Professional Documents
Culture Documents
Dynex Operating & Troubleshooting Manual
Dynex Operating & Troubleshooting Manual
Author Edwin Fullagar Dept. 10188 Tel. 22453 Date 17/08/2006 Page 1 / 11
Subject
The main body of the pumps, including the swashplate, bearings, pistons, piston
shoes and pump valving should not be dismantled. If it is suspected that a problem
exists in these parts, the pump should be removed from service and servicing
undertaken by specifically trained Wärtsilä service personnel. For this reason, this
document covers only the Dynex control system.
2 different Dynex pump types exist, the smaller pump used on the RT-flex50, RT-flex58, RT-
flex60 and RT-flex68 engines is of the type PV6070 and the larger Dynex pump used on the
RT-flex84 and RT-flex96 engines is of the type PV7190. Both pumps use an identical system
of operation to regulate the servo-oil system pressure and flow, however, some significant
differences exist between the pump controls concerned. Additionally, there are several small
differences in the execution of the smaller PV6070 pumps.
2 Description of Process
The Dynex pumps operate using a fixed-stroke, axial piston system, whereby the stroke of all
the pistons is always the same, irrespective of the flow output of the pump. The flow into
each cylinder is controlled by a pair of check-valves, the inlet check-valve and the bypass
valve. The flow out of each cylinder is controlled by the outlet check valve and the bypass
valve. Figure 1 presents the system of operation.
Proportional valve
Orifice 1
Orifice 2
Control circuit
safety valve
Orifice 3
Regulating space
= =
Page: 2 / 11
Date: 17/08/2006=
Outlet check-valve:
• Located at the top of each cylinder, these allow for oil at high pressure to pass to the
high-pressure side of the pump during the compression stroke of the piston. If the
cylinder pressure is lower than the outlet pressure of the pump, no flow through this
valve will take place.
Bypass check-valve:
• Located next to the outlet check valve of each cylinder, this valve controls whether the
oil in the cylinder is returned to the low-pressure side of the pump or is forced out of
the high-pressure side of the pump during the compression stroke of the cylinder.
• This valve can be held off its seat by the control pressure of the pump, which is
regulated by the pump compensator, however, once it shuts it will not re-open until the
end of the compression cycle, as the high cylinder pressure will force the valve to
remain shut.
• As this valve will not open again once it has closed during the compression stroke of
the piston, the flow which is forced through the outlet check-valve is controlled by the
position of the piston when this valve touches its seat. If this valve touches its seat
very early in the compression stroke of the piston, the flowrate of the pump will be
near maximum, if this valve touches its seat when the piston is at the end of its
compression stroke, the flowrate from the pump will be near minimum.
• Clearly the control pressure of the pump regulates at what time during the
compression stroke the bypass check-valve opens and closes, which in turn regulates
the output flow from the pump. If the control pressure is high (more than around 5bar
relative to the inlet pressure of the pump), the pump will deliver no flow at all. If the
control pressure is low, the pump will deliver with maximum flow. The control pressure
of the pump is controlled by the pump compensator, which is the primary focus of
discussion in this document.
If the pump outlet pressure is high enough, the oil will force its way through the proportional
valve (the force from the proportional valve depends upon the electrical pressure setpoint of
the pump) and into the control circuit of the pump. The pressure in the control circuit is
maintained as a balance between the flow through the proportional valve and another orifice
(orifice 2) to the pump inlet pressure (drain). One more orifice (orifice 3) between the pump
compensator and the pushrods for the bypass check-valves does not regulate the pressure
so much as the response speed of the pump. In this way, the control pressure of the pump is
a balance of the electrical current to the proportional valve and the outlet pressure of the
pump.
In the event that very high pump pressure occurs, (for example if the proportional solenoid
current is too high), the overpressure safety valve will open and oil will pass directly to the
control circuit and reduce the pump flow. In this case, the proportional valve is short-
circuited. The larger 7190 pumps have a device to open this valve and dump the pump
pressure in the event of a problem such as a cracked high pressure pipe. This device,
called a “dump valve”, can be used to reduce the outlet pressure of the pump to the
inlet pressure plus about 10bar.
These are the only possibilities available for Dynex-type pumps, as installed on Wärtsilä’s
RT-flex engines.
Overpressure safety
valve setpoint.
DO NOT ADJUST
Dump valve
(yellow) 22mm
Main body of
valve
To return the pump to its normal operating condition, simply tighten the dump valve
again.
and setting of the maximum delivery pressure is not disturbed. Figure: 3 shows how to
unscrew the overpressure valve housing.
Control circuit
safety valve
Figure: 3 – Unscrewing the overpressure safety valve housing (compensator block is shown removed
from pump with solenoid removed). Unscrewing this housing by not more than 2 full turns will reduce
the maximum delivery pressure of the pump to approximately 15bar. Access to this valve housing is
quite limited, so it is recommended to use an open-ended spanner (not a ring spanner, as shown). The
valve housing size is 7/8” A.F., some 22mm spanners may also fit. Do not confuse this valve housing
with the control circuit safety valve (shown with two locknuts)!
2. The delivery pressure of either the big PV7190 pump or the smaller PV6070 pump can
be set to maximum (approximately 240bar) by turning in the adjusting screw at the top
of the solenoid as far as possible. Care must be taken that the adjusting screw is not
made too tight, which may damage the valve seat. This is shown in figure:4.
Control circuit
safety valve –
Caution when
removing,
7.14mm ball
can be easily
lost!
Figure: 4 – Forcing the pump to deliver at full flow up to maximum pressure (approx 240bar) can be
achieved by screwing in the adjusting screw as shown as far as possible. Care must be taken not to
overtighten the screw, damage to the valve seat can result. The process is the same for both PV6070
and PV7190 pumps. On very early versions of the smaller PV6070 pumps, this screw is the minimum
pressure setpoint of the pump.
When loosening the adjusting screw again, the screw position is not critical, it must
only be screwed well away from the valve seat (approximately 2 full turns is enough).
The locknut must always be tightened to hold the final solenoid position.
3. The minimum pressure setpoint of the pump is adjusted as shown in Figure: 5. This
requires a 3/16” Allen key (no metric key will fit) and a 9/16” spanner (an adjustable
spanner and some 14mm spanners will also work).
Figure: 5 – Adjusting the minimum pressure setpoint of the pumps (shown in figure is the larger PV7190
pump compensator assembly). On very early versions of the smaller PV6070 pumps, this adjustment point
did not exist and the minimum pressure was adjusted as shown in figure 4.
Filter cavity
(top of PV7190
compensator
assembly).
Plug (10mm
hex), spring
and filter.
Figure: 6 – Removing the compensator filter (approx. 50µm) installed in the DynexPV7190 pumps. The dirt
trapped in this filter gives a lot of information about the effective level of filtration normally applied to the engine
in service. In normal operation, this filter should be completely clean. The smaller PV6070 pumps do not have
this filter and are thus much more susceptible to the ingress of dirt.
It is also possible that changes to the WECS control system can change the pressure
response and/or control of the Dynex pumps. For this reason, any flow balancing and/or
testing of the Dynex pumps should be done with the electrical cables removed from
the pumps, if possible.
This following table deals with different Dynex control problems and how to fix them. Due to
the small and critical nature of the parts concerned, it is highly recommended that the
pump compensator is removed from the pump before disassembly.
Figure: 7a – Removing Orifice 2 from the PV7190 (big Figure: 7b – Removing Orifice 2 from the PV6070
Dynex pump) compensator. View is from the (small Dynex pump) compensator. Yellow plastic plug
underside of the pump compensator. Hex key size is (as shown) or plugging screw must be removed for
Figure: 8a – Removing Orifice #1 from the PV7190 Figure: 8b – Removing Orifice #1 from the transfer
(big Dynex pump) compensator. Hex key size is tube located between the control plate and the pump
5/64”. on the PV6070 (small Dynex pump). Hex key size is
5/64”. Please note that in normal practice it is possible
to clean the orifice without removing it from the
transfer tube.
See symptom B1 in the troubleshooting table for reference to the pictures above.
Figure: 9a – Removing Orifice #3 from the PV7190 Figure: 9b – Removing Orifice #3 from the control
(big Dynex pump) compensator. Hex key size is plate of the smaller PV6070 pump. On the other side
5/64”. of this screw is the regulating space of the pump.
See symptom D1 in the troubleshooting table for reference to the pictures above.