ELECTRIC SYSTEM PROTECTION DIVISION

PROTECTIVE RELAY SETTING SCHEDULE


SUBSTATION : QATIF BSP RELAY NO: SC-15286
EQUIPMENT: 69KV K. F. 1. A 2 BY: MAF

•tLAY SET: SECONDARY DATE : 01/04/2002


MANUFACTURER
APPLICATION TYPE&RATING SETTINGS
NON-DIR Manufacturer :
GROUND O/C GROUND O/C PROTECTION
GEC
PROTECTION

TIME CHARACT. SWITCHES


(0) (1)
Relay Type: STANDARD
MCGG22 INVERSE

Is = 0.2 x In = 0 2A
Xt = 0.35
Iinst = DEACTIVATED
Rating:

Is: (.05-2.4>0
Xt: (.05-1. OX)
1 ins: (

In = IA
1.5 SEC 1.OA

Device No:
50/51N
BASIS OF SETTINGS:

COMMENTS :

DRAWING NO:
CIRCUIT BREAKER: A525
CT RATIO: 1200/1 VT RATIO:
ECORD NO: 22211 PAGE : 1 OF: 1