Engines Support
Reference Guide
4000 series (gas CAT data link IG/IS-NT + I-CB/CAT Using ICBEdit
engines) GAS
CCM
Scania S6 J1939 + KWP2000 IL/IL-NT Scania S6 Singlespeed /
Scania S6 Singlespeed
from ver.1794335
IG/IS-NT Scania S6 Singlespeed /
ID Scania S6 Singlespeed
from ver.1794335 /
Scania S6 Allspeed /
Scania S6 Allspeed from
ver.1794335
Sisu Fortius engines J1939 IL/IL-NT Standard J1939 engine
(EEM2) IG/IS-NT
ID
Citius engines J1939 IL/IL-NT Standard J1939 engine
ESF
Controller
ECU configuration Speed
documentation control
Commands
Fault codes
Values
ESL
Volvo Auxiliary
ESL
Volvo Propulsion
ESL
DriveConfig/GenConfig
ESL
Scania Allspeed ESL
Scania Singlespeed
Note:
InteliLite/InteliLite-NT controllers do not provide configurable inputs/outputs for engine values but the
values are fixed in IL/IL-NT firmware. ESF is here used to convert ECU fault codes to texts displayed on
the controller screen.
InteliDrive – DriveConfig
Note:
Some values like Start request, Stop request have red background which means that these ECU values
must have assigned a source value from the controller e.g. Starter, Stop pulse. This is checked by
DriveConfig Consistency Check function.
InteliGen/InteliSys-NT – GenConfig
Note:
Some values like Start request, Stop request have red background which means that these ECU values
must have assigned a source value from the controller e.g. Starter, Stop pulse. This is checked by
GenConfig Consistency Check function.
In the latest version of GenConfig the configuration of such values is done automatically.
IL-NT
Till SW version 1.2.1 engine speed can be adjusted according to following formula:
RPM = 1200 + 15 * ECU SpeedAdj
ID-Lite
Engine speed can be adjusted according to following formula:
RPM = 1200 + 15 * ECU SpeedAdj
Specific ECU/protocols
Some ECUs do not offer J1939 like communication and so it was necessary to have a solution dedicated to
each of these units.
We recognize two groups:
1. ECU communicating via Modbus using RS232/485 (e.g. some Cummins engines) – with IL and
IG/IS-NT controllers it is possible to connect such an ECU directly (without I-CB)
2. ECU with completely incompatible communication protocol and way of connection (e.g.
MTU/MDEC CAN bus) – these units are supported with the use of an I-CB unit
CAN RS232
I-CB
Note:
For details about I-CB refer to I-CB-ICBEdit-x.y.pdf manual.
Legend:
X - available
- - not available
EMCP2 + CCM
EMCP II CCM
Configuration
For connection to CAT CCM module it is necessary to use an I-CB module. Configuration of the
controller and I-CB has to be done separately using GenConfig/DriveConfig and ICBEdit tools. For
further information see I-CB manual (I-CB-ICBEdit-x.y.pdf).
Available commands
Note 1:
Check that CAN bus terminating resistors or appropriate jumpers are connected.
ADEM + EMCP3.x
ADEM A4 EMCP3.3
Configuration
Available commands
Recommended wiring
70-pin AMP connector Service connector IG/IS-NT/ID-DCU/IL-NT controllers
on EMCP3
CAN1 (Extension modules/J1939)
34 F
connector - CAN L
CAN1 (Extension modules/J1939)
50 G
connector - CAN H
CAN1 (Extension modules/J1939)
42 C
connector - CAN COM
52 - Power +
65 - Power -
Note2:
Pin layout of the diagnostic connector:
ADEM
ADEM A4
Available commands
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Recommended wiring
J1 70-pin connector IG/IS-NT/ID-DCU/IL-NT controllers
CAN1 (Extension modules/J1939) connector -
34
CAN L
CAN1 (Extension modules/J1939) connector -
50
CAN H
CAN1 (Extension modules/J1939) connector -
42
CAN COM
48, 52, 53, 55 Power +
61, 63, 65, 69 Power -
70 Key switch (ECU PwrRelay output)
CM570
Configuration
Available commands
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Recommended wiring
9-pin diagnostic Deutsch connector IG/IS-NT/ID-DCU/IL-NT controllers
CAN1 (Extension modules/J1939)
C CAN H
connector - CAN H
CAN1 (Extension modules/J1939)
D CAN L
connector - CAN L
B Battery + Power +
A Battery - Power -
CM850
Configuration
Available commands
Start command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Note 1:
Should be used with IGS-NT version 2.1.5 or higher.
Connector 06
Configuration
Available commands
Stop command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
22
GND DATA1- 21 D-SUB 06
RS232 RxD 20 connector
TxD 19
DATA1+ 18
10 – 30
+Vs
VDC
GND
22
B
21 D-SUB 06
RS485(1) 20 connector
19
A 18
22
B
21 D-SUB 06
RS485(2) 20 connector
19
A 18
Note 1:
In case that the GCS doesn't communicate try to activate input Diagnostic mode (pin 07 on connector 06).
CM850 / PCC130x
Cummins CM850&PCC13xx option is intended to be used on Cummins gensets in case that PCC13xx
panel is removed and replaced by ComAp controller and CM850 ECM remains on engine.
Configuration
Available commands
Stop command Source = Stop Not supported Not supported Not supported
pulse
ECU value = Stop
Request
Configuration
Available commands
Recommended wiring
No documentation so far available
ADM2
21-pin
connector
Configuration
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Recommended wiring
21-pin connector ID-DCU controllers
21 CAN1 (Extension modules/J1939) connector - CAN L
19 CAN1 (Extension modules/J1939) connector - CAN H
CAN1 (Extension modules/J1939) connector - CAN
20
COM
1 Battery voltage
3 Battery ground
DDEC IV
Available commands
Stop command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Recommended wiring
6-pin communication connector IG/IS-NT/ID-DCU/IL-NT controllers
E CAN1 (Extension modules/J1939) connector - CAN L
F CAN1 (Extension modules/J1939) connector - CAN H
CAN1 (Extension modules/J1939) connector - CAN
D
COM
DDEC V
Available commands
Stop command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Recommended wiring
Vehicle Interface Harness 68-pin IG/IS-NT/ID-DCU/IL-NT controllers
connector
58 CAN1 (Extension modules/J1939) connector - CAN L
43 CAN1 (Extension modules/J1939) connector - CAN H
44 CAN1 (Extension modules/J1939) connector - CAN COM
61, 62, 65, 66 Power +
63, 64, 67, 68 Power -
15 Binary output ECU PwrRelay
(+24 VDC using relay)
EMR2
M connector F connector
Configuration
Available commands
Controller IG/IS-NT ID-DCU IL-NT ID-Lite
Command GenConfig DriveConfig LiteEdit LiteEdit
Speed request Source = Source = Speed Not configurable Not configurable
SpeedReq RPM request Speed request is Speed request is
Convert = No Limits = see Note based on ECU based on ECU
ECU value = 1 SpeedAdj setpoint SpeedAdj setpoint
Requested speed J1939 value =
Requested speed
Start command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Note 2:
Recommended setting of EMR2 using Serdia PC tool:
Page 30: 4400 = 1 … CAN activation
Page 31: 4470 = 1 … Activate CAN set point by TSC1a
Page 31: 4412 = 1 … Activate TSC1a receive telegram
Page 10: 4900 = 8 … Selection of input channel type for nominal speed value sensor
Recommended wiring
F connector IG/IS-NT/ID-DCU/IL-NT controllers
13 CAN1 (Extension modules/J1939) connector - CAN L
12 CAN1 (Extension modules/J1939) connector - CAN H
14 Power +
1 Power -
Configuration
Available commands
Stop command Source = Stop Source = Stop Not supported Not supported
pulse pulse
ECU value = J1939 value =
Stop Request Stop Request
Torque map selection Source = see Source = see Not supported Not supported
(selects one of user Note 2 Note 2
predefined torque maps - ECU value = ECU value =
depends on ECU Torque Map Torque Map
configuration, see Note 3) Convert = No Lo limit = 0
Normalize = No Hi limit = 10000
Resolution = 1
Droop selection Source = see Source = see Not supported Not supported
(selects one of user Note 2 Note 2
predefined droop values - ECU value = ECU value =
depends on ECU Engine speed Engine speed
configuration, see Note 4) droop droop
Convert = No Lo limit = 0
Normalize = No Hi limit = 10000
Resolution = 1
Droop selection (high Source = see Source = see Not supported Not supported
idle governor) Note 2 Note 2
(selects one of user ECU value = ECU value =
predefined droop values - High idle droop High idle droop
depends on ECU Convert = No Lo limit = 0
configuration, see Note 5) Normalize = No Hi limit = 10000
Resolution = 1
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Note 2:
The analog source value can be adjusted in PLC setpoint (a PLC function with analog output has to be
configured first) or in ExtValueX setpoint (ExtValueXreset binary input has to be configured to logical 1 (on
LBI card select Logical 1 as a source for ExtValueXreset) to ensure continuous refreshing of the value).
ExtValue is not supported in ID-DCU.
Note 3:
0= no modification of torque map
1= switch to torque map 1
2= switch to torque map 2
Note 4:
0 = no modification of droop
1 = selects engine speed depended droop 1
2 = selects engine speed depended droop 2
3= selects engine speed depended droop 3
Note 5:
0 = no modification of droop
1 = High idle droop 1
2 = High idle droop 2
TEM Evolution
Configuration
For connection to TEM Evolution panel it is necessary to use an I-CB module. Configuration of the
controller and I-CB has to be done separately using GenConfig/DriveConfig and ICBEdit tools. For
further information see I-CB manual (I-CB-ICBEdit-x.y.pdf).
Recommended wiring
MEFI4B, MEFI5B
MEFI4
Configuration
Available commands
Stop command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
Comap Electronic Engines Support 36
©ComAp – June 2008, Comap Electronic Engines Support 06-2008.pdf
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Recommended wiring
Connector / Pin IG/IS-NT/ID-DCU/IL-NT controllers
J2 / 9 CAN1 (Extension modules/J1939) connector - CAN L
J2 / 24 CAN1 (Extension modules/J1939) connector - CAN H
J2 / 1 Power +
J1 / 13, 28, 29 Power -
SECM
Configuration
Available commands
Stop command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Recommended wiring
Not available yet
EDC
Electrical connection on NEF engine
1 - Engine wiring
2 - Indicator and control panel
3 - Provided wire harness
4 - JB connection
5 - Relay box
6 - JA connection
7 - Power supply and interface wire harness
8 - JF1 and JF2 connectors
9 - A2 connector of the ECU
10 - A and A1 connectors of the ECU
11 - M connector
Available commands
Stop command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Configuration
Available commands
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Note 2:
Even if Cold Start Request signal is not used, configure it to Logical 0. Otherwise the engine will not start.
Recommended wiring
Interface card IG/IS-NT/ID-DCU/IL-NT controllers
Plug J2: 1, 2 CAN1 bus
Plug J7: 18, 19 ECU PwrRelay binary output
(Key switch) see Note 3
116 Power +
117 Power -
Note 3:
Emergency stop must open this contact.
After voltage on you have to wait 10 seconds before start - if ECU PwrRelay output is used to close this
contact Prestart time has to be set to at least 10 seconds.
Delphi DCM
Configuration
Available commands
Stop command Not supported N/A in ECU Not supported Not supported
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Recommended wiring
62-pin Machine Connector X2 ID-DCU controllers
23 CAN1 (Extension modules/J1939) connector - CAN L
27 CAN1 (Extension modules/J1939) connector - CAN H
CAN1 (Extension modules/J1939) connector - CAN
19
COM
57, 60, 53, 49 Positive power supply
58, 59, 61, 62 Battery ground
ECU type
DIA.NE
DIA.NE
Configuration
Available commands
Start command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Recommended wiring
Hardwareinterface for MODBUS:
Bus terminal RS485 in the GE Jenbacher control cubicle.
Note:
For IS-NT an external RS232/RS485 converter has to be used while the internal RS485 converter is
dedicated to IS-Display. See InteliCommunicationGuide, chapter Converters for the recommended
RS232/RS485 converters.
ECU Types
JDEC
Configuration
Start command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Stop command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Recommended wiring
JDEC (21-pin Diagnostic IG/IS-NT/ID-DCU/IL-NT controllers
connector) gauge
CAN1 (Extension modules/J1939)
U B CAN Low
connector - CAN L
CAN1 (Extension modules/J1939)
V G CAN High
connector - CAN H
CAN1 (Extension modules/J1939)
F F CAN Shield
connector - CAN COM
B E Battery + Power +
E D Battery - Power -
Ignition Binary output ECU PwrRelay
G -
switch
Note 2:
Pin layout of diagnostic gauge:
ECU Types
Configuration
Available commands
ZDR Parameters If analog output is If analog output is Not supported Not supported
not configured, 0 not configured, 0
value is sent on value is sent on
CAN bus. CAN bus.
Source = Possible in
ExtValue1(..4) DriveConfig from
Convert = No version 2.4:
ECU value = ZDR Source = See note
Parametersatz 3
Normalize = No Convert = No
Resolution = 1 J1939 value = ZDR
See note 2 Parametersatz
P-Grad If analog output is If analog output is No configuration No configuration
Drehzahlregler not configured, 0 not configured, 0 Always sends 0 Always sends 0
value is sent on value is sent on
CAN bus. CAN bus.
Source = Possible in
ExtValue1(..4) DriveConfig from
Convert = Yes version 2.4:
ECU value = P- Source = See note
Grad 3
Normalize = No Convert = Yes
Resolution = 1 J1939 value = P-
See notes 2 and 4 Grad
See note 5
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Note2:
Besides configuring the analog output it is necessary to activate binary input function ExtValue1(..4)reset.
Therefore go to LBI card in GenConfig, in the list look for ExtValue1(..4)reset and select "Logical 1" from
"Log Bout" as Source. This ensures that value from setpoint ExtValue1(..4)deflt in Force value group is
periodically sent on the CAN bus as ZDR Parameters / P-Grad Drehzahlregler value.
Note3:
As a source for ZDR Parameters / P-Grad Drehzahlregler an output of PLC function can be used. For
example use mathematic function and assign a PLC setpoint as one of the inputs (Resolution = 1 / 0,01,
Dim = -). The second input set to 0.
Use PLC function output (here PLC Aout 1) as a Source for ZDR Parameters / P-Grad Drehzahlregler.
To change ZDR Parameters / P-Grad Drehzahlregler then go to PLC setpoints and change respective
setpoint in the range 0 - 7 / 7,5.
Note4:
Recommended configuration of analog output in GenConfig is shown below.
Note5:
Recommended configuration of analog output in DriveConfig is shown below.
Recommended wiring
Customer connector Diagnostic IG/IS-NT/ID-DCU/IL-NT controllers
X2 connector
CAN1 (Extension modules/J1939)
29 10 CAN Low
connector - CAN L
CAN1 (Extension modules/J1939)
28 9 CAN High
connector - CAN H
33 Battery + Power +
32 Battery - Power -
Note6:
Pins 26 and 27 should be linked to connect 120Ohm resistor.
Diagnostics
Example 1: Oil pressure alarm from ECD Master is active (inverse background color).
E C U A l a r m L i s t
> * O i l P r e s s u r e W r n
S P N 1 0 0 O C 0 F M 0
S P N 1 0 0 O C 1 F M 0
S P N 1 1 3 1 O C 3 9 F M 1
MDEC
CAN bus
connection
For connection to MTU MDEC system it is necessary to use an I-CB module. Configuration of the
controller and I-CB has to be done separately using GenConfig/DriveConfig and ICBEdit tools. For
further information see I-CB manual (I-CB-ICBEdit-x.y.pdf).
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Recommended wiring
Note1:
For communication with the ComAp controller the CCB2 card has to be present and J1939 has to be
configured using the minidialog.
Note2:
No fault codes in DM1 frame are provided by MTU ADEC system. Diagnostic codes are only available as
analog input "Failure Codes".
Configuration
Available commands
Speed demand If not configured 0 If not configured 0 Not supported Not supported
switches is sent on CAN bus is sent on CAN bus
Source = Source = See note
ExtValue1(..4) 3
Convert = No Convert = No
ECU value = (available in DC
Speed demand since version 2.4)
switches J1939 value =
Normalize = No Speed demand
Resolution = 1 switches
See note 2
Start command Source = Starter Source = Starter Not configurable Not configurable
ECU value = J1939 value = Active according to Active according to
Engine Start Engine Start Starter output Starter output
Stop command Source = Stop Source = Stop Not configurable Not configurable
pulse pulse Active according to Active according to
ECU value = J1939 value = Stop pulse output Stop pulse output
Engine Stop Engine Stop
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Note2:
Besides configuring the analog output it is necessary to activate binary input function ExtValue1(..4)reset.
Therefore go to LBI card in GenConfig, in the list look for ExtValue1(..4)reset and select "Logical 1" from
"Log Bout" as Source. This ensures that value from setpoint ExtValue1(..4)deflt in Force value group is
periodically sent on the CAN bus as Speed demand switches.
Note3:
As a source for Speed demand switches an output of PLC function can be used. For example use
mathematic function and assign a PLC setpoint as one of the inputs (Resolution = 0, Dim = -). The second
input set to 0.
Use PLC function output (here PLC Aout 1) as a Source for Speed demand switches.
To change Speed demand switches value then go to PLC setpoints and change respective setpoint in the
range 0 - 7.
X3 connector
3, 6, 9, 12 +24 V DC (25Amps fuse)
13 +24 V DC (6Amps fuse)
1, 4, 7, 10 GND
ECM
Available commands
Stop command Source = Stop Source = Stop Not supported Not supported
pulse pulse
ECU value = Stop J1939 value = Stop
Request Request
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Recommended wiring
J1 21-pin connector IG/IS-NT/ID-DCU/IL-NT controllers
CAN1 (Extension modules/J1939)
21 CAN Low
connector - CAN L
CAN1 (Extension modules/J1939)
20 CAN High
connector - CAN H
CAN1 (Extension modules/J1939)
22 CAN Shield
connector - CAN COM
7, 8, 15, 16 Battery + Power +
1, 2, 3, 9, 10 Battery - Power -
Configuration
Available commands
Start command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Stop command Source = Stop Source = Stop Not supported Not supported
pulse pulse
ECU value = J1939 value =
Stop Request Stop Request
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Note 2:
To enable speed control over CAN bus set Desired Speed Input Arrangement to "CAN Input" in Perkins
EST program.
Recommended wiring
J1 connector IG/IS-NT/ID-DCU/IL-NT controllers
CAN1 (Extension modules/J1939)
34 CAN Low
connector - CAN L
CAN1 (Extension modules/J1939)
50 CAN High
connector - CAN H
CAN1 (Extension modules/J1939)
42 CAN Shield
connector - CAN COM
48, 52, 53, 70 Battery + Power +
61, 63, 65 Battery - Power -
ECU Types
S6
B1 connector
Configuration
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Note 2:
For all engines Droop enable is applicable and enables droop value stored in the ECU.
For singlespeed engines from ver.1794335 it is possible to adjust droop in two other ways (not combined):
Comap Electronic Engines Support 63
©ComAp – June 2008, Comap Electronic Engines Support 06-2008.pdf
1. Via binary inputs - activate Droop Adjust Enable, then activate and deactivate Droop Adjust Increase
or Decrease to increase/decrease droop value by 0.1%, deactivate Droop Adjust
Enable to store the final value
2. Via analog value - change Requested Droop value (see Note 3)
To check actual droop value configure Single Speed Droop Value.
Note 3:
The analog source value can be adjusted in PLC setpoint (a PLC function with analog output has to be
configured first) or in ExtValueX setpoint (ExtValueXreset binary input has to be configured to logical 1 (on
LBI card select Logical 1 as a source for ExtValueXreset) to ensure continuous refreshing of the value).
ExtValue is not supported in ID-DCU.
Recommended wiring
ECU Types
EEM2
Configuration
Stop command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Recommended wiring
31-pin vehicle
connector
Configuration
Available commands
Note2:
Besides configuring the analog output it is necessary to activate binary input function ExtValue1(..4)reset.
Therefore go to LBI card in GenConfig, in the list look for ExtValue1(..4)reset and select "Logical 1" from
"Log Bout" as Source. This ensures that value from setpoint ExtValue1(..4)deflt in Force value group is
periodically sent on the CAN bus as Droop percentage request.
Note3:
As a source for Droop percentage request an output of PLC function can be used. For example use
mathematic function and assign a PLC setpoint as one of the inputs (Resolution = 0, Dim = %). The second
input set to 0.
Use PLC function output (here PLC Aout 1) as a Source for Droop request.
To change Droop request then go to PLC setpoints and change respective setpoint in the range 0 - 10%.
Recommended wiring
EDC
Configuration
Available commands
Stop command Source = Stop Source = Stop Not supported Not supported
pulse pulse
ECU value = J1939 value =
Stop Request Stop Request
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
ECU Types
EDC3 (EMS1)
Configuration
Available commands
Recommended wiring
Controller EDCIII
Extension CAN H
Deutsch
modules 8-pin
CAN L
(CAN1) connector
- 1 8
Power
+ 27
K2 +24 VDC
36
Binary
outputs 45
K1
K1
ECU PwrRelay
ECU CommOK/ K2
Vlv CommOK
Note 1:
If controller with CANNON9 connector is used, connect CAN H to pin #5 and CAN L to pin #9.
Note 2:
If binary output ECU PwrRelay is not available in the controller, connect pin #5 on Deutsch connector to
battery positive. This signal activates ECU power supply so it can be used with key switch to power up the
ECU only in case when the engine should run.
Note 3:
Vlv CommOK output is closed when the communication is OK and causes engine stop when ECU
communication error occurs. In IGS-NT use inverted ECU comm error output.
Configuration
Available commands
Extension CAN H
Deutsch
modules 8-pin
CAN L
(CAN1) connector
- 1 8
Power
+ 27
K2 +24 VDC
36
Binary
outputs 45
K1
K1
ECU PwrRelay
ECU CommError/ K2
Vlv CommError
Note 1:
If controller with CANNON9 connector is used, connect CAN H to pin #5 and CAN L to pin #9.
Note 2:
If binary output ECU PwrRelay is not available in the controller, connect pin #5 on Deutsch connector to
battery positive. This signal activates ECU power supply so it can be used with key switch to power up the
ECU only in case when the engine should run.
Note 3:
If the engine doesn't crank, check the state of engine mounted auxiliary stop device.
control side
connector
Configuration
Available commands
Start command N/A in ECU N/A in ECU N/A in ECU N/A in ECU
Note 1:
Lo and Hi limits entered in DriveConfig have to be computed according following formula:
Lo limit = -100*[RPM-lo / (RPM-hi – RPM-lo)]
Hi limit = 100*[(5000 – RPM-lo) / (RPM-hi – RPM-lo)]
where RPM-lo and RPM-hi are the desired limits for the output value to ECU.
Note 2:
If ECU is powered up before the controller and doesn't receive speed request over the CAN bus, it
switches to analog input and never listens to CAN bus again. It is recommended to use ECU PwrRelay
output to switch on and off the ECU.
ESM
Configuration
Available commands
Note:
See InteliCommunicationGuide, chapter Converters for the recommended RS232/RS485 converters.
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 234 any 20
HR 0xFEE5 6 234 any 1000
ET1 0xFEEE 6 234 any 1000
EFLP1 0xFEEF 6 234 any 500
LFE 0xFEF2 3 0 any 100
IC 0xFEF6 3 0 any 500
VEP 0xFEF7 6 234 any 1000
DM1m 0xECFF 6 234 any 1000
DM1 0xFECA 6 234 any 1000
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
DM1cl 0xFECC 6 17 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
AAI 0xFE8C 7 0 any 1000
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x03 0 20
DM1cl 0xFECC 6 17 0 -
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DD 0xFEFC 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
DM1cl 0xFECC 6 17 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
EEC3 0xFEDF 6 0 any 250
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
PTI 0xFEF0 6 0 any 100
LFE 0xFEF2 6 0 any 100
AC 0xFEF5 6 0 any 1000
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
WF 0xFEFF 6 0 any 10000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM2 0xFECB 6 0 any 1000
DM3 0xFECC 6 0 any 1000
DM4 0xFECD 6 0 any 1000
DM5 0xFECE 6 0 any 1000
IDLE 0xFEDC 6 0 any 1000
CID 0xFEEB 6 0 any 1000
VID 0xFEEC 6 0 any 1000
Comap Electronic Engines Support 86
©ComAp – June 2008, Comap Electronic Engines Support 06-2008.pdf
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
DM1cl 0xFECC 6 17 0 -
TSC1 0x0000 3 0x03 0 20
Written to ECU
Value name Short name Dimension Type Frame name
Speed Bias Reference SpeedBias % ANA EG
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
EEC3 0xFEDF 6 0 any 250
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
PTI 0xFEF0 6 0 any 100
LFE 0xFEF2 6 0 any 100
AC 0xFEF5 6 0 any 1000
IC 0xFEF6 6 0 any 500
WF 0xFEFF 6 0 any 10000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
EG 0xFF69 0 0x03 0 20
DM1cl 0xFECC 6 17 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Stop Request Stop Request - BIN EBC1
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
SHDWN 0xFEE4 6 0 any 1000
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
AC 0xFEF5 6 0 any 1000
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
WF 0xFEFF 6 0 any 10000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0xDC 0 20
EBC1 0xF001 6 0xDC 0 100
Written to ECU
Value name Short name Dimension Type Frame name
Shutdown Override Sd Override - BIN 00001
Fault Acknowledge Fault Ack - BIN 00002
Received frames
Frame Name PGN Priority Source Destination Period [ms]
10005 10005 3 0 1 500
10006 10006 3 0 1 500
30001 30001 3 0 1 500
30002 30002 3 0 1 500
30003 30003 3 0 1 500
30008 30008 3 0 1 10000
30018 30018 3 0 1 2000
30033 30033 3 0 1 2000
30049 30049 3 0 1 2000
30530 30530 3 0 1 2000
30531 30531 3 0 1 2000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
00001 00001 2 0 1 500
00002 00002 2 0 1 500
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Inhibit fuel injection InhibFuelInjec - BIN ESS
Engine start Engine Start - BIN ESS
Inhibit engine start InhibEngStart - BIN ESS
TorqueConvLockupEngaged TorqConvEngage - BIN ETC1
Output shaft speed OutShaftSpd RPM ANA ETC1
Engine overspeed enable EngOverspdEnab - BIN ETC1
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x03 0 20
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Received frames
Frame Name PGN Priority Source Destination Period [ms]
ERC1 0xF000 6 0 any 100
ETC1 0xF002 3 0 any 10
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
FANDRV 0xFEBD 6 0 any 1000
EEC4 0xFEBE 6 0 any 1000
HIGHVD 0xFEC1 6 0 any 1000
SWID 0xFEDA 6 0 any 1000
EFLP2 0xFEDB 6 0 any 500
EEC3 0xFEDF 6 0 any 250
RETCONF 0xFEE1 6 0 any 1000
ENGCONF 0xFEE3 6 0 any 1000
HR 0xFEE5 6 0 any 1000
CID 0xFEEB 6 0 any 1000
Comap Electronic Engines Support 96
©ComAp – June 2008, Comap Electronic Engines Support 06-2008.pdf
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
PTI 0xFEF0 6 0 any 100
CC 0xFEF1 6 0 any 100
LFE 0xFEF2 6 0 any 100
AC 0xFEF5 6 0 any 1000
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
AF 0xFEFD 6 0 any 500
AUXPUMP 0xFEFE 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
IDLE 0xFEDC 6 0 any 1000
TCH 0xFEDD 6 0 any 1000
VD 0xFEDF 6 0 any 1000
IDLESD 0xFEE4 6 0 any 1000
TIME 0xFEE6 6 0 any 1000
VHOURS 0xFEE7 6 0 any 1000
FCONS 0xFEE9 6 0 any 1000
CC1 0xFEED 6 0 any 1000
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x03 0 20
DM1cl 0xFECC 6 17 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Lock status Lock status - BIN pEP
Stop Request Stop Request - BIN pSTP
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
DM2 0xFECB 6 0 any 500
DM4 0xFECD 6 0 any 500
DM5 0xFECE 6 0 any 500
CFG 0xFEE3 6 0 any 500
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
CC 0xFEF1 6 0 any 500
LFE 0xFEF2 6 0 any 100
AC 0xFEF5 6 0 any 500
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
pM1 0xFF04 6 0 any 500
pIN1 0xFF0A 6 0 any 500
Comap Electronic Engines Support 98
©ComAp – June 2008, Comap Electronic Engines Support 06-2008.pdf
pOUT1 0xFF0B 6 0 any 500
pCFG 0xFF0C 6 0 any 500
pCFGA1 0xFF0D 6 0 any 500
pCFGA2 0xFF0E 6 0 any 500
pCFGPWI 0xFF0F 6 0 any 500
pCFGPWO 0xFF10 6 0 any 500
pCFGDO 0xFF11 6 0 any 500
pM2 0xFF12 6 0 any 500
pM3 0xFF13 6 0 any 500
pM4 0xFF14 6 0 any 500
pLIM 0xFF15 6 0 any 500
pIN2 0xFF17 6 0 any 500
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 3 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x03 0 20
pEP 0xFF03 3 0x03 0 100
pSTP 0xFF16 2 0x03 0 100
DM1cl 0xFECC 6 3 0 -
DM11cl 0xFED3 6 3 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Lock status Lock status - BIN pEP
Stop Request Stop Request - BIN pSTP
Start Lock Start Lock - BIN pSTP
Torque Map Torque Map - ANA pFMC
Engine speed droop Droop - ANA pFMC
High Idle Droop HighIdleDrp - ANA pFMC
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
SID 0xFEDA 6 0 any 1000
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 3 0 1000
DM11cl 0xFED3 6 3 0 1000
Comap Electronic Engines Support 100
©ComAp – June 2008, Comap Electronic Engines Support 06-2008.pdf
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x03 0 20
pFMC 0xFF02 6 0x03 0 500
pEP 0xFF03 3 0x03 0 100
pSTP 0xFF16 2 0x03 0 100
DM1cl 0xFECC 6 3 0 -
DM11cl 0xFED3 6 3 0 -
SIDtx 0xFEDA 6 0x03 0 -
HRtx 0xFEE5 6 0x03 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA CMD
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DD 0xFEFC 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1pr 0xFFCA 6 0 any 1000
DM1cl 0xFECC 6 3 0 1000
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
EGFR 0xF00A 3 0 any 50
SHDWN 0xFEE4 6 0 any 1000
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
AC 0xFEF5 6 0 any 1000
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM11cl 0xFED3 6 1 0 1000
Received frames
Frame Name PGN Priority Source Destination Period [ms]
ERC1 0xF000 6 0 any 100
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
EEC3 0xFEDF 6 0 any 250
SHDWN 0xFEE4 6 0 any 1000
HR 0xFEE5 6 0 any 1000
FCONS 0xFEE9 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
CC 0xFEF1 6 0 any 100
LFE 0xFEF2 6 0 any 100
AC 0xFEF5 6 0 any 1000
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
EDC2BC 0xFF21 6 0 any 50
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 0 0 1000
DM11cl 0xFED3 6 0 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x03 0 20
DM1cl 0xFECC 6 0 0 -
DM11cl 0xFED3 6 0 0 -
HRtx 0xFEE5 6 0x27 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Stop Request StopRequest - BIN CTRL
Cold Start Request ColdStartReq - BIN CTRL
Start Request StartRequest - BIN CTRL
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
STS1 0xFF01 3 0 any 30
STS2 0xFF02 6 0 any 60
STS 0xFF03 6 0 any 90
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x03 0 20
CTRL 0xFF00 3 0x27 0 50
DM1cl 0xFECC 6 17 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Fuel Level Fuel Level % ANA DD
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
ET2 0xFEA4 6 0 any 1000
FD 0xFEBD 6 0 any 1000
SHDWN 0xFEE4 6 0 any 1000
Comap Electronic Engines Support 110
©ComAp – June 2008, Comap Electronic Engines Support 06-2008.pdf
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
WFI 0xFEFF 6 0 any 10000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 3 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 3 0 20
DD 0xFEFC 6 3 0 1000
DM1cl 0xFECC 6 3 0 -
HRtx 0xFEE5 6 3 0 -
Received frames
Frame Name PGN Priority Source Destination Period [ms]
40015 40015 3 0 1 500
40016 40016 3 0 1 500
40066 40066 3 0 1 500
40067 40067 3 0 1 500
40068 40068 3 0 1 500
40069 40069 3 0 1 500
40070 40070 3 0 1 500
40071 40071 3 0 1 500
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
EEC3 0xFEDF 6 0 any 250
SHDWN 0xFEE4 6 0 any 1000
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
CC 0xFEF1 6 0 any 100
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x03 0 20
DM1cl 0xFECC 6 17 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA KSM
P-Grad P-Grad mgh ANA KSM
ZDR Parametersatz ZDR - ANA KSM
Start Request Start Request - BIN KSM
Stop Request Stop Request - BIN KSM
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
TCI4 0xFE98 6 0 any 1000
TCI4b 0xFE98 6 1 any 1000
HR 0xFEE5 6 39 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
EFLP1b 0xFEEF 6 1 any 500
LFE 0xFEF2 6 39 any 100
AC 0xFEF5 6 0 any 1000
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1mb 0xECFF 6 1 any 1000
DM1_MFR 0xFECA 6 39 any 1000
MES1 0xFF80 6 0 any 500
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
KSM 0xEF27 3 0xFD 0 50
Written to ECU
Value name Short name Dimension Type Frame name
Disable Cylinder Cut Out 2 DisCylCut2 - BIN BOUT_1_tx
Request Test Overspeed Request Test Overspeed - BIN BOUT_1_tx
Alarm Reset AlarmReset - BIN BOUT_1_tx
Speed Setting Limit Active SpeedLimAct - BIN BOUT_1_tx
Mode Switch ModeSwitch - BIN BOUT_1_tx
Governor ParameterSet Select. GovParamSel - BIN BOUT_1_tx
Intermittent Oil Priming IntOilPrim - BIN BOUT_1_tx
Engine Start EngineStart - BIN BOUT_1_tx
50/60Hz 50/60Hz - BIN BOUT_1_tx
Speed Demand Analog SpeedDemand RPM ANA TSC1
Override Override - BIN CC
Engine Stop Engine Stop - BIN EBC1
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC1 0xF004 3 128 1 20
TCI6 0xFDD3 6 128 1 1000
ET 0xFE07 6 128 1 500
AAI 0xFE8C 7 128 1 1000
FL 0xFE91 7 128 1 1000
ET2 0xFEA4 6 128 1 1000
AT 0xFEA7 7 128 1 1000
EEC4 0xFEBE 7 128 1 1000
CFG 0xFEE3 6 128 1 500
SHDWN 0xFEE4 6 128 1 1000
HR 0xFEE5 6 128 1 1000
ET1 0xFEEE 6 128 1 1000
EFLP1 0xFEEF 6 128 1 500
AMB 0xFEF5 6 128 1 1000
IC 0xFEF6 3 128 1 500
VEP 0xFEF7 6 128 1 1000
BI_1 0xFF00 6 128 1 1000
BI_2 0xFF01 6 128 1 1000
AFC 0xFF04 6 128 1 1000
BI_3 0xFF10 6 128 1 1000
BI_4 0xFF11 6 128 1 1000
SPD_1 0xFF1E 6 128 1 1000
SPD_2 0xFF24 6 128 1 1000
INF_1 0xFF25 6 128 1 1000
INF_2 0xFF26 6 128 1 1000
INF_3 0xFF28 6 128 1 1000
AI_6 0xFF29 6 128 1 1000
LD_tx 0xFF2E 3 1 128 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0080 3 1 128 20
EBC1 0xF001 6 1 128 100
CC 0xFEF1 6 1 128 100
BOUT_1_tx 0xFF2D 3 1 128 100
SW_tx 0xFF2F 3 1 128 1000
AAItr 0xFE8C 7 1 128 -
EEC4tr 0xFEBE 7 1 128 -
HRtx 0xFEE5 6 1 128 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Stop Request Stop Request - BIN EBC1
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
EEC4 0xFEBE 7 0 any 1000
EEC3 0xFEDF 6 0 any 250
SHDWN 0xFEE4 6 0 any 1000
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
AC 0xFEF5 6 0 any 500
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 17 0 1000
Comap Electronic Engines Support 121
©ComAp – June 2008, Comap Electronic Engines Support 06-2008.pdf
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x03 0 20
EBC1 0xF001 6 0x03 0 100
EEC4tr 0xFEBE 7 17 0 -
DM1cl 0xFECC 6 17 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Accelerator Pedal Position APP % ANA DLN1
AP Low Idle Switch AP Low - BIN DLN1
AP kickdown switch AP kickdown - BIN DLN1
Engine Start Engine Start - BIN DLN1
Emergency Engine Stop Emergency Stop - BIN DLN1
Engine Stop Engine Stop - BIN DLN1
Engine Control Allowed Engine Allowed - BIN DLN1
Retarder Speed Control Off RetarderSpOff - BIN DLN1
Retarder Speed Control Set RetarderSpSet - BIN DLN1
CC-Off CC-Off - BIN DLN1
Increased Speed Sw1 INCSP SW1 - BIN DLN1
Increased Speed Sw2 INCSP SW2 - BIN DLN1
Torque Limit 1 Torque 1 - BIN DLN1
Torque Limit 2 Torque 2 - BIN DLN1
Exhaust brake floor switch ExhBreak Floor - BIN DLN1
Exhaust brake – Brake Assist Switch ExhBreak Assist - BIN DLN1
White smoke limit request WSmoke limit - BIN DLN1
Parking Brake Switch ParkingBrakeSw - BIN CC
Cruise Control Enable Switch CC Enable - BIN CC
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
EEC3 0xFEDF 6 0 any 250
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
DLN2 0xFF81 3 0 any 20
DTCrq 0xDA11 6 0x27 0 500
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TCO1 0xFE6C 3 0xEE 0 20
CC 0xFEF1 6 0x27 0 100
DLN1 0xFF80 3 0x27 0 20
DTCrq 0xDA11 6 0x27 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Accelerator Pedal Position APP % ANA DLN1
AP Low Idle Switch AP Low - BIN DLN1
AP kickdown switch AP kickdown - BIN DLN1
Engine Start Engine Start - BIN DLN1
Emergency Engine Stop Emergency Stop - BIN DLN1
Engine Stop Engine Stop - BIN DLN1
Engine Control Allowed Engine Allowed - BIN DLN1
Retarder Speed Control Off RetarderSpOff - BIN DLN1
Retarder Speed Control Set RetarderSpSet - BIN DLN1
CC-Off CC-Off - BIN DLN1
Increased Speed Sw1 INCSP SW1 - BIN DLN1
Increased Speed Sw2 INCSP SW2 - BIN DLN1
Torque Limit 1 Torque 1 - BIN DLN1
Torque Limit 2 Torque 2 - BIN DLN1
Exhaust brake floor switch ExhBreak Floor - BIN DLN1
Exhaust brake – Brake Assist Switch ExhBreak Assist - BIN DLN1
White smoke limit request WSmoke limit - BIN DLN1
Parking Brake Switch ParkingBrakeSw - BIN CC
Cruise Control Enable Switch CC Enable - BIN CC
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
EEC3 0xFEDF 6 0 any 250
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
DLN2 0xFF81 3 0 any 20
DTCrq 0xDA11 6 0x27 0 500
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TCO1 0xFE6C 3 0xEE 0 20
CC 0xFEF1 6 0x27 0 100
DLN1 0xFF80 3 0x27 0 20
DTCrq 0xDA11 6 0x27 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Nominal speed offset Speed offset % ANA DLN1
Droop enable Droop enable - BIN DLN1
Torque enable Torque enable - BIN DLN1
Engine Start Engine Start - BIN DLN1
Emergency Engine Stop Emergency Stop - BIN DLN1
Engine Stop Engine Stop - BIN DLN1
Nominal Speed 1 NSSW1 - BIN DLN1
Nominal Speed 2 NSSW2 - BIN DLN1
Torque Limit 1 Torque 1 - BIN DLN1
Torque Limit 2 Torque 2 - BIN DLN1
Exhaust brake floor switch ExhBreak Floor - BIN DLN1
Exhaust brake – Brake Assist Switch ExhBreak Assist - BIN DLN1
White smoke limit request WSmoke limit - BIN DLN1
Parking Brake Switch ParkingBrakeSw - BIN CC
Cruise Control Enable Switch CC Enable - BIN CC
Brake Switch Brake Switch - BIN CC
Clutch Switch Clutch Switch - BIN CC
Cruise Control Coast Switch CC Coast - BIN CC
Cruise Control Resume Switch CC Resume - BIN CC
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
EEC3 0xFEDF 6 0 any 250
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
DLN2 0xFF81 3 0 any 20
DTCrq 0xDA11 6 0x27 0 500
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TCO1 0xFE6C 3 0xEE 0 20
CC 0xFEF1 6 0x27 0 100
DLN1 0xFF80 3 0x27 0 20
DTCrq 0xDA11 6 0x27 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Nominal speed offset Speed offset % ANA DLN1
Droop enable Droop enable - BIN DLN1
Torque enable Torque enable - BIN DLN1
Engine Start Engine Start - BIN DLN1
Emergency Engine Stop Emergency Stop - BIN DLN1
Engine Stop Engine Stop - BIN DLN1
Nominal Speed 1 NSSW1 - BIN DLN1
Nominal Speed 2 NSSW2 - BIN DLN1
Torque Limit 1 Torque 1 - BIN DLN1
Torque Limit 2 Torque 2 - BIN DLN1
Exhaust brake floor switch ExhBreak Floor - BIN DLN1
Exhaust brake – Brake Assist Switch ExhBreak Assist - BIN DLN1
White smoke limit request WSmoke limit - BIN DLN1
TSC1 Droop Enable Droop enable 2 - BIN TSC1prop
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
EEC3 0xFEDF 6 0 any 250
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DLN2 0xFF81 3 0 any 20
DTCrq 0xDA11 6 0x27 0 500
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TCO1 0xFE6C 3 0xEE 0 20
CC 0xFEF1 6 0x27 0 100
DLN1 0xFF80 3 0x27 0 20
TSC1prop 0xFFF7 3 0x27 0 50
DTCrq 0xDA11 6 0x27 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Start Request Start Request - BIN GPM24
Stop Request Stop Request - BIN GPM24
Droop percentage request Droop % ANA OHECS
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x03 0 20
OHECS 0xFDCB 3 17 0 500
GPM24 0xFE62 3 0x03 0 100
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Start Request Start Request - BIN GPM24
Stop Request Stop Request - BIN GPM24
Droop percentage request Droop % ANA OHECS
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x03 0 20
OHECS 0xFDCB 3 17 0 500
GPM24 0xFE62 3 0x03 0 100
DM1cl 0xFECC 6 17 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DD 0xFEFC 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 17 0 1000
Comap Electronic Engines Support 136
©ComAp – June 2008, Comap Electronic Engines Support 06-2008.pdf
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x03 0 20
DM1cl 0xFECC 6 17 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Stop Request Stop Request - BIN EBC1
Parking Brake Switch ParkingBrakeSw - BIN CC
Cruise Control Enable
CC Enable - BIN CC
Switch
Brake Switch Brake Switch - BIN CC
Clutch Switch Clutch Switch - BIN CC
Cruise Control Coast
CC Coast - BIN CC
Switch
Cruise Control Resume
CC Resume - BIN CC
Switch
Cruise Control Accelerate
CC Acc Switch - BIN CC
Switch
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
SHDWN 0xFEE4 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
Comap Electronic Engines Support 138
©ComAp – June 2008, Comap Electronic Engines Support 06-2008.pdf
VEP 0xFEF7 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM11cl 0xFED3 6 0x17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x17 0 20
EBC1 0xF001 6 0x17 0 100
CC 0xFEF1 6 0x17 0 100
DM11cl 0xFED3 6 0x17 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Requested speed ReqSpeed RPM ANA TSC1
Stop Request Stop Request - BIN EBC1
Parking Brake Switch ParkingBrakeSw - BIN CC
Cruise Control Enable
CC Enable - BIN CC
Switch
Brake Switch Brake Switch - BIN CC
Clutch Switch Clutch Switch - BIN CC
Cruise Control Coast
CC Coast - BIN CC
Switch
Cruise Control Resume
CC Resume - BIN CC
Switch
Cruise Control Accelerate
CC Acc Switch - BIN CC
Switch
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
SHDWN 0xFEE4 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
Comap Electronic Engines Support 140
©ComAp – June 2008, Comap Electronic Engines Support 06-2008.pdf
VEP 0xFEF7 6 0 any 1000
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM11cl 0xFED3 6 0x17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
TSC1 0x0000 3 0x17 0 20
EBC1 0xF001 6 0x17 0 100
CC 0xFEF1 6 0x17 0 100
DM11cl 0xFED3 6 0x17 0 -
Written to ECU
Value name Short name Dimension Type Frame name
Start Request Start Request - BIN VP_AUXtx
Stop Request Stop Request - BIN VP_AUXtx
Governor Mode Governor Mode - BIN VP_AUXtx
Idle Speed Select Idle Speed - BIN VP_AUXtx
Frequency Select Freq Select - BIN VP_AUXtx
Preheat Request PreheatRequest - BIN VP_AUXtx
Protection Override ProtOverride - BIN VP_AUXtx
Accelerator Pedal Position APP % ANA VP_AUXtx
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DD 0xFEFC 6 0 any 1000
WF 0xFEFF 6 0 any 10000
VP_AUXrx 0xFF47 3 0 any 50
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
VP_AUXtx 0xFF46 3 17 0 20
DM1cl 0xFECC 6 17 0 -
Received frames
Frame Name PGN Priority Source Destination Period [ms]
EEC2 0xF003 3 0 any 50
EEC1 0xF004 3 0 any 20
HR 0xFEE5 6 0 any 1000
ET1 0xFEEE 6 0 any 1000
EFLP1 0xFEEF 6 0 any 500
LFE 0xFEF2 6 0 any 100
IC 0xFEF6 6 0 any 500
VEP 0xFEF7 6 0 any 1000
DD 0xFEFC 6 0 any 1000
WF 0xFEFF 6 0 any 10000
VP_PROPrx 0xFF48 3 0 any 50
DM1m 0xECFF 6 0 any 1000
DM1 0xFECA 6 0 any 1000
DM1cl 0xFECC 6 17 0 1000
Transmitted frames
Frame Name PGN Priority Source Destination Period [ms]
ETC2tx 0xF005 6 17 0 100
VP_PROPtx 0xFF49 3 17 0 20
DM1cl 0xFECC 6 17 0 -
Received frames
Frame Name PGN Priority Source Destination Period [ms]
00001 1 3 0 1 500
10001 10001 3 0 1 500
10002 10002 3 0 1 500
10003 10003 3 0 1 500
10004 10004 3 0 1 500
10005 10005 3 0 1 500
10006 10006 3 0 1 500
10007 10007 3 0 1 500
10008 10008 3 0 1 500
00002 2 3 0 1 500
00003 3 3 0 1 500
30001 30001 3 0 1 500
30002 30002 3 0 1 500
30003 30003 3 0 1 500
Written to ECU
Name
Remote Fault Reset
Remote Emergency Stop
Remote Start/Stop Initiate
This list contains values available in the default configuration. See ICBEdit for the complete list of
supported values.
Name Dimension
Engine RPM RPM
Engine Oil Pressure (gauge) kPa
Engine Oil Temperature °C
Engine Coolant Pressure (absolute) kPa
Engine Coolant Temperature °C
Fuel Temperature °C
System Battery Voltage V
Intake Manifold Air Temperature °C
Inlet Manifold Air Pressure (absolute) kPa
Left Turbo Turbine Outlet Temperature °C
Right Turbo Turbine Outlet Temperature °C
Engine Cylinder #1-16 Exhaust Port °C
Temperature
This list contains values available in the default configuration. See ICBEdit for the complete list of
supported values.
Written to ECU
This list contains values available in the default configuration. See ICBEdit for the complete list of
supported values.
1
Alarms do not appear in the controller Alarm list but only in „I-CB String“ on IS measurement screen or in History.
This list contains values available in the default configuration. See ICBEdit for the complete list of
supported values.