Professional Documents
Culture Documents
Analysis of Electromagnetic Characteristics of Synchronous Condenser Under Stator Inter-Tum Short Circuit Fault
Analysis of Electromagnetic Characteristics of Synchronous Condenser Under Stator Inter-Tum Short Circuit Fault
Abstract—The magnetic field, vibration characteristics of phenomenon of the UHVDC transmission system. Therefore,
stator and rotor, and circulating characteristics of stator the probability of the failure of the synchronous condenser is
parallel branch, of a 300 MVA large capacity synchronous high. Although there is a relay protection device inside the
condenser were researched in cases of the stator inter-turn synchronous condenser, it does not mean that it can prevent
short circuit fault. A stator inter-turn short circuit fault model accidents [3]. It can only take action after the accident. In
was established using the finite element method. Secondly, order to ensure the reliable operation of the synchronous
using the Maxwell stress method and the simulated magnetic condenser and the UHVDC transmission system, it is
field data, the dynamic electromagnetic force of the rotor core necessary to analyze the failure mechanism of the
before and after the turn-to-turn short circuit is calculated.
synchronous condenser.
The Fast Fourier Transform was used to extract the harmonics
of the magnetic flux density. It provides a theoretical basis for The stator inter-turn short circuit fault of the synchronous
the study of stator inter-turn short circuit fault on air-gap flux condenser stator is the same as the external phase-to-phase
density, vibration characteristics of stator and rotor, and short-circuit fault, and the stator phase current after the fault
circulating characteristics of stator parallel branch, and theoretically also generates additional negative-sequence
provides diagnostic criteria for synchronous condenser fault current components [4]. Therefore, the synchronous
monitoring. condenser stator turns short-circuit will generate amplitude.
Extremely large fault currents, such large fault currents not
Keywords—synchronous condenser, inter-turn short circuit,
only threaten the safe operation of the grid, but also subject
finite element method, vibration characteristics
the core to extremely damaging electromagnetic forces.
Under the impact of electromagnetic force, the vibration of
I. INTRODUCTION the motor is intensified, and even a series of serious faults
New generation large capacity synchronous condenser such as further damage of the winding insulation and
has become the best choice for reactive power compensation cracking of the core are caused [5], resulting in huge
of UHVDC power grid because of its advantages of fast economic losses. Therefore, it accurately analyzes the
response, good running stability and long service life [1]. dynamic electromagnetic force of the synchronous condenser
The large capacity grid-connected synchronous condenser is and the concentrated position of the local electromagnetic
a reactive power compensation device that is a synchronous force under the inter-turn short-circuit fault, and optimizes
rotating motor that operates in the state of the motor and the design of the motor core and the importance of the
supplies or absorbs reactive power to the power system accurate and reliable synchronous condenser main protection
without mechanical load, and does not have a steam turbine scheme to reduce the internal short circuit. The destructive
in the thermal power unit. Motivation is mainly used to power of the synchronous condenser has practical value.
absorb or send out reactive power, improve grid power This paper analyzes electromagnetic characteristics of
factor, and thus maintain grid voltage level [2]. synchronous condenser under stator inter-turn short circuit
The large-sized rotating synchronous condenser is large fault. A stator inter-turn short circuit fault model was
in size, complicated in structure, numerous in components, established using the finite element method. Secondly, using
and has a large inrush current due to the commutation failure the Maxwell stress method and the simulated magnetic field
data, the dynamic electromagnetic force of the rotor core
Scientific Research Project of State Grid Hunan Electric Power before and after the turn-to-turn short circuit is calculated.
Company Limited (5216A516002Z). The Fast Fourier Transform was used to extract the
Where N is the total number of turns per pole of the B. Vibration characteristics of stator and rotor
synchronous condenser rotor.
According to the magnetic density calculation method of
the magnetic pull force, the magnetic pull force per unit area
2639
of the stator when the stator winding of the synchronous fundamental frequency and the octave frequency component,
condenser is short-circuited between turns is as shown in (7). and the combination equation (10), so that the circulating
current between the parallel branches contains the
B 2 (α m , t ) fundamental wave component and the third harmonic
q (α m , t ) = (7)
2μ0 component.
According to (7), when the synchronous condenser When both branches have a symmetrical inter-turn short
operates in the inter-turn short-circuit state of the stator circuit, wca1 = wca2 , La1 =La2 , Ra1 =Ra2 , the mutual inductance
winding, the stator core will have radial vibrations of 2, 4 of the two branches is equal. At this time, the potential
and 6 times, the amplitude of the radial vibration and the difference between the branches is 0, and there is no
inter-turn short circuit. The degree is positively correlated. circulation between the parallel branches.
The equation (7) is integrated circumferentially, and the In actual operation, when the stator windings are short-
magnetic pulling force that the rotor receives when the stator circuited between turns, most of them have only one branch
winding of the synchronous condenser is short-circuited is as with a turn-to-turn short circuit, that is, there are fundamental
shown in (8). waves and 3rd harmonic circulation between the parallel
branches.
F =LR 2ʌ q (α , t ) cos α dα = 0
° X ³0 m m m
(8) III. MODELING AND SIMULATION ANALYSIS
® 2ʌ
° FY =LR ³ q (α m , t ) sin α m dα m = 0
¯ 0
A. Finite element model
It can be known from equation (8) that when the In this paper, a 300 MVA synchronous condenser is
synchronous condenser operates in the inter-turn short-circuit given to investigate the influence of stator inter-turn short
state of the stator winding, the rotor has no additional circuit fault. A field-circuit coupling calculation model is
vibration, and its vibration is not affected by the inter-turn built to calculate and analyze electromagnetic field. The
short circuit between the stators. main mechanical and electrical parameters of this motor are
shown in Table 1. The synchronous condenser studied is a
C. Circulating characteristics of stator parallel branch two-pole, and because of its structural space symmetry, there
According to the above equation, the electromotive force is no need to establish a global model when simulating and
of the two parallel branches when the synchronous condenser analyzing the generator.
stator winding is short-circuited is as shown in (9).
TABLE I. PARAMETERS OF SYNCHRONOUS CONDENSER
¬ (
«cos ωt − α m + ψ + ʌ + ) 2
Rated capacity (MVA)
0
(MVA)
Operating power (MW)
42.5
1.7
° F cos (ωt − α ) + F cos (ωt − α ) + F cos ( 3ωt − α ) º
° S1+ m S1- m S3+ m ¼
Rated voltage (kV) 20 Operatingvoltage (kV) 20
® (9)
° ª( I f 0 + I f 2 cos 2ωt ) N Stator outside diameter Stator inner diameter
2500
° Ea2 (α m , t ) = 2qwca2 k w1τ lf Λ 0 « 1240
( )
(mm) (mm)
° «cos ωt − α m + ψ + ʌ + Rotor outside diameter
° ¬ 2 1100 Rotor ring diameter (mm) 1184
(mm)
° FS1+ cos (ωt − α m ) + FS1- cos (ωt − α m ) + FS3+ cos ( 3ωt − α m ) º¼
¯ Stator slots (pieces) 48 Rotor slots (pieces) 32
When the stator windings are short-circuited, the
effective turns wca1 and wca2 of the upper and lower branches According to the basic size of the synchronous
shown in Fig. 1 are no longer equal, and the difference condenser, the finite element model of the synchronous
between the electromotive forces of the parallel branches is condenser is established. The transient field is used to solve
as shown in (10). the problem. The outer circle of the stator is used as the outer
boundary of the solution area. Regardless of the end effect of
the synchronous condenser, the magnetic field at any time is
ª º treated as a two-dimensional constant magnetic field. In
ΔU (α m , t ) = « − Ea1 (α m , t ) + jω La1 I a1 + Ra1 I a1 + jω ¦ M a1i I i » order to calculate accurately, the mesh size of each area is
¬ i ¼ appropriately selected, Because the flux change in the
ª º synchronous condenser mainly concentrates on the air gap,
− « Ea 2 (α m , t ) + jω La 2 I a2 + Ra2 I a2 + jω ¦ M a 2i I i » for the accuracy of calculation, the air gap part needs to be
¬ i ¼
(10) custom-divided to increase the accuracy of the air gap at the
air gap. For other parts, since the flux change is small, Use
For equation (10), when there is only one branch with free splitting. The air gap is divided into two layers, the outer
short-circuit between turns, or if both branches have short- layer is the stator air gap, the inner layer is the rotor air gap,
circuit between turns (but short-circuited and asymmetrical), the rotor air gap rotates synchronously with the rotor, and the
wca1 ≠ wca2 , La1 ≠ La2 , Ra1 ≠ Ra2 , the mutual inductance of the stator air gap is fixed.. The solution domain mesh is shown in
two branches is not equal. There is a circulation between the Fig.2.
parallel branches. Further, from the equation (4), it is known
that the induced electromotive force contains the
2640
Fig. 5. The excited current under short-circuit fault
(a) (b)
Fig. 6. The magnetic field lines in two cases: (a) operating normally; and
(b) operating on stator inter-turn short circuit fault
Fig. 7. The magnetic flux density in two cases: (a) operating normally;
and (b) operating on stator inter-turn short circuit fault
IV. CONCLUSION
When the synchronous condenser operates in the inter-
turn short-circuit state of the stator winding, the magnetic
2641
field lines at the fault are spiral, and the magnetic field is REFERENCES
severely distorted, so that the magnetic field in the entire [1] Teleke S, Abdulahovic T, Thiringer T, et al. Dynamic Performance
synchronous capacitor no longer satisfies the symmetry Comparison of Synchronous Condenser and SVC[J]. IEEE
condition. The stator core will have radial vibrations of 2, 4 Transactions on Power Delivery, 2008, 23(3):1606-1612.
and 6 times, the amplitude of the radial vibration and the [2] Y. B. Cui, Q. Tao, Z. X. Ling, et al. Analysis on design points of large
inter-turn short circuit. The degree is positively correlated. synchronous condenser for UHVDC project[C]. International
Conference on System Reliability and Science, 2016: 12-16.
The rotor has no additional vibration, and its vibration is not
affected by the inter-turn short circuit between the stators. [3] Wang Y, Zhang Y, Zhou Q, et al. Study on Application of New
Generation Large Capacity Synchronous Condenser in Power Grid[J].
The circulating current between the parallel branches Power System Technology, 2017.
contains the fundamental wave component and the third [4] I. S. Jacobs and C. P. Bean, “Fine particles, thin films and exchange
harmonic component. anisotropy,” in Magnetism, vol. III, G. T. Rado and H. Suhl, Eds.
New York: Academic, 1963, pp. 271–350.
ACKNOWLEDGMENT [5] Xiao S, Ge B, Tao D, Liu Z. Calculation of rotor dynamic
electromagnetic force of synchronous generator under the stator
This work was supported by the Scientific Research winding interturn short circuit fault[J]. Transactions of China
Project of State Grid Hunan Electric Power Company Electrotechnical Society, 2018. (in press)
Limited (5216A516002Z). Cong Wang is the corresponding [6] Liu H. Research of Eccentricity and short circuit faults on magnetic
author. field and electromagnetic vibration characteristic of synchronous
generator[D], Heilongjiang Province: Harbin University of Science
and Technology, 2017.
2642