Vision Series TM

Power Quality Recorder

&Benefits
Features
The Vision combines PMI’s leading-edge power quality recorder
technology with a handheld, graphical meter. Use it to view
real-time waveforms, make spot measurements, and take
measurement snapshots, then leave it in place for full power
quality logging. The Vision measures voltage, current, all power
quantities, harmonics, and flicker.

It’s available in three models: the VisionLite, Vision, and VisionPro.

The VisionLite includes a color graphical LCD display, 1MB of


memory for data storage, and high speed USB.

The Vision adds full power quality measurements such as cycle


interval data, 16MB of memory, and Bluetooth for wireless
connectivity.

The VisionPro includes all features of the Vision model, plus


high-speed Megahertz transient capture, 1GB of memory,
Bluetooth, and Ethernet.

Applications
•Office
•Industrial
•Commercial
•Distribution
•Transformers
•3 Phase with neutral monitoring

Power Monitors, Inc.•800



North Main St. Mount Crawford, VA 22841•(800) 296-4120•www.powermonitors.com
VisionLite TM

Power Quality Recorder


Inputs: AC Voltage 0 to 600 RMS continuous per Harmonics: Voltage to the 51st
channel
Current to the 51st
Measures magnitude, phase, THD
AC Current 0 to 5000 amps

Sample Rate 15,360 samples per Communications: Type USB 2.0


second/channel; Standard
256 samples per cycle

Information Data 1 MB
Channels: Voltage 3 channels Storage: Storage
Current 3 channels
Significant 500 records
Change
Measured RMS Voltage Volts Flicker 500 records
Quantities RMS Current Amps
Per Cycle:
Real Power Watts
Record Settings: Interval Graphs 1 second to 4
hour interval
User selected,
Apparent VAs stop-when-full,
Power or wrap around
Reactive VARs memory modes
Power Significant Change 1V to 8V in 1V
Phase Angle Degrees steps
Flicker User-defined, or
Power Factor Watts/VA Settings conform to IEEE
1453/IEC 61000-
4-15
Displacement PF cos (phase angle)
Waveform Voltage and
Capture current threshold,
Power Usage kWh, kVARh, kVAh
periodic capture
Transient n/a
Capture
Accuracy: Voltage 0.33% of full scale

Current 1.0% of full scale w/o probe Power Supply Internal battery, USB charger
Requirements:
Power 1.0% of full scale w/o probe Environmental: IP51 rating

Phase Angle 1.0° w/o probe


Physical Dimension: Size 7” L x 4.5” W x 1.84” H
Weight 1.2 lbs
Power Factor ±0.02 w/o probe

Displacement PF ±0.02 w/o probe Battery: 5 hour run-time

Safety: IEC 61010-1, 600V CAT IV

Power Monitors, Inc.•800



North Main St. Mount Crawford, VA 22841•(800) 296-4120•www.powermonitors.com A
Vision TM

Power Quality Recorder


Inputs: AC Voltage 0 to 600 RMS continuous per Harmonics: Voltage to the 51st
channel
Current to the 51st
AC Current 0 to 5000 amps
Measures magnitude, phase, THD

Sample Rate 15,360 samples per


second/channel; Communications: Type Bluetooth® 2.0
256 samples per cycle Standard Class 1 Wireless,
USB 2.0
Channels: Voltage 4 channels
Current 4 channels Information Data 16 MB
Storage: Storage
Measured RMS Voltage Volts Significant 1000 records
Quantities RMS Current Amps
Change
Per Cycle: Flicker 1000 records
Real Power Watts
Record Settings: Interval Graphs 1 cycle/second
Apparent VAs to 4 hour interval
Power User selected,
Reactive VARs stop-when-full,
Power or wrap around
memory modes
Phase Angle Degrees
Significant Change 1V to 8V in 1V
steps
Power Factor Watts/VA
Flicker User-defined, or
Settings conform to IEEE
Displacement PF cos (phase angle)
1453/IEC 61000-4-
15, and IEEE Std.
Power Usage kWh, kVARh, kVAh 141
Waveform Voltage and
Capture current threshold,
Accuracy: Voltage 0.33% of full scale periodic capture
Transient n/a
Current 1.0% of full scale w/o probe Capture

Power 1.0% of full scale w/o probe Power Supply Internal battery, USB charger
Requirements:
Phase Angle 1.0° w/o probe
Environmental: IP51 rating

Power Factor ±0.02 w/o probe


Physical Dimension: Size 7” L x 4.5” W x 1.84” H
Displacement PF ±0.02 w/o probe Weight 1.2 lbs

Battery: 10 hour run-time


Safety: IEC 61010-1, 600V CAT IV

Power Monitors, Inc.•800



North Main St. Mount Crawford, VA 22841•(800) 296-4120•www.powermonitors.com A
VisionPro TM

Power Quality Recorder


Inputs: AC Voltage 0 to 600 RMS continuous Harmonics: Voltage to the 51st
per channel (±5 KV peak
Current to the 51st
transients)
Measures magnitude, phase, THD
AC Current 0 to 5000 amps
Communications: Type Bluetooth® 2.0
Sample Rate 1 MHz Voltage (16666 Standard Class 1 Wireless,
samples/cycle), 250 kHz USB 2.0
current (4166 samples/ 10/100MB Ethernet
cycle)
Information
Channels: Storage: Data 1 GB
Voltage 4 channels
Storage
Current 4 channels
Significant 1000 records
Change
Measured RMS Voltage Volts Flicker 1000 records
Quantities RMS Current Amps
Per Cycle: Record Settings:
Real Power Watts Interval Graphs 1 cycle/second
to 4 hour interval
User selected,
Apparent VAs stop-when-full,
Power or wrap around
Reactive VARs memory modes
Power Significant Change 1V to 8V in 1V
Phase Angle Degrees steps
Flicker User-defined, or
Power Factor Watts/VA Settings conform to IEEE
1453/IEC 61000-4-
15, and IEEE Std.
Displacement PF cos (phase angle)
141
Waveform Voltage and
Power Usage kWh, kVARh, kVAh
Capture current threshold,
periodic capture
Transient Peak voltage
Accuracy: Voltage 0.33% of full scale Capture threshold

Current 1.0% of full scale w/o probe


Power Supply
Requirements: Internal battery, USB charger

Power 1.0% of full scale w/o probe Environmental:


IP51 rating
Phase Angle 1.0° w/o probe
Physical Dimension:
Size 7” L x 4.5” W x 1.84” H
Power Factor ±0.02 w/o probe
Weight 1.2 lbs

Displacement PF ±0.02 w/o probe Battery:


20 hour run-time

Safety: IEC 61010-1, 600V CAT IV

Power Monitors, Inc.•800



North Main St. Mount Crawford, VA 22841•(800) 296-4120•www.powermonitors.com A