Relay Family By Application

Edison-Pro, Edison ιδεα and Edison relays are all available to solve Putting A New Face On Relay Protection
most protective requirements. The following table indicates the mix of
application solutions available for each family.

Edison-Pro Edison ιδεα Edison


Feeder Protection ■ ■ ■
Feeder Protection with ICSF1 ■ ■
Line Protection ■ ■
Differential
Transformer ■ ■2 ■
Rotating Machine ■
Low Impedance Based ■
Bus Transfer ■ ■ 2

Fast Bus Transfer ■


Capacitor Bank
Voltage Differential ■ ■2
Impedance Based ■ ■2
Neutral Current ■ ■
Neutral Voltage ■ ■2
Generator Protection ■2 ■2 ■
Generator Synchronizing ■
Islanding Detection ■
Synch-Check ■ ■ ■
Load Shedding ■ ■ ■
Voltage/Frequency Protection ■ ■ ■
Motor Protection ■
Programmable Logic ■ ■ ■
Custom Relays ■

1
Incipient Cable Splice Failure detection algorithm. Patent applied for.
2
Check with your Cooper Power System sales representative for availability

Protective Relays and Integrated Systems


Thomas A. Edison Technical Center
P.O. Box 100
11311 Adams Road
© 1999 Cooper Industries, Inc.
Idea™ ιδεα™ and Pro View™ are trademarks of Cooper Industries, Inc. Edison® is a
Franksville, WI 53126-0100
registered trademark of Cooper Industries, Inc. Modbus® is a registered trademark of Modicon. (877)-CPS-INFO fax:(262)-835-1515
Printed in USA Bulletin 99079 October 1999 New Issue www.cooperpower.com
The Best Idea in ιδεα iTP - Line Distance ιδεα iDP - Line Feeder
Protection Protection System Protection System
The Edison ιδεα iTP is a substation IED (Intelligent The Edison ιδεα iDP is a substation IED (Intelligent
Electronic Device) designed for Transmission Electronic Device) designed for Distribution Feeder
With the Edison® ιδεα™ relay platform, Cooper has advanced Protection, Monitoring, and Control. Protection, Monitoring and Control.
the state of the art in integrating control and protection. PROTECTION FEATURES PROTECTION FEATURES
In addition to offering a full suite of protective elements The Edison ιδεα iTP provides complete trans- The Edison ιδεα iDP provides complete feeder
in each relay, the ιδεα incorporates extensive front panel mission protection. Functions available include: protection. Several different scheme files are
■ Four zones each of phase and ground distance available for a variety of overcurrent relay appli-
targeting to allow for fast and efficient visual determination of the relay’s
protection; 3 forward and 1 reverse cations. Available protection functions include:
status, fault type, control modes, etc. The ιδεα also features eight front panel hot keys which permit ■ Zone 1 extension logic or 4th forward zone ■ Phase, Ground, and Negative-Sequence
the user to immediately access selected display screens, view metering, access settings, implement control ■ Directional phase, ground and negative- instantaneous, definite time, and inverse
functions, or even to perform local operations. Although the function of each hot key is predefined for each sequence overcurrent elements; instantaneous, time overcurrent
definite time, and inverse time overcurrent ■ Directional phase and ground elements
Edison ιδεα, these definitions may be changed by the user to meet application specific requirements.
■ Over/under voltage elements ■ Multiple-Step over/under frequency elements
■ Multiple-Shot programmable reclosing ■ Over/under voltage elements
■ Sync-check ■ Multiple-Shot programmable reclosing
MONITORING FEATURES ■ Out-of-step blocking logic ■ Sync-check
More than just protective relays, the Edison ιδεα ■ Targets and Hot-Keys accept customized text ■ Weak feed logic ■ Reverse Power
iTP and iDP provide vital monitoring and meas- inserts - use labels familiar to your field ■ Breaker fail-to-trip and fail-to close detection ■ Breaker fail-to-trip and fail-to close detection
urement of both continuous and operations- personnel ■ Switch-onto-fault logic ■ Fuse-Fail detection
related parameters. Exact capabilities depend ■ Communication aided tripping logic including ■ Incipient Cable Splice Failure detector
on the scheme file selected, and may include Flexible, Programmable
POTT, PUTT, DCUB, DUTT, DTT, DCB, Forward ■ Breaker monitoring
some or all of the following monitoring functions: ■ Preconfigured scheme files for common
Overreaching and Underreaching logic
■ Cooper’s exclusive ICSF (Incipient Cable Splice applications
■ Loss of Load Accelerated tripping
Failure) Detection System for underground ■ Virtually unlimited graphically programmable
■ Load encroachment logic
cable1 predicts water induced cable splice logic - Create whatever logic is necessary
■ Fault location
failures before they occur. ■ Fuse-Fail detection
Compact
■ High-Accuracy metering of Amps, Volts, Watts, ■ Eight setting groups
■ 2 fit side-by-side in 3U of 19” rack space
Vars, and a variety of other quantities
■ Distance-To-Fault calculation Common PC Software
■ Breaker health monitoring including slow/stuck ■ Windows® Software is included
breaker and I2t ■ Uses the same software as the Edison®-Pro
■ Interactive Oscillography relay and Kyle® Form 6 recloser control
■ Relay Replay
■ Sequence of Events Recording Plenty of Inputs and Outputs
■ Up to 10 Current/Voltage Inputs
CONTROL FEATURES ■ Up to 13 Contact Outputs (ALL Trip-Rated)
As a platform for substation automation, the ■ Up to 13 Contact Inputs
Edison ιδεα is unequalled. Incorporating the
Communications Ports
only true graphical programming language in
■ 1 Front Panel RS-232 Port
the protective relay field, the Edison ιδεα allows
■ 1 Rear Panel RS-232 Port
control logic of almost any level of complexity to
■ 1 Addressable Rear Panel RS-485 Port
be easily developed, tested, and downloaded. Future Edison ιδεα models-
■ All ports independent and capable of
The architecture of the Edison ιδεα allows iCP - Capacitor Bank Protection
up to 57600 baud
communication protocols to be downloaded as iGP - Generator Protection
well, providing flexibility of application today and Protocols iSC - Automatic Transfer Control
an upgrade path for any future communications ■ DNP3.0 and Modbus® included. No extra
iXP - Transformer Differential
developments. hardware or software to buy.

Rich Front Panel HMI


■ Front panel programming of settings
■ 25 Programmable LED Targets
■ 8 Programmable Hot-Keys

1
Patent applied for. 2 3 Edison® ιδεα
The World’s Most AVAILABLE PLUG-IN
Versatile Platform For MODULES

Protection, Monitoring ■ 6 Contact Inputs, 4 Contact


Outputs, RS-232,RS-485, IRIG-B,

and Control Transducer Output (standard on


all Edison-Pro relays)

■ 5 current, 3 voltage, 2 contact outputs


Cooper Power Systems’ Edison®-Pro protective relay is a fully programmable platform for
■ 4 current, 4 voltage, 2 contact outputs
the protection, monitoring, control and communications requirements of electrical power
systems. By tightly integrating these usually diverse functions, the Edison-Pro system makes it ■ 7 current, 2 contact outputs

possible to reduce the number of discrete devices, and the resulting inter-wiring needed, to ■ 8 voltage, 2 contact outputs
implement a protection and control scheme.
■ 8 Transducer channels, 5 contact outputs

■ 9 channels, can be used as contact


inputs or outputs
The Edison-Pro system is available in a wide RELAY REPLAY
selection of off the shelf configurations to address ■ Ethernet MMS/UCA2.0 communications
The Edison-Pro relay offers the unique ability to
many specific applications. Or, by using a unique
allow event records to be played back through the
Windows®-based GRAPHICAL programming tool,
relay scheme even with altered relay settings. This
Cooper can customize a scheme to exactly meet
permits incredible “What if?” scenario analysis
your requirements. The Edison-Pro systems’ twelve
permitting the user to determine how the relay
large LED Panel Meters, eight LED Targets and
would have behaved for the same fault if it were
four line LCD can all be programmed to perform
set differently.
the functions that you want, the way you want
them.

And because ProView™ software, the same pro-


gramming tool Cooper uses, is included with every
Edison-Pro relay, adding custom logic and making AVAILABLE SCHEMES
future improvements is easy. ProView software A variety of off-the-shelf schemes
even includes a built-in simulation function to allow are available in each of the following
the testing of scheme logic on a PC prior to families:
deployment in the field.
UTP - Line Distance Protection
MAKING OBSOLESCENCE UDP - Distribution Feeder Protection
OBSOLETE UCP - Capacitor Bank Protection
The unprecedented flexibility of the Edison-Pro UXP - Transformer Differential
system ensures that you get protection and control Protection
appropriate to your needs now and in the future.
ATS - Automatic Transfer and
Modular hardware and modular software make Protection
the Edison-Pro relay the most flexible system UMS - Universal Monitoring System
available! The Edison-Pro relay communications
Programmable Meters Offer a Wide Range of
functions are fully programmable. This provides
Flexibility
the ability to broadcast any measured or calculat-
The twelve large programmable front panel meters eliminate the need
ed quantity by any available protocol. The
for separate, expensive digital meters. Metered or calculated quantities
Edison-Pro relay can even support two or more
may be broadcast by communications protocols or transducer outputs to
protocols simultaneously if needed. Because of
provide a wide range of flexibility in interfacing with SCADA systems.
the modular hardware and software design, the
Edison-Pro can always be upgraded as your
communications needs change.

4 5 Edison®-Pro
Ease of Use. Simple Operation. MULTIPLE RELAY
PROTECTION SYSTEM
Robust Protection. Three Hallmarks Overcurrent Relays

of the Edison Line. IM30DRE Feeder relay with reclosing


DM30E Directional phase and directional
ground overcurrent relay
IM30AE Non-directional three phase
With the Edison line of relays, Cooper brings the industry a family of flexible, modular relays for the and ground overcurrent relay with
protection, control, and monitoring of your power system. From protection against faults to detecting automatic cold load pickup
abnormal conditions, Edison Relays provide a wide range of features to meet all of your protection needs. IM30BE Non-directional overcurrent relay
with dual setting groups
In addition to such workhorse applications as three phase overcurrent or feeder protection, the Edison line IM30DE Non-directional phase overcurrent
also includes such hard to find applications as a cost effective modular low impedance bus differential, a relay with directional ground
vector jump relay for generator islanding protection, and a whole selection of relays suitable for implement- Voltage/Frequency Protection
ing flexible load shedding schemes. UFD34 Three phase frequency and voltage
relay for load shedding
UFD14 Single phase frequency and voltage
SIMPLE OPERATION rear panel mounted RS-485 communications port FLEXIBLE
relay for load shedding
Designed with ease of use in mind, every one of with Modbus protocol standard. Mounting flexibility is also central to the Edison
the twenty plus Edison relays features the exact line. Relays may be ordered in cases that can UM30 Multi-function voltage and
same, exceptionally simple and intuitive user inter- Cooper provides a choice of two Windows based house one, two, or four Edison relays. Edison frequency relay
face featuring front panel setting and event communication packages for the Edison line. relays also feature field interchangeable Generator Protection and Control
records access. The common user interface EdisonComLite is a full featured package giving auto-ranging power supplies providing power UM30SV Vector Jump relay to detect
ensures that knowledge of one Edison relay is you the ability to view or change settings, view supply options from 24 to 240V, AC or DC.
generator islanding
equally applicable to every other relay in the line. live metering data, and examine relay status and The selection between 5A and 1A CT inputs are
MG30X Medium/Large generator
This speeds the learning process for new relays event data. EdisonComPro adds to the already simple jumper settings. With all of this, any
and reduces overall training time. powerful suite of capabilities in the Lite version by Edison relay can be completely reconfigured in protection relay
including: the field in a minimum of time, reducing the IM3GV Small/Medium generator
COMMUNICATION FLEXIBILITY ■ Ability to simultaneously communicate with number of spares required. protection relay
For those times when computer communication is more than one relay IM30G Small generator protection relay
desired, or when connecting the relay to an ■ Dial-up or TCP/IP access For those who desire to secure the benefits of SPM21 Generator synchronizing relay
automation system, each Edison relay includes a ■ Automatic data polling microprocessor relay technology without loosing Differential Protection
■ Automatic event polling the security of multiple relays protecting your
■ Ability to work with and set entire
M-LIB Modular Low Impedance bus
system, Edison relays can be pre-bundled in cost
groups of relays on- or off-line differential system
effective multi-relay enclosures.
MD32T Two winding transformer differential
MD32G Rotating machine differential
Other Relays
IM30CE Split wye capacitor bank unbalance
relay with phase and ground
overcurrent
SCM21 One or two line synch-check relay
IM30T Thermal/Overcurrent relay
MM30 Motor relay
MM30D Motor relay for ungrounded
systems
MU30 Measurement module
MX75 Mini-PLC
MW33 Power relay

Edison relays are available in a variety of case styles including single relay, dual relay, and
19” rack mount chassis which can hold up to four relays. The draw-out construction of the
Edison relays simplifies testing and maintenance.
6 7 Edison Relays ®