EMM R3 VAEMM 3 VAIM425 Uv3.1
EMM R3 VAEMM 3 VAIM425 Uv3.1
IM425-U v3.1
EMM-R3-VA
EMM-µ3-VA
MULTIFUNCTION VOLT/AMMETER
GENERAL
The digital Multifunction Volt/Ammeter series EMM-VA allow monitoring the
main electrical parameters present on a distribution line. The local display of
the electrical parameters is being made through 3 display with red LED,
which grant a good and simultaneous reading of various measures. The
intuitive selection of the measures to visualise, which are signalled by their
corresponding LED, completes a clear and simple front panel, which offer a
lot of useful information.
On top of the instantaneous measuring, these instruments visualise the
maximum peak of the main parameters (maximum peak and maximum
demand or maximum average value).
Multifunction Volt/Ammeter series EMM-VA replace, in an unique device, all
the functions of voltmeters, ammeters and frequency meters, permitting a
great economic saving, due to reducing of dimension and wiring, so as
optimising the instruments management, since one has most of all in one, for
electrical boards, switch-boards and Gen-Sets.
AVAILABLE MODELS
EMM-R3-VA
EMM-µ3-VA
ACCESSORI ED OPZIONI
accessories: transparent cover for frontal protection.
INTRODUCTION
The EMM-R3-VA and EMM-µ3-VA models are only featured for visualising the electrical parameters. The power supply is
taken from the measured voltage or self-supplied.
MESURED PARAMETERS
Parameters Measuring units Identification Symbols
Phase and three phase voltage [V-kV] V L1-N V L2-N V L3-N V L-N
Phase to phase and three phase system voltages [V-kV] V L1-L2 V L2-L3 V L3-L1 V L-L
Phase and three phase currents [A-kA] I L1 I L2 I L3 I
Frequency [Hz] Hz L1
Hour meter [hr] hr1 hr2 hr3
STORED PARAMETERS
Instantaneous Values:
Maximum phase voltage [V-kV] V L1-N max V L2-N max V L3-N max
Minimum phase voltage [V-kV] V L1-N min V L2-N min V L3-N min
Maximum phase to phase voltage [V-kV] V L1-L2 max V L2-L3 max V L3-L1 max
Maximum phase current [A-kA] I L1 max I L2 max I L3 max
Measured value in 15’
Average phase current (maximum demand) [A-kA] I L1 max (avg) I L2 max (avg) I L3 max (avg)
checks Check phase rotation
EMM
INSERTION ON THREE-PHASE
LINE WITH 3 or 4 WIRES
On line with 3 wires (without neutral or
with neutral not supplied)
the N terminal must not be connected
S1
L1 LOAD
P1 S1
L2
P1 S1 S2
L3
P1 P2
N
S1
L1 LOAD
P1 S1
L2
P1 S1 S2
L3
P1 P2
N
S1
L1 LOAD
P1
L2
S1 S2
L3
P1 P2
N
EMM
VOLTAGE INSERTION ON
THREE PHASE LINE WITH 3 WIRES
WITH 2 VT
S1 S2 S1 S2
P1 P2 P1 P2
L1 LOAD
L2
L3
L1 LOAD
L2
S1 S2
L3
P1 P2
EMM
INSERTION ON SINGLE PHASE
LINE
Only for model with phase-neutral
power supply (Vaux L3-N)
LOAD
S1 S2
L
P1 P2
N
E D C E D C
MAX
MAX
L1 VL-N
L1-2 k L1 VL-N
L1-2 k
VL-L VL-L
L2 B L2
B
L2-3
k
A max
avg
L2-3
A
max
avg
k
Hz A L
L3
L3-1
h
L L3
L3-1
Hz A
h
DESCRIPTION:
A: Push-button for visualising of the three phase system parameters with the corresponding indication LED.
By pressing during 5 seconds, user accedes to programming the instrument (SETUP).
B: Push-button for selecting the measures to visualise on display E.
C: LED’s for indicating the measures visualised on display E and the eventual multiplier factor of each parameter
(reading k =kilo x1000).
D: LED for indicating the visualisation of the memorised peak values.
E: Three displays for visualising the measures, subdivided by phases. Should the LED L be glowing, it indicates
the three-phase system value of the selected parameter.
A+B: By pressing the two keys simultaneously at the visualisation mode, it accedes to the visualisation of the
memorised peak values.
SET CT Increase
Set CT ratio
from 1 to 2000 Decrease
SET VT Increase
Set VT ratio
from 0.1 to 400.0 Decrease
seT SCHROLL ON
OFF
Entry to menu:
seT UP seT Up
RESET
SET DO1
SET DO2
SET HR_
--- OFF OFF (the visualization depends on the settings and the I/O status)
To enable the chosen type, press the B key to change the indication on display G from NO to yes. Confirm enabling
cancellation, by pressing the A key. The indication on E display change from yes to --- .
ALR Dl Decrease
With only the HI threshold set, the alarm condition is activated when the parameter set in alarm exceed the threshold.
The digital output is enabled only if the alarm condition remain activated for all delay time set. From the activation of the
digital output, the restore is automatic when the parameter decreases below the hysteresis value.
Digital
output
Alarm
With only the LO threshold set, the alarm condition is activated when the parameter set in alarm drop below the
threshold. The digital output is enabled only if the alarm condition remain activated for all delay time set. From the
activation of the digital output, the restore is automatic when the parameter grow above the hysteresis value.
Digital
output
Alarm
Functioning for
t < delay delay
dropping above
Hysteresis LO
minimum threshold
Threshold LO
With both LO and HI threshold set, the alarm condition is activated when the parameter set in alarm is outside from the
values band limited by LO and HI thresholds. The digital output is enabled only if the alarm condition remain activated for
all delay time set. From the activation of the digital output, the restore is automatic when the parameter return inside the
values band limited by LO and HI thresholds.
Digital
output
seT UP seT Up
RESET
SET DO1
SET DO2
SET HR_
--- OFF OFF (the visualization depends on the settings and the I/O status)
HR_ HI Decrease
VARIABLE LIST
VLN three-phase voltage
AMP three-phase current
VLL phase to phase voltage
FRE frequency
PH_ check the rotation phase voltage connection
By pressing the A key the LED L is enabled and the system values are displayed.
Please note that the unit value may be expressed in kilo, when the corresponding LED C are glowing (indicated in the
front plate as k).
The visualised frequency is referred to the line L3.
L1 VL-N L1 VL-N
k k
VL-L VL-L
L2 L2
k
A k
A
L3 Hz Hz
h
L L3 L
h
EMM-R3-VA EMM-R3-VA
In balanced three phase system mode (BALANC) are available only the visualization [7] and [8]:
In single phase mode (!PH L3) the pages displayed are the following:
L1 VL-N L1 VL-N
k k
VL-L VL-L
L2 L2
k
A k
A
L3 Hz Hz
h
L L3 L
h
EMM-R3-VA EMM-R3-VA
9 56
96 Drill panel
MAX
L1 VL-N R3
L1-2 k
VL-L
L2
92
L2-3
A
96
max
90
k
96
avg
EMM-R3-VA L3 Hz
L3-1
h
L
92
electrical multi meter
20
72 Drill panel
MAX
VL-N R3
L1
888
L1-2 k
VL-L
L2
888
68
65,8
max
L2-3
A avg
72
k
EMM-µ3-VA L
L3
888
L3-1
Hz
h
68
electrical multi meter
9 81 14
For other applications, please contact with CONTREL technical assistance department.