Baneswor Commercial UPDATED - 11-22 - Electrical - Working Drawing

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 19

ELECTRICAL DRAWINGS

COMMERCIAL BUILDING, BANESHWOR - 10, KATHMANDU


N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU

LEGEND CLIENT: MRS. BINITA BHAT

3W
LED circular panel light-3W

Led suspended tubelight 20W GENERAL NOTES


20 A DP metal clad recessed type socket for air con connection 1. These drawings indicate in general
Led square ceiling mounted 18W the projects in terms of Architectural
20 mm dia Conduit with 2 x 6 sq mm + 1 x 1.5 Sq mm Cable design intent with the dimensions of
LED circular panel light-12W (2x7/20+1 x3/20) the building. As indicated, the
contractor shall furnish all items
Led wall light-15W Indoor Oudoor unit Linkin Pipe required for the proper execution and
completion of the work.
LED circular panel light-6W 2. Contractor shall examine and verify
Drain out PEX pipe in natural gravity flow all dimensions and conditions. both
LED Pandent Light-12W on the plans and in the field, and be
responsible for any adjustments and
Mirror Light-11W Wall Mount Type Split Aircon (Indoor) correction.
3. Refer to engineer's detail for sizes
Wall Fan and spacing of all beams, columns,
slabs, foundations and trusses.
4. All interior dimensions are given
1X4 40W LED PANEL from rough brick face to rough brick
20A 3-pin Air Conditioning Power Socket face.
Ceiiling Cassette type Split Aircon 5. Only written dimensions in all cases
Outdoor Globe Type Top Post Light -20W shall be followed.
6. Architectural drawings must always
be read in conjunction with all other
FloodLight-70W relevant services drawings and
contract documents. Any
10W Picture Light discrepancy between these
Wall Mount type Split Aircon drawings and documents should be
LED Cube shape 2 way wall mounted light reported to the engineer for
clarification and verification.
48Ft long 15 hanging bulbs each 3W
32.1530

48 mtr

3 Phase Power socket (wall mounted ) Outdoor Unit

1W Recessed stair wallmounted mini ledlight


Ceiling fan-48"
Exhaust fan Power socket at ceiling
REMARKS
n ...................................................................
n Gang switch ...................................................................
...................................................................
16A power outlet ...................................................................
1
...................................................................
1 Gang Two way switch ...................................................................
...................................................................
Outdoor Globe Type Top Post Light -20W ...................................................................
...................................................................
Distribution board ...................................................................

Main distribution board


2 x 2 Ft LED Panel Light recessed 36 W
ARCHITECTURAL BUILDING
SCALE: 1" = 16'-0"

SHEET NUMBER E1
OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU

CLIENT: MRS. BINITA BHAT


11kV Feeder From NEA

Outdoor Pole Mounted


L.A.

DO-fuse
GENERAL NOTES
1. These drawings indicate in general
TOD
Meter
the projects in terms of Architectural
design intent with the dimensions of
Transformer
100 KVA the building. As indicated, the
contractor shall furnish all items
100kVA STANDBY required for the proper execution and
GENERATOR completion of the work.
150A TPN MCCB 2. Contractor shall examine and verify
36 kA
all dimensions and conditions. both
on the plans and in the field, and be
responsible for any adjustments and
correction.
3.5x95 sq.mm.copper cable armoured 3. Refer to engineer's detail for sizes
and spacing of all beams, columns,
3.5x95 sq.mm L.V XLPE Insulated Copper Power Cable slabs, foundations and trusses.
4. All interior dimensions are given
150 A ATS PANEL from rough brick face to rough brick
face.
5. Only written dimensions in all cases
3.5x95 sq.mm L.V XLPE Insulated Copper Power Cable shall be followed.
6. Architectural drawings must always
be read in conjunction with all other
relevant services drawings and
contract documents. Any
discrepancy between these
drawings and documents should be
reported to the engineer for
150A TPN MCCB clarification and verification.
36 kA

Am, Vm, Hz Meter+RYB 200A TPNE COPPER BUSBAR

R-PH Y-PH B-PH


REMARKS
16A SP MCB 32A TP MCCB 32A TP MCCB 32A TP MCCB 32A TP MCCB 40A SP MCB 32A SP MCB 20A TP MCCB ...................................................................
25 kA 36 kA 36 kA 36 kA 36 kA 25 kA 25 kA 36 kA ...................................................................
...................................................................
...................................................................
...................................................................
...................................................................
BASE SDB SDB 0
...................................................................
SDB 1 SDB 2 SDB 3 SDB 4 SDB 5 LIFT ...................................................................
...................................................................
...................................................................

MAIN DISTRIBUTION BOARD (MDB )


ARCHITECTURAL BUILDING

SHEET NUMBER E2
OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU

4X10 sq.mm. copper cable Unarmoured


Light Circuit - 2.5sq.mm
PVC insulated copper CLIENT: MRS. BINITA BHAT
32A TP MCB stranded cable
15 kA Power Circuit - 4sq.mm
PVC insulated copper
RYB 60A TPNE COPPER BUS stranded cable
GENERAL NOTES
1. These drawings indicate in general
R-PH the projects in terms of Architectural
6A 6A 6A 6A 6A 6A 16A 16A 6A 6A 6A 6A 6A 16A 16A 6A 6A 6A 6A 6A 16A 16A 16A 16A design intent with the dimensions of
the building. As indicated, the
2X4 sq.mm. copper cable Unarmoured contractor shall furnish all items
required for the proper execution and
completion of the work.
2. Contractor shall examine and verify

SPARE
spare

SPARE

SPARE
0P8
AC1

AC4

AC5

0P6
all dimensions and conditions. both

0P2
0P1

0P4

0L2

0L5
0L1

0L4

0L7

0L3

0L6
0P7

AC3
0P5

AC2

0P3
on the plans and in the field, and be
16A DP MCB responsible for any adjustments and
15 kA R-PHASE Y-PHASE B-PHASE correction.
3. Refer to engineer's detail for sizes
and spacing of all beams, columns,
slabs, foundations and trusses.
SDB 0 4. All interior dimensions are given
from rough brick face to rough brick
face.
5. Only written dimensions in all cases
shall be followed.
6. Architectural drawings must always
be read in conjunction with all other
relevant services drawings and
contract documents. Any
discrepancy between these
SP MCB
6A 6A 6A 6A 16A 16A drawings and documents should be
10 kA reported to the engineer for
clarification and verification.

4X10 sq.mm. copper cable Unarmoured


Light Circuit - 2.5sq.mm
PVC insulated copper
32A TP MCB stranded cable
15 kA Power Circuit - 4sq.mm
BL1 BL2 BL3 SPARE BP1 BP2
PVC insulated copper
REMARKS
RYB 60A TPNE COPPER BUS stranded cable ...................................................................
...................................................................
...................................................................
...................................................................
...................................................................
BASEMENT 6A 6A 6A 6A 6A 6A 16A 16A 6A 6A 6A 6A 6A 16A 16A 6A 6A 6A 6A 6A 16A 16A 16A 16A
...................................................................
...................................................................
SDB ...................................................................
...................................................................
...................................................................

SPARE
spare

SPARE

SPARE
1P8
AC1

AC4

AC5

1P6
1P2
1P1

1P4

1L2

1L5
1L1

1L4

1L7

1L3

1L6
0P7

AC3
1P5

AC2

1P3
R-PHASE Y-PHASE B-PHASE
ARCHITECTURAL BUILDING
SCALE: 1/32" = 1'-0"

SDB 1

SHEET NUMBER E3
OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU
4X10 sq.mm. copper cable Unarmoured Light Circuit - 2.5sq.mm 4X10 sq.mm. copper cable Unarmoured
PVC insulated copper
stranded cable
32A TP MCB 32A TP MCB
Power Circuit - 4sq.mm
15 kA 15 kA CLIENT: MRS. BINITA BHAT
PVC insulated copper
RYB 60A TPNE COPPER BUS stranded cable RYB 60A TPNE COPPER BUS

GENERAL NOTES
6A 6A 6A 6A 6A 6A 16A 16A 6A 6A 6A 6A 6A 16A 16A 6A 6A 6A 6A 6A 16A 16A 16A 16A 6A 6A 6A 6A 6A 6A 16A 16A 6A 6A 6A 6A 6A 16A 16A 6A 6A 6A 6A 6A 16A 16A 16A 16A
1. These drawings indicate in general
the projects in terms of Architectural
design intent with the dimensions of
the building. As indicated, the
contractor shall furnish all items

SPARE

SPARE
spare

SPARE

SPARE
required for the proper execution and

spare

SPARE

SPARE
2P8
AC1

AC4

AC5

2P6
2P2
2P1

2P4

2L2

3P8
AC1

AC4
2L5
2L1

2L4

2L7

2L3

2L6
2P7

AC5

3P6
3P2
AC3
2P5

3P1

3P4

3L2
AC2

3L5

3L3

3L6
3P7
3L1

3L4

3L7
2P3

AC3
3P5

AC2

3P3
completion of the work.
2. Contractor shall examine and verify
R-PHASE Y-PHASE R-PHASE Y-PHASE all dimensions and conditions. both
B-PHASE B-PHASE
on the plans and in the field, and be
responsible for any adjustments and
correction.
3. Refer to engineer's detail for sizes
SDB-2 SDB-3 and spacing of all beams, columns,
slabs, foundations and trusses.
4. All interior dimensions are given
from rough brick face to rough brick
face.
5. Only written dimensions in all cases
B-PH shall be followed.
Y-PH 6. Architectural drawings must always
be read in conjunction with all other
2X10 sq.mm. copper cable Unarmoured 2X10 sq.mm. copper cable Unarmoured relevant services drawings and
contract documents. Any
discrepancy between these
drawings and documents should be
reported to the engineer for
clarification and verification.
40A DP MCB 32A DP MCB
15 kA 15 kA

REMARKS
...................................................................
...................................................................
...................................................................
...................................................................
...................................................................
SP MCB SP MCB
6A 6A 6A 6A 6A 6A 6A 6A 16A 16A 16A 16A 16A 16A 16A 6A 6A 6A 6A 6A 6A 6A 6A 16A 16A 16A 16A 16A ...................................................................
10 kA 10 kA ...................................................................
...................................................................
...................................................................
...................................................................

ARCHITECTURAL BUILDING
SCALE: 1/32" = 1'-0"
4L1 4L2 4L3 4L4 4L5 4L6 4L7 4P1 4P2 4P3 4P4 4P5 4P6 4P7 AC1 5L1 5L2 5L3 5L4 5L5 5L6 5L7 5P1 5P2 5P3 5P4 5P5 AC1

SDB 4 SDB 5

SHEET NUMBER E4
OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU

CLIENT: MRS. BINITA BHAT

GENERAL NOTES
X

5 4 3
SECTION

2 1 1. These drawings indicate in general


68'-8"
the projects in terms of Architectural
18'-3" 18'-3" 17'-6" 13'-2"
design intent with the dimensions of
the building. As indicated, the
contractor shall furnish all items
1'-8" 7'-10" 8'-9" 1'-8" 16'-7" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8"
required for the proper execution and
completion of the work.
1'-8"

C
2. Contractor shall examine and verify
all dimensions and conditions. both
C

1'-8"
on the plans and in the field, and be
6'-9"

6
BL
2
responsible for any adjustments and
correction.
3. Refer to engineer's detail for sizes
19'-6"

Z Z
SECTION SECTION
and spacing of all beams, columns,

16'-0"
14'-4"
UP
slabs, foundations and trusses.
Y Y
11'-1"

PARKING SPACE FOR SECTION SECTION


4. All interior dimensions are given
2 WHEELERS AND 4 WHEELERS
from rough brick face to rough brick
face.
36'-11"

5. Only written dimensions in all cases


shall be followed.
1'-8"

1'-8"
B B
6. Architectural drawings must always

37'-11"
be read in conjunction with all other
1
relevant services drawings and
D4
UP
1
contract documents. Any
2 3 discrepancy between these
16'-0"

16'-0"
14'-4"

14'-4"
5
LIFT
6'-0" x 6'-6"
drawings and documents should be
BL
3
reported to the engineer for
BL
1 GUARD ROOM SPACE FOR clarification and verification.
8'-0" x 11'-2"
GENERATOR AND
ELECTRICAL NEEDS

A
1'-8"

1'-8"
A

4'-5"
REMARKS

1'-8" 16'-7" 1'-8" 16'-7" 68'-10" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" ...................................................................
...................................................................
18'-3" 18'-3" 17'-6" 13'-2"
...................................................................
68'-10"
...................................................................
...................................................................
5 3 ...................................................................
4 BASEMENT PLAN
X 2 1
...................................................................
SECTION

...................................................................
...................................................................
LIGHT PLAN ...................................................................

ARCHITECTURAL BUILDING
SCALE: 1" = 16'-0"

SHEET NUMBER E5
OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU

CLIENT: MRS. BINITA BHAT

GENERAL NOTES
X

5 4 3
SECTION

2 1 1. These drawings indicate in general


70'-8" the projects in terms of Architectural
18'-3" 18'-3" 17'-6" 13'-2" design intent with the dimensions of
the building. As indicated, the
1'-8" 7'-10" 8'-9" 1'-8" 16'-7" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" 1'-11"
contractor shall furnish all items
required for the proper execution and
completion of the work.
1'-8"

C
2. Contractor shall examine and verify
W12 W12
all dimensions and conditions. both
C

7" 1'-8"

2'-2"
6'-9"

on the plans and in the field, and be


responsible for any adjustments and

3'-0"

3'-0"
correction.
RENTAL SPACE
3. Refer to engineer's detail for sizes
19'-6"

Z 1467.43 Sq.ft Z
SECTION SECTION

and spacing of all beams, columns,

5'-10"

5'-10"

16'-0"
W1
DN slabs, foundations and trusses.
11'-1"

4. All interior dimensions are given


3

0L
5 from rough brick face to rough brick

4'-10"

4'-10"
0L6
4
4 4
0L4
6
face.
0L
2
5. Only written dimensions in all cases

1"
0L7
40'-3"

2 0L3
shall be followed.
1'-8"

8" 1'-8"
B B

2'-3"
6
6. Architectural drawings must always

37'-11"
2
3
D4 D4 DN
be read in conjunction with all other
1 UP
3
relevant services drawings and

7'-8"

7'-8"
LIFT
FEMALE TOILET 6'-0" x 6'-6" 1 MD contract documents. Any
6'-8" X
1
9'-1"D2 discrepancy between these
16'-0"

14'-4"

16'-0"
2

LOBBY
UP drawings and documents should be
2 D2
reported to the engineer for

2'-3"

2'-3"
MALE TOILET 13'-2" X 19'-9" 6
13'-0" X 7'-3"
W12 1
clarification and verification.
2
D4 1
0L

7'-7"

7'-7"
W2
A
1'-8"

A
W6 W12
3'-2"

D3
D3
W3

2'-4"

2'-4"
UP

REMARKS
1'-8" 16'-7" 1'-8" 9'-3" 6'-0" 1'-4" 1'-8" 6'-6" 9" 8'-7" 1'-8" 11'-6" 1'-8" 1'-5" ...................................................................
2"
9" 9" 16'-7" 10'-11" 6'-0" 1'-5"1'-6" 6'-7" 9" 8'-7" 1'-6" 12'-5" 2'-4" ...................................................................
18'-3" 18'-3" 17'-6" 13'-2" ...................................................................
70'-2" ...................................................................
...................................................................
5 4 3 X
SECTION
2 1 ...................................................................
GROUND FLOOR PLAN
...................................................................
FLOOR AREA: 2492.30 Sq.ft ...................................................................
LIGHT PLAN ...................................................................
...................................................................

ARCHITECTURAL BUILDING
SCALE: 1" = 16'-0"

SHEET NUMBER E6
OCTOBER 2021
N

COMMERCIAL BUILDING
X BANESHWOR - 10, KATHMANDU
5 3
SECTION

4 2 1
71'-11"

18'-3" 18'-3" 17'-6" 13'-2" CLIENT: MRS. BINITA BHAT

1'-8" 7'-10" 8'-9" 1'-8" 16'-7" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" 3'-2"

GENERAL NOTES
1'-8"

C
1. These drawings indicate in general
W12 W12 the projects in terms of Architectural
C

6" 1'-8"

7"1'-5"
design intent with the dimensions of
6'-9"

the building. As indicated, the


contractor shall furnish all items
DW1 required for the proper execution and
RENTAL SPACE
1751.32 Sq.ft completion of the work.
2. Contractor shall examine and verify
19'-6"

9'-8"

9'-8"
Z Z all dimensions and conditions. both
SECTION
BALCONY SECTION

on the plans and in the field, and be

16'-0"
3'-3" x 10'-3" responsible for any adjustments and
correction.
11'-2"

3. Refer to engineer's detail for sizes


3 and spacing of all beams, columns,

2'-8" 1'-6"

1'-6"
5
1L slabs, foundations and trusses.
6
1L6
4
4 4
1L
4 4. All interior dimensions are given

2'-9"
1L
2 from rough brick face to rough brick
1L7 face.
40'-3"

3 1L3

8" 1'-8"
1'-7"

B B 5. Only written dimensions in all cases

2'-3"
6 shall be followed.

37'-10"
3 3 6. Architectural drawings must always
D4
be read in conjunction with all other
D4 1 relevant services drawings and
3 contract documents. Any

7'-8"

7'-8"
DN LIFT UP
1 W4 discrepancy between these
FEMALE TOILET 6'-0" x 6'-6"
6'-8" X 9'-1"D2 drawings and documents should be
1
16'-0"

14'-4"

16'-0"
reported to the engineer for
clarification and verification.
2 D2

2'-3"

2'-3"
MALE TOILET 6
13'-0" X 7'-3"
W12 1
2

3'-9"
1
D4 1L

7'-7"
2
1'-8"

2'-2" 1'-8"
W5
A A
D5
W6 W12
BALCONY
3'-3"

W3 REMARKS
38'-0"x 3'-3"

2'-3"

2'-3"
...................................................................
...................................................................
1" ...................................................................
1'-8" 16'-7" 1'-8" 8" 3'-0" 5'-7" 6'-0" 1'-4" 1'-7" 6'-6" 9'-4" 1'-8" 11'-6" 1'-8" 1'-5" ...................................................................
...................................................................
1'-8" 9'-1" 2'-0" 5'-6" 1'-8" 8" 3'-0" 3'-7" 2'-0" 6'-0" 1'-5"1'-6" 6'-7" 9'-5" 1'-6" 11'-8" 3'-0"
...................................................................
18'-3" 18'-3" 17'-6" 13'-2" ...................................................................
...................................................................
70'-2"
...................................................................
...................................................................

5 4 3 X
SECTION 2 1
FIRST FLOOR PLAN
FLOOR AREA: 2513.41 Sq.ft (WITHOUT BALCONY)
FLOOR AREA: 2668.21 Sq.ft (WITH BALCONY) ARCHITECTURAL BUILDING
SCALE: 3/32" = 1'-0"
LIGHT PLAN

SHEET NUMBER E7
OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU
X

5 3
SECTION

4 2 1
71'-11"
CLIENT: MRS. BINITA BHAT
18'-3" 18'-3" 17'-6" 13'-2"

1'-8" 7'-10" 8'-9" 1'-8" 16'-7" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" 3'-2"

GENERAL NOTES
1'-8"

C 1. These drawings indicate in general


the projects in terms of Architectural
W12 W12 design intent with the dimensions of
C

6" 1'-8"

7"1'-5"
the building. As indicated, the
6'-9"

contractor shall furnish all items


required for the proper execution and
DW1 completion of the work.
2. Contractor shall examine and verify
RENTAL SPACE 1
all dimensions and conditions. both
19'-6"

1771.80 Sq.ft on the plans and in the field, and be

9'-8"

9'-8"
Z Z
SECTION SECTION

BALCONY responsible for any adjustments and

16'-0"
3'-3" x 10'-3" correction.
3. Refer to engineer's detail for sizes
11'-1"

and spacing of all beams, columns,


slabs, foundations and trusses.

1'-8" 8" 2'-0" 1'-6"

1'-2" 2'-0" 1'-6"


5 3
2L 4. All interior dimensions are given
2L6
4
4 4 4 6 from rough brick face to rough brick
2L
face.
2L
2L7
2 5. Only written dimensions in all cases
40'-3"

3 2L3
1'-8"

shall be followed.
B 6
B 6. Architectural drawings must always
be read in conjunction with all other

38'-0"
3 3
relevant services drawings and
D4 D4 1 contract documents. Any
3 DN LIFT UP discrepancy between these
FEMALE TOILET 6'-0" x 6'-6" 1 drawings and documents should be
6'-8" X1 9'-1"D2 reported to the engineer for
16'-0"

14'-4"

14'-4"

16'-0"
clarification and verification.

20'-7"
2 D2 W12
MALE TOILET 6
13'-0" X 7'-3"
W12 1
2
1
D4 2L

2
1'-8"

1'-8"
A A
REMARKS
W6 D5 W12
3'-3"

BALCONY

3'-5"
W3 ...................................................................
3'-3" x 38'-0"
...................................................................

1'-1"

1'-1"
...................................................................
...................................................................
1'-8" 16'-7" 1'-8" 8" 3'-0" 5'-7" 6'-0" 1'-4" 1'-8" 6'-6" 9'-4" 1'-8" 11'-6" 1'-8" 3'-11" ...................................................................
2" ...................................................................
9" 9" 9'-1" 2'-0" 5'-6" 2'-4" 3'-0" 3'-7" 2'-0" 6'-0" 1'-3"1'-8" 6'-7" 9'-5" 18'-8" ...................................................................
18'-3" 18'-3" 17'-6" 13'-2" ...................................................................
...................................................................
72'-8" ...................................................................

5 4 3 X
SECTION 2 1
SECOND FLOOR PLAN
FLOOR AREA: 2526.03 Sq.ft (WITHOUT BALCONY) ARCHITECTURAL BUILDING
FLOOR AREA: 2683.22 Sq.ft (WITH BALCONY) SCALE: 3/32" = 1'-0"

LIGHT PLAN

SHEET NUMBER E8
OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU
X

5 3
SECTION

4 2 1
71'-5"
CLIENT: MRS. BINITA BHAT
18'-3" 18'-3" 17'-6" 13'-2"

1'-8" 7'-10" 8'-9" 1'-8" 16'-7" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" 2'-8"

GENERAL NOTES
1'-8"

C 1. These drawings indicate in general


the projects in terms of Architectural
W12 W12
design intent with the dimensions of
C

7" 1'-8"

2'-1"
the building. As indicated, the
6'-9"

contractor shall furnish all items


required for the proper execution and

3'-0"

3'-0"
completion of the work.
2. Contractor shall examine and verify
RENTAL SPACE all dimensions and conditions. both
19'-6"

Z 1764.89 Sq.ft Z
on the plans and in the field, and be
SECTION
DW2 SECTION

5'-10"

5'-10"
responsible for any adjustments and

16'-0"
BALCONY correction.
1
2'-11" x 10'-9" 3. Refer to engineer's detail for sizes
11'-1"

and spacing of all beams, columns,


5 3 slabs, foundations and trusses.
3L 4. All interior dimensions are given

4'-10"

4'-11"
3L6 4 4 4
4 3L 6 from rough brick face to rough brick
3L
face.
2
3L7 5. Only written dimensions in all cases
40'-2"

3 3L3
1'-8"

8" 1'-8"
B B shall be followed.

2'-3"
6 6. Architectural drawings must always

37'-11"
3 3 be read in conjunction with all other
D4 D4 3'-0" DW3 relevant services drawings and
1
contract documents. Any
3
discrepancy between these

7'-8"

7'-8"
DN LIFT UP
6'-0" x 6'-6" 1 drawings and documents should be
FEMALE TOILET BALCONY
6'-8" X1 9'-1"D2 4'-0" x 22'-10" reported to the engineer for
16'-0"

14'-4"

16'-0"
clarification and verification.
2 D2

2'-3"

2'-3"
MALE TOILET 6
13'-0" X 7'-3"
W12 1
2

3'-10"
1
D4 3L

7'-7"
2
W2
1'-8"

9" 1'-7" 2'-2" 1'-7"


A A
W6 BALCONY D5 W12 REMARKS
3'-3"

38'-0" x 3'-3" W3
...................................................................

9" 1'-7"
...................................................................
...................................................................
...................................................................
1'-8" 16'-7" 1'-8" 8" 3'-0" 5'-7" 6'-0" 1'-4" 1'-8" 6'-6" 9'-4" 1'-8" 11'-6" 1'-8" 3'-11" ...................................................................
2" ...................................................................
9" 9" 9'-1" 18'-5" 6'-0" 1'-5"1'-6" 6'-7" 9'-5" 18'-8"
...................................................................
18'-3" 18'-3" 17'-6" 13'-2" ...................................................................
72'-8"
...................................................................
...................................................................

5 4 3 X
SECTION 2 1
THIRD FLOOR PLAN
FLOOR AREA: 2521.35 Sq.ft (WITHOUT BALCONY) ARCHITECTURAL BUILDING
FLOOR AREA: 2758.65 Sq.ft (WITH BALCONY) SCALE: 3/32" = 1'-0"
LIGHT PLAN

SHEET NUMBER E9
OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU
X

5 3
SECTION

4 2 1
72'-1"
CLIENT: MRS. BINITA BHAT
18'-3" 18'-3" 17'-6" 13'-2"

25'-3" 11'-3" 35'-0"

1'-8" 7'-10" 8'-9" 1'-6" 5'-5" 11'-3" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" 2'-8"

GENERAL NOTES
1'-8"

C
1. These drawings indicate in general
W12 the projects in terms of Architectural
A.BATHROOM W12 2
BALCONY
8'-5"

design intent with the dimensions of


C

7" 1'-8"
8'-6" X 6'-3"

2'-1"
C.BATHROOM 11'-4" x 5'-0"
6'-9"

the building. As indicated, the


8'-8" X 5'-7" D3 6 DINING ROOM
DW6 W9 W9 contractor shall furnish all items
1 L7 13'-2" X 15'-7"
D3 required for the proper execution and

3'-0"

3'-0"
4
completion of the work.
W9 2. Contractor shall examine and verify
1
all dimensions and conditions. both
19'-6"

Z DW2 Z
SECTION SECTION
on the plans and in the field, and be

5'-10"

5'-10"
responsible for any adjustments and

16'-0"
LIVING ROOM BALCONY
3'-3" x 11'-1" correction.
16'-9" X 16'-5"
11'-1"

11'-1"

BALCONY 3. Refer to engineer's detail for sizes


4'-8" x 11'-10" FAMILY ROOM
17'-10" X 10'-3" and spacing of all beams, columns,
4

4 5
4L 4L slabs, foundations and trusses.

4'-2"

4'-2"
BEDROOM 4. All interior dimensions are given
13'-7" X 11'-10" 6 from rough brick face to rough brick

3
DW4 2 D2 6
4L face.

1'-8" 8"
D1
40'-3"

5. Only written dimensions in all cases


1'-8"

B B shall be followed.

6'-0"
6. Architectural drawings must always

37'-11"
4

D2 D2 6
4L

3'-8"
3 be read in conjunction with all other

1
1
4L 4L KITCHEN
relevant services drawings and
13'-2" X 16'-0"

1
contract documents. Any
DN LIFT UP
1 D5 discrepancy between these

3'-1"

3'-1"
6'-0" x 6'-6" 6
drawings and documents should be
5

BEDROOM
BEDROOM reported to the engineer for
16'-0"

14'-4"

16'-0"
1
21'-7" X 16'-4"
14'-6" X 16'-4" clarification and verification.
20'-11"

5'-0"

5'-0"
W7
2
BALCONY
3'-5" x 16'-1"
D3
D3

2'-7"
1
2
CLOSET
8'-0" X 7'-0" V3
1'-8"

9" 1'-7" 2'-2" 1'-8"


A D5 A
A.BATHROOM WASHING

9" 1'-7" 2'-2"


DW5 9'-8" X 7'-2" DW4 BALCONY REMARKS
3'-3"

BALCONY W3 13'-2" X 4'-0"


8'-11" x 3'-3" V2
9'-11" x 3'-3"
...................................................................
...................................................................
V1 V1
...................................................................
...................................................................
1'-8" 9'-1" 3'-0" 2'-6" 2'-0" 1'-8" 2'-3" 2'-6" 4'-6" 7'-4" 1'-8" 6'-6" 9'-4" 1'-8" 11'-6" 1'-8" 3'-4"
2" ...................................................................
9" 9" 9'-1" 3'-0" 2'-6" 5'-11" 2'-6" 4'-6" 7'-5" 1'-6" 6'-7" 9'-5" 1'-6" 11'-8" 4'-11" ...................................................................
...................................................................
18'-3" 18'-3" 17'-6" 13'-2"
...................................................................
72'-1" ...................................................................
...................................................................

5 4 3 X
SECTION 2 1
FOURTH FLOOR PLAN
FLOOR AREA: 2465.69Sq.ft (WITHOUT BALCONY)
FLOOR AREA: 2596.25 Sq.ft (WITH BALCONY) ARCHITECTURAL BUILDING
SCALE: 3/32" = 1'-0"
LIGHT PLAN

SHEET NUMBER E10


OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU
X

5 3
SECTION

4 2 1
71'-11"
CLIENT: MRS. BINITA BHAT
18'-3" 18'-3" 17'-6" 13'-2"

25'-3" 11'-3" 35'-0"

1'-8" 7'-10" 8'-9" 1'-8" 5'-4" 11'-3" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" 2'-8"

GENERAL NOTES
1'-8"

C 1. These drawings indicate in general


10" the projects in terms of Architectural
W12 W12
design intent with the dimensions of
C

7" 1'-8"
BALCONY BELOW

2'-1"
C.BATHROOM the building. As indicated, the
6'-9"

8'-7" X 5'-6" D3 W11 W9 contractor shall furnish all items


required for the proper execution and

3'-0"

3'-0"
D3 completion of the work.
1 2. Contractor shall examine and verify
all dimensions and conditions. both
21'-2"
19'-6"

Z
SECTION
DW2 Z
SECTION on the plans and in the field, and be

5'-10"

5'-10"
PUJA ROOM responsible for any adjustments and

16'-0"
LIVING ROOM 16'-9" X 16'-5" BALCONY correction.
FAMILY ROOM 3'-3" x 11'-1" 3. Refer to engineer's detail for sizes
11'-1"

BELOW
12'-3" X 11'-10" and spacing of all beams, columns,
6 slabs, foundations and trusses.
BEDROOM
4

4. All interior dimensions are given

4'-10"

4'-11"
18'-7" X 12'-7" 5L
4
D2 5 from rough brick face to rough brick
5L D2
1 7 face.
5L 5L

3
6
SD1 5. Only written dimensions in all cases
40'-3"

1'-8"

2'-4" 8" 1'-8"


B B

2'-3"
shall be followed.
6. Architectural drawings must always

37'-11"
W10 D5 D5 be read in conjunction with all other

2'-4"
6
relevant services drawings and

3
3
5L contract documents. Any
4

1
DN LIFT discrepancy between these

4'-3"

4'-3"
MAINTENANCE drawings and documents should be
L2
6'-0" x 6'-6" reported to the engineer for
16'-0"

16'-0"
5 1
GYM/YOGA ROOM clarification and verification.
TERRACE

1'-8" 2'-3" 1'-1"


18'-3" X 15'-3" 6
5L
19'-2"

19'-2"

W10

5'-0"
W7 TERRACE

UP

9" 1'-7" 1'-7" 7" 1'-8" 2'-1"


W10
W12

4'-4"
A W3
A
REMARKS

9" 1'-7" 1'-7"


...................................................................
...................................................................
...................................................................
...................................................................
1'-8" 5'-10" 6'-0" 4'-9" 1'-8" 10'-7" 6'-0" 1'-8" 6'-6" 9'-4" 1'-8" 11'-7" 4'-11" ...................................................................
1"
7'-6" 6'-0" 4'-9" 12'-3" 6'-0" 1'-6" 6'-7" 9'-5" 1'-6" 11'-8" 4'-11" ...................................................................
...................................................................
18'-3" 18'-3" 17'-6" 13'-2" ...................................................................
72'-1"
...................................................................
...................................................................

5 4 3 X
SECTION 2 1
FIFTH FLOOR PLAN
FLOOR AREA: 1908.16 Sq.ft (WITHOUT BALCONY)
ARCHITECTURAL BUILDING
FLOOR AREA: 1938.19 Sq.ft (WITH BALCONY)
SCALE: 3/32" = 1'-0"
LIGHT PLAN

SHEET NUMBER E11


OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU

CLIENT: MRS. BINITA BHAT

GENERAL NOTES
X
1. These drawings indicate in general
5 4 3
SECTION

2 1 the projects in terms of Architectural


68'-8"
design intent with the dimensions of
18'-3" 18'-3" 17'-6" 13'-2"
the building. As indicated, the
contractor shall furnish all items
1'-8" 7'-10" 8'-9" 1'-8" 16'-7" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8"
required for the proper execution and
completion of the work.
2. Contractor shall examine and verify
1'-8"

C
all dimensions and conditions. both
on the plans and in the field, and be
C

1'-8"
6'-9"

responsible for any adjustments and


correction.
3. Refer to engineer's detail for sizes
and spacing of all beams, columns,
19'-6"

Z Z
SECTION SECTION

slabs, foundations and trusses.

16'-0"
14'-4"
UP 4. All interior dimensions are given
Y Y
11'-1"

PARKING SPACE FOR SECTION SECTION


from rough brick face to rough brick
2 WHEELERS AND 4 WHEELERS
face.
5. Only written dimensions in all cases
36'-11"

shall be followed.
6. Architectural drawings must always
1'-8"

1'-8"
B B
be read in conjunction with all other

37'-11"
relevant services drawings and
contract documents. Any
UP
D4 discrepancy between these
SDB base drawings and documents should be
16'-0"

14'-4"

14'-4"

16'-0"
LIFT
6'-0" x 6'-6"
reported to the engineer for
clarification and verification.
GUARD ROOM SPACE FOR
8'-0" x 11'-2"
GENERATOR AND
BP1 BP2
ELECTRICAL NEEDS

A
1'-8"

1'-8"
A

4'-5"
REMARKS
...................................................................
1'-8" 16'-7" 1'-8" 16'-7" 68'-10" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" ...................................................................
...................................................................
18'-3" 18'-3" 17'-6" 13'-2" ...................................................................
68'-10" ...................................................................
...................................................................
5 4 3 X 2 1 ...................................................................
BASEMENT PLAN SECTION

...................................................................
...................................................................
POWER SOCKET PLAN ...................................................................

ARCHITECTURAL BUILDING
SCALE: 1" = 16'-0"

SHEET NUMBER E12


OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU

CLIENT: MRS. BINITA BHAT

5 4 3
SECTION

2 1 GENERAL NOTES
70'-8"

18'-3" 18'-3" 17'-6" 13'-2" 1. These drawings indicate in general


the projects in terms of Architectural
1'-8" 7'-10" 8'-9" 1'-8" 16'-7" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" 1'-11" design intent with the dimensions of
the building. As indicated, the
1'-8"

C contractor shall furnish all items


required for the proper execution and
W12 W12
C completion of the work.

7" 1'-8"

2'-2"
6'-9"

0P6

0P4
2. Contractor shall examine and verify
0P3 0P2
all dimensions and conditions. both

3'-0"

3'-0"
AC2
on the plans and in the field, and be
RENTAL SPACE
responsible for any adjustments and
19'-6"

Z
SECTION
1467.43 Sq.ft Z
SECTION

correction.

5'-10"

5'-10"
AC3

16'-0"
W1
1 Ton
DN 3. Refer to engineer's detail for sizes
11'-1"

1 Ton 1 Ton
and spacing of all beams, columns,
AC4 0P5
slabs, foundations and trusses.

4'-10"

4'-10"
4. All interior dimensions are given
from rough brick face to rough brick

1"
40'-3"

face.
1'-8"

8" 1'-8"
B B

2'-3"
0P7
0P9 5. Only written dimensions in all cases

37'-11"
D4 D4 DN shall be followed.
0P8 UP
6. Architectural drawings must always

7'-8"

7'-8"
LIFT
FEMALE TOILET 6'-0" x 6'-6"
AC1
MD be read in conjunction with all other
AC5 6'-8" X 9'-1"D2
relevant services drawings and
16'-0"

14'-4"

16'-0"
1 Ton
SDB0
LOBBY
UP
contract documents. Any
D2

2'-3"

2'-3"
1 Ton MALE TOILET 13'-2" X 19'-9" discrepancy between these
13'-0" X 7'-3" 0P1
W12 drawings and documents should be
D4
reported to the engineer for
clarification and verification.

7'-7"

7'-7"
W2
A
1'-8"

A
W6 W12
3'-2"

W3 D3
D3

2'-4"

2'-4"
UP

1'-8" 16'-7" 1'-8" 9'-3" 6'-0" 1'-4" 1'-8" 6'-6" 9" 8'-7" 1'-8" 11'-6" 1'-8" 1'-5"
2" REMARKS
9" 9" 16'-7" 10'-11" 6'-0" 1'-5"1'-6" 6'-7" 9" 8'-7" 1'-6" 12'-5" 2'-4"

18'-3" 18'-3" 17'-6" 13'-2" ...................................................................


70'-2" ...................................................................
...................................................................
5 4 3 X
SECTION
2 1 ...................................................................
GROUND FLOOR PLAN ...................................................................
FLOOR AREA: 2492.30 Sq.ft ...................................................................
...................................................................
POWER SOCKET & AC PLAN ...................................................................
...................................................................
...................................................................

ARCHITECTURAL BUILDING
SCALE: 1" = 16'-0"

SHEET NUMBER E13


OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU
X

5 3
SECTION

4 2 1
71'-11"
CLIENT: MRS. BINITA BHAT
18'-3" 18'-3" 17'-6" 13'-2"

1'-8" 7'-10" 8'-9" 1'-8" 16'-7" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" 3'-2"

GENERAL NOTES
1'-8"

C 1. These drawings indicate in general


the projects in terms of Architectural
W12 W12 design intent with the dimensions of
C

6" 1'-8"

7"1'-5"
the building. As indicated, the
6'-9"

1P6
contractor shall furnish all items
1P4 1P2 required for the proper execution and
1P3
DW1 completion of the work.
RENTAL SPACE AC2
1751.32 Sq.ft 2. Contractor shall examine and verify
all dimensions and conditions. both
19'-6"

9'-8"

9'-8"
Z Z on the plans and in the field, and be
SECTION
AC3 BALCONY SECTION

responsible for any adjustments and

16'-0"
3'-3" x 10'-3" correction.
1 Ton 1 Ton 3. Refer to engineer's detail for sizes
11'-2"

1 Ton
and spacing of all beams, columns,
AC4 1P5 slabs, foundations and trusses.

2'-8" 1'-6"

1'-6"
4. All interior dimensions are given
from rough brick face to rough brick

2'-9"
face.
5. Only written dimensions in all cases
40'-3"

8" 1'-8"
1'-7"

B B shall be followed.

2'-3"
1P7
6. Architectural drawings must always

37'-10"
be read in conjunction with all other
D4
relevant services drawings and
D4
1P8 contract documents. Any
discrepancy between these

7'-8"

7'-8"
DN LIFT UP
W4 drawings and documents should be
FEMALE TOILET SDB1
6'-0" x 6'-6"
AC1
AC5 6'-8" X 9'-1"D2 reported to the engineer for
16'-0"

14'-4"

16'-0"
1 Ton clarification and verification.

D2

2'-3"

2'-3"
1 Ton MALE TOILET
13'-0" X 7'-3" 1P1
W12

3'-9"
D4

7'-7"
1'-8"

2'-2" 1'-8"
W5
A A
D5 REMARKS
W6 W12
BALCONY
3'-3"

W3 ...................................................................
38'-0"x 3'-3"

2'-3"

2'-3"
...................................................................
...................................................................
1" ...................................................................
1'-8" 16'-7" 1'-8" 8" 3'-0" 5'-7" 6'-0" 1'-4" 1'-7" 6'-6" 9'-4" 1'-8" 11'-6" 1'-8" 1'-5" ...................................................................
...................................................................
1'-8" 9'-1" 2'-0" 5'-6" 1'-8" 8" 3'-0" 3'-7" 2'-0" 6'-0" 1'-5"1'-6" 6'-7" 9'-5" 1'-6" 11'-8" 3'-0"
...................................................................
18'-3" 18'-3" 17'-6" 13'-2" ...................................................................
...................................................................
70'-2"
...................................................................

5 4 3 X
SECTION 2 1
FIRST FLOOR PLAN
FLOOR AREA: 2513.41 Sq.ft (WITHOUT BALCONY) ARCHITECTURAL BUILDING
FLOOR AREA: 2668.21 Sq.ft (WITH BALCONY) SCALE: 3/32" = 1'-0"

POWER SOCKET & AC PLAN

SHEET NUMBER E14


OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU
X

5 3
SECTION

4 2 1
71'-11"
CLIENT: MRS. BINITA BHAT
18'-3" 18'-3" 17'-6" 13'-2"

1'-8" 7'-10" 8'-9" 1'-8" 16'-7" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" 3'-2"

GENERAL NOTES
1'-8"

C 1. These drawings indicate in general


the projects in terms of Architectural
W12 W12 design intent with the dimensions of
C

6" 1'-8"

7"1'-5"
the building. As indicated, the
6'-9"

2P6
contractor shall furnish all items
2P4
2P3 2P2 required for the proper execution and
AC2 DW1 completion of the work.
2. Contractor shall examine and verify
RENTAL SPACE all dimensions and conditions. both
19'-6"

1771.80 Sq.ft

9'-8"

9'-8"
Z
SECTION
Z
SECTION
on the plans and in the field, and be
AC3 BALCONY responsible for any adjustments and

16'-0"
3'-3" x 10'-3" correction.
1 Ton 3. Refer to engineer's detail for sizes
11'-1"

1 Ton 1 Ton
and spacing of all beams, columns,
AC4 2P5 slabs, foundations and trusses.

1'-8" 8" 2'-0" 1'-6"

1'-2" 2'-0" 1'-6"


4. All interior dimensions are given
from rough brick face to rough brick
face.
5. Only written dimensions in all cases
40'-3"

1'-8"

B 2P7 B 6.
shall be followed.
Architectural drawings must always
be read in conjunction with all other

38'-0"
relevant services drawings and
D4 D4
2P8 contract documents. Any
DN LIFT UP discrepancy between these
FEMALE TOILET 6'-0" x 6'-6" drawings and documents should be
AC5 AC1 reported to the engineer for
6'-8" X 9'-1"D2 SDB2
16'-0"

14'-4"

14'-4"

16'-0"
1 Ton clarification and verification.

20'-7"
1 Ton
D2 W12
MALE TOILET
13'-0" X 7'-3" 2P1
W12
D4
1'-8"

1'-8"
A A
REMARKS
W6 D5 W12
3'-3"

BALCONY

3'-5"
W3 ...................................................................
3'-3" x 38'-0"
...................................................................

1'-1"

1'-1"
...................................................................
...................................................................
1'-8" 16'-7" 1'-8" 8" 3'-0" 5'-7" 6'-0" 1'-4" 1'-8" 6'-6" 9'-4" 1'-8" 11'-6" 1'-8" 3'-11" ...................................................................
2" ...................................................................
9" 9" 9'-1" 2'-0" 5'-6" 2'-4" 3'-0" 3'-7" 2'-0" 6'-0" 1'-3"1'-8" 6'-7" 9'-5" 18'-8"
...................................................................
18'-3" 18'-3" 17'-6" 13'-2" ...................................................................
...................................................................
72'-8" ...................................................................

5 4 3 X
SECTION 2 1
SECOND FLOOR PLAN
FLOOR AREA: 2526.03 Sq.ft (WITHOUT BALCONY) ARCHITECTURAL BUILDING
FLOOR AREA: 2683.22 Sq.ft (WITH BALCONY) SCALE: 3/32" = 1'-0"

POWER SOCKET & AC PLAN

SHEET NUMBER E15


OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU
X

5 3
SECTION

4 2 1
71'-5"
CLIENT: MRS. BINITA BHAT
18'-3" 18'-3" 17'-6" 13'-2"

1'-8" 7'-10" 8'-9" 1'-8" 16'-7" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" 2'-8"

GENERAL NOTES
1'-8"

C 1. These drawings indicate in general


the projects in terms of Architectural
W12 W12
design intent with the dimensions of
C

7" 1'-8"

2'-1"
the building. As indicated, the
6'-9"

3P6
contractor shall furnish all items
3P4 3P2
3P3 required for the proper execution and

3'-0"

3'-0"
AC2 completion of the work.
2. Contractor shall examine and verify
RENTAL SPACE all dimensions and conditions. both
19'-6"

Z 1764.89 Sq.ft Z
on the plans and in the field, and be
SECTION
DW2 SECTION

5'-10"

5'-10"
AC3
responsible for any adjustments and

16'-0"
BALCONY
correction.
1 Ton 2'-11" x 10'-9"
11'-1"

1 Ton 1 Ton 3. Refer to engineer's detail for sizes


and spacing of all beams, columns,
AC4 3P5 slabs, foundations and trusses.
4. All interior dimensions are given

4'-10"

4'-11"
from rough brick face to rough brick
face.
5. Only written dimensions in all cases
40'-2"

1'-8"

8" 1'-8"
B B

2'-3"
3P7
shall be followed.
6. Architectural drawings must always

37'-11"
be read in conjunction with all other
D4 D4 3'-0" DW3 relevant services drawings and
3P8 contract documents. Any

7'-8"

7'-8"
DN LIFT UP discrepancy between these
FEMALE TOILET 6'-0" x 6'-6"
BALCONY drawings and documents should be
AC1
6'-8" X 9'-1"D2 4'-0" x 22'-10" reported to the engineer for
16'-0"

14'-4"

16'-0"
AC5 SDB3 1 Ton
clarification and verification.
D2

2'-3"

2'-3"
1 Ton MALE TOILET
13'-0" X 7'-3" 3P1
W12

3'-10"
D4

7'-7"
W2
1'-8"

9" 1'-7" 2'-2" 1'-7"


A A
W6 BALCONY D5 W12 REMARKS
3'-3"

38'-0" x 3'-3" W3
...................................................................

9" 1'-7"
...................................................................
...................................................................
...................................................................
1'-8" 16'-7" 1'-8" 8" 3'-0" 5'-7" 6'-0" 1'-4" 1'-8" 6'-6" 9'-4" 1'-8" 11'-6" 1'-8" 3'-11" ...................................................................
2"
9" 9" 9'-1" 18'-5" 6'-0" 1'-5"1'-6" 6'-7" 9'-5" 18'-8" ...................................................................
...................................................................
18'-3" 18'-3" 17'-6" 13'-2" ...................................................................
72'-8" ...................................................................
...................................................................

5 4 3 X
SECTION 2 1
THIRD FLOOR PLAN
FLOOR AREA: 2521.35 Sq.ft (WITHOUT BALCONY)
ARCHITECTURAL BUILDING
FLOOR AREA: 2758.65 Sq.ft (WITH BALCONY) SCALE: 3/32" = 1'-0"

POWER SOCKET & AC PLAN

SHEET NUMBER E16


OCTOBER 2021
N

COMMERCIAL BUILDING
X BANESHWOR - 10, KATHMANDU
5 3
SECTION

4 2 1
72'-1"

18'-3" 18'-3" 17'-6" 13'-2" CLIENT: MRS. BINITA BHAT


25'-3" 11'-3" 35'-0"

1'-8" 7'-10" 8'-9" 1'-6" 5'-5" 11'-3" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" 2'-8"
1'-8"

C GENERAL NOTES
W12
1. These drawings indicate in general
A.BATHROOM W12 BALCONY the projects in terms of Architectural
8'-5"

7" 1'-8"
8'-6" X 6'-3"

2'-1"
C.BATHROOM 11'-4" x 5'-0" design intent with the dimensions of
6'-9"

4P4
8'-8" X 5'-7" D3 DINING ROOM the building. As indicated, the
DW6 W9 W9 13'-2" X 15'-7"
D3 contractor shall furnish all items

3'-0"

3'-0"
required for the proper execution and
W9 completion of the work.
2. Contractor shall examine and verify
19'-6"

Z DW2 Z
SECTION SECTION all dimensions and conditions. both

5'-10"

5'-10"
on the plans and in the field, and be

16'-0"
LIVING ROOM BALCONY
3'-3" x 11'-1" responsible for any adjustments and
16'-9" X 16'-5"
11'-1"

11'-1"

BALCONY correction.
4'-8" x 11'-10" FAMILY ROOM 3. Refer to engineer's detail for sizes
17'-10" X 10'-3" and spacing of all beams, columns,

4'-2"

4'-2"
BEDROOM 4P5
slabs, foundations and trusses.
4P3
13'-7" X 11'-10" 4P6 4. All interior dimensions are given
DW4 D2 from rough brick face to rough brick

1'-8" 8"
D1 face.
40'-3"

1'-8"

B B 5. Only written dimensions in all cases

6'-0"
shall be followed.

37'-11"
D2 D2 6. Architectural drawings must always

3'-8"
KITCHEN be read in conjunction with all other
4P1 4P2
13'-2" X 16'-0" relevant services drawings and
DN LIFT UP contract documents. Any
D5

3'-1"

3'-1"
6'-0" x 6'-6" discrepancy between these
BEDROOM SDB4
drawings and documents should be
BEDROOM
16'-0"

14'-4"

16'-0"
21'-7" X 16'-4" reported to the engineer for
14'-6" X 16'-4"
20'-11"

4P7
clarification and verification.

5'-0"

5'-0"
W7
BALCONY
3'-5" x 16'-1"
D3
D3

2'-7"
CLOSET
8'-0" X 7'-0" V3
1'-8"

9" 1'-7" 2'-2" 1'-8"


A D5 A
A.BATHROOM WASHING

9" 1'-7" 2'-2"


DW5 9'-8" X 7'-2" DW4 BALCONY
3'-3"

BALCONY W3 V2 13'-2" X 4'-0"


9'-11" x 3'-3" 8'-11" x 3'-3" REMARKS
...................................................................
V1 V1 ...................................................................
...................................................................
1'-8" 9'-1" 3'-0" 2'-6" 2'-0" 1'-8" 2'-3" 2'-6" 4'-6" 7'-4" 1'-8" 6'-6" 9'-4" 1'-8" 11'-6" 1'-8" 3'-4"
...................................................................
2"
9" 9" 9'-1" 3'-0" 2'-6" 5'-11" 2'-6" 4'-6" 7'-5" 1'-6" 6'-7" 9'-5" 1'-6" 11'-8" 4'-11" ...................................................................
...................................................................
18'-3" 18'-3" 17'-6" 13'-2" ...................................................................
72'-1" ...................................................................
...................................................................
...................................................................
5 4 3 X
SECTION 2 1
FOURTH FLOOR PLAN
FLOOR AREA: 2465.69Sq.ft (WITHOUT BALCONY)
FLOOR AREA: 2596.25 Sq.ft (WITH BALCONY) ARCHITECTURAL BUILDING
SCALE: 3/32" = 1'-0"
POWER SOCKET & AC PLAN

SHEET NUMBER E17


OCTOBER 2021
N

COMMERCIAL BUILDING
BANESHWOR - 10, KATHMANDU
X

5 3
SECTION

4 2 1
71'-11"
CLIENT: MRS. BINITA BHAT
18'-3" 18'-3" 17'-6" 13'-2"

25'-3" 11'-3" 35'-0"

1'-8" 7'-10" 8'-9" 1'-8" 5'-4" 11'-3" 1'-8" 15'-10" 1'-8" 11'-6" 1'-8" 2'-8"

GENERAL NOTES
1'-8"

C 1. These drawings indicate in general


10" the projects in terms of Architectural
W12 W12 design intent with the dimensions of
C

7" 1'-8"
BALCONY BELOW

2'-1"
5P2 C.BATHROOM the building. As indicated, the
6'-9"

8'-7" X 5'-6" D3 W11 W9 contractor shall furnish all items


required for the proper execution and

3'-0"

3'-0"
5P5
D3 completion of the work.
2. Contractor shall examine and verify
all dimensions and conditions. both
21'-2"
19'-6"

Z
SECTION
DW2 Z
SECTION
on the plans and in the field, and be

5'-10"

5'-10"
PUJA ROOM responsible for any adjustments and

16'-0"
LIVING ROOM 16'-9" X 16'-5" BALCONY correction.
FAMILY ROOM 3'-3" x 11'-1" 3. Refer to engineer's detail for sizes
11'-1"

BELOW
12'-3" X 11'-10" and spacing of all beams, columns,
slabs, foundations and trusses.
BEDROOM 4. All interior dimensions are given

4'-10"

4'-11"
18'-7" X 12'-7" from rough brick face to rough brick
D2
5P1 5P4 D2 face.
SD1 5. Only written dimensions in all cases
40'-3"

1'-8"

2'-4" 8" 1'-8"


B B shall be followed.

2'-3"
6. Architectural drawings must always

37'-11"
W10 D5 D5 be read in conjunction with all other

2'-4"
relevant services drawings and
contract documents. Any
DN LIFT discrepancy between these

4'-3"

4'-3"
MAINTENANCE drawings and documents should be
SDB5 reported to the engineer for
6'-0" x 6'-6"
16'-0"

16'-0"
GYM/YOGA ROOM clarification and verification.
TERRACE

1'-8" 2'-3" 1'-1"


18'-3" X 15'-3"
19'-2"

19'-2"

5'-0"
W10 W7 TERRACE

UP

9" 1'-7" 1'-7" 7" 1'-8" 2'-1"


5P3
W10
W12

4'-4"
A W3
A
REMARKS

9" 1'-7" 1'-7"


...................................................................
...................................................................
...................................................................
...................................................................
1'-8" 5'-10" 6'-0" 4'-9" 1'-8" 10'-7" 6'-0" 1'-8" 6'-6" 9'-4" 1'-8" 11'-7" 4'-11" ...................................................................
1" ...................................................................
7'-6" 6'-0" 4'-9" 12'-3" 6'-0" 1'-6" 6'-7" 9'-5" 1'-6" 11'-8" 4'-11"
...................................................................
18'-3" 18'-3" 17'-6" 13'-2" ...................................................................
...................................................................
72'-1"
...................................................................

5 4 3 X
SECTION 2 1
FIFTH FLOOR PLAN
FLOOR AREA: 1908.16 Sq.ft (WITHOUT BALCONY) ARCHITECTURAL BUILDING
FLOOR AREA: 1938.19 Sq.ft (WITH BALCONY) SCALE: 3/32" = 1'-0"

POWER SOCKET & AC PLAN

SHEET NUMBER E18


OCTOBER 2021