Professional Documents
Culture Documents
MNINOD600OSWUK03
MNINOD600OSWUK03
OS-Wire Drives
Installation Manual
PRIMA ELECTRO S.p.A. reserves the right to modify and improve the product described in this manual at
any time and without prior notice. The application of this manual is under customer responsibility. No
further guarantees will be given by PRIMA ELECTRO S.p.A., in particular for any possible faults,
incompleteness and/or difficulties in the operation. In no event will PRIMA ELECTRO S.p.A. responsible
or liable for indirect or consequential damages that may result by the use of such documentation.
MNINOD600OSWUK03 2
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
Contents
MNINOD600OSWUK03 3
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
MNINOD600OSWUK03 4
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
1. Security instructions
1.1 Introduction
This manual contains the information needed for a correct use of the OD600 OS-Wire drives. It describes
the main technical data and contains notes about electromagnetic compatibility requirements and
examples of connections.
For the configuration and connection to the OS-Wire network, please refer to the OD600 browser
manual.
ATTENTION! To use the system in a correct manner, follow the instructions provided in this manual and
pay special attention to the indications below.
WARNING! Danger: This symbol is associated with facts and circumstances that
could damage the system, the equipment and the operators.
NOTES: This symbol is used for operations that have to be executed with great
care in order to ensure their successful completion and denotes information to be
taken into consideration to prevent damage to the equipment in general.
MNINOD600OSWUK03 5
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
2. General purpose
2.1 Introduction
The OD600 OS-Wire implies a vector control strategy and an integral proportional regulator of position,
speed and current through closed loop.
Furthermore this disposes an internal intelligence for the drive complete control and the optimization of
its operative features.
Power supply CA
- Remote and local control
- Current, speed and position control
- D.C. bus voltage monitoring
- Hardware and software protection functions
- Motor and converter thermal protections
- Dynamic and dissipative braking functions
R1 R2 Rint
Rint
R3
PWM
II
* Position - speed Iq* Current PI regulator V* Generation
- feedback Iq - feedback
Id IU
IV
Iq IW
Current
feedback
Position
feedback
MNINOD600OSWUK03 6
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
The equipment described runs on high voltage levels and has dangerous revolving parts (fans).
Failure to observe safety standards and warnings can cause death or severe injuries and
serious damage.
The user is responsible for assembling the power converter and the motor in addition to any
other device in accordance with the applicable safety regulations. He also has to guarantee
compliance with all the other national or local regulations on cable adjustments and
protection, grounding, breakers, overcurrent protection, etc.
Be very careful before touching the motor shaft with your hands. This can be done only when
the system is not powered and the drive is insulated from the mains current.
According to the applicable regulations, stopping the converter by means of its electronic
control enable inputs cannot be regarded as a safety shut-down condition. A fault occurring in
the electronic control components of the converter may result in accidental motor starting.
The intermediate circuit (bus) is under voltage, and when the drive is running the voltage level
in this circuit can be as high as 800 Vdc ! The two poles of the bus are also connected to the
terminals of power connectors. When the power to the drive has been cut out, the contacts of
these connectors remain live for a certain time, as indicated by the warning symbol on the
drive:
Pay attention to the mechanical differences between the different sizes of drive.
MNINOD600OSWUK03 7
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
The label is printed through an indelible black colour, the code and the serial number are indicated with
a EAN128 bar code too. Some of the logos shown below could not be present.
The plate in the picture is for an OD600 OS-Wire 12A size version.
The power stage is realized through IGBT module with protected gate driver circuit.
The converter size is indicated with the In/Imax values, that is to say the rms values of nominal/maximal
current that are supplied as output by the converter.
With reference to these current features, are available 4 different sizes that are indicated with one of
the following abbreviations:
If you exceed the maximum current limit, the drive could generate drive alarms.
MNINOD600OSWUK03 8
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
The table shown below summarizes the standard electrical features of the OD600 OS-Wire drives
according to the size of the converter itself.
MNINOD600OSWUK03 9
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
3. Mechanical installation
3.1 Installation
Once the wirings have been finished, the closed metallic box protection degree is IP20. The installer and
the machines manufacturer will take care of the completion devices for the installation safety.
3.2 Mounting
To install the OD600 OS-Wire are sufficient the snap flasks supplied with the drive.
fix the lower bracket on the panel using a screw (1 or 2, depending on the size)
position the converter on the lower bracket
position and fix the upper bracket using a screw
use M6 screw
In the figure it is shown the version of drive with AUX feedback option.
MNINOD600OSWUK03 10
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
Ø
E
D
B
C C
F
A
Allow a free space for assembling the connecting cables
All dimensions in mm
MNINOD600OSWUK03 11
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
Ø
E
D
B
C C
F
A
Allow a free space for assembling the connecting cables
Allow a free space for assembling the connecting cables
Type A B C D E F Ø
All dimensions in mm
MNINOD600OSWUK03 12
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
X1
STO IN 1
STO IN COM.
STO IN COM.
STO IN 2
X2
GND BR.
OUT BR.
X3
24V BR.
GND BR.
MOT.TH. 2
MOT.TH. 1
24V
B
GND
D
POWER
U
MOTOR
R1
internal
CLAMP
external
RES
R2
+VB
-VB
MAINS SUPPLY
CAUTION!
TERMINAL VOLTAGE IS PRESENT
UP TO 5 MINUTES AFTER
SWITCHING OFF !
A
Allow a free space for assembling the connecting cables
Type A B C D E
All dimensions in mm
MNINOD600OSWUK03 13
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
In the case of multi-axes systems, the drives must be installed by respecting the distances indicated in
the following figure. These distances are necessary to guarantee adequate converter aeration. Any
additional forced ventilation systems are necessary.
X1
STO IN 1
STO IN COM.
STO IN COM.
STO IN 2
X2
GND BR.
OUT BR.
X3
24V BR.
GND BR.
MOT.TH. 2
MOT.TH. 1
24V
GND
POWER
U
MOTOR
R1
internal
CLAMP
external
RES
R2
+VB
-VB
MAINS SUPPLY
CAUTION!
TERMINAL VOLTAGE IS PRESENT
UP TO 5 MINUTES AFTER
SWITCHING OFF !
e
n n n n
Size e n p p'
All dimensions in mm
In the figure it is shown both the version of drive, with and without AUX feedback option.
MNINOD600OSWUK03 14
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
4.1 Introduction
This chapter fully describes the procedure for a correct installation of the OD600 OS-Wire, so the
positions of the different components fitted to the drive including the different connectors. The
connectors are grouped on the front and the bottom part. It also gives the names with which the various
connectors are identified and referred to in the rest of this manual.
The assembly plate in the rack, on which the drives and their filters are mounted, must have a
conductive surface (as a rule, galvanised).
Shielded cables
OS-Wire cable
Use the cable supplied by Prima Electro.
MNINOD600OSWUK03 15
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
by using the ad hoc internal rings, which, during the assembly process, will push the
braiding against a wide surface area of the connector body.
The motor connecting cables, which combine the power, thermal sensor and brake
connections, are generally made up of:
an internally shielded 4-wire power cable
2 separately shielded twisted pairs for the brake and the heat sensor
an external shield
The installation of the motor is extremely simplified using this type of cable.
Ground connection
The grounding system of the plant is connected to the grounding pin of the mains filter of the
drive, on the input side. The other ground pin, which is situated on the filter output side, is
connected to a grounding bar inside the panel. The ground wires start from this bar, separately for
each drive, and are connected to grounding pins or terminals. The drive is the starting point for
the motor ground lead, which, on the motor side, is connected either to the ground terminal PE in
the connector box or to contact no. 2 on the power connector, depending on motor version.
Grounding system
During machine installation, make sure that the grounding system complies with the local
regulations and has a sufficiently low impedance to be able to discharge the disturbances caused
by electromagnetic interferences.
Mains filter
Fit the filters according to the instructions given in this manual.
MNINOD600OSWUK03 16
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
MNINOD600OSWUK03 17
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
Motor Feedback
External Converter
Main Power Clamp
Resistor D
R
A
Motor
Fuses Control
C B Unit
M
Limited distribution: trading modality where the manufacturer limits the supply of devices
to suppliers, customers or users that, separately or together, have a technical skill of the
EMC requirements for the servo-drives application.
MNINOD600OSWUK03 18
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
External
Device
MNINOD600OSWUK03 19
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
7-Digit Display
P2 – Brake
Address Key
P3 – Brake resistor
Motor power
OS-Wire
P4 – Main supply
M1 - Low Voltage
Ground
connector
Motor Feedback
Digital I/O
MNINOD600OSWUK03 20
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
P3 – Brake resistor
Motor power
Address Key
P4 – Main supply
OS-Wire
Aux Feedback
Ground
connect
or
M1 - Low Voltage
Motor Feedback
Digital I/O
OD600 OS-Wire drive connectors views size 18 A - version with AUX feedback option
MNINOD600OSWUK03 21
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
X1
STO IN 1
STO IN COM.
STO IN COM.
STO IN 2
Address Key
OS-Wire
X2
GND BR.
OUT BR.
X3
X2 - Brake 24V BR.
GND BR.
MOT.TH. 2
MOT.TH. 1
X3 - Low Voltage 24V
GND
POWER
U
MOTOR
W
Motor Power Motor Feedback
R1
internal
external
RES
R2
Main Supply
+VB
-VB
Ground
MAINS SUPPLY
CAUTION!
TERMINAL VOLTAGE IS PRESENT
UP TO 5 MINUTES AFTER
SWITCHING OFF !
MNINOD600OSWUK03 22
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
At start-up the current address flashes on the display. By clicking this button key you can select an
address between 0 and 3Fh. The display displays this task and once the controller has sent appropriate
start commands it changes the drive status according to a 0, 1 and 2 sequence. The drive activates its
DRRDY output, indicating that it is ready to accept the enable command. The command is transmitted to
the drive by the controller, through the OS-Wire link. The display shows status 3.
MNINOD600OSWUK03 23
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
TERMINATION
The drawing shows the fixed part of the connector fitted to the drive.
A square wave incremental external encoder (AQB) can be connected to this encoder.
Through this connector you can also manage the handwheel.
MNINOD600OSWUK03 24
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
The signals from the external encoder must conform to the following specifications:
The cable used for connecting the external encoder must have internally shielded twisted
pairs.
The cable must have an external shield. The external and internal shields must be grounded
on both the drive and the encoder end.
The twisted pairs are formed for the following signals: (A+ A-), (B+ B-), (Z+ Z-).
The drawing shows the fixed part of the connector fitted to the drive.
MNINOD600OSWUK03 25
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
The drawing shows the fixed part of the connector fitted to the drive.
The specifications for the external safety device are being defined.
The cables used to connect digital input/output must be 30 [m] long.
MNINOD600OSWUK03 26
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
This can be used for a rapid motor stop, typically in an emergency. In its factory configuration it is not
managed. To be used, it must be enabled or disabled in ODM, in the Flags window. The drive holds the
enabled management of Rapid Halt by default.
The active level of this signal can be programmed in ODM (Flags). The factory configuration is low
active.
The activation of this signal results in the immediate application of the motor brake, according to a
ramp specified in ODM, in parameter 37 (Max Motor Acceleration). At the end of the cycle, with the
motor stationary, the brake also closes, if the motor has one. If the motor does not within the specified
time limit, the brake closes all the same, after a 2 second wait.
The Zero microswitch is always connected to this connector, which must also be indicated in AMP.
Switch type (normally closed or normally open) can be programmed in ODM, in the Flags window. Its
default status is normally closed. During the homing cycle, the movement is controlled by the CNC.
These inputs can be used by the machine logic, by means of the ad hoc function bloc. The drive can
reverse the signal connected by means of the ad hoc flags in ODM, but it does not process the signal.
Input no. 1 (DI1) can be used to indicate the state of the external safety device. This function must be
enabled by means of the appropriate flag in ODM (the specifications for this device are being defined).
Input no. 2 (DI2) can be used for managing the External Drive Disable function. When this function is
active, the DI2 input becomes Drive Enabled:
If the input becomes low, then one of the following events occurs:
if the drive is enabled, it is disabled through an immediate activation of the brake and
warning 132 is given out (External Disable Request)
if the drive is disabled, it remains disabled and the same warning (132) is given out
MNINOD600OSWUK03 27
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
DRIVE
MNINOD600OSWUK03 28
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
The servodrive is automatically deactivated and releases the electromechanical brake when the
connection is opened.
Connect the emergency contact free from tension or connect through a jumper.
Connect GNDBR to the ground and 24VBR to the positive power supply of the electromechanical parking
brake. The drive uses this voltage to open and close the brake, through the M2 connector. When the
drive is not enabled, it leaves the brake blocked, cutting out the 24 V. The drive supplies 24 V and
releases the brake the very moment its control board enables the power to govern the motor phases. In
this manner, the axes do not fall because of gravity. Brake opening and closing times can be
programmed in ODM.
The power supply between pins GND and 24V must always be connected. If you want
to have a controlled braking action in the event of a mains power outage, you must
install a UPS.
MNINOD600OSWUK03 29
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
All errors (e.g. cross circuit) that are not detect can lead to a loss of safety
functioning.
MNINOD600OSWUK03 30
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
3 1 2
MNINOD600OSWUK03 31
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
Remove the jumper between contacts 1 and 3 to cut out the internal resistor.
Indicate the use of the external resistor by means of the appropriate ODM flag. (External brake
resistor connected)
The external resistor must be dimensioned correctly for the quantity of energy to be
dissipated. It must be placed in a protected position, knowing that its temperature can get
very hot, and voltage can be as high as 800 Vdc. Make sure that the heat generated can be
dissipated. Since the drive has no protection for the exterior resistor, it is necessary to
consider the use of a thermal protection.
The external resistor connecting cable must be shielded, and the shield must be connected to
the ground on either side.
MNINOD600OSWUK03 32
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
The OD600 OS-Wire must be supplied from the mains, by an AC three-phase system.
The power stage is a multivoltage one and can operate with any voltage level between:
minimum nominal voltage Vac = 230 Vac
maximum nominal voltage Vac = 480 Vac
Connect the R, S, T terminal blocks to the three-phase power supply and connect the earth conductor to
the PE screw terminal block placed on the front panel.
The three-phase line of the power supply must be protected preferably by an automatic switch or, as
alternative, by a knife switch plus three fuses.
In the case of plants having power components, as for example lines and switches, common to many
servodrives, it is necessary that the features of these devices are calculated making reference to the
whole apparent installed power (kVA) and to the minimum voltage in case of overload, reminding what
follows:
the nominal and peak powers absorbed by each servodrive
operating simultaneity factor
the operating factor of each servodrive
For the values of apparent power absorbed by the drive please consult section Technical Specifications.
For what concerns the safety differential switch, it is recommended the use of a selective
switch with possibility of regulation both for the current intervention threshold and also for
the delay of intervention and not sensible to the impulsive currents: in fact, in some
circumstances, the use of the mains filters, or also the converter itself, or the non-perfect
simultaneity of the three opening phases (that can also be linked to the earthing circuit of
the plant), could trigger the differential switch in conditions as switching on/off of the
converter.
The possibility of adjusting the delay of intervention, together with the possibility of
adjusting the intervention threshold, allow an easy adjustment of the differential switch so as
not to intervene in these circumstances, even though the plant is still maintained within the
necessary safety conditions.
MNINOD600OSWUK03 33
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
Connect the motor cables to the U, V, W terminal blocks by observing the poles indications.
Connect the earth conductor to one of the PE screwed terminal block placed on the front panel
R1
Pin no Name Function Direction
R2
1 R1 Internal/external clamp resistor -
+VB 2 R2 Internal clamp resistor -
-VB
3 +VB Positive end DC bus -
4 -VB Negative end DC bus -
R
5 R 400Vac phase Input
S
6 S 400Vac phase Input
T 7 T 400Vac phase Input
The OD600 OS-Wire drive must be supplied from the mains, by an AC three-phase system.
The power stage of the OD600 OS-Wire is a multivoltage one and can operate with any voltage level
between:
minimum nominal voltage Vac = 110 Vac
maximum nominal voltage Vac = 400 Vac
MNINOD600OSWUK03 34
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
The standard converters must not be supplied with voltages higher than 400 Vac otherwise
the capacitors of the DC bus may be damaged due to dielectric break down.
In these cases it is mandatory to use the special version.
Connect the R, S, T terminal blocks to the three-phase power supply and connect the earth conductor to
the PE screw terminal block placed on the front panel.
The three-phase line of the power supply must be protected preferably by an automatic switch or, as
alternative, by a knife switch plus three fuses.
In the case of plants having power components, as for example lines and switches, common to many
servodrives, it is necessary that the features of these devices are calculated making reference to the
whole apparent installed power (kVA) and to the minimum voltage in case of overload, reminding what
follows:
the nominal and peak powers absorbed by each servodrive
operating simultaneity factor
the operating factor of each servodrive
For the values of apparent power absorbed by the OD600 OS-Wire please consult section Technical
Specifications.
For what concerns the safety differential switch, it is recommended the use of a selective switch
with possibility of regulation both for the current intervention threshold and also for the delay of
intervention and not sensible to the impulsive currents: in fact, in some circumstances, the use of
the mains filters, or also the converter itself, or the non-perfect simultaneity of the three phases
opening (that can also be linked to the earthing circuit of the plant), could trigger the differential
switch in conditions as switching on/off of the converter.
The possibility of adjusting the delay of intervention, together with the possibility of adjusting the
intervention threshold, allow an easy adjustment of the differential switch so as not to intervene
in these circumstances, even though the plant is still maintained within the necessary safety
conditions.
The OD600 CAN has the function of dissipative braking, that is to say the dissipation on an opportune
resistitive element of the electrical energy generated by the servomotor during the deceleration phase.
The use of the external resistance is mandatory for working cycles having heavy loads and anyhow when
the power to be dissipated during the braking phase is higher than the nominal power of the internal
resistance.
Connect the external resistance between the terminal blocks R1 and +VB; R2 is disconnected.
The drive is protected against short-circuits among the terminal blocks R1, R2 and R3.
On the contrary the short-circuit between R3 and the ground can provoke serious damages to the
converter. Therefore it is necessary to take the opportune precautions in the wiring of the machine.
For the connection between the converter and the resistor, use cables of the same section as the power
supply cables; cables must be twisted and the shortest possible; the maximum length of these cables is 2
meters. The lay-out of these cables must be carried out such as to avoid possible interactions with other
signal or power cables.
MNINOD600OSWUK03 35
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
Prima Electro supplies the following model of external resistor (see appendix B for details):
MNINOD600OSWUK03 36
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
5. EMC provisions
5.1 Cables
To prevent the disturbances from radiating outside the converter, shield all the connecting cables.
Pay special attention to the contents of the “Shielding” section.
The cable connecting the net filter to the drive is marked as shielded on the drawing. If the cable is
shorter than 50 cm, shielding is not necessary.
MNINOD600OSWUK03 37
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
In order to reduce the antenna effect, arrange the cable along the base of the metal plate.
Wrong Correct
All lines have to be kept as close as possible to the grounding system wires to reduce the
effective area of the circuit for magnetic coupling.
Wrong Correct
When signal lines and control lines cross power cables, the wires must be spaced at least 20 cm
apart.
Lines with different EMC levels should cross only at an angle of 90°.
For differential signals (e.g. analog reference between CNC and drive, encoder signals etc.), use
twisted pairs.
The same technique can also be used for reducing the emission from power cables.
The converter grounding cables should be as short as possible (< 30 cm.). Use large cross-
sections (> 10 mm²) and high frequency cables (i.e., made up of many thin wires).
Noise sources, such as fuses and transformers, and noise sensitive modules, such as
microprocessors, bus systems, etc., should be kept at a distance of at least 20 cm from the
converter and its cables.
Avoid spare cable coils. Wires which are not used have to be grounded on both ends (this has an
additional shielding effect and prevents the hazards arising from capacitively coupled voltages).
MNINOD600OSWUK03 38
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
5.2 Grounding
In terms of EMC, classical star grounding is no longer sufficient to reduce the effect of relatively
high frequency disturbances as may be caused by converter operations. One gets better results
with a reference surface which has to be connected to the structure of the device over a wide
area (e.g., drive mounted directly onto a bare metal plate, thus ensuring an electric connection
over a large surface with an extremely low impedance).
If a wide reference area is not available, you should install a grounding bar directly next to the
converter, as this device creates bigger potential jumps than the other components in the
electric rack because of the fast switching (if possible, the grounding connection should not be
longer than 30 cm).
Place all grounding wires and shields as close as possible to the ground of the structure to avoid
ground circuits.
If possible, connect the drive’s reference voltage to the ground; to make this connection use a
cable with a cross-section as large as possible and not longer than 30 cm.
Remove insulating layers such as paint, adhesives, etc. from the connections to the ground of
the structure. If necessary, use lock washers with external teeth (DIN 6798) or similar
components to ensure permanent conductive contact. To prevent the corrosion of the
connections to the ground, use combinations of compatible metals and protect the connection
against conductive electrolytes by coating it with a protective material (e.g., grease).
Always connect both ends of the shields to the ground of the structure. The connection must be
made over a wide area in order to ensure good conductivity. This is the only way to eliminate
magnetic field and HF disturbance effects. If the grounding circuits pose a problem, the
receiving end should be connected galvanically and the transmission end capacitively.
When cable shields pass through panels separating areas with different EMC levels, they must be
in contact with the panel.
Cables passing through the exterior panels of shielding structures without any special measures (e.g.
filters) being adopted may have detrimental effects on the shielding capacity of the structure.
Accordingly, make a conductive connection of the cable shields going to the exterior shielding panel, at
the point where the cables enter the structure.
The distance between the last contact point of the shield and its exit from the rack has to be as short as
possible.
MNINOD600OSWUK03 39
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
5.3 Shielding
Magnetic fields shields are effective only when connected to the ground of the structure at
either end.
For electric fields the shield is effective if one end is connected to the ground of the structure.
However, in case of HF electric and magnetic fields (which depend on the length of the line),
you must always connect both ends of the shield because of the concatenated flow
(electromagnetic field).
Shield
Connecting both ends of the shield to the ground of the structure ensures that the wire will
remain within the shielding “cage”.
Connecting both ends of the shield to the ground of the structure does not fully eliminate the
effects of grounding circuits (potential differences in the grounding system of the structure).
However, this occurs very rarely if the instructions given in the sections on “Cables” and
“Grounding” are complied with.
You can also make a capacitive RF connection between the shield and the ground of the
structure. This prevents the occurrence of low frequency interferences due to the grounding
circuits.
Shielded cables passing through areas with different EMC levels must not be interrupted, as this
would reduce the shielding effect considerably. Arrange the cables without breaks up to the next
module.
Make the connection of the shield at low impedance and over a wide surface. Cable ends only 3
cm long (1 cm of wire = 10 nH) reduce the shielding effect within the MHz range by up to 30 dB!
The lines listed below are characterized by particularly high disturbance levels:
Motor power cable
MNINOD600OSWUK03 40
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
shield
shield
Shield
MNINOD600OSWUK03 41
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
5.4 Filters
When powered through the line filters, the drive conforms to the standards on electromagnetic
compatibility, 89-336-EC.
Drives without filters can cause severe disturbances to other users on the same line, whether inside or
outside the electric rack. Hence, the use of a network filter is strongly recommended.
Filter assembly
Fit the filter next to the converter. For lines longer than 30 cm, shield the cable between the
converter and the filter (connect the cable to the ground at either end).
Make a wide connection between the filter base and the grounding of the structure.
Discharge currents
Due to the operating modalities, current discharges of over 100 mA, are generated by eddy capacities in
the filter, the mains unit, the cables and motor windings.
This means that converters with differential switches could be incompatible!
The following filters are recommended by Prima Electro for the OD600 OS-Wire drive.
Filter In [Arms]
FRB84143-A08-R105 8
FRB84143-A16-R105 16
FRB84143-A25-R105 25
Marking
LINE LOAD
MNINOD600OSWUK03 42
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
If only one filter is used for more converters that are parallelly supplied, it is necessary to apply
the following formula:
Where the contemporaneity factor is a number lower or equal to 1 that must be defined by the
machine manufacturer.
MNINOD600OSWUK03 43
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
Basic information on the connections between the drive and the Prima Electro Hyperface SinCos motors
is provided in this chapter.
For detailed information on the motors, see the motors manual.
ENCODER CONNECTOR
Layout of the signals on the connector to the motor, viewed from the outside (attachment side)
12-pin metal contacts round metal connector.
MNINOD600OSWUK03 44
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
POWER CONNECTION
TERMINAL BOARD
Name Function
U,V,W Motor phases
PE Protective GND
B+ Brake positive power
B- Brake ground
T1 Thermal sensor
T2 Thermal sensor
Shield connection
To connect the shield (power cables, thermal sensor, brake) we recommend using a shielded
fairlead instead of a grounding screw, to make the connection safer and easier.
MNINOD600OSWUK03 45
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
NOTE: When connecting the brake, do not reverse the polarity of the voltage.
Noise suppressor built into the brake coil.
MNINOD600OSWUK03 46
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
The working cycle indicated as example represents the limit operating conditions of the braking resistor.
The braking powers are in the negative semi plane, since in this case the motor is operating as a voltage
generator.
MNINOD600OSWUK03 47
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
Hereafter you can find some rules for the correct use of the braking resistor:
the dissipated power during the braking must never be higher than the peak power PPEAK typical
of the braking resistor used. Consult the Braking Resistance table within Chapter 6.
TON and TOFF are safety periods for the resistor preservation and are valid for the peak power
braking PPEAK; the braking can have a higher duration if the dissipated power is less than PPEAK.
the Paverage average power dissipated on the braking resistor is calculated as sum of the
dissipated powers during each braking interval divided for the total time tTOT of the working
cycle, that is:
This value of average power (Paverage) has never to be higher than the continuous power (PCONT )
typical of the braking resistor.
If it is necessary to use the external resistor, please contact the Customer Service.
It is furthermore suggested to contact the Customer Sevice for special or heavy duty applications.
The internal braking resistor can have, for each converter size, only one prefixed value. Prima
Electro S.p.A. has decided that this value is optimized for the 400 Vac power supply voltage.
If the converter is used at voltages lower than 400 Vac, the braking power could not be sufficient, and
could bring the converter to an alarm condition due to overvoltage.
It is therefore recommended to carefully calculate the value of the power that has to be dissipated and
check it with the one that can be dissipated by the resistor at the voltage used.
If the internal resistor value will not result adequate, it is possible to connect to an external resistor.
MNINOD600OSWUK03 48
Prima Electro S.p.A. OD600 – OS-Wire Drives - Installation Manual
Contacts:
PRIMA ELECTRO S.p.A.
Strada Carignano, 48/2
10024, Moncalieri (TO) - ITALY
Tel. +39 011 98 99 800
Web: www.primaelectro.com
e-mail: sales@primaelectro.com
MNINOD600OSWUK03 49