Download as pdf or txt
Download as pdf or txt
You are on page 1of 54

iFlow (UL/FM)

300 bar Inergen Systems


C e r t i f i c a t i o n Tr a i n i n g

Hydraulic Flow
Calculation
Software
BKR-1605b
Preparation

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 2


Preparation

• Confirm design details


• Design standard
• Design concentration
• Design temperature
• Altitude
• Hazard details (dimensions/voids)

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 3


Preparation

• Prepare a pipe isometric


• length and elevation for
all sections
• node points

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 4


Hydraulic Workflow
Access

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 5


Prerequisites

Must complete hazard review portion of estimator


Must be 300 bar, iFlow, Inergen system

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 6


Node Numbers

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 7


Node Numbers

• Node numbers are needed to identify pipe sections


• Node numbers ...
• 1 to 300 for pipe sections
• 301 to 499 for nozzles
• Node points ...
• where flow increases
• where flow splits
• where pipe size changes
• at pressure take off
• at every nozzle

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 8


Node Numbers

• Node points are located at the end of a section - before


a change happens

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 9


Node Numbers

• First section 1-2 cannot be changed


• section 1-2 includes horizontal check valve and discharge
hose

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 10


Node Numbers

Correct
Section 3 - 4
Section 4 - 301

Error
Section 3 - 301

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 11


Node Numbers

Examples (80 litre container)


120 s discharge only
3 4

2 3
1 2 1

No. of Hose / No. of Hose /


Section Fitting Section Fitting
Cont. Pipe Cont. Pipe
1-2 1 H 1-2 1 H
2-3 2 H 2-3 2 H
3-4 3 H

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 12


Node Numbers

Examples (80 litre container)


4 3
4
3

2 2

1 1

No. of Hose / No. of Hose /


Section Fitting Section Fitting
Cont. Pipe Cont. Pipe
1-2 1 H 1-2 1 H
2-3 2 H 2-3 2 H
3-4 3 P Side T 3-4 4 P Side T

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 13


Node Numbers

Examples (80 litre container)


No. of Hose /
120 s discharge only Section Fitting
Cont. Pipe
1-2 1 H
5 2-3 2 H
3-4 3 H
4-5 6 P Side T
3
4
2 1

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 14


Node Numbers

Examples (80 litre container) 120 s discharge only

4 5 6 7

4 3 2 1
1
iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 15
Node Numbers

Examples (80 litre container) 120 s discharge only

4 5 6 7

No. of Hose /
Section Fitting
3 Cont. Pipe
1-2 1 H
2-3 2 H
3-4 3 H
2 4-5 3 P 370 90° L
5-6 6 P 370 Thru T
6-7 8 P 370 Thru T
4 3 2 1
1
iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 16
Node Numbers

Examples (80 litre container) 120 s discharge only

4 5 6 7 8 9 10

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 17


Node Numbers

Examples (80 litre container) 120 s discharge only

4 5 6 7 8 9 10
No. of Hose /
Section Fitting
Cont. Pipe
1-2 1 H
3 2-3 2 H
3-4 3 H
4-5 3 P 370 90° L
2 5-6 6 P 370 Thru T
6-7 9 P 370 Thru T
7-8 12 P 370 Thru T
8-9 15 P 370 Thru T
1 9-10 18 P 370 Thru T

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 18


Node Numbers

Examples (80 litre container) 120 s discharge only

4 5

3 No. of Hose /
Section Fitting
Cont. Pipe
1-2 1 H
2 2-3 2 H
3-4 3 H
4-5 18 P 1750

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 19


Node Numbers

Examples (80 litre container) 11

10
9

120 s discharge only


8

5 3 2
1
4
iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 20
Node Numbers

Examples (80 litre container)


No. of Hose /
Section Fitting
Cont. Pipe
1-2 1 H
2-3 2 H
3-4 3 H
4-5 3 P 370 90° L
5-6 6 P 370 Thru T
6-7 9 P 370 Thru T
7-8 12 P 370 Thru T
8-9 15 P 370 Thru T
9-10 18 P 1300 Thru T
10-11 36 P 300 Side T

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 21


Node Numbers

Nozzle Node Numbers


• No. 301 to 499 are reserved numbers for nozzles
• These numbers must not be used anywhere else

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 22


The Software

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 23


Run Management

“Runs” = Save Files


Each is an independent hydraulic evaluation
Simultaneous Discharge: Runs per project
Selector Valve System: Runs per hazard

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 24


Run Management

“Runs” = Save Files


Each is an independent hydraulic evaluation
Simultaneous Discharge: Runs per project
Selector Valve System: Runs per hazard

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 25


Steps

Hydraulic Options
-Confirm basic data from estimator phase

Nozzle Configuration
-Assign nozzles to hazards / volumes
-Assign agent quantity / orifice diameters

Pipe Data
-Input and review pipe sections

Results
-Review results of hydraulic calculation
-Generate report

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 26


Hydraulic Options

Confirm / Adjust basic design parameters

Major adjustments should be performed via Estimator for best results

Select FVA calculation type, run type, etc…

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 27


Hydraulic Options

Confirm / AdjustNozzle Type


basic design parameters
 Agent Quantity
Major adjustments should be performed via Estimator for best results
= automatic results based on
Select FVA calculationagent
type, runquantity
type, etc…

 Fixed Nozzle
= pipe and nozzle details must
be known, software checks
hydraulic only (existing
system)

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 28


Nozzle Configuration

Automatically assigns based on estimator quantities

Can be adjusted however is desired

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 29


Nozzle Configuration

Help functionality:
Re-Number Nozzles
-Re-numbers all nozzles starting at 301 from Ceiling Void -> Room -> Floor Void

Re-Generate Nozzles:
-Generates nozzles with agent quantities based on estimator parameters again
-WARNING: Overwrites any changed data

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 30


Nozzle Configuration

Values are editable in-table

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 31


Nozzle Configuration

Some built-in error checking provided:

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 32


Nozzle Configuration

Can edit multiple entries at once:

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 33


Pipe Data

In-table editing is available

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 34


Pipe Data

Adding new sections

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 35


Pipe Data

Helper functionality: List all nozzles, their locations, and whether or not they
have been assigned in the Pipe Data table

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 36


Pipe Data

Helper functionality: Duplicate pipe data from another Run in the same project
WARNING: Overwrites current pipe data

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 37


Limits

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 38


Limits

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 39


Limits

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 40


Start Flow Calculation

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 41


Wait For Results

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 42


Calculation Report

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 43


Hazard Results

Time to achieve 95% of the required design concentration

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 44


Pressure Drop Results

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 45


Discharge Results

Time to discharge 95%


of the agent stored

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 46


Nozzle Performance

(see Ansul iFlow Nozzle Drill Size Chart)

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 47


Messages

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 48


Save With Fixed Pipe And Nozzles

Convert to Fixed Nozzle: Store resulting pipe sizes, schedules, orifice diameters
in current hydraulic run.

Create Fixed Nozzle Run: “Save As”, stores resulting pipe sizes, schedules, orifice
diameters in a new copy of the current hydraulic run.

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 49


Save With Fixed Pipe And Nozzles

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 50


Save With Fixed Pipe And Nozzles

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 51


Save With Fixed Pipe And Nozzles

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 52


Save With Fixed Pipe And Nozzles

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 53


Thank You For Your Attention!

iFlow (UL/FM) 300 bar Inergen - Hydraulic Software 54