SINGLE LINE DIAGRAM SOLAR PANEL TECHNICAL DATA

SERVICE ENTRANCE LAYOUT LEGENDS AND SYMBOLS


NOT TO SCALE LONGI 555 W PANEL NOT TO SCALE
DIMENSIONS:2256x1133x35mm (LxWxD)
WEIGHT:27.2 kg
STC VALUES
RATED VOLTAGE=42.10 V
RATED CURRENT=11.35 A
OPEN CIRCUIT VOLTAGE=49.80 V
SHORT CIRCUIT CURRENT=14 A

INVERTER TECHNICAL DATA:


TO LOAD SERVICE ENTRANCE
DEYE SUN-8K-SG05LP1-EU
MAX DC INPUT POWER=10400W Hybrid Inverter, 8kW
START UP VOLTAGE:125 V
PV INPUT CURRENT: 26/26
TO INVERTER
MPPT TRACKERS:4
NO OF STRINGS:2+2
MAX AC OUTPUT POWER:8800W
AC OUTPUT RATED CURRENT:36.4A
USE : (2) 4.0 MAX AC CURRENT:40 A
mm2 PV Wire CURRENT HARMONIC DISTORTION:<3%
Breaker, Rating as indicated
GRID
REC METER BI-DIRECTIONAL
CONNECTION CT
single string 8 pcs solar panels METER BASE
kWhr Meter kWhr Meter
20 A 2 WIRE BY
String 1 M M LOCAL
63 A 250 A POWER SERVICE EQUIPMENT
20 A
USE :8.0 mm2
COMPANY Solar Panels, 400 W
String 4 THWN-2 Cu
100 A SERVICE
ENTRANCE
Wire

5ft
INVERTER'S OUTPUT LOAD COMPUTATION
add kWhr meter symbol
IT = MAXIMUM AC OUTPUT CURRENT x 1.25
IT = 40A x 1.25
IT = 50A

USE:
1 - 63AT, 2P AC MCB
[2 sets of 2 -8.0mm² THWN
BLOCK DIAGRAM
MAIN 1 - 385V AC SPD 40 KAIC
DISTRIBUTION NOT TO SCALE
PANEL
STRING LOAD COMPUTATION
GROUND ROD
IT = STRING SHORT CIRCUIT CURRENT x 1.25 x 1.25 5
IT = 14A x 1.25 x 1.25 8" x 8ft
IT = 21.9A

USE:
2 - 20AT, 2P 550V DC MCB PV MODULE DC MCB ONGRID INVERTER AC MCB
2 - 4mm² PV CABLE IN 42mm Ø PVC PIPE
2 - 600V DC SPD 40 KAIC
DC SPD AC SPD UTILITY GRID

GENERAL NOTES AND SPECIFICATIONS VICINITY MAP SITE PLAN

1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION
OF PHILIPPINE ELECTRICAL CODE.
2. MINIMUM SIZE OF WIRE AND CONDUIT FOR PHOTOVOLTAIC MODULE SHALL BE
4mm² DC CABLE AND 15mm Ø RESPECTIVELY UNLESS OTHERWISE SPECIFIED ON PLAN.
3. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL BE BRAND NEW AND APPROVED TYPE
FOR ALL LOCATION AND PURPOSES.
4. ALL METAL FRAMES SHALL BE PROPERLY AND ADEQUATELY GROUNDED.
5. ALL WEATHER-EXPOSED INSTALLATIONS SHALL USE WEATHERPROOF TYPE MATERIALS,
ESPECIALLY WEATHERPROOF CONDUITS, JUNCTION BOXES AND SAFETY DEVICES.
SITE
6. ALL SPECIAL EQUIPMENT (INVERTERS, PV MODULE AND BATTERY) SHALL BE INSTALLED
IN ACCORDANCE WITH STANDARDS SET BY THE CODE AND MANUFACTURER'S SPECIFICATIONS.
7. BATTERIES AND INVERTERS SHALL BE INSTALLED IN A WELL SECURED AND VENTILATED
LOCATION.
8. ALL INSTALLATION SHALL BE DONE IN GOOD AND NEAT WORKMANSHIP.
9. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF ELECTRICAL
ENGINEER/REGISTERED MASTER ELECTRICIAN OR PROFESSIONAL SOLAR SYSTEM INSTALLER.

APPROVED BY: PRC REG NO. 0059587 CONTRACTOR: PROJECT TITLE: SHEET CONTENT: OWNER: SHEET NO.

PTR NO. 3539617 SINGLE LINE DIAGRAM, SERVICE ENTRANCE JOHN PAUL OBDIN
ENGR. BANJO R. MIRANDILLA LEVANT BAY SOLAR ENTERPRISES 8kW HYBRID SOLAR PV LAYOUT, LEGENDS AND SYMBOLS, BLOCK ADDRESS:
1
DATE ISSUED 01/05/2024
SYSTEM AS BUILT DIAGRAM, GENERAL NOTES AND VILLA PAROMA, CABCABEN, MARIVELES, BATAAN E 1
REGISTERED ELECTRICAL ENGINEER PLACE ISSUED BALANGA CITY ADDRESS: M.CALARA ST., WEST CALAGUIMAN, SAMAL, BATAAN SPECIFICATIONS, VICINITY MAP, SITE PLAN