Avg Measured Phase Current x √3 Calculation as per FAT:
Impedance measured at 415V = 17.80 Ω/phase Shield saturation = 2 Tesla
Over current factor = 5.87 Shield at rated current = 1 Tesla Air cored inductance = 15.52
Imp. at short circuit current = ((17.80*(2/1))+(15.52(5.87-(2/1))))/5.87 Ω/phase
= 16.29 Ω/phase
5.3. Criteria: With reference to FAT -0, +10% by calculation from measured results.
INSTRUMENT USED:
EQUIPMENT CALIBRATION CALIBRATION
SL.NO DESCRIPTION MAKE SL.NO ON DATE DUE DATE 1 MULTIMETER FLUKE 34710194 04.02.2024 04.02.2025 LEAKAGE 2 FLUKE 3591022 01.02.2024 01.02.2025 CLAMP Remark: Calculated Impedance at short circuit current found satisfactory, compared with FAT guarantee value 16.0 Ω/phase.