Professional Documents
Culture Documents
3350-1 - DS - 20240321 Datasheet
3350-1 - DS - 20240321 Datasheet
Automation Controller
Powerful and Flexible Industrial
Automation and Computing Platform
Product Overview
w
q e r t y u i o a
s d g h j k ;
q
q e r t y u i o
f 1*
g
2)
s d h j k
Features
The SEL-3350 is a rugged, easy-to-use automation con- Ethernet. Five Ethernet ports provide high-speed net-
troller designed for substation, industrial, or other harsh work connectivity through five independent
environments. The following features are included in the Ethernet controllers, enabling connections to
system: independent networks or redundant paired net-
work connections. The front Ethernet port pro-
x86-64 Architecture. The Intel Atom microprocessor vides quick and secure engineering access
architecture delivers high performance and broad
without connecting to the local network. Select
operating system and software compatibility.
from RJ45 copper and small form-factor plugga-
Four processor cores and 8 GB of RAM enable
ble (SFP) fiber-optic interfaces for the rear ports.
running multiple time-critical applications simul-
taneously. Serial I/O. With 16 EIA-232/422/485 serial ports stan-
dard and optional expansion to 48 ports (3U chas-
Operating System Choices. You can purchase the sis only), the SEL-3350 can communicate with
SEL-3350 with or without one of the optional
many electronic devices, such as automation con-
operating systems, like SEL RTAC,
trollers, protective relays, communications
SEL Blueframe, or Microsoft Windows, to add radios, and modems. Each port provides IRIG-B
flexibility, functionality, and security. time distribution to the connected devices.
Form Factor. The 19-inch rack-mount chassis is IRIG-B Input/Output. Synchronize the system time to a
designed for substation and industrial control
satellite clock by using the high-precision
applications. The system includes I/O connec-
IRIG-B input. Distribute IRIG-B to downstream
tions for linking to networks, peripherals, storage, devices by using the IRIG-B output and serial
video, alarm, and serial I/O—all with protection ports.
against electrical shock and surge.
Contact Inputs. The SEL-3350 includes one univer-
Power Supply. A wide range of ac/dc power supplies sal contact input (IN101) and supports an
provide compatibility with a variety of power optional contact I/O board (3U chassis only) that
sources. The 1U chassis has a single built-in provides 24 additional contact inputs. These con-
power supply, while the 3U chassis supports two
figurable, wide-range inputs can be used to moni-
replaceable power supply modules for redundant
tor status changes in switches and contact
power sources.
outputs. The universal contact input can also be
Mass Storage. The SEL-3350 contains two 2.5-inch used to measure actual voltage for applications,
SATA drive slots that support field-servicing. like battery monitoring.
High-performance, industrial-rated, solid-state
Contact Outputs. The SEL-3350 includes one Form C
drives (SSD) are available as ordering options.
contact output (OUT101) and supports an
Display Interface. A single DisplayPort interface optional contact I/O board (3U chassis only) that
enables connecting to as many as three indepen- provides eight additional Form A contact outputs.
dent high-definition displays simultaneously via The OUT101 output is normally controlled by the
DisplayPort Multi-Stream Transport (MST). Dig- SEL-3350 system alarm to notify external
ital audio can be streamed through the Display- devices when the SEL-3350 is experiencing
Port interface for simple integration and high- abnormal operating conditions. Reconfigure the
definition surround-sound. OUT101 contact to control it with automation
logic.
USB Connectivity. Front- and rear-panel USB ports
provide connections to keyboards, mice, and Watchdog. If a system lockup is detected, the watch-
many other USB peripherals. Each port has a dog can trigger a system reboot in order to
current-limiting function to protect the system attempt to return to a normal operating state.
from external short circuits while still supporting Remote Management. The SEL-3350 supports remote
high-power USB devices. access over Ethernet.
Applications
The SEL-3350 is an extremely versatile and powerful automation controller that may be used for many applications. You
can customize the SEL-3350 with factory-installed options and/or third-party software to meet the requirements of your
application. Several of the most popular applications are listed in Table 1 and shown later in this section.
Application Description
Intelligent Port switch Connects a single serial port to multiple serial ports.
Network Gateway Connects a single network port to multiple serial ports.
Protocol Gateway Connects multiple systems that use different protocols.
Application Description
Time-Synchronization Source Selects the best time from different sources and provides either or both IRIG-B and
Network Time Protocol (NTP) outputs to connected devices.
Synchrophasor Processor Connects phasor measurement unit (PMU) data to other devices and processes through
protocol conversion.
SCADA Data Concentrator (Remote Terminal Unit Monitors digital and analog inputs to transmit to a central location with standard
(RTU)/Programmable Logic Controller (PLC)) SCADA protocols.
Security Gateway Provides firewall protection to incoming Ethernet communication as well as encryp-
tion for individual Ethernet sessions.
Logic Processor (Automation) Monitors digital and analog inputs to transmit to a central location. It also performs
IEC 61131-3 logic.
SEL-3350
•••
Network Gateway
The SEL-3350 comes standard with four rear Ethernet ports that you can configure to make serial-connected devices
available to high-speed networks. The optional SEL RTAC operating system supports virtual terminal connections
through the Ethernet ports. For example, you can establish secure Telnet sessions and communicate with an intelligent
electronic device (IED) through an SEL-3350 with the SEL RTAC operating system. An example of this application is
shown in Figure 2.
Figure 2.2
Engineering
GPS Clock
SEL-3350
•••
Protocol Gateway
Collect downstream data with client protocols and send these data to your upstream HMI, RTU, or SCADA master with
server protocols, converting the data from one protocol to another in the process. The SEL-3350 is great for data concen-
tration when combined with the optional SEL RTAC operating system that provides multitasking/multiuser and data
handling capabilities. An example of this application is shown in Figure 3.
Figure 2.3
SCADA
GPS Clock
SEL-3350
Modbus Ethernet
Serial SEL ASCII Switch
DNP3
DNP3
IEC 61850
••• Modbus
Time-Synchronization Source
Synchronize the time clocks in attached devices that accept a demodulated IRIG-B time signal. The demodulated
IRIG-B signal is regenerated in the SEL-3350 from an external modulated or demodulated source, such as a GPS satel-
lite clock receiver or other serial or Ethernet communications. If an external clock source is not available, the SEL-3350
generates an IRIG-B signal from its internal clock, allowing device synchronization to a common clock for improved
sequence-of-events analysis. An example of this application is shown in Figure 4. The system time may also be set on
the SEL-3350 from a Simple Network Time Protocol (SNTP) source, a Network Time Protocol (NTP) source, or a Pre-
cision Time Protocol (PTP) source.
Figure 2.4
•••
Synchrophasor Processor
Move synchrophasor data to SCADA operations centers by using standard protocols, such as DNP3. Include time stamps
and time quality in the SCADA message to allow for system-wide use of synchrophasor data. With the logic engine in
the optional SEL RTAC operating system, you can perform complex math and logic calculations on synchrophasor data
collected from SEL relays and other IEEE C37.118-compliant devices. An example of this application is shown in
Figure 5.
Figure 2.5
Local HMI
GPS Clock
SEL-3350
•••
Local HMI
Engineering SCADA
Ethernet Switch
GPS Clock
SEL-3350
Modbus
Serial SEL ASCII
DNP3
DNP3
IEC 61850
••• Modbus
Security Gateway
Combine the SEL-3350 with a secure operating system like the SEL RTAC operating system and third-party application
software that can provide secure engineering access and other Ethernet tunneled serial communications on the automa-
tion network with SSL/TLS or SSH encryption. Implement system security auditing, logging, and password restrictions
to enforce NERC standards. Comply with role-based requirements by implementing per-user security profiles. Option-
ally incorporate serial and wireless encrypting devices to further secure communication to any device. An example of
this application is shown in Figure 7.
Figure 2.7
SCADA
Engineering
SSH, TLS Encryption, and
User Account Management
GPS Clock
SEL-3350 Ethernet
Switch
Sensors
- Door
- Panel/Cabinet
Serial - Motion
Encryption - Fence
...
Alarms
- Visible
- Audible
- Lighting
...
Engineering
Ethernet Switch
TX AUX1
1 2 3 4 1 2 3 4 5 6 7 8
ENABLED LNK RX AUX2
LAMP ALARM TX TX AUX3
TEST 9 10 11 12 13 14 15 16
HDD RX RX AUX4
ETH F USB A
COM 9 COM 10 COM 11 COM 12 COM 13 COM 14 COM 15 COM 16 ETH 2 ETH 4 IN IRIG-B OUT POWER GND
_ A07
/H /N
A01 A02 A03 A04 A05 A06
+
USB 5 USB 6
IN101 NC OUT101
190-4563-01
DISPLAYPORT USB 3 USB 4 COM 1 COM 2 COM 3 COM 4 COM 5 COM 6 COM 7 COM 8 ETH 1 ETH 3 A 08 09 10 11 12 13 A
i7225d
SCHWEITZER
ENGINEERING SEL–3350
LABORATORIES
TX
33 34 35 36 37 38 39 40
RX
TX
41 42 43 44 45 46 47 48
RX
TX
17 18 19 20 21 22 23 24
RX
TX
25 26 27 28 29 30 31 32
RX
TX AUX1
1 2 3 4 1 2 3 4 5 6 7 8
ENABLED LNK RX AUX2
LAMP ALARM TX TX AUX3
9 10 11 12 13 14 15 16
TEST HDD RX RX AUX4
ETH F USB A
IN04 IN05 IN06 IN07 IN08 IN09 IN10 IN11 IN12 COM IN16 IN17 IN18 IN19 IN20 IN21 IN22 IN23 IN24 COM
OUT01 OUT02 OUT03 OUT04 OUT05 OUT06 OUT07 OUT08 IN01 IN02 IN03 IN13 IN14 IN15 200
200 HS HS HS HS
B 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 B
COM 33 COM 34 COM 35 COM 36 COM 37 COM 38 COM 39 COM 40 COM 41 COM 42 COM 43 COM 44 COM 45 COM 46 COM 47 COM 48 P SEL–9325
O POWER
W POWER SUPPLY
E NC NC NC NC + –
/H /N
R 01 02 03 04 05 06
A Power Supply 125–250V
110–240V 50/60Hz
Maximum Burden 62W,150VA
159-1502.A
COM 17 COM 18 COM 19 COM 20 COM 21 COM 22 COM 23 COM 24 COM 25 COM 26 COM 27 COM 28 COM 29 COM 30 COM 31 COM 32
P GND
07 190-3558-01
O
IN IRIG-B OUT W
COM 9 COM 10 COM 11 COM 12 COM 13 COM 14 COM 15 COM 16 ETH 2 ETH 4 E SEL–9325 POWER
R POWER SUPPLY
USB 5 USB 6
B NC NC NC NC + /H – /N
01 02 03 04 05 06
IN101 NC OUT101
Power Supply 125–250V
GND 110–240V 50/60Hz
DISPLAYPORT
Maximum Burden 62W,150VA
159-1502.A
USB 3 USB 4 COM 1 COM 2 COM 3 COM 4 COM 5 COM 6 COM 7 COM 8 ETH 1 ETH 3
A01
A02
A03
A04
A05
A06
A07 GND
07 190-3558-01
i7174a
9.43 9.44
[239.5] [239.8]
1.01 1.00
[25.7] TOP [25.4] TOP
19.00 19.80
[482.6] 1.25
[502.9]
[31.8]
SIDE
4X Ø.25
17.63 [Ø6.4]
LEGEND [447.8]
in
[mm]
1.80 1.25
18.31 [31.8]
[45.7]
[465.1]
RACK MOUNT
9.55
[242.6] TOP
0.96
[24.3] 19.00
[482.6]
5.22 2.25
FRONT SIDE
[132.6] [57.2]
18.31
[465.1]
LEGEND
in
[mm] i9416a
PANEL MOUNT
9.38
[238.2] TOP
1.13
[28.7]
19.80
[502.9]
6.65
FRONT SIDE
[168.9]
17.75 4X Ø0.25
[450.9] [Ø6.4]
5.50 2.25
PANEL CUTOUT
[139.7] [57.1]
LEGEND
18.31
in [465.1]
[mm] i9415a
Specifications
Introduction
SEL-3350 and Automation
Specifications Controller
Compliance Network Time Protocol (NTP) Modes
NTP Client: As many as three configurable servers
Designed and manufactured under an ISO 9001 certified quality
management system NTP Server
47 CFR 15B Class A Simple Network Time Protocol (SNTP) Accuracy
This equipment has been tested and found to comply with the limits ±1 ms: This does not take into account external
for a Class A digital device, pursuant to part 15 of the FCC Rules. factors such as network switches and
These limits are designed to provide reasonable protection against topologies.
harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and can Precise Time Protocol (PTP)
radiate radio frequency energy and, if not installed and used in
PTP Client: Peer delay request and end-to-end path
accordance with the instruction manual, may cause harmful
delay supported
interference in which case the user will be required to correct the
interference at his own expense. Operating Environment
UL Listed to U.S. and Canadian safety standards Operating Temperature
(File E220228; NRAQ) Range: –40° to +85°C (–40° to +185°F)*
CE Mark * Requires Industrial-Grade SSDs. See SEL Application Note,
UKCA Mark “Determining Solid-State Drive (SSD) Lifetimes for SEL
Computing Platforms” (AN2016-03).
RoHS Compliant
Note: UL maximum ambient 40°C. See the instruction manual
General safety information for additional restrictions.
Configurations: 4 RJ45 copper ports Operational Voltage Range: 0–300 Vdc, 0–264 Vac, 45–65 Hz
4 SFP fiber-optic ports
Pickup/Dropout Level:
2 RJ45 and 2 SFP fiber-optic ports
Jumbo Frame MTU: 9000 bytes (Linux only)
Nominal Voltage
See Surge Immunity for cable length restrictions. Dropout Voltage Pickup Voltage
Setting
Serial
24 Vdc 0.0–14.4 Vdc 19.2–30.0 Vdc
SEL multiport serial controller
48 Vdc 0.0–28.8 Vdc 38.4–60.0 Vdc
EIA-232/422/485 Ports: 16 ports standard; 48 ports optional
RJ45 connectors 110 Vdc 0.0–66.0 Vdc 88.0–132.0 Vdc
300–115,200 bps
256 byte TX and RX FIFOs each port 125 Vdc 0.0–75.0 Vdc 105.0–150.0 Vdc
+5 Vdc port power 220 Vdc 0.0–132.0 Vdc 176.0–264.0 Vdc
COM 1–16:
0.5 A, 2.5 W, total 250 Vdc 0.0–150.0 Vdc 200.0–300.0 Vdc
COM 17–48:
1.0 A, 5 W, total 24 Vac 0.0–10.1 Vac 16.4–30.0 Vac
IRIG-B output
48 Vac 0.0–20.3 Vac 32.8–60.0 Vac
See Surge Immunity for cable length restrictions.
110 Vac 0.0–46.6 Vac 75.1–132.0 Vac
Time-Code Inputs and Outputs 120 Vac 0.0–53.0 Vac 89.6–150.0 Vac
Time-Code Inputs
220 Vac 0.0–93.2 Vac 150.3–264.0 Vac
One BNC IRIG-B Input
240 Vac 0.0–106.0 Vac 170.6–264.0 Vac
Format: IRIG-B002 or -B004 (demodulated)
On (1) State: Vih 2.2 V Pickup/Dropout Delay 2–4000 ms @ >24 Vdc/Vac
Setting Range: 4–4000 ms @ 24 Vdc/Vac
Off (0) State: Vil 0.8 V
Continuous Current Draw: 1.0–4.0 mA
Nominal Input Impedance: 3.3 k
Initial Current Draw: <170 mA for 2 ms @ >24 Vdc/Vac
Note: IRIG-B004 control bits comply with IEEE C37.118.1-2011
<170 mA for 4 ms @ 24 Vdc/Vac
(reverse compatible with IRIG-B000 and IEEE C37.118-2005).
Fuse Ratings IN201–IN224 (F1–F24)
Time-Code Outputs
Type: 3x10.1 mm Time-Lag T
One BNC IRIG-B Output, All RJ45 Serial Ports
Current Rating: 0.160 A
Format: IRIG-B004 (demodulated)
Voltage Rating: 250 Vac/Vdc
On (1) State: Voh 2.4 V
Breaking Capacity: 20 A @ 250 Vac/Vdc
Off (0) State: Vol 0.8 V
Note: These fuses are not serviceable.
Output Drive Capacity
Standard Contact Outputs OUT101, OUT205–OUT208
BNC IRIG-B Out: TTL 240 mA (>20 )
Output Type: OUT101/Alarm:
Each Serial Port: TTL 6 mA (>400 )
Relay Form C Break Before Make
Note: IRIG-B004 control bits comply with IEEE C37.118.1-2011 OUT205–OUT208:
(reverse compatible with IRIG-B000 and IEEE C37.118-2005). Relay Form A
Contact Inputs and Outputs Pilot Duty Ratings*: B300 (UL), AC-15 (IEC)
R300 (UL), DC-13 (IEC)
Universal Contact Input IN101 (Bipolar Operation) Rated Voltage**: 24–250 Vdc
Rated Voltage Range: 24–250 Vdc, 24–240 Vac, 50/60 Hz 110–240 Vrms
Operational Voltage Range: 0–300 Vdc, 0–264 Vac, 45–65 Hz Note: The voltage across any of the contact output terminals must not
exceed the operational voltage.
DC Measurement
Accuracy*: ±0.5%, ±250 mV Operational Voltage**: 0–300 Vdc
0–264 Vrms
AC Measurement
Accuracy*: ±2.5%, ±500 mV Contact Protection: MOV protection across open contacts
264 Vrms continuous voltage
RMS Filter Period: 1s 300 Vdc continuous voltage
Pickup/Dropout Level Continuous Carry**: 6 A @ 70°C, 4 A @ 85°C
Setting Range: 15–265 Vdc/Vac rms
Pickup/Dropout Time**: 6 ms (resistive load)
Pickup/Dropout Delay
Setting Range: 0–4,000 ms** Power Supply Burden**: 1 W
Continuous Current Draw: 1.0–4.0 mA @ > 24 Vdc/Vac Mechanical Endurance**: 10,000 no-load operations
Initial Current Draw: <50 mA for < 8 ms Make (Short Duration 30 Adc
* Intended as a measurement function only. Contact Current)**: 1,000 operations @ 250 Vdc
2,000 operations @ 125 Vdc
** Type tested with delay settings of 8 ms at < 48 V and 2 ms at 48 V.
Note: 200 ms on, 15 ms off, current interrupted by independent means.
Standard Contact Inputs IN201–IN224 (Bipolar Operation)
Short-Time Thermal
Input Type: IN201–IN203, IN213–IN215 Withstand**: 50 A for 1 s
electrically isolated, dedicated returns
IN204–IN212, IN216–IN224 Limiting Making
electrically isolated, common returns Capacity**: 1,000 W @ 250 Vdc (L/R = 40 ms)
250 Vdc 0.20 Adc 0.20 Adc Medium Voltage 48–125 Vdc or 110–120 Vac
Voltage Rating: 48–125 Vdc, 110–120 Vac
110 Vrms 0.30 Arms 0.30 Arms
Operational Voltage Range: 38–140 Vdc, 85–140 Vac
240 Vrms 0.20 Arms 0.20 Arms
Frequency Rating: 50/60 Hz
* Per UL 508 and IEC 60947-5-1 for IEC 61010-2-201 compliance.
Operational Frequency
** Parameters verified by SEL per IEC 60255-1:2009 and
Range: 30–120 Hz
IEEE C37.90-2005.
Interruption*: 50 ms @ 48 Vdc,
Fast Hybrid Contact Outputs OUT201–OUT204 500 ms @ 125 Vdc/110 Vac
Output Type: OUT201–OUT204; Fast Hybrid, Form A High Voltage 125–250 Vdc or 110–240 Vac
Pilot Duty Ratings*: B300 (UL), AC-15 (IEC) Voltage Rating: 125–250 Vdc, 110–240 Vac
R300 (UL), DC-13 (IEC)
Operational Voltage Range: 85–300 Vdc, 85–264 Vac
Rated Voltage**: 24–250 Vdc
Frequency Rating: 50/60 Hz
Note: The voltage across any of the contact output terminals must not
exceed the operational voltage. Operational Frequency
Range: 30–120 Hz
Operational Voltage: 0–300 Vdc
Interruption*: 100 ms @ 125 Vdc/110 Vac
Contact Protection: MOV protection across open contacts 500 ms @ 250 Vdc/220 Vac
300 Vdc continuous voltage
Peak Inrush: 5.4 A for 36 ms @ 125 Vdc
Continuous Carry**: 6 Adc @ 70°C, 4 Adc @ 85°C 10.9 A for 49 ms @ 250 Vdc
Pickup Time**: 50 µs (resistive load) 6.7 A for 45 ms @ 110 Vac (156 Vdc)
14.6 A for 53 ms @ 240 Vac (339 Vdc)
Dropout Time**: 8 ms (resistive load) * Tested per IEC 60255-26:2013 with a typical workload.
Power Supply Burden**: <1 W
Recommended External Overcurrent Protection
Mechanical Endurance**: 10,000 no-load operations
Breaker Type: Standard
Make (Short Duration 30 Adc
Contact Current)**: 1,000 operations @ 250 Vdc Breaker Rating: 20 A @ 250 Vdc
2,000 operations @ 125 Vdc Current Breaking Capacity: 10 kA
Note: 200 ms on, 15 ms off, current interrupted by independent means. Grounded Neutral Systems: Device in series with the energized
Short-Time Thermal conductor
Withstand**: 50 Adc for 1 s DC and Isolated Systems: Device in series with both conductors
Limiting Making
Capacity**: 1,000 W @ 250 Vdc (L/R = 40 ms)
Fuse Ratings
Limiting Breaking 10,000 operations Low-Voltage Power Supply F1
Capacity/Electrical 4 operations in 1 s, followed by 2 min Type: 5x20 mm Time-Lag T
Endurance**: idle
Current Rating: 5.0 A
* PerUL 508 and IEC 60947-5-1 for IEC 61010-2-201 compliance.
Voltage Rating: 150 Vdc
** Parameters verified by SEL per IEC 60255-1:2009 and
IEEE C37.90-2005. Breaking Capacity: 1,500 A @ 150 Vdc
Medium-Voltage Power Supply F1
Rated Voltage Resistive Break Inductive Break Type: 5x20 mm Time-Lag T
24 Vdc 10 Adc 10 Adc (L/R = 40 ms) Current Rating: 3.15 A
48 Vdc 10 Adc 10 Adc (L/R = 40 ms) Voltage Rating: 250 Vac, 300 Vdc
Breaking Capacity: 1,500 A @ 250 Vac, 300 Vdc
125 Vdc 10 Adc 10 Adc (L/R = 40 ms)
High-Voltage Power Supply F1
250 Vdc 10 Adc 10 Adc (L/R = 20 ms)
Type: 5x20 mm Time-Lag T
Current Rating: 3.15 A
Power Supplies
Voltage Rating: 250 Vac, 300 Vdc
General
Breaking Capacity: 1,500 A @ 250 Vac, 300 Vdc
Typical Burden*: 20 W, 45 VA (pf = 0.4)
Maximum Burden*: 62 W, 150 VA (pf = 0.4)
DC Ripple: 15% per IEC 60255-26:2013
Technical Support
We appreciate your interest in SEL products and services. If you have questions or comments, please contact us at:
Schweitzer Engineering Laboratories, Inc.
2350 NE Hopkins Court
Pullman, WA 99163-5603 U.S.A.
Tel: +1.509.338.3838
Fax: +1.509.332.7990
Internet: selinc.com/support
Email: info@selinc.com
*PDS3350-01*
This product is covered by the standard SEL 10-year warranty. For warranty details, visit
selinc.com or contact your customer service representative.