Air System Sizing Summary for mzz

Project Name: bancoex mohedano 05/17/2024


Prepared by: UNICLIMA 04:52p. m.

Air System Information


Air System Name mzz Number of zones 1
Equipment Class CW AHU Floor Area 1821,3 ft²
Air System Type SZCAV Location Caracas, Venezuela

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 14,6 Tons Load occurs at Jun 1600
Total coil load 175,4 MBH OA DB / WB 89,9 / 75,9 °F
Sensible coil load 150,3 MBH Entering DB / WB 76,5 / 62,8 °F
Coil CFM at Jun 1600 7712 CFM Leaving DB / WB 56,5 / 54,6 °F
Max block CFM 7712 CFM Coil ADP 53,0 °F
Sum of peak zone CFM 7712 CFM Bypass Factor 0,150
Sensible heat ratio 0,857 Resulting RH 46 %
CFM/Ton 527,6 Design supply temp. 55,0 °F
ft²/Ton 124,6 Zone T-stat Check 1 of 1 OK
BTU/(hr·ft²) 96,3 Max zone temperature deviation 0,0 °F
Water flow @ 10,0 °F rise 35,10 gpm

Central Heating Coil Sizing Data


Max coil load 3,6 MBH Load occurs at Des Htg
Coil CFM at Des Htg 7712 CFM BTU/(hr·ft²) 2,0
Max coil CFM 7712 CFM Ent. DB / Lvg DB 67,0 / 67,5 °F
Water flow @ 20,0 °F drop 0,36 gpm

Supply Fan Sizing Data


Actual max CFM 7712 CFM Fan motor BHP 0,00 BHP
Standard CFM 6961 CFM Fan motor kW 0,00 kW
Actual max CFM/ft² 4,23 CFM/ft² Fan static 0,00 in wg

Outdoor Ventilation Air Data


Design airflow CFM 447 CFM CFM/person 9,93 CFM/person
CFM/ft² 0,25 CFM/ft²

Hourly Analysis Program 5.11 Page 1 of 7


Zone Sizing Summary for mzz
Project Name: bancoex mohedano 05/17/2024
Prepared by: UNICLIMA 04:52p. m.

Air System Information


Air System Name mzz Number of zones 1
Equipment Class CW AHU Floor Area 1821,3 ft²
Air System Type SZCAV Location Caracas, Venezuela

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 7480 7480 4,11 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 145,8 Jun 1600 2,4 1821,3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
mzz pb bancoex 1 145,8 Jun 1600 7480 2,4 1821,3 4,11

Hourly Analysis Program 5.11 Page 2 of 7


Air System Design Load Summary for mzz
Project Name: bancoex mohedano 05/17/2024
Prepared by: UNICLIMA 04:52p. m.

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 89,9 °F / 75,9 °F HEATING OA DB / WB 65,7 °F / 48,8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 1658 ft² 84347 - 1658 ft² - -
Wall Transmission 2 ft² 10 - 2 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 1658 ft² 22438 - 1658 ft² 2377 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 1971 ft² 6667 - 1971 ft² 0 -
Ceiling 1821 ft² 8215 - 1821 ft² 0 -
Overhead Lighting 1821 W 4983 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3500 W 10885 - 0 0 -
People 45 8292 9225 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 145837 9225 - 2377 0
Zone Conditioning - 139765 9225 - 2935 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 7712 CFM 0 - 7712 CFM 0 -
Ventilation Load 447 CFM 6179 15842 447 CFM 614 0
Supply Fan Load 7712 CFM 0 - 7712 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 3% 4375 - 3% 71 -
>> Total System Loads - 150319 25067 - 3620 0
Central Cooling Coil - 150319 25085 - 0 0
Central Heating Coil - 0 - - 3620 -
>> Total Conditioning - 150319 25085 - 3620 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page 3 of 7


System Psychrometrics for mzz
Project Name: bancoex mohedano 05/17/2024
Prepared by: UNICLIMA 04:52p. m.

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 89,9 0,01816 447 400 6179 15842
Vent - Return Mixing Outlet 76,5 0,01037 7712 1315 - -
Central Cooling Coil Outlet 56,5 0,00961 7712 1315 150319 25085
Central Heating Coil Outlet 56,5 0,00961 7712 1315 0 -
Supply Fan Outlet 56,5 0,00961 7712 1315 0 -
Cold Supply Duct Outlet 57,1 0,00961 7480 1315 - -
Zone Air - 76,3 0,00989 7480 1373 139765 9225
Return Plenum Outlet 76,3 0,00989 7480 1373 0 -
Duct Leakage Air Outlet 56,5 0,00961 231 1315 - -
Return Duct Outlet 75,7 0,00989 7712 1371 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,975 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4284,3 BTU/(hr-CFM)
Site Altitude = 2808,4 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 145837 Cooling 139765 76,3 7480 1373 0 0

Hourly Analysis Program 5.11 Page 4 of 7


System Psychrometrics for mzz
Project Name: bancoex mohedano 05/17/2024
Prepared by: UNICLIMA 04:52p. m.

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 65,7 0,00425 447 400 -614 0
Vent - Return Mixing Outlet 67,0 0,00425 7712 554 - -
Central Cooling Coil Outlet 67,0 0,00425 7712 554 0 0
Central Heating Coil Outlet 67,5 0,00425 7712 554 3620 -
Supply Fan Outlet 67,5 0,00425 7712 554 0 -
Cold Supply Duct Outlet 67,5 0,00425 7480 554 - -
Zone Air - 67,1 0,00425 7480 563 -2935 0
Return Plenum Outlet 67,1 0,00425 7480 563 0 -
Duct Leakage Air Outlet 67,5 0,00425 231 554 - -
Return Duct Outlet 67,1 0,00425 7712 563 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,975 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4284,3 BTU/(hr-CFM)
Site Altitude = 2808,4 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -2377 Deadband -2935 67,1 7480 563 0 0

Hourly Analysis Program 5.11 Page 5 of 7


System Psychrometrics for mzz
Project Name: bancoex mohedano 05/17/2024
Prepared by: UNICLIMA 04:52p. m.

Location: Caracas, Venezuela


Altitude: 2808,4 ft.
Data for: June DESIGN COOLING DAY, 1600
0,020
1. Outdoor Air
2. Mixed Air 1
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Duct Heat
6. Room Air
7. Return Duct Outlet
0,016

Specific Humidity ( lb/lb )


0,014

0,012
2
35 7
4 0,010
6
0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page 6 of 7


System Psychrometrics for mzz
Project Name: bancoex mohedano 05/17/2024
Prepared by: UNICLIMA 04:52p. m.

Location: Caracas, Venezuela


Altitude: 2808,4 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Central Heating Coil Outlet
4. Supply Fan Outlet 0,018
5. Duct Heat
6. Duct Heat
7. Room Air
8. Return Duct Outlet 0,016

Specific Humidity ( lb/lb )


0,014

0,012

0,010

0,008

0,006
1 2 37
6 548 0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page 7 of 7