Models G and GB
• General Clean Air • Light Contaminants
• Seismic • High Wind • Variable Volume
August
2022
Models G and GB
Spun Aluminum • Downblast
Centrifugal Roof Exhaust Fans
COLORS
GREEN- CMYK C-54 M-0 Y-100 K-0 RGB R-130 G-195 B-65 BLUE- CMYK C-100 M-56 Y-0 K-18 RGB R-0 G-90 B-156
Enjoy Greenheck’s extraordinary service, before, during and after the sale.
Greenheck offers added value to our wide selection of top performing, energy-efficient
products by providing several unique Greenheck service programs.
• Our Quick Delivery program ensures shipment of our in-stock products within 24 hours of
placing your order. Our Quick Build made-to-order products can be produced in 1-3-5-10-
15-20 or 25-day production cycles, depending upon their complexity.
• eCAPS® online selection guides you to choose the best value products for your building
projects. eCAPS® includes fan, louver, make-up air, energy recovery preconditioner, and
dedicated outdoor air system (DOAS) selections, as well as a damper guide and toolbox.
• Greenheck’s free Computer Aided Product Selection (CAPS®) program, rated by many as the
best in the industry, helps you conveniently and efficiently select the right products for the
challenge at hand.
•O ur 3D service allows you to download, at no charge, easy-to-use AutoDesk® Revit®
3D drawings for many of our ventilation products.
Find out more about these special Greenheck services at greenheck.com
2
Models G and GB
Spun Aluminum • Downblast
Centrifugal Roof Exhaust Fans
Model Comparison
Drive Impeller Performance
Location Mounting Airflow Application
Type Type
Maximum Volume
General/Clean Air
Contaminated Air
Ceiling Mounted
Maximum Static
Spark Resistant
Propeller/Axial
(above 200°F )
High Wind**
Mixed Flow
Recirculate
Centrifugal
Base/Floor
Reversible
Roof Curb
Outdoor
Hanging
Exhaust
Supply
Indoor
Direct
(cfm)
Wall
Belt
G 14,500 2.75
GB 44,700 3.25
* Smoke control available on models: 100, 100HP, 120, 130, 140, 140HP, 160, 160HP, 200, 240, 300, 360, 420 and 480
** High wind limited to sizes 300 and smaller
3
Construction Features
Models G and GB
5 Motor Carefully matched to the fan load and mounted out of the airstream.
Constructed of aluminum and attached with fasteners for easy removal and access to
6 Motor Cover
motor compartment and drive assembly.
Cooling fins located on top of the fan wheel draw outside air through a large space
7 Motor Cooling between the fan shroud and the motor cover directly into the motor compartment.
Positive motor cooling with fresh air results in maximum motor life.
8 Lifting Points Various lifting points are located on the drive frame and bearing plate (on select sizes).
9 True Vibration Vibration isolators, with no metal-to-metal contact, support the drive assembly and
Isolation wheel for long life and quiet operation.
Belts, pulleys, and keys are oversized 150% of driven horsepower. Machined-cast
10 Drive Assembly
pulleys are adjustable for final system balancing. Belts are static-free and oil-resistant.
11 Heavy-gauge aluminum with formed edges for added strength and provides
Lower Windband
weather resistance.
12 Curb cap (with integral deep spun venturi) is constructed of aluminum and is one-piece for
Curb Cap
a weathertight fit.
Not Internal Conduit A large diameter conduit for installing electrical wiring through the curb cap into the
Shown Chase motor compartment.
13 Nameplate Permanent embossed aluminum plate for exact model and serial number identification.
Galvanized
14 Rigid wire protects the fan discharge from birds and small objects.
Birdscreen
One-piece, heavy-gauge aluminum with a rolled bead for extra strength directs exhaust
15 Fan Shroud
air downward.
16 Mounting Holes Curb cap has prepunched mounting holes to ensure correct attachment to the roof.
Reinforced
18 High wind fans include additional reinforcement for maximum strength.
Windband
High wind load fans are certified for use with Greenheck model GPFHL, GPFHD, GPF or
Roof Curb
equivalent in high wind applications. Roof curbs ship separate for field installation with
(page 11) attachment details provided.
4
Construction Features
Models G and GB
7
5
14
1
11
13
12
8
MODEL G
DIRECT DRIVE
DRIVE FRAME 8
(BELT DRIVE)
6 9
3
10
8
2 15
17
18
MODEL GB
BELT DRIVE 16
5
Applications
Models G and GB
Seismic - G and GB With changes in building codes and standards, more equipment is being
required to be seismically certified in areas of the country not commonly
thought of as being in seismically active zones.
The International Building Code (IBC) is designed to provide model
code regulations that safeguard public health and safety in all U.S.
communities. This code is intended to improve the performance and
design of nonstructural systems subject to seismic events.
The State of California, one of the most active seismic areas in the United
States, has the Department of Health Care Access and Information
(HCAI) to regulate the design and construction of health care facilities
to ensure they are safe and capable of providing
services to the public after a seismic event.
HCAI developed their own unique certification
process to incorporate the IBC and ASCE
testing standards to ensure equipment remains
operable after a seismic event.
Note: All G and GB models meet seismic
requirements.
Protocols designed for seismic standards:
All Greenheck seismically certified models have been tested using the most severe seismic event that is
found on the Spectral Response Map per IBC Figures 1613.5 (1-2). Our testing is performed under the
Seismic
worst case scenario using the highest mapped seismic load, highest level occupancy category, worst
Testing Criteria
case site class, and highest code mandated importance factor, thereby allowing Greenheck’s seismically
certified fans to be used anywhere in the United States under any conditions.
The California Department of Health Care Access and Information (HCAI) requires all certified models be
California HCAI Test shake table tested in accordance with ICC ES AC-156, in which the fans are physically subjected to the
Protocols same or greater forces than they will see during a seismic event. Subjecting Greenheck model G and GB
fans to this type of testing ensures the fans will operate without problems after a seismic event.
The HCAI certification numbers and supporting documents can be viewed on HCAI’s
HCAI Certification
website ensuring that the fan has been subjected to and passed rigorous testing standards.
6
Applications
Models G and GB
U.S. continent
averaged
tornado frequency.
Protocols designed to protect against wind-borne debris and severe wind loads:
A static load that is 1.5 times the design load (91.5 pounds per square foot of pressure) is applied both
Structural
positively and negatively to simulate wind force loads in each direction. Structural Performance per
Performance Load
Dade County Protocol TAS-202 (ASTM-E330).
Miami-Dade NOA View the certifications on the Miami-Dade County website. Models G and GB are the first downblast
Numbers aluminum fans in the industry to have received a Miami-Dade NOA for high wind and hurricane zones.
Florida Product Approval ensures approved products can be used anywhere in the State of Florida
Florida Product
which are not governed by the Miami-Dade County high wind regulations. More information is available
Approval
on the Florida Building Code website. Florida Product Approval FL13225.1 for models G and GB.
7
Vari-Green® Motor Option
Model G Features
• Dial-on Motor Control - a potentiometer (dial-on
Greenheck’s electronically commutated (EC) motor control) is mounted on the motor for easy
Vari-Green (VG) motor is the industry’s first fully speed adjustment for system balance. Simply turn
controllable motor. It combines motor technology, the dial. There are no belts and pulleys to adjust.
controllability and energy efficiency into a single • Control Wire Inputs - the motor accepts a 0-10V DC
low-maintenance unit. When combined with signal from Building Automated Systems or other
Greenheck fans, all the CFM and static pressure controls to adjust motor speed.
ranges of a belt drive can be attained with the
benefits of a direct drive. Vari-Green Advantages
• Initial cost is similar to a belt drive
Motor Information
HP Voltages Phase Enclosure • Lower operating cost
1/15 115, 208-230 1 TENV • No maintenance: no belts, pulleys or bearings
1/10 115, 208-230, 277 1 TENV
1/6 115, 208-230, 277 1 TENV • Easy RPM adjustment
1/4 115, 208-230, 277 1 TENV
1/2 115, 208-230, 277 1 ODP
1/2 115, 208-230, 277 1 TENV
Comparisons: Belt, Direct Drive with PSC
3/4 115, 208-230, 277 1 ODP and Direct Drive with Vari-Green
1 115, 208-230, 277 1 ODP
1 115, 208-230, 277 1 TENV Motor Turndown Comparison
1 115, 208-230 1 TEFC 50% 75% 100%
600
1 208-240, 380-480 3 TEFC
2 208-230 1 TEFC 500 G-120
with PSC
2 208-240, 380-480 3 TEFC
INPUT POWER (WATTS)
400
3 208-230 1 TEFC 300
Not recommended
EEnergy
3 208-240. 380-480 3 TEFC GB-120
Single Phase* Savings
S
200
5 208-240. 380-480 3 TEFC
7 1/2 380-480 3 TEFC 100 G-120 with
10 380-480 3 TEFC 0
0 350 FAN SPEED (RPM) 1750
* GB is a belt driven fan
Benefits The length of each curve indicates the practical turndown range.
Data is for 1/2 hp motors with load of 0.35 Bhp at full speed
• The motor can attain up to IE5 efficiency ratings and
reduce energy consumption. Constant Volume Life Cycle Analysis
• Watt savings of 30-70% depending on RPM. Three Year Cost Comparison
Note: As motor speed is turned down, efficiency
$2,000
stays high as compared to an AC motor that
decreases dramatically. 1,750
8
Vari-Green® Control Options
% of Operation
of energy used by 1,750 100
80$$$$$$$$$$$$$$$$$$$$$$$$
decreasing the speed 1,500 60$$$$$$$$$$$$$$$$$$$$$$$$
40$$$$$$$$$$$$$$$$$$$$$$$$
of the fan when demand 1,250 20$$$$$$$$$$$$$$$$$$$$$$$$
is low. This lessens the 0%$$$$$$$$$$$$$$$$$$$$$$$$
1,000 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
amount of conditioned 750 Series 1 Time of Day
air exhausted, and 500 Demand-controlled ventilation offers significant energy savings by
in turn, reduces the 250
exhausting only the necessary amount of air throughout the day.
total operating costs $0
associated with air Constant Volume - Load Shape
Variable Constant
% of Operation
100
conditioning and heating Volume Volume 80
60
in multistoried buildings Heating Cost
40
Cooling Cost
including hotels, Fan Operating Cost
20
0%
multifamily complexes, 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Vari-Green® Controls
Transformer - Provides 24V power from the existing • Multifamily structures including apartments, condos,
line voltage at the fan to the Vari-Green motor and hotels; residential kitchens and bathrooms
controls. Dual voltage primary (120/240V) transformer • Institutional facilities such as schools, prisons,
provided with the fan. multistory office buildings; bathrooms
Hand/Off/Auto- Creates either a control or an Air Quality, Volatile Organic Compounds (VOC) -
accessory to other controls. Four modes are Control a Vari-Green motor via changes in VOCs.
selectable. Hand mode: control of the motor at this VOCs are gasses that are emitted from humans,
device. Off mode: stops the motor. Auto-Local mode: building materials, perfumes, foods, and furniture
select a speed at this control and toggle the fan on off-gassing. Range is 0-2000 CO2 ppm equivalent.
or off via voltage or dry inputs. Auto-Remote mode:
• Institutional facilities including schools,
accept a speed reference signal from other devices
courthouses, hospital bathrooms, waiting
and passes that to the motor when a voltage or dry
rooms, cafeterias
input signal is received. Provides 24V power for other
controls and an auxiliary contact for damper control. • Commercial buildings including office space in
conference rooms, bathrooms or breakrooms
Remote Dial - Allows for remote, manual airflow
adjustments. Wall plate with dial may be mounted in a Air Quality for Temperature and Humidity - Control
standard 2x4 inch electrical junction box. the Vari-Green motor via changes in temperature,
humidity, or both. Range is 32° to 120°F and 0% to
Two-Speed Control - Control allows motor RPM to 100% relative humidity.
be set at two independent speeds (high or low). Meets
minimum airflow requirements with the ability to bump • Multifamily structures including apartments,
up to high speed in an emergency or meet maximum condos, hotels, with placement in bathrooms and
airflow requirements, or reset down to low speed for utility rooms
energy conservation. • Commercial buildings such as office buildings for
Constant Pressure Control - Control the Vari-Green® placement in general office space, conference
motor via static (variable volume) or velocity (constant rooms, utility rooms, bathrooms, or breakrooms
CFM) pressure on the inlet or outlet side of the fan.
Available with duct or room probes for use in:
9
Vari-Green® Drive
Features VGD-100+
Features Analog Input (0-10V, 4-20mA)
Vari-Green Drive model VGD-100+ is constructed Damper Actuator Output (24VDC)
with a NEMA-4X rated enclosure to ensure a Control Voltage Output (24VDC)
long life operating under outdoor environmental LED Indication Lights (3)
conditions. Every Vari-Green Drive is compatible Relay Output (2)
with all Vari-Green controls or any industry Digital Input - Dry (2)
control sending a 0-10V or 4-20mA signal. Digital Input - Voltage (2)
Model VGD-100+ is also equipped with Modbus/ RS-485 (Modbus/BACnet)
BACnet® communications allowing for seamless
Bluetooth/Smart Device Interface
integration to building management systems.
On-Board PID Control
Optional Pressure Transducer
Benefits
• Variable volume control from the factory on • Eliminate compatibility issues as the motor and
larger fan sizes where Vari-Green motors drive are factory-matched.
are not available.
• Induction motors are reliable, efficient and readily
• R3 filtering and short leads mitigate harmonics. available if replacements are needed.
• Quick start-up and simplistic commissioning
as each drive comes preprogrammed and
installed from the factory.
10
Roof Curbs, Options and
Accessories
11
Roof Curbs, Options and
Accessories
Dampers Coatings
Designed to prevent A wide variety of coatings and colors are available.
outside air from entering Greenheck coatings and resistance charts can be
back into the building found in the Performance Coatings Commercial
when fan is off. Includes and Industrial Fans catalog and in our Product
gravity and motorized Application Guide—Performance Coatings for
dampers. Damper sizes Ventilation Products.
are shown on each
Permatector™ is our standard coating.
performance data page.
Typically used for applications that
TM
PERMATECTOR
12
Typical Installations
Models G and GB
Recommended
Roof Opening
Wheel Rotation
Direction of rotation is very critical. Rotation in the wrong direction will result in
excessive horsepower, possible motor burnout, and increased noise levels.
Check rotation by energizing the unit momentarily. The rotation should be the same
as the rotation decals affixed to the unit and is clockwise when viewed from the top
Counterclockwise
of the unit.
Airflow
Clockwise
Airflow
13
Typical Installations
Models G and GB
GB - 240HP - A - 5 - VG/VGD - 1 - 34 - X
Motor RPM (Direct Drive only)
X = UL 705
A = 1725 D = 1550
F = UL Smoke
B = 1140 E = 1050 Control Systems
Configuration C = 860 G = 1300
G - Direct Drive
GB - Belt Drive
Fan Size Motor HP Curb Cap Size (inches)
060 through 540 6 = 1/6 10 = 1 50 = 5
4 = 1/4 15 = 11/2 75 = 71/2
Wheel Pressure Level 3 = 1/3 20 = 2 100 = 10 Performance Revision
HP - High Pressure 5 = 1/2 30 = 3 150 = 15
7 = 3/4
VG = Vari-Green®
International
(See CAPS for performance)
K = 950 RPM J = 1475 RPM
14
Roof Downblast Exhaust
Size-060: G
0.6
193⁄8
(492) 140 RPM (Direct)
RPM (Vari-Green)
Density 0.075 lb/ft3
0.5 Density 1.2 kg/m3
120
VE
CUR
100 0.4
TEM
Static Pressure (Pa)
*12 ⁄81
SYS
(308) 80
THIS
06
0.3
0-
T OF
GV
06
0-
LEF
60 D
3 (76)
THE
0.2 06
TO
0-
G
CT
13⁄4 (44) 40
ELE
06
TS
17 0-
0.1 E
NO
(432) 20
DO
0 0.0
0 60 120 180 240 300 360
Damper Size = 8 x 8 (203 x 203) Volume (cfm)
Roof Opening = 131/2 x 131/2 (343 x 343)
Shroud Thickness = 0.064 (1.6) 0 100 200 300 400 500 600
Motor Cover Thickness = 0.040 (1.0) 3
Volume (m /hr)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 15 lbs. (7 kg)
All dimensions in inches (millimeters). *May be greater depending on motor. Direct Drive RPM
^Weight shown is largest cataloged Open Drip-Proof motor. E-1050-RPM G-1300-RPM D-1550-RPM VG-1725-RPM
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
15
Roof Downblast Exhaust
Size-070: G
0.6
193⁄8
(492) 140 RPM (Direct)
RPM (Vari-Green)
Density 0.075 lb/ft3
0.5 Density 1.2 kg/m3
120
VE
CUR
100 0.4
07
TEM
Static Pressure (Pa)
0-
VG
SYS
*12 ⁄8
1
HIS
(308) 80
07
0.3
FT
0-
TO
D
LEF
60
HE
3 (76)
OT
0.2
07
TT
0-
G
EC
1 ⁄4 (44)
3 40
EL
TS
NO
17 0.1
07
DO
(432) 20
0-
E
0 0.0
0 90 180 270 360 450 540
Damper Size = 8 x 8 (203 x 203) Volume (cfm)
Roof Opening = 131/2 x 131/2 (343 x 343)
Shroud Thickness = 0.064 (1.6) 0 200 400 600 800
Motor Cover Thickness = 0.040 (1.0) Volume (m /hr)
3
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 15 lbs. (7 kg)
All dimensions in inches (millimeters). *May be greater depending on motor. Direct Drive RPM
^Weight shown is largest cataloged Open Drip-Proof motor. E-1050-RPM G-1300-RPM D-1550-RPM VG-1725-RPM
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
16
Roof Downblast Exhaust
Size-080: G
0.9
213⁄4 220
(552) RPM (Direct Drive)
RPM (Vari Green)
200
E
0.8
CURV
3
Density 0.075 lb/ft
Density 1.2 kg/m3
180
08
M
0.7
0-
YSTE
VG
160
HIS S
0.6
OF T
(371) 08
0.5 0-
120 D
EFT
HE L
100 0.4
T
4 (102)
TO
80 08
0.3 0-
CT
G
13⁄4 (44)
ELE
60
TS
0.2
17
NO
40 08
(432) 0-
E
DO
0.1
20
0 0.0
Damper Size = 10 x 10 (254 x 254) 0 100 200 300 400 500 600
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
17
Roof Downblast Exhaust
Sizes-090 • 095: G
1.0
213⁄4 RPM
(552) RPM (Vari Green)
095-VG 3
Density 0.075 lb/ft
CURVE
090
-VG Density 1.2 kg/m3
200 0.8
YSTEM
095-
D
090
THIS S
*14 ⁄85
FT OF
095-
09 G
0-G
E
THE L
100 0.4
4 (102)
TO
095
13⁄4 (44) 09 -E
LECT
0-
E
17 50 0.2
T SE
(432)
NO
DO
0 0.0
0 200 400 600 800 1000 1200
Damper Size = 10 x 10 (254 x 254)
Roof Opening = 131/2 x 131/2 (343 x 343) Volume (cfm)
Shroud Thickness = 0.064 (1.6)
0 500 1000 1500 2000
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6) 3
Volume ( m /hr )
^Approximate Unit Weight = 22 lbs. (10 kg)
All dimensions in inches (millimeters). *May be greater depending on motor. Direct Drive RPM
^Weight shown is largest cataloged Open Drip-Proof motor. E-1050-RPM G-1300-RPM D-1550-RPM VG-1725-RPM
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
18
Roof Downblast Exhaust
Size-097: GB • G
Previously Size- GB-071
243⁄8 1.4
RPM (Belt)
(619) 097-A
1/
RPM (Direct)
8
HP
RPM (Vari-Green)
300 1.2 HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
250 1.0
1/
1/6
Static Pressure (Pa)
*233⁄4
4H
HP
200 0.8
P
(603)
17
25
150 0.6
097-B
43⁄8 (111)
14
35
13⁄4 (44) 100 0.4 11
097-C 40
19
86
(483) 50 0.2 0
720
0 0.0
Damper Size = 12 x 12 (305 x 305) 0 50 100 150 200 250 300 350 400
Roof Opening = 151/2 x 151/2 (394 x 394) Volume (cfm)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0) 0 100 200 300 400 500 600
Curb Cap Thickness = 0.064 (1.6) 3
Volume (m /hr)
^Approximate Unit Weight G/GB = 54/60 lbs. (24/27 kg)
All dimensions in inches (millimeters). *May be greater depending on Direct Drive RPM
motor. ^Weight shown is largest cataloged Open Drip-Proof motor. C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
19
Roof Downblast Exhaust
Size-098: GB • G
Previously Size- GB-081
243⁄8
RPM (Belt)
(619) RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
VE
Static Pressure (in. wg)
CUR
Static Pressure (Pa)
*233⁄4
EM
(603)
YST
S
HIS
FT
43⁄8 (111)
TO
EF
EL
13⁄4 (44)
TH
TO
19
CT
(483)
LE
SE
T
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
20
Roof Downblast Exhaust
Size-099: GB • G
Previously Size- GB-091
243⁄8
(619) RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
VE
CUR
Static Pressure (in. wg)
Static Pressure (Pa)
TEM
*233⁄4
(603)
SYS
HIS
FT
TO
43⁄8 (111)
LEF
E
13⁄4 (44)
TH
TO
19
CT
LE
(483)
SE
T
O
N
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
21
Roof Downblast Exhaust
Size-100: GB • G
Previously Size- GB-101 • G-103
243⁄8
(619) RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
E
URV
Static Pressure (in. wg)
C
*233⁄4
TEM
Static Pressure (Pa)
(603)
SYSS
THI
OF
43⁄8 (111)
13
EFT
50
EL
13⁄4 (44)
TH
TO
19
CT
(483)
LE
SE
T
O
N
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
22
Roof Downblast Exhaust
Size-100HP: GB • G
Previously Size- GB-101HP • G-103HP
RVE
Density 1.2 kg/m3
M CU
Static Pressure (in. wg)
Static Pressure (Pa)
YSTE
*233⁄4
(603)
IS S
F TH
TO
43⁄8 (111)
LEF
HE
13⁄4 (44)
OT
TT
19
EC
(483)
EL
TS
NO
O
D
Damper Size = 12 x 12 (305 x 305)
Roof Opening = 151/2 x 151/2 (394 x 394)
Shroud Thickness = 0.051 (1.3) Volume (cfm)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6) 3
^Approximate Unit Weight G/GB = 58/63 lbs. (26/29 kg) Volume (m /hr )
All dimensions in inches (millimeters). *May be greater depending on Direct Drive RPM
motor. ^Weight shown is largest cataloged Open Drip-Proof motor. A-1725 RPM VG-2550-RPM
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
23
Roof Downblast Exhaust
Size-120: GB • G
Previously Size- GB-121 • G-123
243⁄8
RPM (Belt)
(619) RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
E
*233⁄4
RV
CU
(603)
EM
ST
SY
IS
43⁄8 (111)
TH
OF
FT
13⁄4 (44)
LE
E
TH
19
TO
(483) CT
LE
T SE
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
24
Roof Downblast Exhaust
Size-130: GB • G
Previously Size- GB-131 • G-133
283⁄8
RPM (Belt)
(721) RPM (Direct)
A RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
E
RV
(603)
CU
EM
ST
SY
4 (102)
IS
TH
OF
13⁄4 (44)
FT
LE
E
19
TH
TO
(483) T
EC
EL
TS
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
25
Roof Downblast Exhaust
Size-140: GB • G
Previously Size- GB-141 • G-143
E
URV
MC
*233⁄4
STE
(603)
SY
HIS
FT
4 (102)
TO
EF
EL
13⁄4 (44)
TH
22
TO
CT
(559)
LE
SE
T
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
26
Roof Downblast Exhaust
Size-140HP: GB • G
Previously Size- GB-141HP • G-143HP
283⁄8
(721) RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
VE
CUR
Static Pressure (in. wg)
*233⁄4
EM
(603)
YST
22
SS
00
THI
OF
4 (102)
EFT
EL
13⁄4 (44)
TH
TO
22
CT
LE
(559)
SE
T
NO
DO
Damper Size = 16 x 16
Volume (cfm)
Roof Opening = 181/2 x 181/2 (470 x 470)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0) 3
Volume (m /hr )
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight G/GB = 75/83 lbs. (34/38 kg)
All dimensions in inches (millimeters). *May be greater depending on Direct Drive RPM
motor. ^Weight shown is largest cataloged Open Drip-Proof motor. B-1140-RPM A-1725-RPM VG-2200-RPM
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
27
Roof Downblast Exhaust
Size-160: GB • G
Previously Size- GB-161 • G-163
283⁄8
(619) RPM (Belt)
2
1.5
HP
RPM (Direct)
2.5
HP
160-A RPM (Vari-Green)
600
HP
1H
Density 0.075 lb/ft3
P
Density 1.2 kg/m3
500 2.0
3/4
1/2
Static Pressure (in. wg)
E
RV
H
H
P
Static Pressure (Pa)
CU
*233⁄4 400
17
EM
1/3
(603)
25
1.5
ST
HP
SY
15
HIS
75
300
FT
TO
160-B
13
4 (102) 1.0
EF
75
1/
EL
4
12
TH
HP
200 11
50
13⁄4 (44)
TO
40
CT
160-C
LE
22
SE
0.5 94
5
T
100 86
NO
(559) DO 0
0 0.0
0 1000 2000 3000 4000 5000
Damper Size = 16 x 16
Volume (cfm)
Roof Opening = 181/2 x 181/2 (470 x 470)
Shroud Thickness = 0.051 (1.3) 0 2000 4000 6000 8000
Motor Cover Thickness = 0.040 (1.0) 3
Volume (m /hr)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight G/GB = 101/88 lbs. (46/40 kg)
Direct Drive RPM
All dimensions in inches (millimeters). *May be greater depending on
motor. ^Weight shown is largest cataloged Open Drip-Proof motor. C-860-RPM B-1140-RPM A-1725-RPM
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
28
Roof Downblast Exhaust
Size-160HP: GB
Previously Size- GB-161HP
283⁄8
(721)
RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
E
URV
*233⁄4
EM C
Static Pressure (in. wg)
(603)
YST
IS S
F TH
TO
4 (102)
LEF
13⁄4 (44)
THE
TO
22
CT
(559)
LE
SE
T
NO
O
D
Damper Size = 16 x 16 (406 x 406)
Roof Opening = 181/2 x 181/2 (470 x 470)
Shroud Thickness = 0.051 (1.3) Volume (cfm)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 88 lbs. (40 kg) 3
Volume (m /hr)
All dimensions in inches (millimeters). *May be greater depending on motor.
^Weight shown is largest cataloged Open Drip-Proof motor.
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
29
Roof Downblast Exhaust
Size-180: GB • G
Previously Size- G-183
2.5
351⁄2 600 RPM (Belt)
2
(902)
HP
1.5
RPM (Direct)
HP
1H
RPM (Vari-Green)
P
HP
2.0 Density 0.075 lb/ft3
Density 1.2 kg/m3
3/4
H
RVE
1/2
14
CU
HP
Static Pressure (in. wg)
400
60
M
Static Pressure (Pa)
STE
*28 1.5 180-B
13
SY
(711)
35
HIS
FT
1/
11
1/
TO
4
11
85
HP
HP
40
EF
1.0
51⁄2 (140)
EL
10
TH
55
200 180-C
94
TO
13⁄4 (44) 0
CT
8
LE
81 60
SE
30 0.5 73
0
T
NO
(762) 0
DO
49
5
0 0.0
Damper Size = 24 x 24 (610 x 610) 0 1000 2000 3000 4000 5000 6000
Roof Opening = 261/2 x 261/2 (673 x 673)
Volume (cfm)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0) 0 2000 4000 6000 8000 10000
Curb Cap Thickness = 0.064 (1.6) 3
^Approximate Unit Weight G/GB = 108/142 lbs. (49/64 kg) Volume (m /hr)
All dimensions in inches (millimeters). *May be greater depending on Direct Drive RPM
motor. ^Weight shown is largest cataloged Open Drip-Proof motor. C-860-RPM B-1140-RPM
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
30
Roof Downblast Exhaust
Size-180HP: GB
351⁄2
RPM (Belt)
(902)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
RVE
Static Pressure (in. wg)
*28
CU
(711)
EM
ST
SY
HIS
FT
51⁄2 (140)
TO
EF
13⁄4 (44)
EL
TH
30
TO
(762)
CT
LE
SE
T
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
31
Roof Downblast Exhaust
Size-200: GB • G
Previously Size- G-203
351⁄2
(902) RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
VE
CUR
Static Pressure (in. wg)
Static Pressure (Pa)
*28
TEM
(711)
SYS
HIS
FT
51⁄2 (140)
TO
EF
EL
13⁄4 (44)
TH
30
TO
(762)
CT
LE
SE
T
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
32
Roof Downblast Exhaust
Size-200HP: GB • G
351⁄2
RPM (Belt)
(902)
5
RPM (Direct)
3H
HP
RPM (Vari-Green)
P
2H
11
HP
200
HP
P
/2
Density 0.075 lb/ft3
-A
HP
Density 1.2 kg/m3
17
25
1H
Static Pressure (Pa)
URVE
P
*28
ME C
(711)
3/4
SYST
14
40
HP
THIS
1/
51⁄2 (140)
T OF
125
2
5
HP
LEF
1 ⁄4 (44)
3
THE
107
0
TO
30
CT
885
(762)
ELE
TS
700
NO
DO
Damper Size = 24 x 24 (610 x 610)
Roof Opening = 261/2 x 261/2 (673 x 673) Volume (cfm)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6) Volume (m /hr x 1000)
^Approximate Unit Weight = 166 lbs. (75 kg)
All dimensions in inches (millimeters). *May be greater depending on
motor. ^Weight shown is largest cataloged Open Drip-Proof motor.
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
33
Roof Downblast Exhaust
Size-220: GB
423⁄4
(1086) RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
VE
UR
(800)
MC
TE
YSS
HIS
53⁄4 (146)
FT
TO
EF
13⁄4 (44)
EL
TH
34
TO
(864)
CT
LE
SE
T
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
34
Roof Downblast Exhaust
Size-220HP: GB
423⁄4
(1086) RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
VE
CUR
*311⁄2
EM
YST
S
HIS
FT
53⁄4 (146)
TO
EF
EL
13⁄4 (44)
TH
TO
34
CT
(864)
LE
SE
T
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
35
Roof Downblast Exhaust
Size-240: GB • G
3.0
423⁄4 RPM (Belt)
(1086) RPM (Direct)
2H
5
HP
RPM (Vari-Green)
RVE
P
2.5 HP
11
600
M CU
Density 0.075 lb/ft3
/2
Density 1.2 kg/m3
114
1 H /4 H
0
HP
Static Pressure (in. wg)
STE
2.0
Y
3
IS S
*311⁄2 450
24
TH
0-
(800)
B
1.5
OF
910
1/
EFT
2
HP
53⁄4 (146) 300
825
L
1/ 1
HE
3 /4
1.0
HP H
OT
1 ⁄4 (44)
3 725
TT
34 625
EC
150
(864) 0.5
L
525
SE
425
OT
N
DO
0 0.0
Damper Size = 24 x 24 (610 x 610) 0 2 4 6 8 10 12
Roof Opening = 301/2 x 301/2 (775 x 775) Volume (cfm x 1000)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0) 0.0 4.1 8.2 12.3 16.4
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 165 lbs. (75 kg) Volume (m /hr x 1000)
3
All dimensions in inches (millimeters). *May be greater depending on Direct Drive RPM
motor. ^Weight shown is largest cataloged Open Drip-Proof motor. C-860-RPM B-1140-RPM
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
36
Roof Downblast Exhaust
Size-240HP: GB
423⁄4
(1086) RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
RVE
*311⁄2
CU
(800)
EM
ST
SY
HIS
FT
53⁄4 (146)
TO
EF
13⁄4 (44)
EL
TH
34
TO
T
(864)
EC
EL
S
T
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
37
Roof Downblast Exhaust
Size-260: GB
50
(1270) RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
E
URV
Static Pressure (in. wg)
EM C
Static Pressure (Pa)
*36
(914)
YST
IS S
F TH
TO
81⁄4 (210)
LEF
HE
13⁄4 (44)
OT
TT
40
EC
EL
(1016)
TS
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
38
Roof Downblast Exhaust
Size-300: GB • G
2.5
RPM (Belt)
50 RPM (Direct)
5
(1270)
H
RPM (Vari-Green)
300-C
P
HP
2.0 Density 0.075 lb/ft3
3
480 89 Density 1.2 kg/m3
HP
86 0
0
11
1 H HP
2
78
/2
1.5
3/4
HP
0
HP
*36
(914) 320
660
1/
1.0
2
HP
81⁄4 (210)
540
1/
3
160
13⁄4 (44)
HP
0.5
420
40
(1016) 300
0 0.0
0 3 6 9 12 15
Damper Size = 34 x 34 (864 x 864) Volume (cfm x 1000)
Roof Opening = 361/2 x 361/2 (927 x 927)
0.0 6.4 12.8 19.2
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.051 (1.3) Volume (m /hr x 1000)
3
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 320 lbs. (145 kg)
Direct Drive RPM
All dimensions in inches (millimeters). *May be greater depending on
motor. ^Weight shown is largest cataloged Open Drip-Proof motor. C-860-RPM
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
39
Roof Downblast Exhaust
Size-300HP: GB
50
(1270) RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
*36
RVE
Static Pressure (in. wg)
(914)
CU
Static Pressure (Pa)
EM
ST
SY
HIS
81⁄4 (210)
FT
TO
EF
13⁄4 (44)
EL
TH
40
TO
(1016)
CT
LE
SE
N OT
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
40
Roof Downblast Exhaust
Size-330: GB
583⁄4
(1492) RPM (Belt)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
RVE
Static Pressure (Pa)
*381⁄2
CU
(978)
M
STE
SY
HIS
FT
87⁄8 (225)
TO
EF
13⁄4 (44)
EL
TH
TO
46
T
EC
(1168)
EL
S
T
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
41
Roof Downblast Exhaust
Size-360: GB
583⁄4
(1492) RPM (Belt)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
*381⁄2
E
Static Pressure (in. wg)
RV
Static Pressure (Pa)
(978)
CU
EM
ST
SY
IS
TH
87⁄8 (225)
OF
FT
LE
13⁄4 (44)
E
TH
46
TO
T
EC
(1168) L
SE
T
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
42
Roof Downblast Exhaust
Size-360HP: GB
583⁄4
(1492) RPM (Belt)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
VE
Static Pressure (in. wg)
*381⁄2
CUR
Static Pressure (Pa)
(978)
EM
YST
S
HIS
FT
87⁄8 (225)
TO
EF
EL
13⁄4 (44)
TH
TO
46
CT
(1168)
LE
SE
T
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
43
Roof Downblast Exhaust
Size-420: GB
651⁄4
(1657)
RPM (Belt)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
*44
E
RV
CU
EM
ST
SY
93⁄4 (248)
IS
TH
OF
13⁄4 (44)
FT
LE
52
E
TH
(1321)
O
T
CT
LE
T SE
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
44
Roof Downblast Exhaust
Size-480: GB
733⁄4
(1873) RPM (Belt)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
E
RV
(1200)
CU
EM
ST
SY
IS
111⁄4 (286)
TH
OF
FT
13⁄4 (44)
LE
E
TH
58
TO
(1473) C
T
LE
SE
N OT
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
45
Roof Downblast Exhaust
Size-500: GB
83
(2108) RPM (Belt)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
E
RV
CU
EM
ST
SY
141⁄2 (368)
IS
TH
OF
13⁄4 (44)
FT
LE
E
64
TH
T
O
(1626) T
EC
SEL
T
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
46
Roof Downblast Exhaust
Size-540: GB
83
(2108) RPM (Belt)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
E
RV
CU
EM
ST
SY
IS
141⁄2 (368)
TH
OF
FT
13⁄4 (44)
LE
E
TH
64
O
T
T
(1626) EC
EL
TS
NO
DO
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
47
Quick Delivery and Quick Build Programs
COLORS
GREEN- CMYK C-54 M-0 Y-100 K-0 RGB R-130 G-195 B-65 BLUE- CMYK C-100 M-56 Y-0 K-18 RGB R-0 G-90 B-156
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and
in the Library under Warranties.