TECHNICAL DATA SHEET

HOSE REEL DRUM (SWINGING TYPE)


1.0 REFERENCE STANDARDS IS: 884 – 1985.

2.0 APPROVALS NIL

3.0 SIZE OF HOSE 20mm X 36 Mtrs. LONG HOSE TUBING


1” NB (F) BSPT INLET (WITH BALL VALVE)
4.0 MATERIAL OF CONSTRUCTION

4.1 HUB MS IS: 513


4.2 SIDES MS IS: 513
4.3 SWIVEL JOINT SS 304
4.4 WALL BRACKET IS: 2062
4.5 HOSE REEL TUBING THERMOPLASTIC HOSE (IS:12585 TYPE II)
4.6 SHUT OFF NOZZLE SS 304 (IS: 3444 Gr. 1)
4.7 STOP VALVE (1” NB) BRASS AS PER IS: 778.
AS PER DRAWING
5.0 DIMENSIONS

6.0 NORMAL WORKING PRESSURE 7 Kgf/cm2

7.0 OPERATIONAL FLOW TEST NOT LESS THAN 24 LPM @ 7KGF/CM2

8.0 RANGE OF JET NOT LESS THAN 6 MTRS @ 7KGF/CM2

9.0 HYDRAULIC PRESSURE TEST FOR 21 KGF/CM2 (g) (For 2.5 min.)
HOSE REEL DRUM (W/O HOSE TUBING)

10.0 FINISH 2 COATS OF P.O. RED PAINT, SHADE NO.


538 OF IS:5. CONFIRMING TO IS 2932.

11.0 MARKING MARKED: -

MANUFACTURER’S NAME  SHAH BHOGILAL JETHALAL & BROS.


YEAR OF MFG. 
LENGTH & SIZE (ON HOSE TUBING)  20mm X 36 Mtrs.
INSTRUCTION  INSTRUCTION FOR USE
APPROVAL (ON HOSE TUBING)  ISI MARKED

12.0 WARRANTY& GUARANTEE 12 MONTHS FROM THE DATE OF SUPPLY


0 For Approval NP DYP 08.11.2022
Rev Description BY APPD DATE
DATA SHEET NO. SHEET NO.
SBJ/280/MS-I/DS 1 OF 1 TITLE : HOSE REEL DRUM (Swinging Mounted)

Shah Bhogilal Jethalal & Bros.


72, Siddhivinayak Estate, Opp. Kitchen Express, Santej – 382721.
SIZE OF HOSE:

1. SIZE : 20 mm I.D.
2. LENGTH : 36 Mtrs.

HYDRO TEST: 21 KGF/CM2 (FOR 2.5 MINUTES)

6 SHUT OFF NOZZLE SS 304


THERMOPLASTIC HOSE
5 HOSE REEL TUBING
AS PER IS:12585 TYPE-II
4 SWIVEL JOINT SS 304
ISOMETRIC VIEW 3 WALL BRACKET IS: 2062
2 SIDES M.S. IS: 513
1 HUB M.S. IS: 513
NO. DESCRIPTION MATERIAL
PART LIST
DRAWN BY: CHECKED BY: SCALE:
TOL. WHERE NOT SPECIFIED ± 10mm ALL DIM. ARE IN M.M. M.S.PANCHAL M.M.SHAH N.T.S
TITLE:
Shah Bhogilal
Jethalal & Bros. DRG. NO. DATE:
REV. 0
SPECN.
72, SIDDHI VINAYAK ESTATE, SANTEJ- 382721. SBJ/256/MS-20 03.07.2021 IS:884
NOTE : DUE TO OUR POLICY OF CONTINUOUS IMPROVEMENT SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE