Professional Documents
Culture Documents
TT Mag Issue 001
TT Mag Issue 001
new Technology
Changing the Heart
of Power Systems
LOOKING FOR
NEW MARKETS?
WE WILL SHOW YOU HOW.
Advertize
with TT
and strengthen your presence
in the transformer market.
Contact
transformer-technology.com
4 Table of
contents
Index Contents
Table of
Table of Contents_04
Editor’s Letter_06
At a Glance_12
Coming Events_21
Energy_22
22
Feature
High Temperature Insulation
Interview
Systems: An Option for Resilient
Jon Trout is Manager of Transmission
Transformers_28 Design for FirstEnergy, who has
experienced many changes in the world
New Loads, New Problems: of transformer technology over the
years. In this interview we were curious
Why Harmonics Destroy to find out what changes he considers
to be the most important.
Transformers_34
Bushings_56
Coming in June_66
Transformer Technology March 2019 5
Issue 1
28 48
Transformer
Natural Esters
Resiliency
Natural ester fluids have been around
Richard P Marek reviews the latest for more than a century. Recently
developments and trends towards more environmental pressure
highly moveable large power has emphasized the need for an
transformers designed to improve grid environmentally safe dielectric fluid
resiliency. to replace mineral oils. Modifications
to improve electrical properties and
oxidation stability made this possible.
By Corné Dames
56
Power Factor
This article outlines the advantages
of performing Power Factor
frequency-sweep and voltage-sweep
Dear Readers,
When I was first offered to become the Editor in filler for advertising. As you can see, this first
Chief, three thoughts came to mind immediately: issue is all about “New” Transformer Technology
First was, why me, did everyone else turn it down? and we barely scratched the surface. Rest assured
The second was the reason for the first; my pas- this theme will be repeated from time to time as
sion for transformers was less about their tech- we see the need for publishing changes and up-
nical nature than it was about their reliability. dates. The June issue will be themed “The Revo-
As the Vice President of Reliability for one of the lution in Dry Type Transformers” given the many
North American leading companies in transform- changes taking place in that segment of the in-
er maintenance, oil testing, training and field ser- dustry. Future issues in September and December
vice, that has been my primary focus, not on their will focus on “Testing and Monitoring Best Prac-
technology. tices” and “Critical Failure Modes and Prevention”,
respectively.
But the third and perhaps most important object-
ion was: why? Why did we need a magazine called Recently, I had a chance to attend or review seve-
Transformer Technology? It was the answer to that ral major conferences and/or exhibitions, which,
last question that made the difference – a realiza- by the way, will be one of our goals at Transformer
tion that we need a North and South American fo- Technology – keeping you up to date with events
cused publication that would bring the best and or conferences related to or affecting transform-
the brightest together, as readers, as contributors, ers. The first event was the bi-annual IEEE PES
as advertisers. You have before you, I am proud to Conference in Denver last year and the second
say, our first issue, focused on new technology or was DistribuTECH, which was held this year in
adaptations and updates of older technology for New Orleans. What amazed me most about both
transformers. events was how much digital technology, software
and Artificial Intelligence (AI) or Machine Learn-
The authors have been tremendously gracious to ing (ML) seemed to be the rage. Will any of these
share their knowledge and expertise without ha- changes in the marketplace impact transformer
ving a previous issue as a template. That is an technology in the future? You can be certain they
accomplishment in and of itself. Their willingness will and we will be there, reporting on what is new
to trust and to meet the deadlines and submit to and relevant.
an editing process still in development, has been
something I will personally remember and trea- That leads me to a commitment: Just because
sure. Excellence is one of my most important per- something is new does not mean it is useful or re-
sonal challenges and something they achieved in levant. At a recent Reliability Conference, I coined
our first issue. the term UIoT or the Useful Internet of Things.
That was in the midst of a full day of short presen-
There were two important aims that we defined tations devoted to AI and ML from the perspective
before embarking on this project. The first was of reliability. With over 30 presenters, it became
that we would produce a magazine, both digi- hard to separate the wheat from the chaff. How
tal and print, a daily news feed and an interac- much of what is coming will be needed or useful?
tive website distinguished by excellence. We have Our hope is to sift through the chaff and bring you
a team handling the heavy lifting when it comes only the wheat as it relates to transformer tech-
to the actual articles from drafts to layout and nology.
print, and they are delight to work with. And my
own personal champion, Rachel Linke, has been As an engineer, I like to look at things from the
tremendous in keeping me and our contributors perspective of a problem to be solved, and most
organized and on track. Thank you all for your engineers I know are the same way. We were
commitment to excellence as well. Also, a great drawn to engineering by the need to know and
thank you to Dale Bissonette and all the people the desire to solve problems. Electrical, mecha-
at SDMyers, who have sponsored my journey into nical, chemical or any engineering discipline for
the world of transformers and transformer tech- that matter all have as the core the desire to
nology and reliability for nigh on a decade now. know and to understand. Most engineers are life-
Without their support, none of this would have long learners and the writers in this issue are
been possible. great examples of that. I expect you’ll hear from
them again in these pages. I commit to you, our
The second was that we created a learning arc, readers, that we will strive to be a great source
where we could approach transformer technolo- of new knowledge, while building on the exist-
gy in a cohesive and logical manner, rather than ing body of knowledge that has stood the test of
cobbling together a bunch of articles, most of time. We will also face the challenge of a chang-
which did not relate to each other, just to be the ing of the guard as boomers retire and a new
Transformer Technology March 2019 7
Issue 1
Alan M Ross
What if much of that legacy
knowledge isn’t worth pass-
ing on in the first place? What
if things have changed – and
are changing – so rapidly in
our field of electrical system
reliability that much of that
legacy knowledge is outdated,
or even worse, what if it is flat
out wrong? Would we want to
make sure the next generation
learned it?
Thank you,
Transformer Technology
Editor in Chief
Alan M Ross
CRL, CMRP
Magazine
8
SUB
SCR
I B E TO
$75 /year
DIGITAL Subscription includes 4
successive issues per year
FREE
Receive print copies of the
Annual subscription magazine in your letterbox
and enjoy the joy of reading
To subscribe visit
transformer-technology.com
Transformer Technology March 2019 9
Issue 1
10 Editors &
IMPRESSUM
Impressum Editors
Editor in Chief
Alan M. Ross, CRL, CMRP Editor in Chief
Contributing Editors Alan M. Ross CRL, CMRP
Diego Robalino, PhD, PMP, IEEE Senior Transformer maintenance
Member and reliability
Corné Dames, Independent Transformer 26 years industry
Consultants experience
Lee Murray, Transformer reliability
content editor
Graphic design
Bekoncept Communication Boutique
Photo Contributing Editor
Shutterstock.com Diego Robalino PhD, PMP
Cover photo courtesy of SDMyers IEEE Senior Member
Transformer condition
Sales & Marketing assessment and
Kevan Sears diagnostics
kevan.sears@apc.media 20+ years industry
experience
Marketing Global
Marin Dugandzic
marin.dugandzic@apc.media
Publisher:
APC MEDIA LLC
11210 West Rd, Roswell
GA 30075, USA
transformer-technology.com
Transformer Technology March 2019 11
Issue 1
It’s easy
to keep in
the loop!
WITH
At a Glance
At the end of last year, China had poured at least $57 billion into the
projects, according to Bloomberg New Energy Finance.
Issue 1
Source: Enerdata
14 AT A GLANCE
Source: ABB
Issue 1
The GSU Resilience Transformer is easy to load and ship and its
plug and play bushings allow for an extremely short
installation time. The transformer is also
designed with environmentally-friendly
synthetic ester fluid so it
can be installed near water
or sensitive areas.
Source, Photo: MR
Source: MIDEL
Transformer Technology March 2019 17
Issue 1
The New York Power Authority (NYPA) was recognized for its
first-of-its-kind transformer asset health system that helps to
predict failures in electricity generation transformers before they
occur with a Technology Transfer Award from the Electric Power
Research Institute (EPRI), NYPA announced in the press release.
Source, Photo: MR
Source: EPRI
Transformer Technology March 2019 19
Issue 1
Obtaining the license will enable the company to better service their
growing customer base, Delta Star said in a press statement.
YOUR PASSION
AND KNOWLEDGE
ARE IMPORTANT
TO US
PUBLISH
WITH TT
Are you passionate and knowledgeable
Contact us at
info@transformer-technology.com
to find out how you can
become part of the
Transformer Technology
community.
Transformer Technology March 2019 21
Issue 1
Events
BANGKOK, THAILAND
IEEE Transformers
Committee - Spring
Meeting
March 24 - 28, 2019
ANAHEIM, CALIFORNIA
CWIEME Shanghai
March 26-28, 2019
SHANGHAI, CHINA
HANNOVER MESSE
April 1-5, 2019
HANNOVER, GERMANY
86th International
Conference of Doble
Clients
April 7-12, 2019
BOSTON,
MASSACHUSETTS
CWEXPO 2019
May 8-10, 2019
SHENZHEN, CHINA
CWIEME BERLIN
May 21-23, 2019
Photo by Shutterstock
BERLIN, GERMANY
22
Jon Trout
Feature
Interview
Photo by FirstEnergy
Issue 1
Transformer Technology
the transformer.
their designs to smaller
additional material is in
Manufacturers optimize
Jon Trout’s current role is Manager – Transmission Design for FirstEnergy, responsible for the Transmission Design activities in
the Akron, OH office. Jon’s previous experience at FirstEnergy included significant experience with Transformer specification and
purchasing. Jon also has experience at SD Myers, working with industrial applications on Transformer Life Cycle analysis, including
condition assessments, online DGA monitoring and transformer electrical testing.
23
24 Feature
Interview
Transformer Technology: What is the most through when I’m evaluating a manufacturer is
significant transformer design and manufacturing to look at the different aspects of their design
change you have seen in your career? process and their manufacturing process. When
I’m evaluating a plant, I’m looking to see how
Jon Trout: The increase in the accuracy of our they control the flow of material through the
design techniques has really changed the way plant, how they handle transformer windings,
transformers are manufactured and built. how the material is handled, and make
Transformer design continues to advance, and observations on the press board and wire.
the technology around analyzing the various Cleanliness is very important. What sort of set
aspects of the transformer continue to improve. up is there to maintain the cleanliness of the
Manufacturers optimize their designs to windings? Because the contamination of the
smaller and smaller margins. That optimization windings can be a big problem, and maintaining
impacts how the transformer gets built, how good cleanliness around the winding room is
much safety margin is involved, and how much very important.
additional material is in the transformer.
I look for how they maintain the other areas
Issue 1
1
Photo by FirstEnergy
2
2) FirstEnergy’s grid modernization program in Pennsylvania.
Transformer Technology March 2019 27
Issue 1
JT I’ve always
described
engineering as a series of JT Gassing is an excellent indicator of
potential problems. Sometimes the
trade-offs. It’s always a gassing is in a situation where you need to be
case of trying to optimize able to trend the information to see what’s
your situation for what happening. I have some experience working
you’re trying to achieve. alongside a steel manufacturer, helping them
Manufacturers and evaluate the conditions of their transformers
utilities and the owners based on some online gas monitoring, and we
of these transformers are were able to watch some units over the course
all playing that balancing of time that were gassing. By observing trends,
act of how to optimize however, we could see that the gassing was
the situation. Utilities steady over time, which meant there was no
and transformer owners apparent incipient fault happening.
have financial constraints
around the available One particular unit had a significant spike of
resources they have to gassing at a very specific time, and that unit
acquire the equipment then settled back down there very little gassing
that they need. Likewise, over the next few months. And if you don’t
manufacturers have know what you’re looking for, you may see a
constraints around spike like that and overreact, or maybe under
their resources of what react to a gassing situation that seems under
materials they can control when you haven’t seen the spikes. It’s a
purchase. So everyone is challenge in the industry that everyone’s trying
looking to optimize the to get their hands around. But we’ve got a lot
situation. of experience in the industry, and it’s ever-
evolving. There’s always new challenges and
I think that we’re going new opportunities to understand the condition
to find that the designs of transformers based on the gassing and other
that are being put out oil quality tests.
now will be adequate and
Richard P Marek received his BSEE from For many years, utilities have used transformers designed to improve
Purdue University and has been employed mobile transformers or complete grid resiliency. Using advanced
with DuPont since 1998. His previous work mobile substations to mitigate insulation systems allows
experience includes a total of 28 years as outage risks in their smaller capacity innovative design techniques that
a transformer design engineer. He is a sen- substations. These fast deployable result in smaller size and lower
ior life member of IEEE where he has been units have offered the advantages weight transformers. Initially
active in the Transformers Committee since of quick availability of replacement developed specifically for mobile
1982 and he was chairman/convenor of the equipment. They are mobile, transformers and substations,
high temperature liquid immersed trans- compact, lightweight, and versatile, the hybrid insulation system has
former standards IEEE C57.154 and IEC generally covering multiple voltage evolved to allow much larger units
60076-14. He is also an IEC TC14 delegate ratings. Designed to match the to be transported more easily and
for the US TAG. regional road weight limits, they can rapidly to areas with emergency
be installed and operating in a very situations. Among various design
short time. Now, this same concept methods for reducing the size and
is being applied to large power weight of power transformers, high
applications. temperature insulation systems
offer a key tool.
This article reviews the latest
developments and trends towards Many modern design techniques and
highly moveable large power state-of-the-art optimal technical
Transformer Technology March 2019 29
Issue 1
solutions have already driven Application of High-Temperature This document introduced many
designs to be smaller and more Insulation Materials in Liquid- key definitions necessary to
compact. However, the use of high Immersed Power Transformers” [1] describe new insulation systems
temperature materials and insulation was published after this working which are defined by temperature
systems allows a step change in the group first published a thorough class rather than by specific
ability to make designs significantly background paper in 1994 titled combinations of solid materials
more compact, compared to so- “Background Information on High- in a liquid. These concepts were
called “conventional” designs, based temperature Insulation for Liquid- patterned after the insulation
on cellulose insulation and mineral Immersed Power Transformers” [2]. system approach to motors and
oil. In order to reach maximum In 2008, the development of a dry type transformers which has
size reduction, new insulation document was begun by IEEE: worked well for many years.
components must also be developed IEEE Standard C57.154 –
using high temperature materials. “Standard for the Design, Testing,
and Application of Liquid-
For many years standards Immersed Distribution, Power, and
development has played a major Regulating Transformers Using
role in expanding high temperature High-Temperature Insulation
Photo: Delta Star
Issue 1
temperature insulation, were shipped principle was to make the units resiliency units to the New York
and were fully energized in less than modular, transportable and quick to City utility in 2016 for its network.
a week. install. The challenge was to reduce These units will act as emergency
the transformer’s size and weight to replacements in case of unplanned
From a design standpoint, the less than 59,000 kg. The final design outages, such as those caused by
transformer, called the RecX, had actually weighs in at less than hurricanes or may also be used for
to meet numerous installation 57,200 kg and is small enough to be planned outages. Normally, failure
requirements, including storage shipped by truck, while maintaining of one of these large transformers
and transportation specifications its performance and reliability. causes many issues including:
that required a small footprint and
light weight to ship on standard A similar fast-deployable transformer
• Long lead times for new
transformers (up to 14 months)
trucks. Building on ABB’s mobile
transformer expertise, they chose a
concept was developed in another
ABB project in Spain. In this case,
• Multiple spares needed for various
rated transmission transformers
high temperature hybrid insulation three 250 MVA, 400 kV units with • Shipping and logistic issues
system to reduce both size and
weight. Alone or in hybrid solutions
multiple voltage ratings on the LV
side were built using a shell type
• On-site assembly that can take
weeks and is weather dependent
with cellulosic pressboard, insulation construction. The design evaluation
systems based on aramid maintain showed significant weight and As it was demonstrated in January
excellent electrical, thermal and size reduction was possible by 2017, the mobile resilience
mechanical characteristics over a using a hybrid insulation system transformers allowed the utility
transformer’s service life. Reduced in the transformer windings. The to respond to these events, where
aging, high resistance to shrinkage new unit with hybrid insulation not multiple transformers may be
and compression, combined with only achieved a base rate increase impacted and normal spares or
the excellent dynamic mechanical of 25% compared to the installed system redundancy may not be able
strength of aramid paper and board, unit (250 MVA vs. 200 MVA), but to address the issues. SIEMENS
all help ensure that coil structures it represented a more than double provided six transportable resilience
will remain tight and are able to base rate increase, compared to the transformers to help replace units
withstand short-circuit forces, maximum rating of the conventional within days rather than weeks in
even after years of service. The cellulose mineral oil unit (250 MVA times of outages due to extreme
RecX 200 MVA prototype bank of vs. only 117 MVA). weather or other major events.
single phase units were designed The new transformers are highly
Photo: ABB
to replace a 600 MVA, 345/138 kV A new step of innovation was optimized for weight and dimension
autotransformer. The RecX design reached when SIEMENS delivered through advanced design and
32 Transformer
Resiliency
emergency applications. The selected installations and improve a solution against major events,
concept could be of benefit the resiliency of the overall system, CIGRE A2 Colloquium, Zurich,
for upgrading existing space since they can be deployed faster 2013
constrained substations, as well. using conventional trucks.
Transformer Technology March 2019 33
Issue 1
34 HARMONICS
Photo by Shutterstock
Transformer Technology March 2019 35
Issue 1
Eddy Currents
Application of non-sinusoidal due to the crowding effect of the The resultant increase in eddy
excitation voltages to transformers leakage magnetic fields at the coil currents increases the operating
increase the iron losses in the extremities. The eddy current losses temperature of the core iron, which
magnetic core of the transformer in increase as the square of the current in turn begins to deteriorate the
much the same way as in a motor. in the conductor and the square insulation between the core iron
A more serious effect of harmonic of its frequency. The increase in laminations. This leads to greatly
loads served by transformers transformer eddy current loss due to increased I2R losses, beyond the
is due to an increase in winding harmonics has a significant effect design limits of the transformer,
eddy current losses. Eddy currents on the operating temperature of the and overheating of the actual
are circulating currents in the transformer. Transformers that are winding insulation. Once the winding
conductors induced by the sweeping required to supply power to nonlinear insulation allows the energized
action of the leakage magnetic field loads must be de-rated based copper winding to contact the
on the conductors. Eddy current on the percentages of harmonic grounded core-iron, an internal
concentrations are higher at the components in the load current and failure will result. This process is
ends of the transformer windings the rated winding eddy current loss. illustrated in Figure 1.
and damaged.
Transformer Technology March 2019 37
Issue 1
Eddy
1 1 1 1 1 1 1 1 1 1
Current
Impedance 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Heating
I2R 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 5.0
Eddy
1 1 1 1 10 1 1 1 1 1
Current
Impedance 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 Heating
I2R 0 0 0 0 50 0 0 0 0 0 50.0
Transformer Technology March 2019 39
Issue 1
Solutions
new loads will hopefully not fail the voltage distortion exceeds 3%,
within days of the new loads being the utility should provide some form
installed. of mitigation to correct the problem.
40 DIELECTRIC
RESPONSE
Photo by Shutterstock
Transformer Technology March 2019 41
Issue 1
DFR References
As mentioned previously, since the The practical application of DFR in the solid insulation by dielectric
beginning of the use of insulation in the field generated the interest response methods.
materials, a method to determine in the industry and international
an acceptable condition for its organizations took lead on Considering the great acceptance
use in electrical applications was the investigation of this “new of the technology in the field, the
required. The dielectric response technology” revolutionizing the CIGRE Working Group (WG) A2.34
of any insulation material can be testing practices in the field. incorporates dielectric response
obtained in the time domain or in methods in time and frequency
the frequency domain. Time domain In 2002, CIGRE developed the domain in section 5.1.3 in the
dielectric response has been in Technical Brochure 254 – “Dielectric Technical Brochure 454 published
place for over 100 years and the Response Methods for Diagnostics in 2011. Dielectric response
typical “Insulation Resistance” test of Power Transformers”. This report methods are included as “Special
became, by far, the easiest and most from the Task Force (TF) D1.01.09 or Advanced Measurements”. DFR
practical approach to understand the focused on three dielectric response or FDS is an advanced testing
condition of the solid insulation. techniques: technique used in the field to
determine the water content in the
• Return Voltage solid cellulose insulation of oil-
The complex impedance Measurements (RVM) paper insulation, insulation failures,
Peter Werelius and Bjorn Bengtsson maybe the most important part, case
introduced IDA (Insulation Diagnostics studies and comparative analysis
Analyzer) mainly for cable and using Karl Fisher Titration (KFT) to
transformer testing. validate the moisture estimation
Transformer Technology March 2019 43
Issue 1
In the North American world, the IEEE The work carried out by the IEEE
Transformer Committee revised the transformer committee ended up
document IEEE 62 Part 1– “Guide for with the publication in 2013 of
Diagnostic Field Testing of Electric the IEEE Std. C57.152 – “Guide
Power Apparatus – Oil filled Power for Diagnostic Field Testing of
Transformers, Regulators, and Fluid-Filled Power Transformers,
Reactors”. One of the fundamental Regulators and Reactors”. The
reasons to revise this document amount of information put together
was the application of new testing in this document is difficult to
techniques not described in this describe in just a few lines, but
document and considered important this guide added the Informative
for the current requirements of ANNEX G introducing to the IEEE
manufacturers and end-users references the Dielectric Frequency
especially in the field. It is interesting Response Method. Annex G provides
to notice that IEEE 62 (R2005) a brief description of the DFR
provided in section 6.3.12 two method and its interpretation for oil-
tables with general guidelines for paper insulation systems in power
interpreting data expressed in transformers.
percent saturation of water in oil and Enough about history. Let us focus
in percent moisture by dry weight of now on the recently published guide
paper. for DFR testing.
44 DIELECTRIC
RESPONSE
Issue 1
The modelling algorithm requires Besides the modelling part, it is As any other electrical test, the
specific information to evaluate the important to understand that the test very first recommendations are
condition of the insulation system. is performed in the field following the related to safety. For many readers,
The normally fixed information is: same instrument-to-object hook up safety is not just a best practice
a. Liquid Insulation relative principles as those used for power but also a life style. Therefore, local
permittivity εr factor / dissipation factor testing at and federal regulations required to
b. Thermal activation energy for line frequency. Figure 1 shows the perform the test as well as safety
solid and liquid insulation hook up diagram of the DFR test set instructions provided by the test set
c. Temperature of the insulation to a commonly used two-winding manufacturer must be followed. One
under test transformer. more advantage of DFR is that the
test involves a LV excitation signal
The outcome of the test will provide: Section 5 provides the best practices typically ≤140 VRMS.
a. Liquid insulation conductivity (σ) and configurations to perform the test
b. Moisture in solid insulation (m) in the field.
In the field, working conditions Section 6 provides the guidelines to Overcome the effect of noise (EMI)
might not be optimal. Section 5 generate the test report, including an on the measurement signal, the use
provides guidelines to minimize example of the report. of a voltage amplifier is considered
the effect of external factors on as optional in the field, especially
the test performance as well as the Maybe the most important part for low capacitance specimens and
measurement configurations. At this of the guide is without a doubt tests at temperatures close to zero
stage, the reader should be aware Section 7 – Measurement Analysis degrees Celsius.
that the most accurate estimation and Interpretation. In this section,
of moisture in the solid insulation the guide provides the differences The Annexes included in the
is related to the test between between the dielectric response document cover:
windings in a UST (ungrounded of liquid and solid insulation A. Dielectric Frequency Response
specimen test) test mode. In a two- graphically represented in Figure 2. Analysis – Theory and validation
winding transformer, the capacitance The liquid insulation dielectric B. Non-moisture related
of interest is the inter-winding properties can be described by factors influencing the DFR
insulation between high and low a simple parallel RC-circuit, the measurements
voltage windings represented in capacitance representing the liquid C. Examples of typical measurement
Figure 1 as CHL. Other insulation permittivity and the resistance the challenges
systems, between high voltage liquid conductivity. The dielectric D. Bibliography
winding and ground (CH) or between properties of solid insulation are
the low voltage winding and ground more complex, both capacitance Closing Note
(CL) are susceptible to the influence and losses vary with frequency in a
of bushings and sometimes-other manner that cannot be described by This article is a brief summary
components inside the transformer a simple parallel or series RC-circuit. of a well-developed document
such as tap changers. Nevertheless, provided by IEEE and its members.
the GST measurements are often After a clear understanding of the Authors consider imperative for
taken to identify non-typical behavior of the materials under an asset managers, utility operators,
responses related to contamination alternating excitation signal in a wide transformer manufacturers and
or degradation of the insulation frequency spectrum, different factors testing service providers to acquire
system. affecting the dielectric response are this document and follow the
described. One of the most important guidelines given.
factors to take into account is the The article is co-authored by Dr.
Figure 2. DFR of mineral oil (left); presence of EMI in the surrounding Roberts Neimanis, Product Manager
DFR of paper only (right) test area. at Megger Sweden.
10000 100
1000
100
10
10
1
1
0.1
0.01
Photo by Shutterstock
0.001 0.1
0.0010 0..010 0..1 11 01 00 1000 0.0010 0..010 0..1 11 01 00 1000
Issue 1
New Developments in
Natural Ester Fluids:
Modification by
Addition of
Nanoparticles
Applied in Electrical
Transformers
by Corné Dames
Issue 1
Advantages of Natural
Esters
to the natural
management solutions • Lower lifecycle costs and better
• Higher flash and fire points that utilization of assets
ester fluids there assist in overall safety which can
result in lower substation upgrade
• Coming from renewable resources
makes them recyclable and
should be an costs. reusable
• Interactions between the fluid and • Lower gassing tendency under
improvement to cellulose have been identified to electrical stresses and better
extend insulation life resistance to sludge formation
the key electrical • 95% bio-based, providing a very • Due to their viscosity and ability
high degree of sustainability to polymerise when thin layers
properties of the • A unique ability to absorb are exposed to warmth and air
fluid. moisture contained in aging paper
that can extend insulation life by a
flow, they do not spread along the
surface and into subsurface soil
factor of as much as five in the case of spillage
In general, vegetable
oil is fully miscible
with traditionally
used mineral oils, so
it can be used to refill
existing transformers.
Additionally, corrosive
sulphur is not present in
natural esters.
Considering their fire
point is much higher
than that of mineral
oil, natural esters are a
much safer choice for
areas where a) there
is a risk of human life,
b) there are high down
time costs, c) there is
difficult evacuation of
surrounding areas, and
d) where transformer
replacement time
and cost are posing a
problem.
Issue 1
Disadvantages of Natural
Esters
Preparation of Electro-
insulating Ester Fluid
Issue 1
Primary Particles
Nanofiller Oxide Purity (%) Variation Surface Treatment
size (nm)
>96% TiO2 20 Hydrophilic SiO2
TiO2
<4% SiO2 UV resistive
TiO2 99+ 20
_
Al2O3 y 99,97 20-30
_
Al2O3 y 99,99 10
>98 SiO2
SiO2 <2 (3-Aminopropyl) 20 Hydrophilic (3-Aminopropyl)
Triethoxysilan Lipophilic Triethoxysilan
SiO2 99+ 20 Hydrophilic
>98 ZnO
ZnO <2 (3-Aminopropyl) 30 Hydrophilic (3-Aminopropyl)
Triethoxysilan Lipophilic Triethoxysilan
ZnO 99+ 20
ZnO 99+ 30
Issue 1
Coiltech 2019
25-26 September Pordenone - Italy
marcogarofalo.net
3246
390
International
2988
353 2407
303
Exhibiting companies 252 Visitors 1982
1802
226
175 1286
125 941
Domestic
85 676
47 397
2010 2011 2012 2013 2014 2015 2016 2017 2018 2010 2011 2012 2013 2014 2015 2016 2017 2018
Owner/Co-owner 18%
T2 Advanced powertrains for electric vehicles
President/CEO/Vice president 6%
T3 Electric motor industries
Other top management 3%
T4 Transformers
Head of Purchasing and sourcing 12%
T5 Electric motors for pumps and compressors
Purchasing and sourcing staff 6%
T6 Special electrical machines and actuators
Other staff 7%
T7 Testing on high efficiency electric motors
T8 Electric motors for household appliances
*Source: Information obtained by the Coiltech Marketing Team on the base
T9 Materials of personal phone interviews, encounters, and other research
T10 Technologies and systems
T11 Software
Sign up for your free e-ticket: www.visitcoiltech.com or if you prefer contact us: coiltech@quickfairs.net
56 Power
Factor
Photo by Shutterstock
Transformer Technology March 2019 57
Issue 1
Introduction
The Engineer
It is widely known that the best Although this paper focuses on The Power Factor
way to assess a Power Factor applying Power Factor sweep Voltage-Sweep Test
measurement is to compare measurements to the C1 insulation (aka the Voltage Tip-Up Test)
the most recent measurement system of bushings, the same
to a series of previous baseline analysis strategies are valid for Performing a Power Factor
measurements that were obtained assessing Power Factor sweep measurement at multiple test-
at consistent test-intervals. However, measurements performed on the voltages helps identify compromised
many asset owners do not have overall winding insulation of a power insulation as well as invalid Power
a collection of reliable baseline transformer. Factor measurements.
test results for their transformer At a minimum, an oil-and-paper
fleet, which makes assessing the In general, the analysis involves insulation system should be tested
condition of an insulation system determining whether the shape of at two test-voltages (e.g. 2 kV and
and determining the appropriate a trace is normal or abnormal. If 10 kV). In most cases, a Power
course of action a challenge. either of the sweep measurements Factor measurement performed
produces an abnormal trace, and on bushing insulation should not
the measurements are valid, then be voltage sensitive. Therefore,
the insulation system should be regardless of the applied test-
investigated and/or tested more voltage, the measured Power Factor
frequently in the future. value should be the same.
Issue 1
0.65
Figure 1. Acceptable
0.60 C1 Power Factor
frequency-sweep
traces
0.50
0.45
0.40
0.35
0.30
0 100 200 300 400
Frequency (Hz)
H1 H2 H3
comparison.
Transformer Technology March 2019 61
Issue 1
The first case involves Power Factor measurements that were performed on three
Haefely 115 kV bushings (specified in Table 1), see Figure 2.
Table 1.
0.45%
0.40%
0.35%
0.30%
0.25%
0 100 200 300 400
Frequency (Hz)
H1 H2 H3
Based on the results in Figure 2, the 10 kV Power Factor for H3 is higher than its nameplate
value, whereas the 10 kV Power Factor for the other two bushings is below their respective
nameplate values. Notice that the 2 kV and 10 kV Power Factor measurements for the
H3 bushing are dissimilar. In contrast, the 2 kV and 10 kV Power Factor measurements
for the H1 and H2 bushings are reasonably similar, which further suggests that the H3
measurements are abnormal.
When comparing the Power Factor frequency-sweep traces among similar-unit bushings,
the shape of the traces should be reasonably similar. Clearly, the shape of the H3 trace is
dissimilar relative to the traces of the other two bushings. Moreover, the H3 trace decreases
versus frequency and has the distinctive fish-hook in the lower frequency range; this is
typically indicative of compromised insulation.
Interestingly, the 10 kV Power Factor for H3 is below 1.5 to 2 times its nameplate value,
which the industry generally considers to be acceptable. However, the H3 bushing is clearly
behaving differently than the other two similar bushings, which is cause for concern.
This case demonstrates that Power Factor sweep measurements are more sensitive to
compromised insulation than conventional 10 kV Power Factor measurement. The H3
bushing should be flagged as the weak link among the three bushings, and if returned to
service, should be tested more frequently to gauge the severity of the situation.
62 Power
Factor
The second case involves Power Factor measurements performed on three Lapp POC
Series 2 115 kV bushings (specified in Table 2), see Figure 3.
Table 2.
0.40%
Figure 3. C1 Power
Factor results for
three Lapp POC
0.35% Series 2 115 kV
Power Factor (%)
bushings
0.30%
0.25%
0.20%
0 100 200 300 400
Frequency (Hz)
H1 H2
The Power Factor frequency-sweep trace for the H3 bushing is not plotted because its
10 kV Power Factor value is three times its nameplate value, which is already enough
to condemn the H3 bushing. In other words, the Power Factor frequency-sweep trace
for the H3 bushing only confirms what we already know. Additionally, the 2 kV and 10
kV Power Factor values for the H3 bushing differ significantly — further evidence to
condemn the H3 bushing.
Based on the results in Figure 3, the 10 kV Power Factor value for H1 is higher than
its nameplate value, whereas the 10 kV Power Factor value for the H2 bushing is the
same as its nameplate value. Additionally, the frequency-sweep trace for the H1 bushing
is clearly dissimilar relative to the frequency-sweep trace for the H2 bushing. The H1
trace decreases versus frequency and has developed the distinctive fish-hook in the
low-frequency range — typically indicative of compromised insulation. Although the 10
kV Power Factor for H1 is well below 1.5 to 2 times its nameplate value, the H1 bushing
is clearly behaving differently than the H2 bushing. As a result, the H1 bushing should
be tested more frequently to gauge the severity of the situation.
Transformer Technology March 2019 63
Issue 1
The third case involves Power Factor measurements performed on three Westinghouse
Electric Type-S 37 kV bushings (specified in Table 3). The Power Factor measurements
are summarized in Figure 4.
This case provides an example of three sister-unit bushings that produced three
completely different Power Factor frequency-sweep traces. The Power Factor frequency-
sweep trace for the H1 bushing is a typical example of a trace produced by a healthy
bushing, whereas the Power Factor frequency-sweep trace for the H2 bushing is a
typical example of a trace produced by a questionable bushing. However, the Power
Factor frequency-sweep trace for the H3 bushing is an example of an abnormal or non-
typical frequency-sweep trace, which warrants concern.
Table 3.
Figure 4. C1 Power
1.50%
Factor results for
three Westinghouse
1.30% Type-S 37 kV
bushings
Power Factor (%)
1.10%
0.90%
0.70%
0.50%
01 00 2003 00 400
Frequency (Hz)
H1 H2 H3
Based on experience, there appears to be a bushing insulation failure mode where the
measured capacitance (pF) value of the bushing is dissimilar different relative to its
nameplate value and to the other sister-unit bushings. For this type of insulation failure,
in addition to the measured capacitance (pF) value being different than expected, the
Power Factor frequency-sweep trace becomes more-or-less linear and exhibits a steep
incline from left-to-right (as demonstrated by the H3 bushing in Figure 4).
Interestingly, the H1 and H2 bushings tested with capacitance values well below their
respective nameplate values; the capacitance value of the H3 bushing is above its
nameplate value. If the measurements provided in Figure 4 can be verified, then the
insulation system of the H3 bushing is behaving abnormally, and if returned to service,
it should be tested more frequently to gauge the severity of the situation.
64 Power
Factor
This case involves Power Factor measurements performed on three Lapp POC 138 kV
bushings (specified in Table 4), see Figure 5.
Table 4.
Nameplate
2 kV PF 10 kV PF 10 kV PF – 2 kV PF
Power Factor
0.60%
Figure 5. C1 Power
0.55% Factor results for
three Lapp POC 138
0.50% kV bushings
Power Factor (%)
0.45%
0.40%
0.35%
0.30%
0.25%
0.20%
01 00 2003 00 400
Frequency (Hz)
H1 H2 H3
Based on the results in Figure 5, the Power Factor values for all three bushings are higher
than their respective nameplate values. Notice that the Power Factor measurement for the
H2 bushing is clearly voltage sensitive. Furthermore, the Power Factor frequency-sweep
traces for the three bushings are erratic and jagged. In general, jagged Power Factor
frequency-sweep traces are indicative of invalid Power Factor measurements. Regardless
of whether an insulation system is healthy or compromised, its Power Factor frequency-
sweep trace should be smooth.
By analyzing only the 10 kV Power Factor measurements, it is not obvious that the References
Power Factor measurements for the three bushings are invalid; however, the voltage and [1] IEEE Std. C57.152-2013, IEEE
frequency-sweep test results make it obvious that the Power Factor measurements are Guide for Diagnostic Field
invalid. In this case, the customer determined that the primary-side bushing terminals were Testing of Fluid-Filled Power
not short-circuited together when the C1 Power Factor measurements were performed; Transformers, Regulators, and
this identified the cause of the abnormal Power Factor measurements. Reactors.
Conclusion
Additional Information
With both the voltage and frequency-sweep measurements on hand, invalid measurements For more information and Case
are easier to identify. The equipment operator can use the sweep measurements to quickly Studies regarding the Power
identify and correct invalid measurements in the field before the transformer is placed Factor Sweep Tests, please
back into service. The engineer can use the sweep measurements to identify invalid Power email a request for my extended
Factor measurements, especially when they must rely on the data provided within a test paper titled “The Value of
report. Performing Power Factor Sweep
Finally, Power Factor sweep measurements help to accurately assess the condition of a Measurements on Bushings”.
bushing’s insulation system. This helps the asset owner choose the best course of action.
Transformer Technology March 2019 65
Issue 1
www.omicronenergy.com/transformer
66 Coming
in June
THINK ABOUT...
Don`t
think
about
MARKETING
LET US DO IT FOR YOU
ALL-INCLUSIVE TRANSFORMER
MONITORING PROGRAM
WWW.DOBLE.COM/DOBLEASSURANCE