Installation:
Launch the setup.exe that is located on the root of the DASSIDirect DA Server installation folder. This will be
in the following location if you are installing the software from the Device Integration 2012 R2 DVD:
DVDDrive:\DIFolders\SI\SIDirect\3.0
Once the setup has been launched you should see the screen below. Click the next button to proceed with
the installation.
Next accept the license agreement and then click the Next button.
https://knowledge.insourcess.com/Visualization_and_Supervisory_Control/DA_%2F%2F_OI_Servers/Implement_and_Suppor…
Updated: Thu, 26 Jan 2023 00:52:44 GMT
Powered by
2
The DA Server installation will shut down any DA Servers that are currently running during the installation. The next screen
is an acknowledgment of this fact and a warning that the installation may require a reboot. Press the Next button to proceed.
Choose the location where you would like to install the DA Server and then click the Next button and then Next at the
following screen to proceed. The default location for a 64 bit Operating System will be the location in the screenshot below:
https://knowledge.insourcess.com/Visualization_and_Supervisory_Control/DA_%2F%2F_OI_Servers/Implement_and_Suppor…
Updated: Thu, 26 Jan 2023 00:52:44 GMT
Powered by
3
Click the Finish button to complete the installation of the DA Server.
https://knowledge.insourcess.com/Visualization_and_Supervisory_Control/DA_%2F%2F_OI_Servers/Implement_and_Suppor…
Updated: Thu, 26 Jan 2023 00:52:44 GMT
Powered by
4
Using an existing configuration file
The DA Server configuration (.aacfg) files are stored in the specific location depending on the version of the DA Server that is
installed. The following locations are for the associated Operating Systems below:
New Version
Older Version(s)
C:\Program Files\Wonderware\DAServer\DASSIDirect\Bin
New Version
https://knowledge.insourcess.com/Visualization_and_Supervisory_Control/DA_%2F%2F_OI_Servers/Implement_and_Suppor…
Updated: Thu, 26 Jan 2023 00:52:44 GMT
Powered by
5
C:\ProgramData\Wonderware\DAServer\DASSIDirect
Older Version(s)
C:\Users\All Users\Wonderware\DAServer\DASSIDirect
If you already have an existing system with the same configuration as you wish to use you can simply copy the .aacfg file
from the working machine to the equivalent location on the new machine. If your new configuration is named something other
than DASSIDirect.aacfg you will need to switch to the new configuration by right clicking the configuration under the
DASSIDirect and then choosing “Use Another Configuration Set” and selecting the appropriate configuration file. If the DA
Server is activated it will need to be de-activated before you can switch to another configuration.
https://knowledge.insourcess.com/Visualization_and_Supervisory_Control/DA_%2F%2F_OI_Servers/Implement_and_Suppor…
Updated: Thu, 26 Jan 2023 00:52:44 GMT
Powered by
6
The first step for creating a new configuration will be to right click on the configuration and choose “Add PortCp57 Object.
This tech note does not cover the option for configuring the DASSiDirect for redundant PLC feature. Information for setting
up this feature can be found in Wonderware tech note 854 at the link below:
https://wdnresource.wonderware.com/s.../1/t002649.htm
If you wish to add an S7-300 or S7-400 PLC you will choose the option for “Add S7cp Object” as in the screenshot below:
https://knowledge.insourcess.com/Visualization_and_Supervisory_Control/DA_%2F%2F_OI_Servers/Implement_and_Suppor…
Updated: Thu, 26 Jan 2023 00:52:44 GMT
Powered by
7
For a S7-200 PLC you will create an S7_200 Object instead of the S7cp object.
Below are the most common settings for an S7-300 and S7-400 configuration:
S7-300
Remote TSAP:
Connection Resources: 3
S7-400
Remote TSAP:
https://knowledge.insourcess.com/Visualization_and_Supervisory_Control/DA_%2F%2F_OI_Servers/Implement_and_Suppor…
Updated: Thu, 26 Jan 2023 00:52:44 GMT
Powered by
8
Remote Rack No: 0
Connection Resources: 3
The next step will be to create topics. To do this you will click on the Device Groups tab within the S7cp object. Next right
click and choose Add and create a topic name. If multiple topics are going to be used it is recommended to stagger the Update
intervals using prime numbers.
https://knowledge.insourcess.com/Visualization_and_Supervisory_Control/DA_%2F%2F_OI_Servers/Implement_and_Suppor…
Updated: Thu, 26 Jan 2023 00:52:44 GMT
Powered by
9
Next you will save the configuration by clicking the save icon in the upper right corner and if prompted click
yes to save the changes.
The last step will be to right click on the DASSIDirect DA Server and choose Activate Server.