ESDR 4T

T h e M u ltista g e
C u rre n t D iffe re n tia l P ro te ctio n
S elf-T ested F acility U ser F riendly F acility

Leonhard-Reglerbau
ESDR 4T - THE CURRENT DIFFERENTIAL PROTECTION L

MEASURING • CONVERSION
——————————————————————
COMPARING • MONITORING • PROTECTION

USE Monitoring and protection of


generators, motors and
transformers in unit connection

MEASUREMENT and CONVERSION of the three-phase current at both sides of the


protection object for the differential protection

ADAPTATION • transformer ratio


• vector group
• transformer ratio
(separate for every measuring point)

MONITORING • referring to the nominal current in % or A


• 2- or 3-pole short circuit or earth leakages
• of the differential current Id (difference)
• of the restraint current IS (sum)

TRIPPING CHARACTERISTIC separate adjustable for Id/IN and IS/IN

DISPLAY of the differential and restraint


of the error and operation messages as
well as the measuring values on a LC display

OUTPUT differential protection: via 4 relays


all freely parameterizable via relay manager

ANSI ANSI 87G, ANSI 87M and ANSI 87GT

FEATURES high overload capacity long-term stability


use for selective protection

Leaflet..ESDR 4T • File..ESDR 4T Prospekt Englisch e4t-1401-p.doc • Version..e4t.1401.p/e • Printed..2001-04-07

© Leonhard-Reglerbau GmbH Stuttgart, (+49) 7 11/7 89 54-0 ESDR 4T Leaflet - Page 1


ESDR 4T - OVERVIEW OF FUNCTIONS L
ESDR 4T is a three-phase current differential pro- Features
tection unit for generators, motors and transformers
in unit connection (protection object). The currents » Microprocessor driven measuring method
flowing in the individual conductors are measured by » 10 Bit measuring of the measuring values
means of current transformers installed at both sides
» Measurement: 3-phase system at both sides of
of the protection object. These current transformers
the protection object (6 measuring values)
form the limits of the protection area. Any two-phase
or three-phase short circuits and earth leakages are » Transformer ratio of the measuring transform-
recognized by the ESDR 4T as fault currents. By ers for every primary value separately adjust-
means of freely parameterizable relays, the unit able
indicates any overruns of the adjusted fault current » Adjustable transformer ratio of the transformer
limits. In the event that fault currents occur outside » Selectable transformer vector group (VDE 0532)
of the protection area, the unit does not cause an
» Minimal command time: 40 ms
opening operation. Hence the unit can be used in
protection systems requiring selective tripping op- » 5 mm LC display (green illuminated)
erations. » An internal test routine monitors cyclically the
readiness for operation of the device
To adapt the network configuration to the ESDR 4T
» Mounting
it is possible to change the phase shift of the trans-
→ DIN housing with screwed plug system (cur-
former via selecting the vector group in the display. rent measuring inputs 4 mm² screw terminals)
The different nominal currents of the high- and low → Flush-mounting (IP54 front)
voltage side of the transformer, the transformer ratio → Snap-on rail installation optionally
as well as the transformer ratio can be set in the » Advantages
display, too. Every measuring point can be set sepa- → Reduction of work and expenses
rately. Through this the ESDR 4T becomes a more → Easy commissioning
universal use. → User-friendly operation
→ Safe operation
→ Increased availability
Input / Output

» 6 measuring inputs
→ Primary value for each transformer set ad-
justable separately
→ Secondary values selectable as ../1 A or as
../5 A measuring inputs
» Relay outputs (potential-free)
Monitoring
→ Differential protection:
3 × change-over contact, 1 × closer
» Differential current......................... to 1.25 × IN
» Digital inputs
→ Differential protection » Restraint current ................................. to 3 × IN
4 x metallically separated (Output of the monitorings up to four relays)

Network configuration adjustable in the display Overview - Measuring Inputs

» Transformer ratio of the transformer » 1A Current measuring input..... ESDR 4T01


» Vector group of the transformer » 5A Current measuring input..... ESDR 4T05
(secondary value has to be selected at the order )
» Transformer ratio of the measuring transformer
(primary value for every transformer set sepa-
rately)

Page 2 - ESDR 4T Leaflet © Leonhard-Reglerbau GmbH Stuttgart, (+49) 7 11/7 89 54-0


ESDR 4T - WIRING DIAGRAM L

Possible protected objects: Block Generator


differential protection differential protection

G G
T

Standard
35 36 33 34 31 32

Current IL1 transducer set 2 Standard


The transducer ratio is adjustable

for differential current measurement


Transducer set 2

in the display.

Current IL2 transducer set 2


for differential current measurement

9 10 11 12 13 14 15 16 17 18 19
Blocking
Current IL3 transducer set 2
for differential current measurement
Acknowledgement

Parameterization off

Common

0 V DC
Protected object

24 V DC

Relay 4 8

Relay 3
Readiness for operation
7
25 26 27 28 29 30

Current IL3 transducer set 1


The transducer ratio is adjustable

for differential current measurement


Relay 2
5
Transducer set 1

in the display.

ESDR 4T

Current IL2 transducer set 1


for differential current measurement
3

Relay 1
2

Current IL1 transducer set 1


for differential current measurement
1
L1
L2
L3

Printed 12/2000; subject to technical modifications. 2000-12-01 ESDR 4T Anschlußplan e4tleo-4800-ap.skf

© Leonhard-Reglerbau GmbH Stuttgart, (+49) 7 11/7 89 54-0 ESDR 4T Leaflet - Page 3


OVERVIEW OF FUNCTIONS AND TRIPPING CHARACTERISTIC L
Overview ESDR 4T
Network configuration adjustable
• Transformer ratio of the transformer
• Nominal currents of the high- and low-voltage side of the transformer
selectable
• Vector group of the transformer (according to DIN VDE 0532)
in the display
• Transformer ratio separate for measuring transformer set 1 and set 2
• Secondary nominal current either ../1 A or ../5 A (has to be indicated at the order)
Basic Unit
• Power supply 24 VDC
• Parameterizing via three push-buttons and two-line LC display (5 mm, green illuminated)
• Fulfills ANSI 87G, ANSI 87M and ANSI 87GT Standard
• Range of differential current protection (2step) 5..100 % × IN in 1 % steps
• Range of restraint current protection 50..300 % × IN in 1 % steps
e4t.1401.p/e

Tripping Characteristic

Id
Y= [%]
I N
Ia Protected Ib I a + Ib
object IS = Id = Ia - Ib
Monitoring step 2, fixed limit (100 %) 2
100
X12, Y2 and Y1: adjustable Monitoring step 2
(X12 = 100 % / Y2 = 35 %) Monitoring step 2
fixed limit (85 %)
Monitoring step 1
(X12 = 100 % / Y1 = 10 %) 1= 2 2

Monitoring step 1
Characteristic gradient = 10 % fixed limit
(85 %-Y2+Y1)
1

P (X12/Y2)
P (X12/Y1)

35

IS
10 X= [%]
IN

100 200 300 400 500 2000-12-08


ESDR 4T Auslösekennlinie e4tleo-5000-kenn.skf

Page 4 - ESDR 4T Leaflet © Leonhard-Reglerbau GmbH Stuttgart, (+49) 7 11/7 89 54-0


TECHNICAL DATA AND DIMENSIONS L
Technical Data
Measuring current ...................................... ../1 A or ../5 A Potential free outputs..............contact material: AgCdO
Measuring frequency ........................................40..70 Hz Electrical life cycle (ohmic load) .................................
min. 100.000 cycles at 2 A / 250 VAC
Power supply ...........................................24 VDC (±25 %) Load............................ max. 2 A at 250 VAC or 24 VDC
Power consumption ..........................................max. 6 W Max. switching voltage ...................................250 VAC
Ambient temperature .......................................-20..70 °C Insulation voltage ........................................ 2,200 Veff
Ambient humidity ..............................95 %, not condense Switching capacity DC .......................................45 W
Measuring input current ........... consumption < 0.15 VA Protection functions..... minimum command time 40 ms
Current-carrying capacity ............................... 5.0 × IN
Rated short-time current (1 s)........ 100.0 × IN (for 1 s) Housing ........................... type APRANORM DIN 43 700
30.0 × IN (for 10 s) Dimensions (snap-on rail) ........... 144 × 72 × 199 mm
Accuracy .........................................maximal 1 % × IN Dimensions (front)....................... 144 × 72 × 162 mm
Reference voltage .........................................±0.15 % Front cutout........................................... 138 × 67 mm
Max. temperature deviation .........................12 ppm/K Connection....................... screw terminals depending
on plug connector 2,5 mm² or 4 mm²
Digital inputs ................................metallically separated
Insulation voltage 2,200 Veff Front foil.............................................. insulated surface
Input range ............................... 18..250 V (DC or AC) Protection system ...............................IP 21, front IP 54
Input resistance ................................................ 68 kΩ Weight ....................depending on model, ca. 1,000 g
Disturbance test (CE) ...................... tested according to
applicable EN guidelines

Dimensions

Snapp track mounting

Leonhard - Reglerbau
Stuttgart ESDR 4 differential current
protection
IS L1 L2 L3 [ ]
Ia protected Ib
Id object

Ia + Ib
IS =

72.0
operation and error messages 2
Id = Ia - Ib
Id
IN variable release characteristic
monitoring message display clear
release
10 % ON

16.5
Y error
lock
IS
X IN select digit cursor

45.0
110.0
A Mounting clamp
Section A
37 38 39 40 41 42

24
25 26 27 28 29 30 31 32 33 34 35 36

ø4.0 ø4.0
50

143.0
50.0

144.0

ø4.0 ø4.0

55.8 4.6
46.5
63

65.0 132.0 8.0


A
180.0

Leonhard-Reglerbau GmbH, Handwerkstrasse 29, D-70565 Stuttgart


Phone: (+49) 7 11/7 89 54-0, Telefax: (+49) 7 11/7 89 54-1 00, eMail: sales@leonhard-reglerbau.de e4t.1401.p/e