Notes: Matchline N.301000 MM For Con'T SEE DWG NO. &AA-E-ZA 522.4.1C7101X.1001 (EN)
Notes: Matchline N.301000 MM For Con'T SEE DWG NO. &AA-E-ZA 522.4.1C7101X.1001 (EN)
Notes: Matchline N.301000 MM For Con'T SEE DWG NO. &AA-E-ZA 522.4.1C7101X.1001 (EN)
ING 1. ALL DIMENSIONS, CO-ORDINATES AND ELEVATIONS ARE IN MILLIMETERS (MM), UNLESS
VAIL OTHERWISE SPECIFIED.
PRE D
W IN 2. ALL ELEVATIONS ARE WITH REFERENCE TO PLANT H.P.P OF +100000MM.
PLANT 3. MAIN EARTH GRID CONDUCTORS SHALL GENERALLY BE LAID AT A DEPTH OF MINIMUM
NORTH TR
U
MATCHLINE N.301000 mm FOR CON'T 1000 MM BELOW THE GROUND LEVEL, WHERE THIS FOULS WITH OTHER UNDERGROUND
EN
OR SEE DWG NO. &AA-E-ZA 522.4.1C7101X.1001 (EN) FACILITIES, EARTH GRID SHALL BE INSTALLED DEEPER.
TH 4. EARTHING CONDUCTOR AND EARTH ELECTRODE LOCATIONS ARE TENTATIVE ONLY, FINAL
LOCATION SHALL BE SUIT TO SITE CONDITION.
CONNECTED TO
45.9
.5
7 5. THE INSTRUMENT JUNCTION BOXES SHALL BE LOOP EARTHED WITH 6 SQMM COPPER
21
CABLE AND CONNECTED TO JUNCTION BOX RACK. THE INSTRUMENT JUNCTION BOX RACK
MAIN GRID
REFER SHALL BE EARTHED TO MAIN GRID / EARTH BAR THROUGH 25SQMM CABLE.
1 6. ELECTRICAL CONTRACTOR SHALL MEASURE THE EARTH RESISTANCE OF THE GRID AFTER
DETAIL-A
25mm² SUCCESSFUL INSTALLATION. ADDITIONAL EARTH ELECTRODES SHALL BE INSTALLED IF
95mm² i NECESSARY TO ACHIEVE PLANT EARTH RESISTANCE OF LESS THAN 1 OHM.
7. CABLE TRAYS SHALL BE BONDED TOGETHER AND CONNECTED TO MAIN GRID / EARTH BAR
PR AT THE BATTERY LIMIT OF MODULE AND AT THE BOUNDARY BETWEEN HAZARDOUS
EV
WI AILI
02 AND NON-HAZARDOUS AREA.
8. ALL PIPELINES SHALL BE BONDED TOGETHER AND CONNECTED TO THE MAIN GRID /
ND NG 45.9
7 1 EARTH BAR AT THE BATTERY LIMIT OF MODULE AND AT THE BOUNDARY BETWEEN
EL+ 110500 HAZARDOUS AND NON-HAZARDOUS AREA.
STD 25mm² 9. THE CATHODIC PROTECTION EQUIPMENT (AJB, NJB, PDB, NDB, TEST STATIONS) LOCATIONS
02 E2QTB
ARE SHOWN IN VENDOR DRAWING 0012EP9510 E-ZA 4EF.0801.001 (EN), THOSE EQUIPMENT
SHALL BE EARTHED TO MAIN GRID / EARTH BAR THROUGH 25SQMM CABLE.
10. REMOVABLE FENCE AND GATE SHALL BE EARTHED USING 25SQMM CABLE FROM NEARBY
( TYP. 02 ) EARTH BAR / MAIN GRID AS PER INSTALLATION HOOKUP NO. EEC-E1QGC.
2
LEGEND
240mm² b 240 sq.mm BARE CU CABLE CONDUCTOR MAIN EARTHING GRID
240mm² i
240 sq.mm PVC INSULATED CU CABLE CONDUCTOR MAIN EARTHING GRID
CONNECTED TO
B1RSB
TYP. DETAIL FOR CABLE TRAY EARTHING 25mm² 25 sq.mm PVC INSULATED CU CABLE EARTH CONDUCTOR
( TYP. 04 )
MAIN GRID
Looking North 6mm² 6 Sq.mm PVC INSULATED CU CABLE EARTH CONDUCTOR
3 02
25mm² 95mm² Al
95 sq.mm ALUMINIUM CONDUCTOR FOR LIGHTNING CONNECTIONS
95mm² i
AIR TERMINAL
STD
STANDARD HOOK-UP DETAILS
XXX
INTERFACE TEST CLAMP
2 ( TYP. XX ) TYPICAL MULTIPLIER
( TYP. 04 )
NO. DRAWING TITLE DRAWING NO.
MAIN GRID
KEY PLAN
AILING
PREV G
WIND AILIN
PREV
WIND
42.42
21.5
PR
PR 25 EV
EV .05 AIL
AIL WI ING
WIN ING ND 46
9502Y02
IG BACK-UP UNIT
(24m X 10m)
M
*
PRODUCTS
STD
02
*
**
E2QBP-1
CONNECTED TO
**
**
( TYP. 02 )
MAIN GRID
REFER
7 DETAIL-A
25mm²
95mm² i THIS DRAWING
2000
4000
6000
8000
10000
LE Project Code LGS Project Code
Singapore SLUP
Looking Plan LE Doc. No. LGS Doc. No.
&AA-E-ZA 522.4.1C5901X.1001 (EN) -