Gfa SVF Di501 e

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

Project:

Customer:
Engineer:
Pump Manufacturer:

Technical Data
Submittal Document
Model GFA
Across the Line Start
Electric Fire Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

Note: The drawings included in this package are for controllers covered under our standard
offering. Actual AS BUILT drawings may differ from what is shown in this package.
February 2020
Technical Data
Model GFA Electric Fire Pump Controller Options

1M
From normal incoming 3L3 T3
power through

M
Disconnecting Means 3L2 T2
(IS/CB)
3L1 T1

CR4
1M

3L1 3L2

Standard & Built to NFPA 20 (latest edition)


Certification □ CE Mark: Various EN, IEC & CEE directives and standards
Protection Rating
IP55

Enclosure Paint Specifications


Accessories • Red RAL3002
• Bottom entry gland plate • Powder coating
• Glossy textured finish
• Isolating switch and circuit breaker:
Isolating switch rated not less than 115% of motor full load current
Disconnecting Circuit breaker continuous rating not less than 115% of motor full load current
Means Overcurrent sensing non-thermal type, magnetic only
Instantaneous trip setting of not more than 20 times the motor full load current
• Individual operating handles
• Flange mounted
Emergency Start • Pull and latch activation
Handle • Integrated limit switch
• Across the line start (direct on line)
• Operate shunt trip to open circuit breaker
Locked Rotor • Factory set at 600% of motor full load current
• Trip between 8 and 20 seconds
Electrical • Voltage phase to phase (normal power)
Readings • Amperage of each phase when motor is running
Pressure • Continuous system pressure display
Readings • Cut-in and Cut-out pressure settings

This is a Marketing document. Please consult factory for more information.


February 2020 2
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GFA Electric Fire Pump Controller Options

• Pressure readings with date stamp


Pressure and • Event recording with date stamp
Event recorder • Under regular maintained operation, events can be stored in memory for up to 5 years.
• Data viewable on operator interface display screen
• Pressure transducer for fresh water application
• Pressure sensing line connection 1/2” Female NPT
Pressure Sensing • Rated for 0-500PSI working pressure (calibrated at 0-300psi)
• Externally mounted with protective cover
• Power available • Phase unbalance • Deluge valve start
• Phase reversal • Locked rotor • Remote automatic start
• Motor run • Fail to start • Remote manual start
Visual Indications
• Pump room alarm • Low discharge pressure • Overcurrent
& Alarms
• Motor trouble • Pump on demand/Automatic start • Undercurrent
• Phase loss • Emergency start • Undervoltage
• Low water level • Manual start • Overvoltage
SPDT-8A-250V.AC
• Power available
• Phase reversal
Remote Alarm • Motor run
Contacts • Common pump room alarm
• Overvoltage • Undervoltage • Phase unbalance
• Common motor trouble
• Overcurrent • Undercurrent • Fail to start
• Embedded microcomputer with software PLC logic
• 4.2” color touch screen (HMI technology)
ViZiTouch Light
• Upgradable software
Operator Interface
• Expandable storage
• Multi-language
• Start on pressure drop
Automatic Start
• Remote start signal from automatic device
• Start pushbutton
• Run test pushbutton
Manual Start
• Deluge valve start
• Remote start from manual device
• Manual with Stop pushbutton
Stopping
Operation • Automatic after expiration of minimum run timer **
• Minimum run timer **(off delay)
Field Adjustable &
Timers • Sequential start timer (on delay)
Visual Countdown
• Manual test timer
• Pressure
Actuation
• Non-pressure
Visual Indication
• Automatic
Mode
• Non-automatic

** Can only be used if approved by the AHJ

February 2020 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 3
Technical Data
Model GFA Electric Fire Pump Controller Options

A4 Flow switch provision C20 Manual start alarm contact (DPDT)


A9 Low zone pump control function C21 Deluge valve start alarm contact (DPDT)
A10 Middle zone pump control function C22 Remote automatic start alarm contact (DPDT)
A11 High zone pump control function C23 Remote manual start alarm contact (DPDT)
Non-pressure actuated controller w/o pressure High pump room temperature alarm contact
A13 C24
transducer and run test solenoid valve (DPDT)
Lockout/interlock circuit from equipment Additional visual and alarm contact (Specify
A16 Cx
installed inside the pump room function) (DPDT)
Built in alarm panel same as B11 but 220- Low suction pressure transducer for fresh
B11B
240VAC supervisory power D1 water rated at 0-300PSI with visual indication
High motor temperature c/w thermoster relay and alarm contact
B19A
and alarm contacts (DPDT) Low suction pressure transducer for sea water
High motor temperature c/w PT100 relay and D1A rated at 0-300PSI with visual indication and
B19B alarm contact
alarm contacts (DPDT)
Ground fault alarm detection c/w visual Addition of run test solenoid valve for fresh
B21 D5E
indication and alarm contact (DPDT) water rated for 0-500psi
C1 Extra motor run alarm contact (DPDT)
C4 Periodic test alarm contact (DPDT) Addition of run test solenoid valve for sea
D5F
water rated for 0-500psi
C6 Low discharge pressure alarm contact (DPDT)
Low pump room temperature alarm contact D14 Anti-condensation heater & thermostat
C7
(DPDT) D14A Anti-condensation heater & humidistat
Low water reservoir level alarm contact
C10 Anti-condensation heater & thermostat &
(DPDT) D14B
humidistat
High electric motor temperature alarm contact
C11
(DPDT) D15 Tropicalization
High electric motor vibration c/w visual
C12
indication and alarm contact (DPDT) D18 CE Mark with factory certificate
Pump on demand / automatic start alarm
C14 Motor heater connection (external single
contact (DPDT) D27
phase power source and heater on/off contact)
C15 Pump fail to start alarm contact (DPDT) Motor heater connection (internal single phase
D27A
C16 Control voltage healthy alarm contact (DPDT) power source and heater on/off contact)

Flow meter valve loop open c/w visual D28 Customized drawing set
C17
indication and alarm contact (DPDT)
Field programmable I/O board -
High water reservoir level c/w visual indication D34A
C18 8 Input / 5 output
and alarm contact (DPDT)
C19 Emergency start alarm contact (DPDT) D37 Window kit for operator interface

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

This is a Marketing document. Please consult factory for more information.


February 2020 4
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GFA Electric Fire Pump Controller Options

L01 Other language and English (bilingual)


L02 French
L03 Spanish
L04 German
L05 Italian
L06 Polish
L07 Romanian
L08 Hungarian
L09 Slovak
L10 Croatian
L11 Czech
L12 Portuguese
L13 Dutch
L14 Russian
L15 Turkish
L16 Swedish
L17 Bulgarian
L18 Thai
L19 Indonesian
L20 Slovenian
L21 Danish
L22 Greek
L23 Arabic
L24 Hebrew
L25 Chinese

February 2020 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 5
Technical Data
Model GFA Electric Fire Pump Controller Options

ViZiTouch Light Operator Interface

3
1

BLACK PANTONE 82-3-2 C

4 5 6 7 8
8

9
10

11 12

1 - Power on LED 8 - USB port


2 - Color touch screen 9 - START button
3 - Alarm LED 10- Contextual navigation pad
4 - HOME page button 11 - STOP button
5 - ALARM page button 12 - RUN TEST button
6 - CONFIGURATION page button
7 - HISTORY page button

This is a Marketing document. Please consult factory for more information.


February 2020 6
Manufacturer reserves the right to modify this information without notice
0 1 2 3 4 5 6 7 8

Electric Fire Pump Controller Optional

A
Full Voltage / Across The Line Model: GFA
REV.
0. FIRST ISSUE
DESCRIPTION DD/MM/YY
04/02/16 Drawing No.
A
1. TITLE BLOCK INFORMATION CHANGED 11/11/16
Dimension Built as per NFPA 20-2013 standard 2. REVISED LOGO 18/06/18 GFA-DI501 /E
GFX-S1-ViZi

834 [33"]
300 [113
4"]
19 [3
4"]
B 1"]
750 [292 B

25 [1"]

C C
See Notes

PT1
Power Table
1"]
900 [352
D D
1"]
1002 [392
Voltage Min Max
1

1"]
493 [192 O .

50 HP 100 HP
E 220 - 240 E

30 kW 55 kW

75 HP 150 HP
Sensing Line Door Swing 380 - 400 - 415
F Connection 1/2 " F.NPT F
988 [39"] 55 kW 110 kW
1"]
85 [34

23 [1"]
1"]
80 [34

G G
194 [73
4"]
325 [123
Notes:
4"] 1"]
140 [52
- IP55 assembly.
- All dimensions are in millimeters [Inches].
- Center of ViZiTouch screen: 582 [23"] from bottom.
- Paint: textured red RAL 3002.
H - Bottom conduit entrance through removable gland plate recommended. H
350 [133
4"] 200 [8"] - Use watertight conduit and connectors only.
- Protect equipment against drilling chips.
- Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.
I I
PROJECTION

0 1 2 3 4 5 6 7 8
Copyright © 2020 Tornatech Inc.All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
P.1
0 1 2 3 4 5 6 7 8

Electric Fire Pump Controller Optional

A
Full Voltage / Across The Line Model: GFA
REV.
0. FIRST ISSUE
DESCRIPTION DD/MM/YY
01/02/16 Drawing No.
A
Wiring schematic Built as per NFPA 20-2013 standard
1.
2.
TITLE BLOCK INFORMATION CHANGED
REVISED LOGO
11/11/16
18/06/18 GFA-WS500 /E
GFX-S1-ViZi

IS
1L3

B
1L2 J11
P1 To I/O Electric Board B
1L1

J6 P1
(P.2 / G5)
4

CB1 ST To J45 VIZITOUCH


(P.2 / F4)
2
Main Board
C P2 C
J3

(+) J16
(-)

D D
J13 J14
3L1

COM

COM

COM

COM

COM

COM

COM

COM
GND
24V

DI0

DI1

DI2

DI3

DI4

DI5

DI6

DI7
3L2
3L3
To J57 (P.2/F8)

1M
E E
3L3
3L2
3L1

17

F F

CR4
3L1 (P.2/E8)
CT3 68 Black
69 White
G G
CT2 66 Black
67 White To J76 (P.2/F6)

CT1 64 Black
65 White

H H

1M**

I T1 T2 T3
Note: I
- Drawing for information only.
M Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.
** Contact closes when emergency starts is in "ON" position.
0 1 2 3 4 5 6 7 8
Copyright © 2020 Tornatech Inc.All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
P.2
0 1 2 3 4 5 6 7 8

Electric Fire Pump Controller Optional

A
Full Voltage / Across The Line Model: GFA
REV.
0. FIRST ISSUE
DESCRIPTION DD/MM/YY
01/02/16 Drawing No.
A
Wiring schematic Built as per NFPA 20-2013 standard
1.
2.
TITLE BLOCK INFORMATION CHANGED
REVISED LOGO
11/11/16
18/06/18 GFA-WS500 /E
GFX-S1-ViZi

B B

C C

D XTR1 D
1
X1 H2
PT1 24VAC
3L2 To
X2 H1 3L1-2-3
3 3L1 (P.1 / D1)
To
To ST
E
CR4 (P.1 / C1)
CT1-2-3
(P.1 / G2) E
3L1 To CR4
1M 1M (P.1 / G2)
CR4-1
CR4-2
1M-1
1M-2
1M-3

White
Black

3L3

3L2
3L2

3L1
3L1
Red

4
2

1
3

67
69
68

66
65
64
PT1-IN

PT2-IN

7 5 3 1 7 6 5 4 3 2 1
14
11
12

12
11
14

12
11
14

AI4-IN

AI3-IN

2 1
SV1

GND

GND

REC
(+)

(+)

(+)

(+)

ST2
(-)

(-)

(-)

(-)

N
L
J8

+
G

F
J1
8 6 4 2 J57 F
J18 J36 J38
J76 J53
J14 J15 J16 J17 J43 J45 J44 J47

P1
I/O Electric Board To ViZiTouch (P.1 / C8)
Main Board
G G
(Fail Safe)
J25
J19 J40 J42 J37 J39 J41
TB1 TB2 TB3 TB4 TB5 21 23 25 27 29 31 33 35 37
22 24 26 28 30 32 34 36 38
14
11
12

14
11
12

14
11
12

14
11
12

14
11
12

14
11
12

LS1 **

t
rm
n

al

LS1-1
le
le

ou
t

w
H

r
H
Ru

Sta

Lo
ers

ub
ab

J1* J2*

ck
Ala

Lo
LS1-2

oir
Tro
il

l
tor

ev

ua
va

rt

e
erv
om

Sta

alv
n
eR
Mo

rA

Ma
tor

es
eV
Ro

to
we

rR
as

Mo

te

Au

lug
mo

te
mp
Ph
Po

te

De

Wa
Re

mo
Pu

Re
I I

* Remove this jumper to use this feature


** Contact closes when emergency start is in "ON" position.
0 1 2 3 4 5 6 7 8
Copyright © 2020
2020 Tornatech Inc.All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
P.3
0 1 2 3 4 5 6 7 8

Electric Fire Pump Controller Optional

A
Full Voltage / Across The Line Model: GFA
REV.
0. FIRST ISSUE
DESCRIPTION DD/MM/YY
01/02/16 Drawing No.
A
Terminals diagram Built as per NFPA 20-2013 standard
1.
2.
TITLE BLOCK INFORMATION CHANGED
REVISED LOGO
11/11/16
18/06/18 GFA-WS500 /E

Field Connections Field Connections Alarm Contacts


GFX-S1-ViZi

Terminals Wire Size:


Terminals Wire Size: 12 - 24 AWG
Normal Power Connections 12 - 24 AWG 0.5 Nm
0.5 Nm
B B
I/O Electric Board
I/O Electric Board Normally Opened
Closes to alarm J19 - 14

Remote Manual Start


23
Motor Run Normally Closed J19 - 11
24 Opens to alarm J19 - 12

Control Terminal Strip


25
GND
1M
GND
IS1 Lockout 26 Normally Closed
T1 T2 T3 L1 L2 L3 Opens to alarm J40 - 14
27
C Remote Auto Start *J1 Power Available Normally Opened J40 - 11 TB1 C
28
(Fail Safe) Closes to alarm J40 - 12
29
Deluge Valve *J2
Ground 30 Normally Opened
M Incoming Power 31
J25 Closes to alarm J19 - 14
Water Reservoir Low Phase Reversal Normally Closed J19 - 11 TB2
32
Opens to alarm J19 - 12
33
34 Normally Opened
35 Closes to alarm J19 - 14
D Pump Room Normally Closed J19 - 11
D
36
Alarm TB3
Opens to alarm J19 - 12
37
38
Normally Opened
Closes to alarm J19 - 14
Motor Trouble Normally Closed J19 - 11 TB4
Opens to alarm J19 - 12

E E

F F

G G

H H

I I

* Remove this jumper to use this feature

0 1 2 3 4 5 6 7 8
Copyright © 2020 Tornatech Inc.All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.