SUKMA KELANTAN 2026 - PEMBINAAN ARENA TERTUTUP, KOMPLEKS

SUKAN BUKIT MERBAU, PASIR PUTEH, KELANTAN ( REKA DAN BINA )

WATER DEMAND CALCULATION

Water demands are based on ONE (1) day storage.

1.0 Water Demand Calculation :

1.1 Domestic Tank

Stadium :
SPAN Requirement : 55 Ltr/ person
Total No. of Person : 1000 pax
Total water demand = 1000 person x 55 Ltr/person
= 55,000 Ltr
= 12,100 Igals

Suction Tank Cap. = 1/3 x 12,100


= 4,033 Igals

Storage Tank Cap. = 2/3 x 12,100


= 8,067 Igals

Tank Size (FRP) :

a) Suction Tank : 4m x 2m x 3 m (h)


Effective Cap. : 4,752 igals

b) Storage Tank 1 : 4m x 3m x 2m (h)


Effective Cap. : 4,488 igals

c) Storage Tank 2 : 4m x 3m x 2m (h)


Effective Cap. : 4,488 igals

1.2 Flush Valve Tank

Storage capacity basesd on type of fittings :

SPAN Requirement : 180 Ltr / Water Closet


180 Ltr/ Urinal

Water Demand 1|Page


Flush Valve Tank No. 1

Total Fittings : 11 nos. WC


7 nos. Urinal

Total water demand for WC = 180 Ltr x 18 nos.


= 3,240 Ltr
= 713 Igals

Tank Size (FRP) = 2 x 1 x 2 m (h)


Effective Cap. = 748 igals

Flush Valve Tank No. 2

Total Fittings : 9 nos. WC


2 nos. Urinal

Total water demand for WC = 180 Ltr x 11 nos.


= 1,980 Ltr
= 436 Igals

Tank Size (FRP) = 2 x 1 x 2 m (h)


Effective Cap. = 748 igals

Water Demand 2|Page


Water Demand 3|Page