)................................................................................................................................................................. 150
AO PLC 1 ...................................................................................................................................................................... 136
AO PLC 2 ...................................................................................................................................................................... 136
AO Position Flow Gate .................................................................................................................................................. 208
AO Position Flow Gate (B) ............................................................................................................................................ 150
AO Range ..................................................................................................................................................... 141, 157, 208
AO Range (B)................................................................................................................................................................ 150
AO Setpoint ................................................................................................................................................................... 111
AO Speed...................................................................................................................................................................... 112
Appendix ........................................................................................................................................................................ 231
Assembling the Electrical Components ............................................................................................................................ 47
Authorization for Control Commands ............................................................................................................................... 22
Auto Correction .............................................................................................................................................................. 160
Auto Zero Active ............................................................................................................................................................. 176
Auto Zero Limit ............................................................................................................................................................... 176
Automatic control ............................................................................................................................................................. 11
Automatic control measurement unit (KME) ..................................................................................................................... 41
Basic Operating Functions ............................................................................................................................................... 23
Basic Tare ...................................................................................................................................................................... 106
Batch Automatic Record................................................................................................................................................. 121
Batch control .................................................................................................................................................................... 88
Batch Mode .................................................................................................................................................................... 120
Tab.07: Meaning of the identifier in the rapid selection table (5) ...................................................................................... 27
Tab.08: Bin weigher parameters ...................................................................................................................................... 29
Tab.09: Operating keys for controlling hopper fill level ..................................................................................................... 30
Tab.10: Parameter sets: Usage and activation ................................................................................................................ 31
Tab.11: Keys for the calibration programs........................................................................................................................ 32
Tab.12: Keys in the VHM configuration dialog ................................................................................................................. 33
Tab.13: Fields for setting the address .............................................................................................................................. 33
Tab.14: Parameters for the display .................................................................................................................................. 34
Tab.15: Keys in the list of scales ...................................................................................................................................... 34
Tab.16: Setting startup routine ......................................................................................................................................... 35
Tab.17: Alternatives ......................................................................................................................................................... 35
Tab.18: The details and process of taring ........................................................................................................................ 37
Tab.19: The details and process of zero setting............................................................................................................... 38
Tab.20: The details and process of taring for the bin weigher .......................................................................................... 38
Tab.21: The details and process of checking the weight of the bin weigher .................................................................... 39
Tab.22: The details and process of improving bin level regulation ................................................................................... 40
Tab.23: The details and process of taring the 2nd bin weigher ........................................................................................ 40
Tab.24: The details and process of checking the weight of the 2nd bin weigher.............................................................. 41
Tab.25: Suggested sequence for initial start-up ............................................................................................................... 47
Tab.26: Basic parameters ................................................................................................................................................ 48
Tab.27: Carrying out calibration ....................................................................................................................................... 49
Tab.28: Suggested actions............................................................................................................................................... 53
Tab.29: Using parameter sets in the DISOCONT Tersus................................................................................................. 55
Tab.30: Abbreviations frequently used in parameters ...................................................................................................... 56
Tab.31: Step-by-step specification of signal links............................................................................................................. 57
Tab.32: Signal sources and their descriptions.................................................................................................................. 57
Tab.33: Meaning of the columns ...................................................................................................................................... 57
Tab.34: The meaning of the Level parameter segment for an internal True signal .......................................................... 58
Tab.35: Example of the assignment of a binary channel to a physical input channel....................................................... 58
Tab.36: Event classes ...................................................................................................................................................... 58
Tab.37: Event groups ..................................................................................................................................................... 211
Tab.38: The states and points in time in the flow chart .................................................................................................. 232
Tab.39: The relevant parameters ................................................................................................................................... 233
Tab.40: Designations in the signal flow diagram ............................................................................................................ 235
Tab.41: Controller models and how they are used ......................................................................................................... 235
Tab.42: Signals, blocks and parameters in the constant controller ................................................................................ 237
Tab.43: Special cases for KP and TN parameters ......................................................................................................... 237
Tab.44: Set-up notes for parameters in the constant controller...................................................................................... 238
Tab.45: Characteristics in special operational states ..................................................................................................... 239
Tab.46: The control parameters for the step controller .................................................................................................. 241
Tab.47: Switching and operational states....................................................................................................................... 241
Tab.48: Some signals of the control logic....................................................................................................................... 242
Tab.49: Process: discharge weighing with a regulating loss-in-weight feeder................................................................ 244
Tab.50: The meaning of the abbreviations in the block diagram .................................................................................... 249
Tab.51: Legend .............................................................................................................................................................. 253
Tab.52: The meaning of the signals ............................................................................................................................... 255
Tab.53: Blocks available for processing binary signals .................................................................................................. 261
Tab.54: The length of the counting pulse ....................................................................................................................... 268
Tab.55: The significance of the pulse weight ................................................................................................................. 268
Tare (Bin) ............................................................................................................................................................... 142, 158
Tare Correction .............................................................................................................................................................. 106
Tare Correction Check ................................................................................................................................................... 106
Taring the 2nd bin weigher ............................................................................................................................................... 40
Taring the bin weigher ...................................................................................................................................................... 38
Taring the Coriolis flowthrough measurement .................................................................................................................. 37
Temperature Active ........................................................................................................................................................ 185
Temperature Cooling ..................................................................................................................................................... 186
Temperature Hysteresis ................................................................................................................................................. 186
Temperature MAX .......................................................................................................................................................... 186
Temperature Measurement ............................................................................................................................................ 185
Temperature Norming MAX ........................................................................................................................................... 185
Temperature Norming MIN............................................................................................................................................. 185
Temperature Norming Offset.......................................................................................................................................... 185
Temperature Norming Range......................................................................................................................................... 185
Test that the Control is Functioning .................................................................................................................................. 47
The Coriolis measuring principle ...................................................................................................................................... 10