ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PHILIPPINE ELECTRICAL
CODE, WITH THE RULES AND REGULATIONS OF NATIONAL AND LOCAL AUTHORITIES CONCERNED IN THE
ENFORCEMENT OF ELECTRICAL LAWS AND WITH THE RULES AND REGULATIONS OF THE UTILITY COMPANY
CONCERNED A B B' C D
2. SERVICE VOLTAGE TO THE BUILDING SHALL BE 230V, 60HTZ, SINGLE PHASE THREE WIRE SYSTEM. 8462
4. ALL INSTALLATION SHALL BE CONCEALED FROM VIEW, WIRING SHALL BE ENCASED IN POLYVINYL
CHLORIDE (PVC) SCHEDULE 40 EXCEPT POWER AND TELEPHONE SERVICE ENTRANCE WHICH SHALL BE IN
RIGID STEEL CONDUIT UNLESS OTHERWISE NOTED.
1
5. MINIMUM WIRE AND CONDUIT SHALL BE 3.5 MM TW AND 12 MM TRADE SIZE, RESPECTIVELY UNLESS
OTHERWISE SPECIFIED.
6. PULL BOXES OF APPROPRIATE SIZES SHALL BE PROVIDED, EVEN IF NOT INDICATED IN DRAWINGS TO
3760
4160
4160
ACCOMODATE THE NUMBER OF SPLICES OR WIRES.
7. ALL FLOURESCENT LAMPS SHALL BE PROVIDED, WITH POLYESTER FILLED, PRE HEAT THERMALLY
PROTECTED HIGH POWER FACTOR BALLASTS.
2
8. ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE APPROPRIATE FOR BOTH LOCATION AND
INTENDED USE.
2650
2450
2450
9. LIGHT CONTROL SWITCHES SHALL BE RATE 10 AMP 250 VOLTS AND SHALL NOT CARRY LOAD GREATER
THAN 50 AMPS, LIGHT SWITCHES SHALL BE INSTALLED FOR OPERATION WITH VERTICAL MOTION.FOR
11770
EACH SPARE CIRCUIT IN PANEL BOARD, PROVIDE EMPTY 19 MM DIA. RISER TERMINATING IN A 50 MM X 100
3
MM OCTAGONAL BOX ABOVE CEILING.
14758
10.ELECTRICAL INSTALLATION SHALL BE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED ELECTRICAL
2598
ENGINEER
3400
MOUNTING HEIGHTS:
5580
1. PANEL BOARD - 1.70m FROM TOP OF PANEL BOARD TO
4
FINISH FLOOR LINE.
2950
1960
2. LIGHT SWITCH - 1.37 M FROM CENTER OF DEVICE TO FINISH
FLOOR LINE
5
3. CONVENIENCE OUTLET - 0.30 FROM CENTER OF DEVICE TO
994
COUNTER TOP OR FLOOR FINISH LINE.
2600
4. TELEPHONE OUTLET 0.30 m FROM CENTER TO OUTLET TO
FIN FLR LINE.
1350
S2
5. RANGE OUTLET - 0.60 m FROM CENTER OF OUTLET TO FIN
FLR LINE
8712
7. SPECIAL PURPOSE OUTLET AS REQUIRED BY EQUIPMENT
SERVICE.