Professional Documents
Culture Documents
181-10062 3-06-2015 HB PVmasterII-III User-Manual en
181-10062 3-06-2015 HB PVmasterII-III User-Manual en
For users
–– Observer
–– Fitter
–– Expert
NOTE
This manual describes the operator application (web application) for all
PVMaster II and PVMaster III units. The general term „PVMaster“ is used in
the following in order to simplify the whole documentation.
No.: 181-10062
Date: 06/2015
Revision: 3
Translation: 0.3
Software versions
2 PVMaster
Table of contents
2 Safety 9
3 Introduction 11
4.2.9 Navigation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.2.10 Device states . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.3 Menu options and user interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.3.1 Overview (start user interface). . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.3.2 Status and values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.3.2.1 State. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.3.2.2 InterCOM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4.3.2.3 PV generator (DC side) . . . . . . . . . . . . . . . . . . . . . . . . 52
4.3.2.3.1 DC values. . . . . . . . . . . . . . . . . . . . . . . . . . 52
4.3.2.3.2 Generator scan. . . . . . . . . . . . . . . . . . . . . . 55
4.3.2.3.3 String currents. . . . . . . . . . . . . . . . . . . . . . . 56
4.3.2.4 Grid. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4.3.2.4.1 AC values . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4.3.2.4.2 Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
4.3.2.4.3 Limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
4.3.2.4.4 Energy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
4.3.2.4.5 Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . 73
4.3.2.5 Temperatures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
4.3.2.6 Inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
4.3.2.6.1 Digital inputs. . . . . . . . . . . . . . . . . . . . . . . . 82
4.3.2.6.2 Digital outputs. . . . . . . . . . . . . . . . . . . . . . . 84
4.3.2.6.3 Analogue inputs. . . . . . . . . . . . . . . . . . . . . . 85
4.3.3 History and statistics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
4.3.3.1 Day. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
4.3.3.1.1 Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
4.3.3.1.2 String currents. . . . . . . . . . . . . . . . . . . . . . . 93
4.3.3.2 Month. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
4.3.3.3 Year . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
4.3.3.4 Total . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
4.3.4 Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
4.3.4.1 Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
4.3.4.1.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . 103
4.3.4.1.2 System clock. . . . . . . . . . . . . . . . . . . . . . . 110
4.3.4.1.3 Network. . . . . . . . . . . . . . . . . . . . . . . . . . . 112
4.3.4.2 Grid. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
4.3.4.2.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . 115
4.3.4.2.2 Energy. . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
4.3.4.2.3 Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . 124
4.3.4.2.4 Insulation monitoring
(or monitoring the grounding resistance). . 136
4.3.4.2.5 Limit (infeed/grid security management). . 141
4.3.4.3 Grid stabilisation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
4.3.4.3.1 Voltage (reactive power control for
static grid voltage stabilisation). . . . . . . . . 147
4.3.4.3.2 Frequency stabilisation. . . . . . . . . . . . . . . 156
4.3.4.3.3 LVRT (dynamic grid stabilisation) . . . . . . . 159
6 Index 247
WARNING
Failure to heed information flagged up by the word WARNING may lead to
serious or fatal injuries.
CAUTION
Failure to heed information flagged up by the word CAUTION may lead to
minor injuries.
ATTENTION
Failure to heed information flagged up by the word ATTENTION may lead to
damage to equipment.
The safety information and warning notices are accompanied by the following
signs:
REFERENCE
Reference to further documentation.
2 Safety
PVMaster Safety 9
Intended use
CAUTION
Risk of burns from hot components!
The heat sink of the inverter, the inductor, the transformer, the filters and the
fuses get hot during operation.
• Make sure that the components have cooled down to room temperature
before starting work.
• Alternatively, wear protective clothing and gloves when working near hot
components.
CAUTION
Risk of burns from hot cooling agent!
The cooling agent reaches high temperatures during operation.
• Make sure that the cooling agent has cooled down to room temperature
before starting work.
ATTENTION
Risk of damage to equipment if instructions are not followed!
• Compliance with the connection conditions and technical specifications is
mandatory.
• Pay attention to the standards for electrical installation, e.g. conductor
cross-sectional area, protective earth and earth connection.
• Follow the installation instructions relevant to the specific country in any
given case and comply with the requirements set out by the local energy
supply company.
• Do not touch electronic components or contacts. Components can be de-
stroyed by electrostatic discharge.
CAUTION
Hazard posed by electromagnetic fields!
Potential health hazard for people with pacemakers, metallic implants or hear-
ing aids.
• Such people should consult their doctor before working on a system with
inverters.
10 Safety PVMaster
General information about the application manual
3 Introduction
Example: PVMaster TT only Within the application manual, descriptions that only apply to certain PVMaster
device types are marked accordingly to the left of the descriptive text in ques-
tion.
PVMaster Introduction 11
User interfaces of the PVMaster
12 Introduction PVMaster
Using the operator application
4.1.1 Requirements
A PC with an internet browser is required to run the operator application. The
minimum requirements for the PC for running the operator application are listed
in Tab. 4.1.
The PC for running the operator application can be connected locally to the
device or network or it is operated easily through a corresponding remote data
transmission via the internet.
NOTE
A crossover Ethernet network cable (crossover cable) may be required to
establish a local connection between the PC and the device. Some network
adapters or network devices support automatic crossover (Auto-MDI-X), so a
non-crossover network cable may be sufficient.
http://192.168.36.1 or 192.168.36.1
If the operator application is first called up with the IP address of
the device in the internet browser used, or if its browser cache
was first deleted (section 4.1.2.1, p. 15), a display of the load-
ing process will first appear. The loading process can take up to
a few minutes depending on the quality of the connection, e.g. for
slow data transmission speeds (GSM etc.). The loading process is
significantly quicker for a local connection.
NOTE
If the operator application cannot be started in the internet browser, the set-
tings of the network adapter used for the local PC should be checked and
changed if necessary (e.g. the set IP address range). Changes to the settings
of the internet browser may also be necessary (settings of the local network,
proxy server settings, etc.).
A start dialogue then appears to automatically check the quality of the connec-
tion or manually select the change of user interface.
NOTE
If the operator application has already previously been called up with an identi-
cal IP address and if the browser cache has not been deleted (section 4.1.2.1,
p. 15), the loading process will be omitted and the start dialogue will be
displayed directly.
NOTE
The caching of the operator application and user data (e.g. for authentication
at higher user levels, see section 4.2.2.1, p. 21) is performed separately for
each connection, i.e. dependent on the IP address of the destination device.
For this reason, the operator application is completely reloaded next time it is
started following changes to the IP address of the destination device, for ex-
ample, if there are no application data in the browser cache for the connection
with this IP address. The caching of the operator application is also version-
specific; it is therefore completely reloaded as necessary following a software
update of the destination device (see section 4.3.4.1.1, p. 103).
NOTE
If there are problems with running the operator application, the temporary files
should be deleted manually via the internet browser settings and the applica-
tion memory should be deleted via the MS Silverlight configuration.
1) Further control elements are used (selection box, option field, activation field, etc.).
2) For details on the display text box see section 4.2.6.1, p. 25
3) For details on the configuration text box see section 4.2.6.2, p. 25
The main information on the current device status and the key current values
are shown within the compact view (Fig. 4.1). Device settings cannot be entered
or changed in the compact view, but the full user interface can be called up in
the compact view via the button (2).
3 4
7 8 9
5 6 2
Fig. 4.1: Compact view for displaying the device status and key current values
1. The IP address and serial number of the destination device are displayed
in the lower section of the compact view, the quality of the connection with
the destination device is shown in a bar chart and the system clock of the
destination device is indicated
2. Button for calling up the full user interface
3. Display of current device status in the PVMaster traffic light display (sec-
tion 4.2.10, p. 28)
4. Display of state of software release switch (section 4.2.5, p. 24). In the
compact view, the state of the software release switch is merely displayed
and cannot be changed
5. Number of unconfirmed or new event messages (section 4.3.5.2, p. 229)
6. Number of unconfirmed or new event messages regarding device malfunc-
tions that have occurred (section 4.3.5.1, p. 221)
7. Display of key current DC values (in PV generator), the current DC voltage
[V] and the current DC current [A]
8. Display of total yield [kWh] of the target device achieved so far
9. Display of key current AC values (grid measured values), current supply
voltage [V], current grid current [A], current AC power [kW] and the current
percentage infeed capacity based on the rated power of the device
11 6 7 8 9
10
1 2 3 4 5
Fitter All options from the "Observer" user level are available at the "Fitter" user level.
In addition, the device can be fully configured and commissioned at this level.
The use of this user level requires authentication by entering a password. The
following options are also possible:
–– Software release (section 4.2.5, p. 24) can be switched on and off to acti-
vate or deactivate the active infeed operation
–– Saving of device options (section 4.2.7, p. 26) and restart of device (sec-
tion 4.2.8, p. 26)
–– Change of device settings: system clock (section 4.3.4.1.2, p. 110),
network settings (section 4.3.4.1.3, p. 112), initialisation of grid monitor-
ing by selecting country code (section 4.3.4.2.3, p. 124), change of rated
network frequency and limitation of total power (section 4.3.4.2.1, p. 115),
configuration of internal data logger and remote data transmission (sec-
tion 4.3.4.7, p. 214), insulation monitor (section 4.3.4.2.4, p. 136), limita-
tion of power as part of infeed management and Limit (by grid operator)
(section 4.3.4.2.5, p. 141), network support functions (section 4.3.4.3,
p. 147), input and output functions (section 4.3.4.4, p. 166), communica-
tion between inverters (section 4.3.4.5, p. 198), string current measure-
ment (section 4.3.4.6, p. 210)
–– Administration of energy data and configuration of energy determination and
conversion factors (section 4.3.4.2.2, p. 118)
–– Completion of software updates (section 4.3.4.2.1, p. 115)
–– Extended functions: Calculation of current generator curve (characteris-
tic curve measurement function) and saving of measured values identi-
fied (section 4.3.2.3.2, p. 55), check function for digital outputs (sec-
tion 4.3.5.4, p. 234), display of average string current values for further
processing in an online portal (section 4.3.2.3.3, p. 56), etc.
Expert This user level is reserved for select experts. The use of this user level requires
authentication by entering a password. The following options are also possible:
–– Manual control options: Freezing MPP tracking and manual specifica-
tion of DC voltage setpoints and skipping the power measurement (sec-
tion 4.3.2.3.1, p. 52)
–– Change to additional device settings: Change to rated supply voltage and
user-defined grid monitoring settings (section 4.3.4.2.3, p. 124), user-de-
fined settings for insulation monitor (section 4.3.4.2.4, p. 136), user-defined
settings for dynamic network support functions (section 4.3.4.3.3, p. 159),
advanced settings for communication between inverters (section 4.3.4.5,
p. 198), advanced settings for remote data transmission (section 4.3.4.7,
p. 214), configuration of automatic acknowledgement of malfunctions (sec-
tion 4.3.5.1, p. 221)
Administrator At this user level, special menu options are available that are only used by LTI
ReEnergy GmbH as part of the production and testing of the PVMaster (e.g.
calibration, etc.).
NOTE
Access to the "Administrator" user level is reserved for LTI ReEnergy GmbH
and the relevant authentication data for this user level are not published. The
corresponding menu options and user interfaces at this user level will not be
discussed further in this application manual.
4.2.2.1 Authentication/authorisation
When switching to a higher user level in the selection box (2) in Fig. 4.2,
p. 18, a dialogue box (Fig. 4.3) may first be displayed indicating that the
authorisation to switch to the selected user level does not currently exist. To
continue with the authentication, confirm the dialogue box with the "OK" button.
Fig. 4.3: D
ialogue box in the absence of authorisation for the user level re-
quested
A further dialogue box (Fig. 4.4) for authentication is then displayed. This dia-
logue box shows an activation code generated specifically for the destination
device.
In order to obtain the requisite access password for the requested user level of
the destination device, contact the support team at LTI ReEnergy GmbH and
enter your contact details, the displayed activation code, the required user level
and the required period of validity of the access password, so that the requisite
access password can be generated for you.
Fig. 4.4: D
ialogue box for displaying the activation code and for entering the
access password
NOTE
Make a note of the access password when you get it in case you need it later;
you may be prompted to enter the access password again in order to authen-
ticate access to higher user levels (e.g. after a software update of the destina-
tion device or following deletion of the temporary application memory).
NOTE
Access passwords are always issued for a limited period of time (maximum
of 365 days) and specifically for the requested user level. Access passwords
are generally also linked to the MAC address of the destination device and are
therefore only valid for the destination device for which the access password
was generated. In other words, access passwords must as a rule be requested
separately for each new destination device. In exceptional cases, access
passwords that are not linked to a specific destination device can be issued
(e.g. for users of a number of devices). Please contact the support team at LTI
ReEnergy GmbH to discuss this.
Once you have received the access password, please enter it in the input field
of the dialogue box (Fig. 4.4) to authenticate your access and confirm the entry
by clicking on the "OK" button.
Once a valid access password has been correctly entered, a window (Fig. 4.5)
appears with information about the access password entered (MAC address
of the destination device, validity not linked to a specific destination device,
maximum user level and period of validity). Confirm this window by pressing the
"OK" button.
The user level can then be changed accordingly with the selection box (2) in
Fig. 4.2, p. 18.
NOTE
Upon entry of the authentication data, it is stored in the MS Silverlight applica-
tion memory of the PC used, so that the access password does not have to
be entered when changing the user level next time the operator application is
opened. The MS Silverlight application memory must be activated for this (see
also 4.1.2.1, p. 15).
NOTE
If the operator application is used on a PC that is publicly accessible to other
people, for example, the authentication data should be deleted manually in the
operator application after use by pressing the button (3) in Fig. 4.2, p. 18.
NOTE
All temporarily saved authentication data will be lost as soon as the MS Sil-
verlight application memory (see also section 4.1.2.1, p. 15) is deleted. In
this case, access passwords may have to be entered separately for each new
destination device to change the user level.
Clicking on the "OK" button in the dialogue box ends the break in operation
of the operator application and communication with the destination device is
resumed.
The software release switch functions in the same way as a real switch. Its
status is generally only changed by manually operating the button and remains
unchanged when the device is restarted (section 4.2.8, p. 26), for example.
NOTE
Changing device settings with the relevant configuration text boxes (sec-
tion 4.2.6.2, p. 25) is in some cases only possible when the software release
switch is deactivated. Permanent saving of changes to device settings (sec-
tion 4.2.7) and manual device restarts (section 4.2.8, p. 26) are generally
only possible when the software release switch is deactivated.
From Fitter As soon as a configuration text box has been enabled for entries and changes,
the displayed value can be changed accordingly. Once the new value has been
entered, the change must be confirmed with "Enter". The validity of the entered
value is checked accordingly.
Once a valid entry has been made in an enabled configuration text box for edit-
ing a device setting, the "Save" button (6) in Fig. 4.2, p. 18 is enabled in order
to indicate to the user that there is a change to the device settings that has not
yet been permanently saved (see section 4.2.7, p. 26). Exceptions to this, for
example, are certain configuration text boxes for specifying setpoints.
NOTE
Depending on the respective unit parameter, changes made via the relevant
configuration text box are adopted directly in operation and become effective.
However, some parameter changes first need to be changed permanently
(section 4.2.7, p. 26) and the unit then needs to be restarted (section 4.2.8,
p. 26) before these changes take effect.
The "Save" button is locked for the time being if the device
settings are not changed and can not be actuated in this
state.
The "Save" button is enabled as soon as at least one unit
parameter has been changed through a configuration text
box (section 4.2.6.2, p. 25). The enabling of the "Save"
button is used to indicate to the user that a change to the
device settings has not yet been permanently saved.
The "Save" button remains in this enabled state until the changes to the device
settings have been saved. However, changes can only be saved when the soft-
ware release switch (section 4.2.5, p. 24) is deactivated. When the enabled
"Save" button is actuated with the software release switch activated, changes
to device settings are not permanently saved. This is then indicated in a corre-
sponding information window (Fig. 4.7). Successful saving of the changes to the
device settings is indicated to the user through a visible change in the status of
the "Save" button (locked).
From Fitter
The waiting time after performing a manual restart of the device using the "Re-
start" button is dependent on the menu option currently selected and the quality
of the connection with the destination device.
4.2.9 Navigation
Navigation within the operator application is performed with the main menu in
the tree view permanently displayed on the left-hand side (see (10) in Fig. 4.2,
p. 18). The individual menu options in what are referred to as menu groups
and menu sub-groups are sorted by functions and areas. Menu groups and
menu sub-groups are visually marked with an arrow on the left-hand side next
to the displayed menu options. Clicking on the arrow displayed or the button
for the menu group or menu sub-group you require displays the menu options
available under these items. In order to open the required menu option or user
interface, the user navigates through the menu groups or menu sub-groups
displayed in the main menu. The required user interface is not opened until
the subordinate menu options have been activated. The menu option currently
selected is displayed with a red marking against the menu option in question. To
simplify navigation, the "Back" button (see (11) in Fig. 4.2, p. 18) can be used
to return to the menu options previously used, where applicable.
NOTE
The "Forward" or "Back" functions of the internet browser itself cannot be used
to navigate within the operator application.
Once the operator application has been opened, the user interface for the
"Overview" (section 4.3.1, p. 39) menu option is always automatically dis-
played as the start user interface.
NOTE
Depending on the user level selected, different menu options are available in
the main menu. In other words, the availability of the individual menu options
in the main menu changes dynamically when the user level changes.
NOTE
The menu options available in the main menu differ according to the PVMaster
version. Not all of the functions and menu options described in this application
manual are available for some versions.
NOTE
Special operating modes of the PVMaster (e.g. in "Single MPPT mode", see
section 4.3.4.5, p. 198) include processes that may deviate from Fig. 4.8,
p. 31 within the internal operational control.
Tab. 4.3: P
ossible device states in multi-MPPT mode or
when the device is currently the master in single MPPT mode
Status traffic
No. Plain text message 2) 7-segment display 3)
lights 1)
0 Reset device
1 Initialize device
4)
2 Grid monitoring: okay ←→
4)
3 Switch-on disabled / DC voltage too low
4)
4 Switch-on disabled / DC voltage sufficient
4)
5 Error: source still active → →
6 Error: ready to acknowledge → →
4)
7 Grid monitoring error: source still active → →
8 Grid monitoring error: ready to acknowledge → →
9 Standby: DC voltage too low (Vdc < Vdc_Start)
10 Switch-on procedure: DC voltage sufficient
11 Switch-on procedure: power measurement active
12 Measured power sufficient... switch on AC contactor
13 MPP tracking active
14 Generator scan active
15 MPP tracking active... AC power low
16 Switch-off procedure: power measurement active
17 Switch-off procedure: power too low
1) Display in compact view (section 4.1.3, p. 16) and in the operator application (section 4.2, p. 18)
2) Available as plain text message in the top main bar of the user interface (section 4.2, p. 18)
3) Display also available in the operator application (see section 4.3.2.1, p. 41)
4) With a dot in the 7-segment display
Tab. 4.4: P
ossible device states when the device is currently “Slave”
in single MPPT mode
Status traffic
No. Plain text message 2) 7-segment display 3)
lights 1)
1 Slave: device starts / auto-initialisation
4)
2 Control point: mains ok ←→
4)
3 Slave: Switch-on lockout/DC voltage too low
4)
4 Slave: Switch-on lockout/DC voltage sufficient
4)
5 Error state: cannot be cancelled (fault still active) → →
6 Error state: can be cancelled → →
4)
7 Network failure: Cause still active → →
8 Network failure: can be cancelled → →
9 Slave: Standby: DC voltage too low
10 Slave: waiting for request for connection
11 Slave: check request for connection
12 Slave: connection requested... Main contactor
13 Slave: feed active
15 Slave: check request for disconnection
16 Slave: check request for disconnection (passive)
17 Slave: disconnection occurs
1) Display in compact view (section 4.1.3, p. 16) and in the operator application (section 4.2, p. 18)
2) Available as plain text message in the top main bar of the user interface (section 4.2, p. 18)
3) Display also available in the operator application (see section 4.3.2.1, p. 41)
4) With a dot in the 7-segment display
Tab. 4.6: Menu options and sub-groups of the "Status and Values" menu group
Menu option and area Meaning
Menu option for detailed display of the cur-
rent device status. The current device status
is displayed as a binary display of three
status words (section 4.3.2.1, p. 41).
Menu option for status and value display for
device intercommunication via the Inter-
COM interface. This is where, for example
the communication and synchronisation
statuses and current device and total power
values are displayed, along with energy
values, device states and functional actual
values (section 4.3.2.2, p. 48). This menu
option is only available if InterCOM device
intercommunication is also being used (sec-
tion 4.3.4.5, p. 198).
This menu sub-group contains menu options
for displaying and visualising actual val-
ues relating to the PV generator (DC side)
(section 4.3.2.3, p. 52). This includes
the display of DC measured values (volt-
age, current, power), the state of insulation,
individual string current values and Other
values, such as solar radiation values,
module temperatures, wind speeds and
wind direction. In addition, there are also a
few diagnostic functions (e.g. characteristic
curve measurement function for calculating
and processing the current generator char-
acteristic curve).
Tab. 4.7: M
enu options and sub-groups of "History and Statistics" menu group
Menu option and area Meaning
This menu sub-group contains menu options
for selectable retrieval of recorded historic
data and measured values (voltages, cur-
rents, powers, string current values, etc.) as
day history data that can be displayed in a
table and processed, or can be displayed
graphically in day graphs (section 4.3.3.1,
p. 86).
This menu option is used to retrieve historic
month energy data for a selected month
(section 4.3.3.2, p. 97). The individual day
energy values are displayed and processed
either in tabular form or in a month diagram
(bar chart).
This menu option is used to retrieve historic
year energy data for a selected year (sec-
tion 4.3.3.3, p. 100). The individual month
energy values are displayed and processed
either in tabular form or in a year diagram
(bar chart).
This menu option is used to retrieve his-
toric overall energy data (section 4.3.3.4,
p. 102). The individual year energy values
are displayed and processed either in tabu-
lar form or in an overall diagram (bar chart).
Tab. 4.8: Menu options and sub-groups of the "Configuration" menu group
Menu option and area Meaning
Tab. 4.9: Menu options and sub-groups of the "Diagnosis" menu group
Menu option and area Meaning
The user interface for this menu option is
used to display the number of new fault
messages and to display and process the
malfunctions that have occurred in a tabular
view. This is where the user can confirm
new (unread) fault messages (delivery con-
firmations). In addition, current malfunctions
can be acknowledged and settings relating
to automatic acknowledgement of malfunc-
tions can be displayed and configured (sec-
tion 4.3.5.1, p. 221).
The user interface for this menu option is
used to display the number of new event
messages and to display and process the
unusual events that have occurred in a
graphically prepared tabular view (sec-
tion 4.3.5.2, p. 229). This is where the user
can confirm new (unread) event messages
(delivery confirmations).
The user interface for this menu option is
used for detailed diagnoses and displays of
the operating cycle. This is where all past
status changes (status word 1 and status
word 2) for a selected time period are sorted
and displayed and where they can be pro-
cessed (section 4.3.5.3, p. 231).
The user interface for this menu option1) can
be used to switch the digital outputs manual-
ly and thus check the functions of the digital
outputs (fan, heat exchanger, liquid pump,
etc.) (section 4.3.5.4, p. 234).
1) This menu option is available from the "Fitter" user level.
1 4 5 2
7 8
Fig. 4.9: User interface for the "Overview" menu option (start user interface)
1. The link button takes the user to the user interface for the
menu option for the detailed view of the generator features
(section 4.3.2.3, p. 52). The current DC voltage in [V] and
current DC current in [A] are displayed in the display text
boxes here.
2. The link button takes the user to the user interface for the
detailed view of the grid values calculated (section 4.3.2.4.1,
p. 61). The main grid values are displayed in the display
text boxes here. The current grid voltage effective value in [V]
(as an average for all three linked voltages), the current grid
current in [A] of the device (as an average of the three phase
currents), the current total active power of the device in [kW]
and the power-related utilisation level of the device in [%] are
displayed here.
3. These display text boxes show the day yield currently achieved in [kWh],
the month yield currently achieved in [kWh] and the total yield currently
achieved in [kWh]. Details of how the energy is determined and the
conversion factors are configured are described in section 4.3.4.2.2,
p. 118.
4. This link button takes the user directly to the user inter-
face for the menu option for displaying and managing
fault messages (section 4.3.5.1, p. 221). The number
of new (not yet confirmed) fault messages is displayed
within the display text box.
5. This link button takes the user directly to the user inter-
face for the menu option for displaying and managing
event messages (section 4.3.5.2, p. 229). The number
of new (not yet confirmed) event messages is displayed
within the display text box.
6. This area of the start user interface contains an overview of the symbols
for displaying the main statuses and values of integrated device func-
tions. The symbols shown here are not link buttons and are therefore not
intended for navigating around the operator application.
Symbol with display of the state of the insulation moni-
tor (for details see section 4.3.4.2.4, p. 136). If the
insulation resistance is not monitored by the device, the
symbol display is highly transparent.
Symbol with display of status of integrated function for
file transfer to an online destination server via FTP (for
details see section 4.3.4.7, p. 214). If file transfer is
deactivated, there is no status display and the symbol
display is highly transparent.
The DNS and/or FTP client is in an error state.
Automatic sending of files cannot take place. The
local internet connection of the PVMaster devices
may be faulty.
The DNS client is currently attempting to resolve
the names or the FTP client is currently sending a
file to the FTP destination server.
The DNS and FTP client are both in the "Ready" or
"OK" state.
Symbol used to display the current status of communica-
tion with any generator connection boxes (or sub-array
junction boxes) with string current measurement (see
section 4.3.4.6, p. 210). The status displayed here
relates merely to communication via the CAN interface
and does not constitute an assessment of the string
currents measured. If string current monitoring is deacti-
vated, there is no status display and the symbol display
is highly transparent.
4.3.2.1 State
Within the “State” (Fig. 4.10) menu option, the current device status is shown in
a 7-segment display format (Tab. 4.4, p. 30 and Tab. 5.2, p. 238) in the up-
per section of the user interface. The device states are shown in the same way
as the display of statuses in the 7-segment displays of the basic device in the
PVMaster enclosure (see also Chapter 5.1.1, p. 40).
Fig. 4.10: U
ser interface of the “State” menu option in the "Status and Values"
menu group
The current device status and the statuses of the main integrated device func-
tions of the PVMaster are mapped in a total of three 32-bit status words.
The current decimal values of the three status words are displayed in the lower
section of the user interface of the “State” (Fig. 4.10) menu option. The display
of the three current status words with the corresponding descriptive texts are
displayed in the respective binary format in the middle section of the user inter-
face.
The following statuses of the respective function are possible:
The first two status words (Tab. 4.10, p. 43 and Tab. 4.11, p. 46) contain
statuses and release conditions for the internal operating cycle controller. All
changes within status word 1 or status word 2 are recorded on the microSD
card by the internal data logger. All recorded status changes within the first two
status words within a selectable time period can be retrieved, displayed and
processed with the “State” menu option in the "Diagnosis" menu group (see
section 4.3.5.3, p. 231).
NOTE
A maximum total of the last 1000 status changes to the first two status words
are retained in the data memory for retrieval (section 4.3.5.3, p. 231). Entries
with older status changes are automatically deleted and can no longer be
retrieved.
The third status word (Tab. 4.12, p. 47) contains the statuses of special
device functions. Changes to some of these statuses are described as "Unu-
sual events" and recorded by the integrated data logger. "Unusual events" are
retrieved, displayed and processed conveniently in the "Events" menu option in
the "Diagnosis" menu group (section 4.3.5.2, p. 229).
NOTE
A total of the last 100 event messages are retained in the data memory for
retrieval (section 4.3.5.2, p. 229). Entries with older events are automatically
deleted and can no longer be retrieved.
Tab. 4.10: Content of status word 1
No. Function Description
Display of switching state (e.g. of a circuit breaker) of a higher-level medium-
voltage switchgear.
The state is only displayed if this function is used. To this end, a digital input
for evaluating a corresponding auxiliary contact can be assigned the relevant
MVS (Medium-voltage
0 function (function 21 in Tab. 4.19, p. 168, see section 4.3.4.4.1, p. 166). 1)
switchgear): switch state
If this function is used, the active state is a necessary condition for connection
and active infeed operation (see no. 6). If the switching state is inactive, the
device is in an error state (ID 10/11 in Tab. 4.31, p. 224, see section 4.3.5.1,
p. 221).
Display of switching state (e.g. of a circuit breaker) of a higher-level low-volt-
age switchgear.
The state is only displayed if this function is used. To this end, a digital input
for evaluating a corresponding auxiliary contact can be assigned with the
LVS (Low-voltage switch- relevant function (function 25 in Tab. 4.19, p. 168, see section 4.3.4.4.1,
1
gear): switch state p. 166). 1)
If this function is used, the active state is a necessary condition for connection
and active infeed operation (see no. 6). If the switching state is inactive, the
device is in an error state (ID 10/08 in Tab. 4.31, p. 224, see section 4.3.5.1,
p. 221).
Display of state of an optional external release facility.
The state is only displayed if this function is used. To this end, a digital input
for evaluating an external release switch, for example, can be assigned the rel-
2 External release evant function (function 8 in Tab. 4.19, p. 168, see section 4.3.4.4.1, p. 166).
1)
If this function is used, the active state is a necessary condition for connection
and active infeed operation (see no. 6).
1) Alternatively, the signal can be sourced from another device in the InterCOM device network through InterCOM device
intercommunication (section 4.3.4.5, p. 198).
2) This function is not available for each PVMaster device type
3) If grid monitoring external to the device is used, whereby a digital input for evaluation is assigned the corresponding function (function
20 in Tab. 4.19, p. 168, see section 4.3.4.4.1, p. 166), the release state according to the evaluated signal is displayed here. The
signal for grid monitoring external to the device can also be sourced from another device in the InterCOM device network through
InterCOM intercommunication (section 4.3.4.5, p. 198).
4) A display of the status of this function is also available in the relevant symbol on the initial "Overview" user interface (section 4.3.1,
p. 39)
4.3.2.2 InterCOM
InterCOM communication is used for intercommunication between several PV-
Master devices within a local device network (e.g. within a PVMaster station). A
description of the functions of InterCOM device intercommunication and detailed
information about configuration can be found in section 4.3.4.5, p. 198.
If the InterCOM intercommunication has been activated and correctly configured
(see section 4.3.4.5, p. 198), the "InterCOM" menu option is available in the
"Status and Values" menu group.
The key statuses and actual values for InterCOM device intercommunication
are displayed within the user interface for this menu option (Fig. 4.11, p. 49).
Changes to device settings are not possible in this user interface.
5 6 7
a b c d e f g- m
1 2 3 4
Fig. 4.11: User interface of the "InterCOM" menu option in the "Status and
Values" menu group
Current power values and the set power limits of the local InterCOM device
network are displayed in the lower section of the user interface.
1. Display of the current total apparent power in [kVA] of the entire local Inter-
COM device network is shown here in a display text box.
2. Display of the set maximum value for the apparent power in [kVA] of the
total local InterCOM device network in a configuration text box. This configu-
ration text box is merely used for display and is generally locked for entries
in this user interface. This setting can be changed in the user interface of
the "General" menu option in the "Grid" menu sub-group of the "Configura-
tion" menu group (section 4.3.4.2.1, p. 115).
3. Display of the current total active power in [kW] of the entire local InterCOM
device network is shown here in a display text box.
4. Display of the set maximum value for the active power in [kW] of the total
local InterCOM device network in a configuration text box. This configura-
tion text box is merely used for display and is generally locked for entries in
this user interface. This setting can be changed in the user interface of the
"General" menu option in the "Grid" menu sub-group of the "Configuration"
menu group (section 4.3.4.2.1, p. 115).
5. The set communication address of the respective InterCOM node (Inter-
COM node ID) is displayed in this section. All InterCOM devices of the local
InterCOM device network are generally listed sorted by the respective set
InterCOM node ID in this user interface.
4.3.2.3.1 DC values
The user interface for the "DC values" menu option is shown in Fig. 4.12 and
contains, for example, display elements for displaying current actual values in
the PV generator (DC side).
1
6
2 5
3 7
4 8
9
10
11
12 14
13 15
Fig. 4.12: U
ser interface of the "DC values" menu option in the "Status and
Values" menu group
If a red link button is shown next to a display text box, this indicates that
this value has been recorded as standard by the integrated data logger
and that the corresponding recorded day history data can be called up in
the diagram generator. Pressing this link button calls up the corresponding
user interface to display the day history data (section 4.3.3.1.1, p. 86).
10. The insulation monitoring state is displayed here via status fields and as a
plain text message in a display text box. The possible states are listed in
Tab. 4.18, p. 140.
11. Meteorological measured values, where present, that have been recorded
via analogue inputs of the PVMaster device are displayed in the lower sec-
tion of the user interface. The measured values are displayed in two tab
options, "Irradiation and Temperature" and "Wind".
12. Display of current solar radiation G1 in [W/m²] in a display text box. This
value is only available if a corresponding solar radiation measurement via
an analogue input of the PVMaster device is evaluated and this analogue
input has been assigned the respective function (see section 4.3.4.4.3,
p. 189, no. 6 in Tab. 4.23, p. 190).
13. Display of current solar radiation G2 in [W/m²] in a display text box. This
value is only available if a corresponding solar radiation measurement via
an analogue input of the PVMaster device is evaluated and this analogue
input has been assigned the respective function (see section 4.3.4.4.3,
p. 189, no. 7 in Tab. 4.23, p. 190).
14. Display of current module temperature M1 in [°C] in a display text box. This
value is only available if a corresponding temperature measurement via an
analogue input of the PVMaster device is evaluated and this analogue input
has been assigned the respective function (see section 4.3.4.4.3, p. 189,
no. 12 in Tab. 4.23, p. 190).
15. Display of current module temperature M2 in [°C] in a display text box. This
value is only available if a corresponding temperature measurement via an
analogue input of the PVMaster device is evaluated and this analogue input
has been assigned the respective function (see section 4.3.4.4.3, p. 189,
no. 13 in Tab. 4.23, p. 190).
15 17
16 18
Fig. 4.13: " Wind" tab option in the user interface for the "DC values" menu op-
tion
16. Display of current wind speed V1 in [m/s] in a display text box (Fig. 4.13).
This value is only available if a corresponding wind speed measurement via
an analogue input of the PVMaster device is evaluated and this analogue
input has been assigned the respective function (see section 4.3.4.4.3,
p. 189, no. 8 in Tab. 4.23, p. 190).
17. Display of current wind speed V2 in [m/s] in a display text box (Fig. 4.13).
This value is only available if a corresponding wind speed measurement via
an analogue input of the PVMaster device is evaluated and this analogue
input has been assigned the respective function (see section 4.3.4.4.3,
p. 189, no. 9 in Tab. 4.23, p. 190).
18. Display of current wind direction D1 in [°] in a display text box (Fig. 4.13).
This value is only available if a corresponding wind direction measure-
ment via an analogue input of the PVMaster device is evaluated and
this analogue input has been assigned the respective function (see sec-
tion 4.3.4.4.3, p. 189, no. 10 in Tab. 4.23, p. 190).
19. Display of current wind direction D2 in [°] in a display text box (Fig. 4.13).
This value is only available if a corresponding wind direction measure-
ment via an analogue input of the PVMaster device is evaluated and
this analogue input has been assigned the respective function (see sec-
tion 4.3.4.4.3, p. 189, no. 11 in Tab. 4.23, p. 190).
4 3
7
1
5
2
3 4
Fig. 4.15: U
ser interface of the "String currents" menu option in the "Status and
Values" menu group
1. Number of SCBs connected to the PVMaster or activated via the configura-
tion (section 4.3.4.6, p. 210) in a display text box. According to the number
of available SCBs displayed here, the corresponding entries for selection of
the SCBs are available in the selection box (2).
2. Selection box for selecting the SCBs for displaying the corresponding states
and measured values within the user interface. Only those SCBs that have
been activated via the configuration (section 4.3.4.6, p. 210) can be select-
ed within this selection box. If an SCB is selected via the selection box, the
status of communication is displayed via (3) and (4), and the string currents
for this selected SCB are displayed in (6), (7) and (8). The actual values for
this selected SCB are also displayed in the other tab options,"Other values"
and "Average values".
3. If there is a malfunction in the CAN communication with the SCB selected
via the selection box (2), the communication error is indicated via this status
field. More detailed information is displayed in plain text message form
in the display text box (4). Information is generally only displayed via this
status field if communication with SCBs has been activated through the
configuration (section 4.3.4.6, p. 210).
4. Display text box with information about the status of CAN communication
as a plain text message. The possible messages and what they mean are
covered in Tab. 4.29, p. 213 (section 4.3.4.6, p. 210). Messages are gen-
erally only displayed in this display text box if communication with SCBs has
been activated through the configuration (section 4.3.4.6, p. 210).
5. The corresponding states and measured values of the SCBs selected via
selection box (2) are displayed in three tab options in the middle section of
the user interface.
a) "String currents": Present string current values are displayed and as-
sessed in this tab option (Fig. 4.15).
b) "Other values": Current meteorological measured values are displayed
in this tab option (Fig. 4.16).
From Fitter c) "Average values": This tab option (Fig. 4.17) is available from the "Fitter"
level upwards and is used to display chronological average values for
the string currents and meteorological measured values that are used
for the .csv files for upload to an FTP destination server (section 4.3.4.7,
p. 214).
6. The present string current values in [mA] for the SCBs selected via the
selection box (2) are displayed in display text boxes in this section of the
"String currents" tab option. A total of up to fifteen string currents per SCB
can be measured and displayed here. In addition to the respective display
text boxes, a status field for evaluating each measured value is also dis-
played. The evaluation of the string current values is always dependent on
the average value - displayed in text box (7) - for all activated string current
measurements for the selected SCBs. However, only individual string cur-
rent values in excess of 300 mA are evaluated.
If the evaluation of a string current for the SCBs selected via the
selection box (2) has been deactivated via the configuration (sec-
tion 4.3.4.6, p. 210), no value is displayed in the corresponding dis-
play text box. A "-" is simply displayed instead. In this case, a symbol
is always displayed in the corresponding status field.
In the case of a negative difference between the individual string cur-
rent value and the average value for all string current values for the
SCBs selected via the selection box (2) of less than 20%, this minor
negative difference is indicated with a green symbol in the relevant
status field. If there is no assessment of the string current value
because the string current value is less than 300 mA or the individual
string current value is higher than the average value, a green symbol
is again displayed in the relevant status field, regardless of the dif-
ference between the individual string current value and the average
value for all string current values.
If the negative difference between the individual string current value
and the average value for all string current values for the SCBs
selected via the selection box (2) is between 20% and 40%, this is
indicated with a yellow warning symbol in the relevant status field for
string current values greater than 300 mA.
If the negative difference between the individual string current value
and the average value for all string current values for the SCBs
selected via the selection box (2) is greater than 40%, this very large
difference is indicated with a red warning symbol in the relevant status
field for string current values greater than 300 mA.
7. To evaluate the individual string current values for the SCBs selected via the
selection box (2), an average value for all activated string current measure-
ments for the selected SCBs is calculated and displayed in this display text
box in [mA].
8. Up to fifteen string current values for the SCBs selected via the selection
box (2) are displayed in this diagram as a bar chart. The use of colours for
the individual string current bars (green, yellow or red) represents the as-
sessment of the string current values and corresponds to the status fields of
the individual display text boxes for the string current values (6).
The current meteorological measured values are displayed in the "Other values"
tab option (Fig. 4.16).
9 11
10
Fig. 4.16: " Other values" tab option in the user interface for the "String currents"
menu option in the "Status and Values" menu group
9. If the analogue input for the selected SCBs is used to evaluate a solar
radiation measurement and if the analogue input for the SCBs has been
assigned the respective function (section 4.3.4.6, p. 210), the current solar
radiation value in [W/m²] is displayed in this text box.
10. If the analogue input for the selected SCBs is used to evaluate a wind
speed measurement and if the analogue input for the SCBs has been as-
signed the respective function (section 4.3.4.6, p. 210), the current wind
speed in [m/s] is displayed in this text box.
11. If the PT100 input for the selected SCBs is used to measure the tempera-
ture, the current temperature measured value in [°C] is displayed in this text
box.
From Fitter The "Average values" tab option (Fig. 4.17) is available from the "Fitter" user
level upwards and is used to display sliding average values for the string cur-
rents and meteorological measured values. These sliding average values are
used to create string box .csv files; there is then the option of sending these
files to any FTP destination server via the integrated FTP client (section 4.3.4.7,
p. 214). The average value interval is dependent on the set data logger cycle
time (standard value of 15 minutes, for example).
REFERENCE
Any desired change to the average value interval must be made by configuring
the individual SCBs. Information about configuring the SCBs can be found in
the SCB installation manual.
14 16
15
12
13
Fig. 4.17: " Average values" tab option in the user interface for the "String cur-
rents" menu option in the "Status and Values" menu group
12. The sliding average values for the individual string currents for the SCBs
selected via the selection box (2) are displayed in [mA] in display text boxes
in this section of the "Average values" tab option.
13. Display of string current sliding average value in [mA] for all activated string
current measurements for the SCBs selected via the selection box (2).
14. Display of chronological sliding average value for current solar radiation
value in [W/m²] in a display text box (if analogue input for the selected SCBs
is used to measure the solar radiation).
15. Display of chronological sliding average value for current wind speed value
in [m/s] in a display text box (if analogue input for the selected SCBs is used
to measure the wind speed).
16. Display of chronological sliding average value for current temperature value
in [°C] in a display text box (if PT100 input for the selected SCBs is used to
measure the temperature).
4.3.2.4 Grid
The "Grid" menu sub-group of the "Status and Values" menu group contains
menu options for displaying actual values relating to the grid (AC side). The
subordinate menu options facilitate the display and visualisation of AC meas-
ured values (voltages, currents, frequency, powers, power factors), and the
display of active current and power limitations, energy values and the current
configuration and status of grid monitoring functions.
4.3.2.4.1 AC values
The user interface for the first "AC values" menu option of the "Grid" menu sub-
group (Fig. 4.18) contains display elements for displaying actual values in the
grid (AC side).
5
1
2
6
9
7
12
10
11
13
Fig. 4.18: U
ser interface of the "AC values" menu option in the "Status and
Values" menu group
If a red link button is shown next to a display text box, this indicates that
this value has been recorded as standard by the integrated data logger
and that the corresponding recorded day history data can be called up in
the diagram generator. Pressing this link button calls up the corresponding
user interface to display the day history data (section 4.3.3.1.1, p. 86).
1. Here, the values of the three phase voltages or power linked phase voltages
measured at the current time are displayed in text boxes in [V], depending
on the selection made in the left selection box (5).
2. Display of current linked voltage in [V] in a display text box. The value dis-
played is the average value for the three measured linked grid voltages.
3. As part of grid monitoring (section 4.3.4.2.3, p. 124), a chronological slid-
ing average value for each of the three grid phase voltages measured (1) is
calculated and monitored in order to monitor the quality of the grid voltage.
The moving averages are displayed in [V] in these display boxes, depending
on the selection made in the left selection box (5).
4. The current measured grid frequency in [Hz] is shown in this display text
box.
5. The grid voltage values and grid frequency are redundantly measured in
the PVMaster with two independent controllers (main and backup controller)
in order to meet specific requirements regarding functional safety (sec-
tion 4.3.4.2.3, p. 124). The selection box on the right is used to select the
values to be displayed for the grid voltage values and the grid frequency in
the display text boxes (1), (2), (3) and (4). If "µC1" is selected, the meas-
ured values of the main controller are displayed, while "µC2" will display the
measured values of the backup controller. The selection box on the left is
used to choose whether the grid voltage single values should be displayed
in the display text boxes (1) and (3) as phase values (setting “ph-n”) or as
linked voltages (setting “ph-ph”).
6. The direction of rotation of the grid voltage system identified is displayed
via these status fields depending on the phase sequence of the connec-
tion. The PVMaster has an automatic adaptation of the rotating field, which
means that the phase sequence is not relevant to the connection to the grid
voltage system.
7. The current grid currents measured for the three phases L1, L2 and L3 are
displayed in [A] via these display text boxes.
8. The current average value for the grid currents measured for the three
phases (7) is displayed here in [A] in a display text box.
9. This status field is used to indicate that current limitation is currently active
in the PVMaster device (e.g. due to active derating as a result of elevated
temperature values). Details of the current limitation are given in the user
interface for the "Limit" menu option of the "Grid" menu sub-group in the
"Status and Values" menu group (section 4.3.2.4.3, p. 65).
10. Display of respective current active power values for the three phases L1,
L2 and L3 in [kW] in display text boxes.
11. The current total active power fed into the grid is displayed here in [kW] in
a display text box. This value represents the sum of the three phase active
powers (10).
12. This status field is used to indicate that active Limit is currently active in
the PVMaster device (e.g. due to active Limit by the grid operator as part
of infeed/grid security management (NSM). Details of the current active
Limit are given in the user interface for the "Limit" menu option of the "Grid"
menu sub-group in the "Status and Values" menu group (section 4.3.2.4.3,
p. 65).
13. Link button for direct navigation around the user interface of the "Limit"
menu option in the "Grid" menu sub-group of the "Status and Values" menu
group, in order, for example, to have further details about currently active
current limitation or active Limit displayed.
4.3.2.4.2 Power
An overview of all current power values is given in the user interface for the
"Power" menu option of the "Grid" menu sub-group in the "Status and Values"
menu group (Fig. 4.19). All phase power values and apparent, reactive and ac-
tive Limits currently active are displayed here.
1 3
4 6
7 9
10
11
12
Fig. 4.19: U
ser interface for "Power" menu option in the "Status and Values"
menu group
If a red link button is shown next to a display text box, this indicates that
this value has been recorded as standard by the integrated data logger
and that the corresponding recorded day history data can be called up in
the diagram generator. Pressing this link button calls up the corresponding
user interface to display the day history data (section 4.3.3.1.1, p. 86).
1. Display of respective current apparent power values for all three phases L1,
L2 and L3 in [kVA] in display text boxes.
2. The current total apparent power is displayed here in [kVA] in a display text
box. This value represents the sum of the three current phase apparent
powers (1).
3. This status field is used to indicate that apparent Limit is currently active in
the PVMaster device (e.g. if the rated power of the PVMaster device has
been reached). Details of the current apparent Limit are given in the user
interface for the "Limit" menu option of the "Grid" menu sub-group in the
"Status and Values" menu group (section 4.3.2.4.3, p. 65).
4. Display of respective current reactive power values for all three phases L1,
L2 and L3 in [kVAr] in display text boxes.
5. The current total reactive power is displayed here in [kVAr] in a display text
box. This value represents the sum of the three current phase reactive pow-
ers (4).
6. This status field is used to indicate that reactive Limit is currently active in
the PVMaster device (e.g. if the PVMaster device has already reached its
maximum possible apparent power or, specifically with PVMaster II, it has
reached its minimum power factor of 0.85). Details of the current reactive
Limit are given in the user interface for the "Limit" menu option of the "Grid"
menu sub-group in the "Status and Values" menu group (section 4.3.2.4.3,
p. 65).
7. Display of respective current active power values for all three phases L1, L2
and L3 in [kW] in display text boxes.
8. The current total active power is displayed here in [kW] in a display text box.
This value represents the sum of the three current phase active powers (7).
9. This status field is used to indicate that active Limit is currently active in
the PVMaster device (e.g. due to active Limit by the grid operator as part
of infeed/grid security management (NSM). Details of the current active
Limit are given in the user interface for the "Limit" menu option of the "Grid"
menu sub-group in the "Status and Values" menu group (section 4.3.2.4.3,
p. 65).
10. Display of respective current power values for all three phases L1, L2 and
L3 in display text boxes.
11. The current power factor is displayed here in a display text box. This value
represents an average value for the current power factors for all three
phases (10).
12. Link button for direct navigation around the user interface of the "Limit"
menu option in the "Grid" menu sub-group of the "Status and Values" menu
group, in order, for example, to have further details about currently appar-
ent, reactive or active Limit displayed.
4.3.2.4.3 Limit
The active limitations of the device current and the apparent, active and reactive
Limits are displayed in the “Limit” menu option in the "Grid" menu sub-group of
the "Status and Values" menu group.
4 3 2 1
10 9 8
13 12 11
14 15 16 17 18 19
Fig. 4.20: U
ser interface of the “Limit” menu option in the "Status and Values"
menu group
1. Display of rated current of the PVMaster device in [A] in a configuration text
box. This configuration text box is generally locked for entries, as this value
cannot be edited.
2. The maximum device current currently possible is displayed here in [A]
in a display text box. In addition to active temperature-dependent current
derating, where applicable, the displayed maximum possible device current
also takes account of the apparent Limit functions. If grid voltage values are
elevated, for example, it is possible to limit the maximum possible device
current.
3. The current average value for the grid currents measured for the three
phases is displayed here in [A] in a display text box. It is displayed in the
same way as the display in element (8) in Fig. 4.18 (section 4.3.2.4.1,
p. 61).
4. This status field is used to display any limitation of the device current or ap-
parent, reactive and/or active Limits currently active.
5. If temperature values are elevated, there is an automatic derating of the
current device current. Once a corresponding temperature threshold for a
7. Status field for displaying currently active active Limit, e.g. if the rated power
of the PVMaster device has been reached (10) or the active power of the
device is reduced as part of total active Limit (total active power of local
InterCOM device network) (14). The value displayed in this status field also
takes into account the functional active Limit functions (16), (17), (18) and
(19).
8. Configuration text box for displaying the rated active power in [kW] of the
PVMaster device. This configuration text box is generally locked for entries,
as this value cannot be edited. The rated active power of the device is also
the maximum active power of the device.
9. The total active power of the PVMaster device currently fed into the grid
is displayed here in a display text box in [kW] or [%]. The display in [kW]
is analogous to the display in element (11) in Fig. 4.18 (section 4.3.2.4.1,
p. 61). The selection as to whether the value is to be displayed in [kW] or
as a percentage value in relation to the rated active power of the device (8)
is made in the selection box to the right of the display box.
10. Status field for displaying currently active reduction of the current active
power of the PVMaster device (9) to the rated active power of the PVMaster
device (8).
11. Display of the set maximum value for the active power in [kW] of the total
local InterCOM device network in a configuration text box. This configura-
tion text box is merely used for display and is generally locked for entries in
this user interface. This setting can be changed in the user interface of the
"General" menu option in the "Grid" menu sub-group of the "Configuration"
menu group (section 4.3.4.2.1, p. 115).
12. The current total active power of the entire local InterCOM device network is
shown here in a display text box in [kW].
13. Status field for displaying currently active reduction of the current active
power of the entire local InterCOM device network (12) to the set maximum
value for the active power for the entire local InterCOM device network (11).
14. Symbol with display text box for displaying the current maximum possible
active power in [%]. In addition to the currently active functional active Limit
functions (16), (17), (18) and (19), the value displayed also factors in an
insufficient grid voltage, where applicable, and the associated reduction in
20
23 22 21
24
26 25
Fig. 4.21: "Reactive power" tab option in the “Limit” menu option
20. Status field for indicating the active reactive power limit at the current time
(e.g. if the PVMaster device has already reached its maximum possible
apparent power or, specifically with PVMaster II, it has reached its minimum
power factor of 0.85)
21. Configuration text box for displaying the maximum reactive power of the
PVMaster device in [kVAr]. This configuration text box is generally locked for
entries, as this value cannot be edited.
22. The current total reactive power of the PVMaster device is displayed here in
[kVAr] in a display text box. This value represents the sum of the three cur-
rent phase reactive powers.
23. Status field for displaying currently active reduction of the current reactive
power of the PVMaster device (22) to the maximum reactive power of the
PVMaster device (21).
24. Once the LVRT process is complete (see section 4.3.4.3.3, p. 159), the
reactive power of the PVMaster device is reduced for a certain period of
time so that the PVMaster is not more underexcited in its reaction when the
grid voltage is restored than it was before the fault occurred. The status field
indicates the status of this reduction function accordingly.
25. The maximum chronological change in the reactive power of the PVMaster
device in [kVAr/s] is displayed in this configuration text box. This configura-
tion text box is generally locked for entries, as this value cannot be edited.
26. Status field for displaying the current status of the reactive Limit to limit the
rate of change in the reactive power in accordance with (25).
The statuses and values for all apparent Limit functions are displayed within the
third tab option, "Apparent power".
27
30 29 28
33 32 31
Fig. 4.22: "Apparent power" tab option in the “Limit” menu option
27. Status field for displaying currently active apparent Limit, e.g. if the rated ap-
parent power of the PVMaster device has been reached (30) or the appar-
ent power of the PVMaster device is active in order to reduce the apparent
power of the entire local InterCOM device network (32).
28. Configuration text box for displaying the rated apparent power of the PV-
Master device in [kVA]. The rated apparent power of the PVMaster device is
also the maximum apparent power of the device. This configuration text box
is generally locked for entries, as this value cannot be edited.
29. The current total apparent power of the PVMaster device is displayed here
in [kVA] in a display text box. This value represents the sum of the three cur-
rent phase apparent powers.
30. Status field for displaying currently active reduction of the current appar-
ent power of the PVMaster device (29) to the rated apparent power of the
PVMaster device (28).
31. Display of the set maximum value for the apparent power in [kVA] of the
total local InterCOM device network in a configuration text box. This configu-
ration text box is merely used for display and is generally locked for entries
in this user interface. This setting can be changed in the user interface of
the "General" menu option in the "Grid" menu sub-group of the "Configura-
tion" menu group (section 4.3.4.2.1, p. 115).
32. The current total apparent power of the entire local InterCOM device net-
work is shown here in a display text box in [kVA].
33. Status field for displaying currently active reduction of the current apparent
power of the entire local InterCOM device network (32) to the set maximum
value for the apparent power for the entire local InterCOM device network
(31).
4.3.2.4.4 Energy
The user interface for the "Energy" menu option in the "Grid" menu sub-group
of the "Status and Values" menu group is used to display the energy values
achieved so far (fed-in energy) by the PVMaster device, device network or total
plant, as applicable.
NOTE
The device settings for determining energy, the correction of energy meter
values and editing conversion factors and the currency to be used for the pay-
ment display can be configured in the "Energy" menu option in the "Grid" menu
sub-group of the "Configuration" menu group (section 4.3.4.2.2, p. 118).
1 2
Fig. 4.23: U
ser interface of the "Energy" menu option in the "Status and Values"
menu group
The energy values achieved so far by the PVMaster device are displayed in the
“Inverter unit” tab option.
If a red link button is shown next to a display text box, this indicates that
this value has been recorded as standard by the integrated data logger
and that the corresponding recorded historical energy data can be called
up in the diagram generator. Pressing this link button calls up the cor-
responding user interface to display the energy diagrams (section 4.3.3,
p. 86).
1. The evaluation/counting of the energy fed in so far or the energy of the
PVMaster device can be implemented by evaluating the S0 pulse output of
an installed meter. To do this, the digital input used in the PVMaster device
must be assigned with the corresponding function (function 34 in Tab. 4.19,
p. 168, see section 4.3.4.4.1, p. 166). If an S0 pulse input is not evaluat-
ed, the energy forecast is implemented automatically through integration of
the measured grid-side active power. The option field shows the applicable
method used for energy determination of the PVMaster device. This option
field is for display purposes only.
2. If the fed-in energy is evaluated by evaluating the S0 pulse output of an
installed meter and if the PVMaster device digital output used for the
evaluation has been assigned the appropriate function (function 34 in Tab.
4.19, p. 168, see section 4.3.4.4.1, p. 166), then the recorded pulses are
displayed in this status field. The S0 pulse counting can be configured in the
"Energy" menu option within the "Grid" menu sub-group of the "Configura-
tion" menu group (section 4.3.4.2.2, p. 118).
NOTE
It is possible that not every recorded pulse will be displayed via this status
field; this will depend on the current frequency of the S0 pulse interface and
the quality of the connection between the PVMaster device and the local PC.
3. A display text box is used here to display the energy fed in so far by the
PVMaster device or the energy for the current day in [kWh]. The day energy
value can be corrected manually in the "Energy" menu option within the
"Grid" menu sub-group of the "Configuration" menu group (section 4.3.4.2.2,
p. 118). The energy fed in so far by the PVMaster device, or day energy in
[kWh], is also displayed in the start user interface “Overview” (section 4.3.1,
p. 39).
4. Display of the energy fed in so far by the PVMaster device or the energy for
the current month in [kWh] in a display text box. The month energy value
can be corrected manually in the "Energy" menu option within the "Grid"
menu sub-group of the "Configuration" menu group (section 4.3.4.2.2,
p. 118). The energy fed in so far by the PVMaster device, or month en-
ergy in [kWh], is also displayed in the start user interface “Overview” (sec-
tion 4.3.1, p. 39).
5. A display text box is used here to display the energy fed in so far by the PV-
Master device or the energy for the current year in [kWh]. The year energy
value can be corrected manually in the "Energy" menu option within the
"Grid" menu sub-group of the "Configuration" menu group (section 4.3.4.2.2,
p. 118).
6. Display of the total energy fed in so far by the PVMaster device, or energy in
[kWh], in a display text box. The total energy value can be corrected manu-
ally in the "Energy" menu option within the "Grid" menu sub-group of the
"Configuration" menu group (section 4.3.4.2.2, p. 118).
The total energy fed in so far by the PVMaster device, or energy in [kWh], is
also displayed in the "Overview" start user interface (section 4.3.1, p. 39).
7. This display text box is used to display the total CO2 avoidance in [kg]
achieved so far by the PVMaster device. The displayed value is derived
from the conversion of the total energy fed in so far or the energy (6) pro-
duced by the PVMaster device with a predefined conversion factor. The
conversion factor used can be edited with the "Energy" menu option in the
"Grid" menu sub-group of the "Configuration" menu group (section 4.3.4.2.2,
p. 118).
8. The total payment achieved by the PVMaster device in the set currency
is displayed here. The displayed value is derived from the conversion of
the total energy fed in so far or the energy (6) produced by the PVMaster
device with a predefined payment factor. The payment factor used, and
the currency displayed, can be edited with the "Energy" menu option in the
"Grid" menu sub-group of the "Configuration" menu group (section 4.3.4.2.2,
p. 118).
If the S0 pulse output of an installed higher-level meter used to meter the total
energy of the total plant is evaluated by a PVMaster device digital input and this
digital input used for the evaluation has been assigned the appropriate function
(function 35 in Tab. 4.19, p. 168, see section 4.3.4.4.1, p. 166), then a second
tab option "Total plant" can be selected (Fig. 4.24). This tab option then displays
the energy values achieved so far by the device network or the total plant.
9 10
11
12
13
14
15
16
Fig. 4.24: "Total plant" tab option in the "Energy" menu option
9. The activation field indicates whether an S0 pulse output of an installed
higher-level meter used to meter the total energy of the total plant is evalu-
ated via a PVMaster device digital input or if a PVMaster device digital input
has been assigned the relevant function (function 35 in Tab. 4.19, p. 168,
see section 4.3.4.4.1, p. 166).
10. This status field displays the pulses recorded by the S0 pulse interface.
The S0 pulse counting is configured in the "Energy" menu option within the
"Grid" menu sub-group of the "Configuration" menu group (section 4.3.4.2.2,
p. 118).
NOTE
It is possible that not every recorded pulse will be displayed via this status
field; this will depend on the current frequency of the S0 pulse interface and
the quality of the connection between the PVMaster device and the local PC.
11. A display text box is used here to display the energy fed in so far by the en-
tire device network or total plant, or the energy for the current day in [kWh].
The day energy value can be corrected manually in the "Energy" menu
option within the "Grid" menu sub-group of the "Configuration" menu group
(section 4.3.4.2.2, p. 118).
12. Display of the energy fed in so far by the entire device network or total
plant, or the energy for the current month in [kWh] in a display text box. The
month energy value can be corrected manually in the "Energy" menu option
within the "Grid" menu sub-group of the "Configuration" menu group (sec-
tion 4.3.4.2.2, p. 118).
13. A display text box is used here to display the energy fed in so far by the en-
tire device network or total plant, or the energy for the current year in [kWh].
The year energy value can be corrected manually in the "Energy" menu
option within the "Grid" menu sub-group of the "Configuration" menu group
(section 4.3.4.2.2, p. 118).
14. Display of the total energy fed in so far by the entire device network or total
plant, or energy in [kWh], in a display text box. The total energy value can
be corrected manually in the "Energy" menu option within the "Grid" menu
sub-group of the "Configuration" menu group (section 4.3.4.2.2, p. 118).
15. This display text box is used to display the total CO2 avoidance in [kg]
achieved so far by the entire device network or total plant. The displayed
value is derived from the conversion of the total energy fed in so far or the
energy (6) produced by the entire device network or total plant with a prede-
fined conversion factor. The conversion factor used can be edited with the
"Energy" menu option in the "Grid" menu sub-group of the "Configuration"
menu group (section 4.3.4.2.2, p. 118).
16. The total payment achieved so far by the entire device network or total plant
in the set currency is displayed here. The displayed value is derived from
the conversion of the total energy fed in so far or the energy (6) produced
by the entire device network or total plant with a predefined payment factor.
The payment factor used, and the currency displayed, can be edited with
the "Energy" menu option in the "Grid" menu sub-group of the "Configura-
tion" menu group (section 4.3.4.2.2, p. 118).
4.3.2.4.5 Monitoring
The user interface for the "Monitoring" menu option (Fig. 4.25) in the "Grid"
menu sub-group of the "Status and Values" menu group contains elements for
displaying the current status of the integrated grid monitoring functions. Moni-
toring settings cannot be edited in this user interface. It is for display purposes
only.
NOTE
A detailed display of the current state of the integrated grid monitoring and
the respective settings for the grid monitoring functions is given in the user
interlace for the "Monitoring" menu option in the "Grid" menu sub-group of the
"Configuration" menu group (section 4.3.4.2.3, p. 124). The respective set-
tings for the grid monitoring functions can be edited in this user interface from
the "Fitter" user level upwards.
1
2
3 4 5
Fig. 4.25: U
ser interface of the "Monitoring" menu option in the "Status and
Values" menu group
1. The country code ("Grid code") used to initialise functions and limit values
of the integrated grid monitoring functions is displayed here in plain text in a
display text box.
2. Activation field for indicating whether parameters or limit values for the grid
monitoring functionalities were changed manually for a country code ("Grid
code") after initialisation and as result differ from the parameters or limit val-
ues stored for the country code ("Grid code"). This activation field is gener-
ally locked for changes and is merely intended for display purposes.
3. Display of rated grid voltage in [V] in a configuration text box. The limit value
percentages of the grid voltage monitoring functions (section 4.3.4.2.3,
p. 124) and grid voltage-dependent network support functions (sec-
tion 4.3.4.3, p. 147) are based on this rated value. This configuration text
box is merely used for display and is generally locked for entries in this user
interface. This setting can be edited in the user interface for the "General"
menu option in the "Grid" menu sub-group of the "Configuration" men (sec-
tion 4.3.4.2.1, p. 115) or in the user interface of the "Monitoring" menu
option in the "Grid" menu sub-group of the "Configuration" menu group (sec-
tion 4.3.4.2.3, p. 124).
4.3.2.5 Temperatures
A few important temperature values in the PVMaster device are measured to
monitor correct operation of the device. The user interface for the "Tempera-
tures" menu option (Fig. 4.26) in the "Status and Values" menu group contains
a display of all temperature measurements for the PVMaster device. Depend-
ing on some of these measured values, a temperature-dependent reduction
of the present device current (derating) takes place at elevated temperatures,
for example, to protect components inside the device against overheating. At
extremely high temperature levels, it is possible that the device will be deacti-
vated and the corresponding error state will be triggered (see section 4.3.5.1,
p. 221).
NOTE
Only temperature values measured internally in the PVMaster device or re-
corded via the PT100 or analogue inputs of the PVMaster are displayed in this
user interface. Temperature measurements via the PT100 inputs of connected
String Combiner Boxes (SCBs) are displayed in the "String currents" menu
option within the "PV generator" menu sub-group of the "Status and Values"
menu group (section 4.3.2.3.3, p. 56).
REFERENCE
A description of the available PT100 inputs and analogue inputs of the PVMas-
ter device, and information about the options for connecting further tempera-
ture sensors and measurements can be found in the respective PVMaster
installation manual.
If a red link button is shown next to a display text box, this indicates that
this value has been recorded as standard by the integrated data logger
and that the corresponding recorded day history data can be called up in
the diagram generator. Pressing this link button calls up the corresponding
user interface to display the day history data (section 4.3.3.1.1, p. 86).
1 6
2 7
3 8
4 9
5 10
11
Fig. 4.26: U
ser interface of the "Temperatures" menu option in the "Status and
Values" menu group
1. The current heat sink temperature of the basic device in the PVMaster en-
closure is displayed here in [°C] in a display text box. If the values obtained
from this temperature measurement are elevated, a temperature-dependent
reduction of the present device current (derating) takes place to protect
components inside the device against overheating. If the heat sink tem-
perature is extremely high, it is possible that the device will be deactivated
and the corresponding error state will be triggered (ID 06/01, see Tab. 4.31,
p. 224).
NOTE
For PVMaster devices with liquid cooling, the rise in temperature of the heat
sink temperature in the basic device is also monitored and, in the case of sud-
den changes in the temperature, the corresponding error state is triggered (ID
06/02, see Tab. 4.31, p. 224). With PVMaster III devices, the rise in capacitor
temperature in the basic device is also monitored and, when there are sudden
changes in the temperature, the corresponding error state is triggered.
2. Display of the temperature of the capacitor at the current time inside the
basic device in the PVMaster enclosure in [°C] in a display text box. If the
capacitor temperature measurement is very high, the device current at the
current time is reduced according to the temperature (derating) in order to
protect components inside the device from overheating. If the temperature
of the power stage is extremely high, the device may be disabled and the
corresponding error state triggered.
3. Display of the current temperature inside the basic device in the PVMaster
enclosure in [°C] in a display text box. If the values obtained from this tem-
perature measurement are elevated, a temperature-dependent reduction
of the present device current (derating) takes place to protect components
inside the device against overheating. If the temperature inside the basic
device is extremely high, it is possible that the device will be deactivated
and the corresponding error state will be triggered (ID 06/03, Tab. 4.31,
p. 224, see section 4.3.5.1, p. 221).
4. Display of the current temperature of the filter inductor in the PVMaster
enclosure in [°C] in a display text box. If the values obtained from this tem-
perature measurement are elevated, a temperature-dependent reduction
of the present device current (derating) takes place to protect components
inside the device against overheating. If the temperature of the filter inductor
is extremely high, it is possible that the device will be deactivated and the
corresponding error state will be triggered (ID 06/04, Tab. 4.31, p. 224, see
section 4.3.5.1, p. 221).
5. Display text box for displaying the measured transformer temperature in
[°C]. If the values obtained from this temperature measurement are el-
evated, a temperature-dependent reduction of the present device current
(derating) takes place to protect the transformer and components inside the
device against overheating. If the temperature of the transformer is extreme-
ly high, it is possible that the PVMaster device will be deactivated and the
corresponding error state will be triggered (ID 06/05, Tab. 4.31, p. 224, see
section 4.3.5.1, p. 221).
PVMaster TT/EN only For PVMaster devices with an integrated low-voltage transformer (TT model
series) or external low-voltage transformer (EN model series), the measured
transformer temperature is always displayed in this display text box.
PVMaster EM only For PVMaster devices with an external medium-voltage transformer, the
measured transformer temperature in [°C] is displayed in this display text
box if the temperature sensor is evaluated via a PT100 input of the PVMas-
ter device and this PT100 input has been assigned the corresponding func-
tion (function 2 in Tab. 4.24, p. 194, see section 4.3.4.4.3.1, p. 193).
The transformer temperature is also displayed if this temperature value is
supplied by another InterCOM node in a local InterCOM device network
(function 0 in Tab. 4.28, p. 207, section 4.3.4.5.2, p. 206).
The measured value for the transformer temperature must be available and
displayed here (by means of direct measurement via a PT100 input or via
InterCOM device intercommunication) in order for the value to be monitored
and for the requisite temperature-dependent reduction of the present device
current (derating), where applicable, or the excess temperature shutdown
function to be monitored.
ATTENTION
In a device network with several PVMaster devices and the use of a com-
mon medium-voltage transformer, the temperature-dependent derating of
the current can only effectively protect the transformer against overheating if
the transformer temperature is known for all PVMaster devices in the device
network and as a result all devices are involved in the reduction of the present
current.
All devices 6. The current temperature inside the enclosure is displayed here in [°C] in a
display text box.
The temperature sensor required for this is available in each PVMaster as
standard and is evaluated via a PT100 input on the device. To this end, the
corresponding PT100 input of the device is assigned the corresponding
function as standard (no. 3 in Tab. 4.24, p. 194, section 4.3.4.4.3, p. 189).
There is also the option of using the PT100 input used for this to measure
another temperature if the number of free PT100 inputs is not sufficient for
temperature measurements required by the user.
7. Display of the measured value for an optional “Outdoor” temperature meas-
urement via a PT100 input of the PVMaster device in [°C] in a display text
box. This temperature is only displayed if a corresponding temperature sen-
sor has been connected to a PT100 input of the PVMaster device and this
PT100 input has been assigned the relevant function (no. 8 in Tab. 4.24,
p. 194, section 4.3.4.4.3.1, p. 193).
8. Display of the measured value for an optional “Cabinet ambient” tempera-
ture measurement via an PT100 input of the PVMaster device in [°C] in
a display text box. This temperature is only displayed if a corresponding
temperature sensor has been connected to a PT100 input of the PVMaster
device and this PT100 input has been assigned the relevant function (no. 6
in Tab. 4.24, p. 194, section 4.3.4.4.3.1, p. 193).
9. Display of the measured value for an optional “Station interior” temperature
measurement via a PT100 input of the PVMaster device in [°C] in a display
text box. This temperature is only displayed if a corresponding temperature
sensor has been connected to a PT100 input of the PVMaster device and
this PT100 input has been assigned the relevant function (no. 7 in Tab.
4.24, p. 194, section 4.3.4.4.3.1, p. 193).
10. Display of the measured value for an optional “Transformer ambient” tem-
perature measurement via a PT100 input of the PVMaster device in [°C]
in a display text box. This temperature is only displayed if a corresponding
temperature sensor has been connected to a PT100 input of the PVMaster
device and this PT100 input has been assigned the relevant function (no. 5
in Tab. 4.24, p. 194, section 4.3.4.4.3.1, p. 193).
11. The optional temperature measurements "Main Combiner Box 1" to "Main
Combiner Box 4" obtained via the PT100 inputs of the PVMaster device
are displayed in [°C] in display text boxes in the "Main Combiner Box" tab
option. These temperature values are only displayed if corresponding tem-
perature sensors have been connected to PT100 inputs of the PVMaster
device and these PT100 inputs have been assigned the relevant functions
(nos. 9, 10, 11 and 12 in Tab. 4.24, p. 194, section 4.3.4.4.3.1, p. 193).
11
12
Fig. 4.27: "Module temperature" tab option of the "Temperatures" user interface
12. Display of the measured value for an optional module temperature meas-
urement "Module temperature M1" via an analogue input of the PVMaster
device in [°C] in a display text box. This temperature is only displayed if
a corresponding temperature measurement is evaluated via an analogue
input of the PVMaster device and this analogue input has been assigned the
relevant function (no. 12 in Tab. 4.23, p. 190, section 4.3.4.4.3, p. 189).
13. Display of the measured value for an optional module temperature meas-
urement "Module temperature M2" via an analogue input of the PVMaster
device in [°C] in a display text box. This temperature is only displayed if
a corresponding temperature measurement is evaluated via an analogue
input of the PVMaster device and this analogue input has been assigned the
relevant function (no. 13 in Tab. 4.23, p. 190, section 4.3.4.4.3, p. 189).
13 15
14
Fig. 4.28: “Ext. Temperature” tab option of the "Temperatures" user interface
14. Display of measured value for an optional temperature measurement "Tem-
perature Ext. 1" via an analogue input of the PVMaster device in [°C] in a
display text box. This temperature is only displayed if a corresponding tem-
perature measurement is evaluated via an analogue input of the PVMaster
device and this analogue input has been assigned the relevant function (no.
14 in Tab. 4.23, p. 190, section 4.3.4.4.3, p. 189).
1 2 3 4 5
Fig. 4.29: U
ser interface of the “Dig. Inputs” menu option in the "Status and
Values" menu group
1. Display of assignment numbers of the respective digital inputs of the PV-
Master device in display text boxes.
NOTE
The number of available digital inputs varies according to the PVMaster device
type.
2. The current physical statuses of the respective digital inputs are displayed in
these status fields.
3. If a logical inversion is activated via the configuration of the digital inputs
(section 4.3.4.4.1, p. 166), this setting is displayed accordingly via these
activation fields of the respective digital inputs.
4. The respective assigned functions of the digital inputs are displayed in these
display text boxes as plain text. The possible functions of digital inputs are
listed and described in Tab. 4.19, p. 168 (section 4.3.4.4.1, p. 166).
5. These status fields indicate the respective function status dependent on
the physical status of the respective digital inputs and taking account of any
activated logical inversion of the signal status.
1 2 3 4
Fig. 4.30: U
ser interface of the “Dig. Outputs” menu option in the "Status and
Values" menu group
1. Display of assignment numbers of the respective digital outputs of the PV-
Master device in display text boxes.
NOTE
The number of available digital outputs varies according to the PVMaster
device type.
1 2 3 4 5
Fig. 4.31: U
ser interface of the “Ana. Inputs” menu option in the "Status and
Values" menu group
1. Display of assignment numbers of the respective analogue inputs of the
PVMaster device in display text boxes.
NOTE
The number of available analogue inputs varies according to the PVMaster
device type.
2. The current unscaled analogue raw values for the respective analogue
inputs of the PVMaster device are displayed here in display text boxes.
3. Display of physical unit of displayed analogue raw values for the respective
analogue inputs in display text boxes as plain text. The respective displayed
unit corresponds to the respective configuration of the signal type for the
analogue signal (section 4.3.4.4.3, p. 189).
4. The respective assigned functions of the analogue inputs are displayed in
these display text boxes as plain text. The possible functions of analogue
inputs are listed and described in Tab. 4.23, p. 190 (section 4.3.4.4.3,
p. 189).
5. The respective function value is displayed here in display text boxes in the
corresponding unit for the function. The value displayed corresponds to the
filtered and scaled analogue raw value, in accordance with the configuration
of the respective analogue input (section 4.3.4.4.3, p. 189).
4.3.3.1 Day
The menu options in the "Day" menu sub-group of the "History and Statistics"
menu group are used to retrieve, display and process recorded values through
the integrated data logger. This "day history data" for a selectable day can be
displayed graphically using the relevant diagram functions or displayed in tabu-
lar form.
NOTE
The individual day history data, recorded by the integrated data logger, is
retained for retrieval for a total of 365 days. Older data cannot be retrieved via
the operator application.
4.3.3.1.1 Diagram
The user interface of the first menu option "Diagram" (Fig. 4.32) in the "Day"
menu sub-group allows recorded measured values for a selectable day to be
retrieved, displayed and processed.
1 2
3
4 5 6 7 8 9
10
Fig. 4.32: U
ser interface of the "Diagram" menu option in the "History and Sta-
tistics" menu group
1. This is where the required day or date for which the recorded values are to
be displayed is selected. The date can be selected and configured either via
the calendar function or by means of manual entries within the configuration
text box. However, only days in the past can be selected. Furthermore, it is
not possible to retrieve recorded values that are older than 365 days.
2. This selection box is used to specify the number of days to be displayed
from the desired day or date. You can select a maximum of 7 days. The
waiting times may increase correspondingly, depending on the choice of
days to display and the connection quality between the PVMaster device
and the local PC.
3. Three tab options are available in the user interface. The first tab option
"Diagram" (Fig. 4.32) contains a diagram generator for graphic representa-
tion of recorded data. The second tab option "Table" (Fig. 4.33, p. 89) is
used for tabular representation of the values and for saving the retrieved
day history data to the local PC. The last "User-defined signals" tab option
(Fig. 4.34) is used to configure up to four user-defined signals to be record-
ed by the integrated data logger.
4. The display of the selected signal in the left-hand scale of the diagram can
be activated or deactivated via this activation field.
5. Selection box for selecting the required signal on the left-hand scale of the
diagram. All the values and signals available as standard are listed and
described in Tab. 4.14, p. 91.
NOTE
Changes to the required signal via this selection box will not result in signifi-
cant waiting times, as all signals and values for a given day are always loaded
at the same time.
6. Selection box for selecting the signal colour to be used for the left-hand
scale of the diagram. The selected colour is used to label the left-hand scale
and for the corresponding signal.
7. The display of the second selected signal in the right-hand scale of the dia-
gram can be activated or deactivated via this activation field.
8. Selection box for selecting the second required signal on the right-hand
scale of the diagram. All the values and signals available as standard are
listed and described in Tab. 4.14, p. 91.
NOTE
Changes to the required signal via this selection box will not result in signifi-
cant waiting times, as all signals and values for a given day are always loaded
at the same time.
9. Selection box for selecting the signal colour to be used for the right-hand
scale of the diagram. The selected colour is used to label the right-hand
scale and for the corresponding signal.
10. The selected signals for the chosen date and the selected number of days
are displayed in the diagram in their selected colours. The overall signal
progression over the entire selected day or selected days is constantly dis-
played in the top section of the diagram. The left-hand and right-hand scales
are always scaled in the top section of the diagram such that the overall
signal progression is shown in full. The position and width of the window
shown in this section above the signal progression can be varied accord-
ingly. The user can determine the section of the signal progression to be
displayed in the bottom section of the diagram by adjusting the position and
width of this window. The left-hand and right-hand scales on the lower sec-
tion of the diagram are always configured such that selected section of the
selected signals is displayed in full. This creates a corresponding enlarge-
ment effect to allow partial sections of the day history data to be analysed in
more depth.
The second tab option “Table” (Fig. 4.33) is used for tabular presentation of the
values and for saving the retrieved day history data to the local PC.
12
11
The last "User-defined signals" tab option (Fig. 4.34) is used to configure up to
four user-defined signals to be recorded by the integrated data logger.
13 14
15 16
Fig. 4.34: "User-defined signals" tab option in the "Diagram" menu option
13. The respective signal names of the user-defined signals, via which the se-
lection in the diagram generator or the display in tabular view is performed,
are displayed here. A total of up to four user-defined signals ("User 1" to
"User 4") can be configured.
Changes from 14. The four user-defined signals to be recorded by the integrated data logger
Fitter are assigned via these selection boxes ("mapping"). The selection boxes
contain predefined signals for selection. The predefined signals available in
the selection boxes are listed and described in Tab. 4.15, p. 92. Following
selection of a predefined signal via these selection boxes, the correspond-
ing parameter ID is displayed in the relevant configuration text box (15) and
the corresponding parameter sub-ID in the respective configuration text box
(16). Alternatively, "User-defined" can be selected from the list in the selec-
tion box, and then the parameter ID and parameter sub-ID for the required
signal or parameter is entered manually via the configuration text boxes (15)
and (16).
15. Configuration text boxes for displaying and configuring the parameter ID for
the respective required signal or parameter for assignment ("mapping") to
a user-defined signal to be recorded by the integrated data logger. When
predefined signals are selected from selection box (14), only the parameter
ID is displayed and the configuration text box is locked for entries. If "User-
defined" is selected from the list in the selection box (14), the parameter
ID for the required signal or parameter must be entered manually via the
configuration text box.
16. Configuration text boxes for displaying and configuring the parameter sub-
ID for the respective required signal or parameter for assignment ("map-
ping") to a user-defined signal to be recorded by the integrated data logger.
When predefined signals are selected from the selection box (14), only the
parameter sub-ID is displayed and the configuration text box is locked for
entries. If "User-defined" is selected from the list in the selection box (14),
the parameter sub-ID for the required signal or parameter must be entered
manually via the configuration text box.
Tab. 4.14: Available signals and values recorded by the data logger
No. Description Description Table
0 DC voltage [V] DC generator voltage in [V] Vdc
1 DC current [A] DC generator current in [A] Idc
2 DC power [kW] DC generator power in [W] Pdc
Linked grid voltage as average value for the three linked
3 AC voltage [V] Uac
grid voltages in [V]
Average value for the measured grid currents for the three
4 AC current [A] Iac
phases in [A]
Total active power as a sum of the three phase active pow-
5 AC power [kW] Pac
ers in [W]
Power factor as an average value for the power factors for
6 Power factor cosPhi
all three phases
Total reactive power as a sum of the three phase reactive
7 Reactive power [kVAr] Q
powers in [kVAr]
8 Grid frequency [Hz] Grid frequency in [Hz] Freq
9 Temperature transformer [°C] Temperature of transformer in [°C] T_Transf
10 Temperature filter choke [°C] Temperature of filter inductor in [°C] T_Choke
11 Temperature heat sink [°C] Temperature of heat sink of basic device in [°C] T_Heats
12 Temperature cabinet [°C] Temperature inside enclosure in [°C] T_Cabinet
Optional Temperature Ext. measurement via a PT100 input
13 Temperature External [°C] T_Ext
of the PVMaster in [°C]
Solar radiation G1 via an analogue input of the PVMaster in
14 Irradiation 1 [W/m²] Irrad_1
[W/m²]
Solar radiation G2 via an analogue input of the PVMaster in
15 Irradiation 2 [W/m²] Irrad_2
[W/m²]
Module temperature M1 via an analogue input of the PV-
16 Module temperature 1 [°C] T_M1
Master in [°C]
Module temperature M2 via an analogue input of the PV-
17 Module temperature 2 [°C] T_M2
Master in [°C]
Temperature Ext. Ext1 via an analogue input of the PVMas-
18 External temperature 1 [°C] T_Ext1
ter in [°C]
Temperature Ext. Ext1 via an analogue input of the PVMas-
19 External temperature 2 [°C] T_Ext2
ter in [°C]
Wind speed V1 via an analogue input of the PVMaster in Wind_
20 Wind speed 1 [m/s]
[m/s] Speed1
Wind speed V2 via an analogue input of the PVMaster in Wind_
21 Wind speed 2 [m/s]
[m/s] Speed2
Wind direction D1 via an analogue input of the PVMaster in
22 Wind direction 1 [°] Wind_Dir1
[°]
Wind direction D2 via an analogue input of the PVMaster
23 Wind direction 2 [°] Wind_Dir2
in[°]
24 User-defined signal 1 User-defined signal, recorded by the data logger User1
25 User-defined signal 2 User-defined signal, recorded by the data logger User2
26 User-defined signal 3 User-defined signal, recorded by the data logger User3
27 User-defined signal 4 User-defined signal, recorded by the data logger User4
NOTE
The integrated data logger for this SCB day history data works with a cycle
time of fifteen minutes. This is therefore the highest possible time resolution for
representation in the diagram or table.
2 1
3
6
7
5
Fig. 4.35: U
ser interface of the "String currents" menu option in the "History and
Statistics" menu group
1. This is where the required day or date for which the recorded values from
the respective SCB are to be displayed is selected. The date can be select-
ed and configured either via the calendar function or by means of manual
entries within the configuration text box. However, only days in the past can
be selected. Furthermore, it is not possible to retrieve recorded values that
are older than 365 days.
2. Selection box for selecting the SCB for displaying the corresponding SCB
day history data within the user interface. Only those SCBs that have been
activated via the configuration (section 4.3.4.6, p. 210) can be selected
within this selection box.
3. Two tab options are available in the user interface. The first tab option "Dia-
gram" (Fig. 4.35) contains a diagram generator for graphic representation of
recorded SCB day history data. The second tab option "Table" (Fig. 4.36) is
used for tabular representation of the values and saving the retrieved SCB
history data to the local PC.
4. The diagram area is located in the upper section of the "Diagram" tab
option. The selected string currents (5) for the selected SCBs (2) for the se-
lected day (1) are shown here in their respective colours, with the left-hand
scale representing the scaling of the string currents in [mA]. The scaling is
always configured such that all selected string currents are displayed fully
in the diagram. In addition, there is also the option of displaying another
recorded signal (solar radiation, wind speed or temperature) in the dia-
gram, selectable from the selection box (6), with the right-hand scale in the
diagram representing the scaling of the selected signal. The colour of the
selected signal and the right-hand scale is the same as the colour selected
in the selection box (7).
5. The string currents to be displayed in the diagram (4) are selected via these
fifteen activation fields. The activated string currents are shown in the dia-
gram in their respective colours.
6. Selection box for selecting a further recorded SCB signal (solar radiation,
wind speed or temperature) for displaying in the diagram (4). The selected
signal is then displayed in the diagram in the colour selected in the selection
box (7), with the right-hand scale in the diagram representing the scaling of
the signal.
7. Selection box for selecting the colour to be used for the signal in the dia-
gram chosen via the selection box (6) and for the right-hand scale of the
diagram.
8. The displayed diagram is not updated automatically. If the current date has
been selected via (1), the diagram can be updated by pressing this button,
in order to have new SCB values recorded by the data logger included in
the diagram.
The second tab option "Table" (Fig. 4.36) is used for tabular representation of
the values and for saving the retrieved SCB day history data to the local PC.
10
9
Fig. 4.36: "Table" tab option in the "String currents" menu option
9. The "scrollable" table field for a tabular display of the values recorded for
the SCB for the selected day (1), selected via the selection box (2), contains
a separate column for each string current channel (I01 to I15). There are
up to fifteen string current values and these are displayed in [mA]. The last
three columns are used for displaying
a) the solar radiation (G0) in [W/m²]
b) the wind speed (W_V0) in [m/s]
c) the measured temperature (T0) in [°C].
The time stamp for the recorded values, consisting of the date and time, is
always displayed in the first column.
10. The values for the selected day (1) for the SCB selected via the selection
box (2), shown in the table field (9) can be saved to the local PC in a .csv
file. This button opens a file browser on the local PC in order to specify a
destination location and file name for the .csv file.
4.3.3.2 Month
The user interface for the "Month" menu option (Fig. 4.37) in the "History and
Statistics" menu group is used to retrieve, display and process the day energy
values of the PVMaster device recorded by the integrated data logger. The day
energy values for a selectable month can be displayed graphically using the ap-
propriate bar chart function or be displayed in tabular form.
1
2
4 5 6
Fig. 4.37: U
ser interface of the "Month" menu option in the "History and Statis-
tics" menu group
1. The required month for which the recorded day energy values of the PV-
Master device are to be displayed in an overview is selected here. The
month is selected via two selection boxes that can be used to select the
required year and month.
2. Two tab options are available in the user interface. The first tab option "Dia-
gram" (Fig. 4.37) contains a bar chart generator for representation of the
individual day energy values of the PVMaster device. The second tab option
"Table" (Fig. 4.38) is used for tabular representation of the values and for
saving the retrieved day energy values to the local PC.
3. The day energy values for the month selected via (1) - up to 31 - are repre-
sented in a bar chart in the diagram area of the "Diagram" tab option. The
bar chart is always scaled such that the highest day energy value for the
selected month is also shown in full.
4. Selection box for selecting the values to be displayed in the bar chart. The
"Energy [kWh]" is selected from the list as standard here, which means that
the day energy values for the selected month will be represented as energy
in [kWh] in the bar chart displayed. Alternatively, the calculated values for
the CO2 avoidance in [kg] or the calculated payment in the set currency can
be displayed in the bar chart. The conversion factors set and used accord-
ingly are indicated in the configuration text boxes (5) and (6).
5. Display of the set conversion factor for calculating the CO2 avoidance from
an energy value in a configuration text box. This configuration text box
is only used for display purposes and is generally locked for entries. The
conversion factor used can be edited with the "Energy" menu option in the
"Grid" menu sub-group of the "Configuration" menu group (section 4.3.4.2.2,
p. 118).
6. Display of the set conversion factor for calculating the payment from an
energy value in a configuration text box. This configuration text box is only
used for display purposes and is generally locked for entries. The conver-
sion factor used can be edited with the "Energy" menu option in the "Grid"
menu sub-group of the "Configuration" menu group (section 4.3.4.2.2,
p. 118).
7. Display of total energy in [kWh] for the selected month.
The second tab option "Table" (Fig. 4.38) is used for tabular representation of
the values and saving the retrieved day energy values for the selected month to
the local PC.
4.3.3.3 Year
The user interface for the "Year" menu option (Fig. 4.39) in the "History and
Statistics" menu group is used to retrieve, display and process the month en-
ergy values of the PVMaster device recorded by the integrated data logger. The
month energy values for a selectable year can be displayed graphically using
the appropriate bar chart function or be displayed in tabular form.
1
2
4 5 6
Fig. 4.39: U
ser interface of the "Year" menu option in the "History and Statis-
tics" menu group
1. The required year for which the recorded month energy values of the PV-
Master device are to be displayed in an overview is selected here in a selec-
tion box.
2. Two tab options are available in the user interface. The first tab option
"Diagram" (Fig. 4.39) contains a bar chart generator for representation of
the individual month energy values of the PVMaster device. The second tab
option "Table" is used for tabular representation of the values and for saving
the retrieved month energy values to the local PC.
3. The month energy values for the year selected via (1) - up to 12 - are rep-
resented in a bar chart in the diagram area of the "Diagram" tab option. The
bar chart is always scaled such that the highest month energy value for the
selected year is also shown in full.
4. Selection box for selecting the values to be displayed in the bar chart. The
"Energy [kWh]" is selected from the list as standard here, which means that
the month energy values for the selected year will be represented as energy
in [kWh] in the bar chart displayed. Alternatively, the calculated values for
the CO2 avoidance in [kg] or the calculated payment in the set currency can
be displayed in the bar chart. The conversion factors set and used accord-
ingly are indicated in the configuration text boxes (5) and (6).
5. Display of the set conversion factor for calculating the CO2 avoidance from
an energy value in a configuration text box. This configuration text box
is only used for display purposes and is generally locked for entries. The
conversion factor used can be edited with the "Energy" menu option in the
"Grid" menu sub-group of the "Configuration" menu group (section 4.3.4.2.2,
p. 118).
6. Display of the set conversion factor for calculating the payment from an
energy value in a configuration text box. This configuration text box is only
used for display purposes and is generally locked for entries. The conver-
sion factor used can be edited with the "Energy" menu option in the "Grid"
menu sub-group of the "Configuration" menu group (section 4.3.4.2.2,
p. 118).
7. Display of total energy in [kWh] for the selected year.
The second tab option "Table" (Fig. 4.40) is used for tabular representation of
the values and saving the retrieved month energy values for the selected year
to the local PC.
4.3.3.4 Total
The user interface for the "Total" menu option (Fig. 4.41) in the "History and
Statistics" menu group is used to retrieve, display and process the year energy
values of the PVMaster device recorded by the integrated data logger. The year
energy values can be displayed graphically using the appropriate bar chart
function or be displayed in tabular form.
2 3 4
Fig. 4.41: U
ser interface of the "Total" menu option in the "History and Statis-
tics" menu group
1. The year energy values for the PVMaster device are represented in a bar
chart in the diagram area. The bar chart is always scaled such that the high-
est year energy value achieved is also shown in full.
2. Selection box for selecting the values to be displayed in the bar chart. The
"Energy [kWh]" is selected from the list as standard here, which means that
the year energy values will be represented as energy in [kWh] in the bar
chart displayed. Alternatively, the calculated values for the CO2 avoidance
in [kg] or the calculated payment in the set currency can be displayed in the
bar chart. The conversion factors set and used accordingly are indicated in
the configuration text boxes (3) and (4).
3. Display of the set conversion factor for calculating the CO2 avoidance from
an energy value in a configuration text box. This configuration text box
is only used for display purposes and is generally locked for entries. The
conversion factor used can be edited with the "Energy" menu option in the
"Grid" menu sub-group of the "Configuration" menu group (section 4.3.4.2.2,
p. 118).
4. Display of the set conversion factor for calculating the payment from an
energy value in a configuration text box. This configuration text box is only
used for display purposes and is generally locked for entries. The conver-
sion factor used can be edited with the "Energy" menu option in the "Grid"
menu sub-group of the "Configuration" menu group (section 4.3.4.2.2,
p. 118).
5. Display of total energy in [kWh] for the PVMaster device.
4.3.4 Configuration
The menu group “Configuration” contains menu options for displaying/configur-
ing the actual device settings and for implementing software updates.
NOTE
Depending on the respective device parameters, changes made via the
corresponding configuration text box are effectively immediately in opera-
tion. However, some parameter changes first need to be permanently saved
(section 4.2.7, p. 26) and a new device start implemented (section 4.2.8,
p. 26) before the changes become effective.
NOTE
Changes to device settings via configuration text boxes (section 4.2.6.2,
p. 25) are only possible, in certain cases, when the software release switch
(section 4.2.5, p. 24) is deactivated. The permanent storage of changed
device settings (section 4.2.7, p. 26), and the manual implementation of
device restarts (section 4.2.8, p. 26), is normally only possible when the
software release switch is deactivated.
4.3.4.1 Device
This menu sub-group contains menu options for displaying general device
data (software versions, operating hours, microSD card status, ... see sec-
tion 4.3.4.1.1, p. 103), implementing software updates, displaying and setting
the system clock (section 4.3.4.1.2, p. 110), and displaying/configuring net-
work settings (section 4.3.4.1.3, p. 112).
4.3.4.1.1 General
The menu option “General” in the menu sub-group “Device” of the menu group
“Configuration” is available as of user level “Observer”. The corresponding user
interface (Fig. 4.42) is used to display the software versions, operating hours
and the status of the microSD card, as well as to implement software updates.
2 3
4 5 6
7 8 9
10 11 12
13 14
15 16
17
Fig. 4.42: U
ser interface of the menu option “General” in the menu sub-group
“General” of the menu group “Configuration”
1. In the section “Device description”, the device description, the device ID and
the article number of the device are displayed in three separate display text
boxes.
2. The software package version appears in this display text box. The soft-
ware package contains all the software components, which have their own
release notes in each case.
as of Fitter 3. This button is used to start the update wizard for running software updates
(section 4.3.4.1.1.1, p. 106). The option field on the right-hand side defines
the procedure for the software update. The software update can be imple-
mented either from the data carrier of the local PC (recommended) or from
the microSD card in the basic device of the PVMaster unit.
4. The firmware version in the main controller of the PVMaster device control
section is shown in this display text box. The main controller carries out the
operational control of the PVMaster device, as well as control processes
and monitoring functions.
NOTE
You may be asked for the firmware version of the main controller if you contact
LTI ReEnergy GmbH Support.
5. This display text box shows the device firmware CRC value (Cyclic Re-
dundancy Check). The check value can be used to detect any errors which
occur during storage or transmission.
6. The boot loader version for the main controller is shown in this display text
box.
7. The firmware version of the communication controller of the PVMaster
device control section is shown here in a display text box. The communica-
tion controller implements the communication tasks (Ethernet, Modbus/TCP,
data logging, DNS Client and FTP Client etc.).
8. This display text box shows the communication software CRC value (Cyclic
Redundancy Check). The check value can be used to detect any errors
which may occur during storage or transmission.
9. The boot loader version for the communication controller is shown in this
display text box.
10. The backup controller firmware version is shown in this display text box. The
backup controller implements monitoring functions in parallel with the main
controller (grid voltages and grid frequency etc.).
11. This display text box shows the ENS software CRC value (Cyclic Redun-
dancy Check). The check value can be used to detect any errors which may
occur during storage or transmission.
12. The ID of the active power stage data record is shown in this display text
box.
13. The version number of the user application (web application) is shown here.
NOTE
When you contact LTI ReEnergy GmbH Support, you may be asked for the
version number of the user application.
14. The software version of the 4.3” touch display (if present) in the enclosure
door of the PVMaster device (Chap. 3.2, Page 11) is shown in this display
text box.
15. The operating hours counter of the PVMaster device is shown in this display
text box, divided into hours and minutes. This counter takes into account the
entire operation (passive/standby and active infeed operation) of the PV-
Master device.
16. The operating hours of the PVMaster device during active infeed mode are
recorded by a separate operating hours counter and shown in this display
text box divided into hours and minutes.
17. The status of the micro SD card in the basic device of the PVMaster device
is shown in this section. The total capacity and the storage space used on
the micro SD card is shown here.
NOTE
To protect the file system of the microSD card from unwanted fragmentation,
most of the files required during the operating time of the device are already
present on the microSD card. There will therefore only be minor changes to
the occupied storage space during the operating time.
The necessary .upa files for the software update are supplied together with
each PVMaster software release (Tab. 4.17, p. 109). In normal cases, the .upa
file “PVM2 00cVx.xxxx ParaRevXX_UpdateComplete.upa” should be used (No.
1 in Tab. 4.17, p. 109).
After starting the update wizard, the user must follow the instructions in the indi-
vidual dialogue boxes in order to implement the software update. The individual
dialogue boxes of the update wizard are described in Tab. 4.16, p. 107.
Tab. 4.16: Procedure for the software update using the update wizard
No. Dialogue Description
After starting the update wizard, the Start dialogue box ap-
pears with two buttons. The update wizard can be closed
Start dia- again with the "Main screen" button. This automatically
1
logue returns the user to the (main) operator application. The next
dialogue box of the update wizard can be called up with the
"Next" button.
This dialogue box (Fig. 4.43, p. 108) is used to select the
.upa file for the software update from the local PC via a
browser. The user can return to the "Start dialogue box"
with the "Back" button. The file browser opens as soon as
"Search for update package" is pressed. After the file has
been selected, the name of the .upa file will be displayed
Dialogue
under the button and the "Install" button will be enabled.
box for
2 The update process is started when the "Install" button is
selection of
pressed and the dialogue box displaying the update pro-
the .upa file
gress is then shown.
This dialogue box is only displayed if the option "Update
from local PC" has been previously selected in the (main)
operator application in the option field (see (11) in Fig. 4.42,
p. 104). Otherwise the dialogue box displaying the update
progress is displayed directly.
Dialogue
After the update procedure has been started, the actual
box dis-
status and progress during the ongoing update procedure is
3 playing
displayed. The update procedure can be stopped using the
the update
"Exit" button (should not normally be used).
progress
When the software update is completed (Fig. 4.44, p. 108),
a display appears to indicate whether the update procedure
was fully and successfully implemented or not. In addition,
all the steps implemented during the update procedure are
displayed, together with all the relevant diagnosis output in
Dialogue the case of an error. The update wizard can be closed by
box after pressing the "Close" button. A dialogue box may appear with
comple- the prompt to delete any temporary files still present in the
4
tion of the internet browser.
update NOTE
procedure
Following a software update which also
updated the operator application (web ap-
plication), the temporary files in the internet
browser must be deleted (see also sec-
tion 4.1.2.1, p. 15).
Fig. 4.43: Dialogue box for selecting the .upa file required for the update
Tab. 4.17: Description of the folders and files of a PVMaster software release
No. Description
…\ SWpackage (upa-Update) \ PVM2 00cVx.xxxx ParaRevXX_Update-
Complete.upa
Using this .upa file as part of a software update means that all firmware
components and parameter data of the PVMaster device, and the opera-
tor application (web application), will be updated. System-specific or
customer-specific settings are not lost during this process but will auto-
1 matically be restored at the end.
NOTE
In normal cases, the software update of the PVMaster de-
vice should be implemented using this .upa file. This always
ensures that all software components have the same and
updated status.
…\ SWpackage (upa-Update) \ PVM2 00cVx.xxxx ParaRevXX_Up-
dateWebInterface.upa
This .upa file will only update the software of the operator application
(web application). The firmware components and parameter data of the
2
PVMaster device are not updated when this .upa file is used.
The use of this .upa file is applicable if, for example, there are problems
with the execution of the operator application (web application) (e.g. be-
cause necessary files on the microSD card are corrupt).
…\ SWpackage (upa-Update) \ PVM2 00cVx.xxxx ParaRevXX_Updat-
eDevice.upa
Using this .upa file for a software update means that all firmware com-
3 ponents and parameter data of the PVMaster device will be updated.
System-specific or customer-specific settings are not lost during this pro-
cess but will automatically be restored at the end. The operator applica-
tion (web application) is not updated when this .upa file is used.
…\ SWpackage (upa-Update) \ PVM2 00cVx.xxxx ParaRevXX_Produc-
tion.upa
This .upa file is used to restore the default parameters. Using this .upa
file for a software update means that all firmware components and pa-
rameter data of the PVMaster device will be updated and the default pa-
rameter settings restored. System-specific and customer-specific settings
are completely lost during this process and must subsequently be reset
4 manually where necessary. The operator application (web application) is
not updated when this .upa file is used.
NOTE
This .upa file should only be used in exceptional cases for
a software update. Always contact Support at LTI ReEnergy
GmbH before doing so in order to obtain alternative solu-
tions for the problems that have occurred.
…\PVMasterII Packet Vx.xxxx (SD-Image)\...
Folder with the files for the microSD card required to implement the
operator application. The files in this folder can be manually copied to the
microSD card to restore the functions or update the operator application.
If the previously recorded data (day history data, energy data, status his-
5 tory, etc.) need to be kept, the folders "LOG_DAY", "LOG_DEF", "LOG_
POR" and "LOG_SCB" on the microSD card must not be overwritten.
NOTE
In the event that the file system on the microSD card is
corrupt, the microSD card must be formatted before the
copying procedure (FAT32, no quick format).
as of Fitter
NOTE
The update wizard for implementing the software updates can alternatively
be called up directly via the browser, by entering the IP address of the device
in the address line of the internet browser with the suffix ...\update.htm. If the
network settings of the destination device are unchanged (delivery condition,
cf. also section 5.1.2, p. 241), the entry in the address line is then, e.g.:
http://192.168.36.1\update.htm or 192.168.36.1\update.htm
This makes sense, e.g. when problems occur during the execution of the
operator application (web application). If, however, the update wizard is called
up directly via the browser, the dialogue texts are not translated into the set
language and various status outputs will be omitted during and after a software
update. In normal cases, therefore, the update wizard should always be ac-
cessed using the button (11) in Fig. 4.42, p. 104 within the operator applica-
tion.
NOTE
It is recommended, when implementing a software update with remote data
transmission, that the update is carried out via the control centre PC (Chap-
ter 3.2, p. 108), particularly if the remote data transmission is unsafe and slow
and/or when several PVMaster devices in a device network need updating in a
common local network. In this case, the use of a "Remote desktop" connection
to the control centre PC is recommended to implement the software update.
This avoids waiting times and unexpected interruptions during the update pro-
cedure and the data traffic via the remote data transmission can be minimised
as the update file only needs to be uploaded once to the control centre PC.
1 2 4 3
Fig. 4.45: U ser interface of the menu option “System clock” in the menu sub-
group “General” of the menu group “Configuration”
1. The actual date is displayed in a calendar view in this section. The date
setting can be changed manually, if the option “Set manually” is activated in
option field (3), in the calendar view.
2. The actual time is shown in an analogue clock display, and the hours,
minutes and seconds are also shown in separate selection boxes. The time
setting can also be changed manually in the selection boxes if the option
“Set manually” is activated in option field (3).
3. The method to set or configure the system clock is selected via this option
field. The system clock can be set, e.g. manually via the calendar view (1)
and the selection boxes (2) (option “Set manually”). Alternatively, the system
clock of the PVMaster device can be synchronised with the system clock of
the local PC (option “Sync. with PC”). If the local PC has an internet con-
nection, the system clock of the PVMaster device can also be synchronised
with an internet time server (SNTP server) (option “Sync. with time server”).
The UTC offset setting will be taken into account here.
The system clock of the PVMaster device is only changed after the button
(6) “Set” is pressed.
4. This activation field is used to activate or deactivate the automatic changeo-
ver between summer and winter time or to display the activated setting.
5. The time zone of the PVMaster device is set as the UTC offset using this
selection box. The activated setting is taken into account, e.g. when setting
the system clock of the PVMaster device through synchronisation with an
internet time server (SNTP server). The UTC offset parameter setting is also
taken into account in the created .csv files (see section 4.3.4.7, p. 214) so
that the online portal system being used can implement the correspondingly
required correction of the time stamp.
6. Manually implemented changes to the system clock settings of the PVMas-
ter device are accepted by pressing the “Set” button. When the options
“Sync. with PC” or “Sync. with time server” are selected, the system clock is
only changed after the “Set” button has been pressed.
NOTE
After any changes are made, the changed device settings must be perma-
nently saved (section 4.2.7, p. 26) and the device must be restarted again
manually (section 4.2.8, p. 26).
NOTE
From device firmware V1.07-00 on the PVMaster, the system clock is resyn-
chronised with a time server automatically via an integrated SNTP client after
each switch-on procedure.
4.3.4.1.3 Network
as of Fitter The menu option “Network” in the menu sub-group “Device” of the menu group
“Configuration” is available as of user level “Fitter”. The user interface of this
menu option (Fig. 4.46) is used to display and edit the network settings of the
PVMaster device and to administrate the list with the network addresses of all
PVMaster devices in the local network.
4 7
Fig. 4.46: U
ser interface of the menu option “Network” in the menu sub-group
“General” of the menu group “Configuration”“
1. The MAC address of the PVMaster device is shown in this display text box.
It is not possible to manually change the MAC address.
2. These configuration text boxes are used to display and edit the IP address,
the subnet mask settings and the default gateway of the PVMaster device in
decimal format.
NOTE
The IP address of the modem or router used (GSM, DSL, etc.) should be used
to set the default gateway of the PVMaster device so that all the remote data
transmission functions are operational.
NOTE
Alternatively, the IP address setting can be displayed and configured via the
7-segment displays by using the two buttons (see section 5.1.2, p. 241).
3. Changes to the network settings of the PVMaster device via the configura-
tion text boxes (2) are permanently saved in the device by pressing the
“Set” button. It is not necessary to press “Save” (section 4.2.7, p. 26). A
dialogue box then appears with the prompt to carry out a new device start.
NOTE
The "Set" button should only be pressed when the software release switch
(section 4.2.5, p. 24) is deactivated.
The changes to the network settings of the PVMaster device only become
effective after the device is started again.
The network list with the connection settings of all PVMaster devices in the
local network is administrated in the lower section of the user interface (Fig.
4.46, p. 113). All added destination devices and network addresses are then
available in the selection box for selecting the destination device (section 4.2.3,
p. 23) in order to enable the rapid switchover to other destination devices in
the network.
4. The network settings of added PVMaster devices are shown in this table
field. The table field comprises four columns. The respective IP address
of the individual destination devices are shown in the first column. After all
added connections have been checked using the button (6) “Check connec-
tion”, the communication state is shown in the “Connection” column. The
actual state of the respective destination device software release switches
(section 4.2.5, p. 24) is shown in the “SW enabled” column. If the soft-
ware release switches of the destination devices are activated, it is not
possible to carry out a save process for the network lists of these destina-
tion devices using the “Broadcast” button (7). The “Updated” column shows
whether the network list has been successfully saved in the destination
devices after the “Broadcast” button (7) has been pressed.
New connections can be added and existing entries edited or deleted using
the buttons (5) in the table field.
NOTE
The PVMaster device currently used for the "Host" function (initial connection
takes place via this device) is always shown as an entry in the network list.
The IP address of this device is shown in bold. This entry in the network list
cannot be deleted or edited using the buttons (5).
5. These buttons can be used to add new connections to PVMaster destination
devices in the network list or to edit/delete existing entries in the network
list.
6. This button can be used to check the connection settings of all destina-
tion device entries in the network list (4). After this button is pressed, the
connection settings of the individual entries in the network list are checked
sequentially. The corresponding progress of the connection check is shown
to the right of the button. After completion of the connection checks, the con-
nection states and the state of the software release switch (section 4.2.5,
p. 24) of the respective destination devices are shown in the correspond-
ing columns “Connection” and “SW enabled” in the network list (4).
7. After the connection check has been made using the “Check connection”
button (6), the changed or updated network list can be permanently saved
to all destination devices listed as entries in the network list by pressing the
“Broadcast” button. The requirement is that the software release switches
(section 4.2.5, p. 24) of the respective destination devices are not acti-
vated. The successful, permanent storage of the network list is shown in the
“Updated” column for each entry in the network list.
The permanent storage of the network list with all PVMaster devices in the
local network using the “Broadcast” function ensures that, if another PV-
Master device is to be used as the “Host” device within the local network, it
is possible to rapidly switch the connection to the other destination devices
using the selection box (section 4.2.3, p. 23).
4.3.4.2 Grid
This menu sub-group contains the menu options to display the main measured
values (voltages, frequency, active power, total system output values) and to
display/edit settings (rated voltage, rated frequency, total system Limits, etc.) re-
lating to the grid aspects. In addition, energy values and conversion factors can
be edited here. The menu option for displaying and editing grid monitoring func-
tion settings also plays an important role. This menu sub-group also includes
menu options for displaying/editing the settings for insulation monitoring, and for
configuration and checking of the active Limit by the grid operator as part of grid
feed/Limit (by grid operator).
4.3.4.2.1 General
as of Fitter The first menu option “General” in the menu sub-group “Grid” of the menu group
“Configuration” is available as of user level “Fitter”. The corresponding user
interface (Fig. 4.47, p. 116) contains elements for displaying actual values on
the grid side (AC side), and for displaying/editing the rated values of the grid
voltage and grid frequency. In addition, this user interface can also display and
edit the maximum apparent and active power of the local InterCOM device net-
work (see also section 4.3.2.2, p. 48 and section 4.3.4.5, p. 198).
1 2
5 6 7 8
Fig. 4.47: U
ser interface of the menu option “General” in the menu sub-group
“Grid” of the menu group “Configuration”
If a red link button is shown next to a display text box, this indicates that
this value has been recorded as standard by the integrated data logger
and that the corresponding recorded day history data can be called up in
the diagram generator. Pressing this link button calls up the corresponding
user interface to display the day history data (section 4.3.3.1.1, p. 86).
Changes as of Expert 1. This configuration text box is used to display the rated value of the grid volt-
age in [V]. The limit values as a percentage of the grid voltage monitoring
functions (section 4.3.4.2.3, p. 124) and grid voltage-dependent grid stabili-
sation functions (section 4.3.4.3, p. 147) are based on this rated value.
NOTE
In some cases it may be necessary to change the rated value of the grid volt-
age so that the monitoring function based on this value can function correctly
and accurately. The rated value can be changed as of user level "Expert". This
setting can also be changed in the user interface of the menu option "Monitor-
ing" in the menu sub-group "Grid" of the menu group "Configuration" (sec-
tion 4.3.4.2.3, p. 124).
2. The rated value for the grid frequency in [Hz] is displayed and can be edited
in a selection box. The limit values as a percentage of the grid frequency
monitoring functions (section 4.3.4.2.3, p. 124) and static grid frequency
stabilisation (section 4.3.4.3.2, p. 156) are based on this rated value.
The PVMaster can be operated in a grid with either the rated frequency
50Hz or 60Hz. The standard rated frequency of 50Hz is preset in the deliv-
ery condition or default setting of the PVMaster.
This setting can also be changed in the user interface of the menu option
“Monitoring” in the menu sub-group “Grid” of the menu group “Configuration”
(section 4.3.4.2.3, p. 124).
NOTE
The setting for the rated frequency must be implemented correctly, particularly
when the grid monitoring functions are deactivated. This could otherwise lead
to instability of the control system.
3. This section contains display text boxes that display the actual measured
values of the three phase voltages in [V], the actual linked grid voltage in [V]
as an average of the three measured linked grid voltages, the three sliding
averages of the measured phase voltages in [V] for monitoring the grid volt-
age quality and the actual measured grid frequency in [Hz].
The grid voltage values and grid frequency are redundantly measured in the
PVMaster with two independent controllers in order to meet specific require-
ments regarding functional safety (section 4.3.4.2.3, p. 124). This selection
box is used to select the values to be displayed for the grid voltage values
and the grid frequency in the display text boxes in this section. If “µC1” is
selected, the measured values of the main controller are displayed, while
“µC2” will display the measured values of the safety controller.
These actual values can also be displayed using the menu option “AC
values” in the menu sub-group “Grid” of the menu group “Status and Values”
(section 4.3.2.4.1, p. 61).
4. The actual total active power fed into the grid is displayed here in [kW] in
a display text box. This value represents the sum of the three phase active
powers. This actual value can also be displayed using the menu option “AC
values” in the menu sub-group “Grid” of the menu group “Status and Values”
(section 4.3.2.4.1, p. 61).
5. The actual total apparent power in [kVA] of the entire local InterCOM device
network is shown here in a display text box. This actual value can also be
displayed using the menu option “InterCOM” in the menu group “Status and
Values” (section 4.3.2.2, p. 48).
6. The set maximum value for the apparent power in [kVA] of the entire local
InterCOM device network can be displayed and edited in this configuration
text box.
Any change to the maximum value for the apparent power of the entire local
InterCOM device network is automatically taken over by the other InterCOM
nodes if communication with all InterCOM nodes is functional within an In-
terCOM device network (see section 4.3.4.5, p. 198). However, permanent
storage of the new maximum value in the device settings of all InterCOM
nodes must be implemented by using the button (9).
7. The actual total active power in [kW] of the entire local InterCOM device
network is shown here in a display text box. This actual value can also be
displayed using the menu option “InterCOM” in the menu group “Status and
Values” (section 4.3.2.2, p. 48).
8. The set maximum value for the active power in [kW] of the entire local Inter-
COM device network can be displayed and edited in this configuration text
box.
Any change to the maximum value for the active power of the entire local
InterCOM device network is automatically taken over by the other InterCOM
nodes if communication with all InterCOM nodes is functional within an In-
terCOM device network (see section 4.3.4.5, p. 198). However, permanent
storage of the new maximum value in the device settings of all InterCOM
nodes must be implemented by using the button (9).
9. The “Save” button is used to permanently store the changed maximum
power values of the entire local InterCOM device network in the device set-
tings of all InterCOM nodes.
NOTE
The requirement for the successful permanent storage of the changed maxi-
mum powers in the device settings of all InterCOM nodes using the "Save"
button is that the software release switch (section 4.2.5, p. 24) in each
device is not activated and that communication with all InterCOM nodes in the
local InterCOM device network is active.
4.3.4.2.2 Energy
as of Fitter The menu option “Energy” in the menu sub-group “Grid” of the menu group
“Configuration” is available as of user level “Fitter”. The corresponding user
interface (Fig. 4.48) contains elements for the display and configuration of the
meter values with the energy values achieved so far (fed-in energy) of the PV-
Master device, device network or total plant, as applicable, and for the configu-
ration of device settings for energy determination and changing of conversion
factors or the currency to be used in the payment display.
The energy values achieved so far can be displayed and manually corrected, if
necessary, in the tab option “Inverter unit”. The device settings for energy deter-
mination can also be configured here and changes can be made to the conver-
sion factors and the currency used for the payment display of the PVMaster
device.
NOTE
A manual correction of the energy values must always be implemented so that
the meter states for the actual date, month, year and meter status with the
total energy achieved so far always remain consistent with each other.
NOTE
A manual correction of the energy values using the corresponding configura-
tion text boxes does not lead to subsequent correction of the recorded energy
values that can be called up via the corresponding bar diagram generators
(section 4.3.3.2, p. 97 to section 4.3.3.4, p. 102).
1 3
2
10
11 12 13
Fig. 4.48: U
ser interface of the menu option “Energy” in the menu sub-group
“Grid” of the menu group “Configuration”
If a red link button is shown next to a display text box, this indicates that
this value has been recorded as standard by the integrated data logger
and that the corresponding recorded historical energy data can be called
up in the diagram generator. Pressing this link button calls up the cor-
responding user interface to display the energy diagram (section 4.3.3,
p. 86).
as of Fitter 1. The evaluation/counting of the energy fed in so far or the energy of the
PVMaster device can be implemented by evaluating the S0 pulse output of
an installed meter. To do this, the digital input used in the PVMaster device
must be assigned with the corresponding function (function 34 in Tab. 4.19,
p. 168, see section 4.3.4.4.1, p. 166). If an S0 pulse input is not evaluat-
ed, the energy forecast is implemented automatically through integration of
the measured grid-side active power. The displayed option field shows the
applicable method used for energy determination of the PVMaster device.
This option field is for display purposes only.
2. These configuration text boxes are used to display and edit the S0 inter-
face relationship for the energy metering. These configuration text boxes
are used to define as of which number of counted S0 pulses [P] the energy
meter should be increased by the set energy in [Wh].
These configuration text boxes are only released for user inputs when the
evaluation of an energy consumption meter S0 pulse output takes place and
the digital output of the PVMaster device used for this purpose has been
assigned the corresponding function (function 34 in Tab. 4.19, p. 168, see
section 4.3.4.4.1, p. 166).
Any changes to this setting first need to be permanently saved (sec-
tion 4.2.7, p. 26) and a new device start implemented (section 4.2.8,
p. 26) before the changes become effective.
3. This configuration text box is used to display and edit another factor to be
taken into account during the evaluation of an energy consumption meter
S0 interface (e.g. to take into account a current transformer upstream of the
energy consumption meter).
This configuration text box is only released for user inputs when the evalu-
ation of an energy consumption meter S0 pulse output takes place and
the digital output of the PVMaster device used for this purpose has been
assigned the corresponding function (function 34 in Tab. 4.19, p. 168, see
section 4.3.4.4.1, p. 166).
Any changes to this setting first need to be permanently saved (sec-
tion 4.2.7, p. 26) and a new device start implemented (section 4.2.8,
p. 26) before the changes become effective.
4. If the fed-in energy or the energy is evaluated by evaluating the S0 pulse
output of an installed meter and if the PVMaster device digital output used
for the evaluation is assigned the appropriate function (function 34 in Tab.
4.19, p. 168, see section 4.3.4.4.1, p. 166), then the recorded pulses are
displayed in this status field.
NOTE
It is possible that not every recorded pulse will be displayed via this status
field; this depends on the actual frequency of the S0 pulse interface and the
connection quality between the PVMaster device and the local PC.
5. A configuration text box is used here to display and manually correct (where
necessary) the energy fed in so far by the PVMaster device or the energy of
the actual day in [kWh].
The energy fed in so far by the PVMaster device or the yield for the actual
day in [kWh] is also displayed in the start user interface “Overview” (sec-
tion 4.3.1, p. 39) and in the menu option “Yield” in the menu sub-group
“Grid” of the menu group “Status and Values” (section 4.3.2.4.4, p. 69).
6. This configuration text box is used here to display and manually correct
(where necessary) the energy fed in by the PVMaster device or the energy
of the actual month in [kWh].
The total energy fed in so far by the PVMaster device or yield in [kWh] for
the current month is displayed in the start user interface “Overview” (sec-
tion 4.3.1, p. 39) and in the menu option “Yield” in the menu sub-group
“Grid” of the menu group “Status and Values” (section 4.3.2.4.4, p. 69).
7. This configuration text box is used here to display and manually correct
(where necessary) the energy fed in by the PVMaster device or the energy
of the actual year in [kWh].
The energy fed in so far by the PVMaster device or the energy of the actual
year in [kWh] is also displayed in the user interface of the menu option
“Yield” in the menu sub-group “Grid” of the menu group “Status and Values”
(section 4.3.2.4.4, p. 69).
8. This configuration text box is used here to display and manually correct
(where necessary) the total energy fed in so far by the PVMaster device or
the energy in [kWh].
The total energy fed in so far by the PVMaster device or the energy in
[kWh] is also displayed in the Start user interface “Overview” (section 4.3.1,
p. 39) and in the user interface of the menu option “Energy” in the menu
sub-group “Grid” of the menu group “Status and Values” (section 4.3.2.4.4,
p. 69).
9. This display text box is used to display the total CO2 avoidance in [kg]
achieved so far by the PVMaster device. The displayed value results from
the conversion of the total energy fed in so far or the energy (8) produced by
the PVMaster device with the set conversion factor (11).
The total CO2 avoidance in [kg] achieved so far by the PVMaster device
is displayed in the user interface of the menu option “Energy” in the menu
sub-group “Grid” of the menu group “Status and Values” (section 4.3.2.4.4,
p. 69).
10. The total payment achieved by the PVMaster device in the set currency (13)
is displayed here. The displayed value results from the conversion of the
total energy fed in so far or the energy (8) produced by the PVMaster device
with the set payment factor (12).
The total payment achieved so far by the PVMaster device in the set curren-
cy is displayed in the user interface of the menu option “Energy” in the menu
sub-group “Grid” of the menu group “Status and Values” (section 4.3.2.4.4,
p. 69).
11. This configuration text box is used to display and edit the conversion factor
in [kg/kWh] for calculating the CO2 avoidance from the fed-in energy [kWh]
of the PVMaster.
The conversion factor is preset to the value 0.596 in the default setting or
delivery condition of the PVMaster.
(Source: Federal Office for the Environment, FG I 4.5., as at April 2008).
12. This configuration text box is used to display and edit the conversion factor
for calculating the payment based on the fed-in energy [kWh] in a configu-
ration text box.
The conversion factor is preset to the value 0.2 in the default setting or de-
livery condition of the PVMaster.
13. This configuration text box is used to display and edit the displayed currency
or payment unit.
The currency “EUR” is preset in the default setting or delivery condition of
the PVMaster.
as of Fitter If the S0 pulse output of an installed higher-level meter used to meter the
total energy of the total plant is evaluated by a PVMaster device digital
output and this digital output used for the evaluation was assigned the ap-
propriate function (function 35 in Tab. 4.19, p. 168, see section 4.3.4.4.1,
p. 166), then a second tab option “Total plant” can be selected (Fig. 4.49,
p. 122). This tab option then displays the energy values achieved so far by
the device network or the total plant and these can be corrected manually
where necessary.
15
14
16
17
18
19
20
21
22
Fig. 4.49: Tab option “Total plant” in the menu option “Energy” (Configuration)
14. These configuration text boxes are used to display and edit the S0 interface
relationship for the energy metering by a higher-level energy consumption
meter used to meter the energy of the total plant. These configuration text
boxes are used to define as of which number of counted S0 pulses [P] the
energy meter should be increased by the set energy in [Wh].
Any changes to this setting first need to be permanently saved (sec-
tion 4.2.7, p. 26) and a new device start implemented (section 4.2.8,
p. 26) before the changes become effective.
15. This configuration text box is used to display and edit another factor to be
taken into account during the evaluation of an energy consumption meter
S0 interface (e.g. to take into account a current transformer upstream of the
energy consumption meter).
Any changes to this setting first need to be permanently saved (sec-
tion 4.2.7, p. 26) and a new device start implemented (section 4.2.8,
p. 26) before the changes become effective.
16. This status field displays the pulses recorded by the S0 pulse interface of
the energy consumption meter for the total plant.
NOTE
It is possible that not every recorded pulse will be displayed via this status
field; this depends on the actual frequency of the S0 pulse interface and the
connection quality between the PVMaster device and the local PC.
17. A configuration text box is used here to display and manually correct (where
necessary) the energy fed in so far by the entire device network or total
plant, or the energy of the actual day in [kWh].
The energy fed in so far by the entire device network or total plant, or the
energy of the actual day in [kWh], is also displayed in the tag option “Total
plant” in the user interface of the menu option “Energy” in the menu sub-
group “Grid” of the menu group “Status and Values” (section 4.3.2.4.4,
p. 69)
18. A configuration text box is used here to display and manually correct (where
necessary) the energy fed in so far by the entire device network or total
plant, or the energy of the actual month in [kWh].
These actual values can also be displayed in the tab option “Total plant” in
the user interface “Energy” of the menu sub-group “Grid” in the menu group
“Status and Values” (section 4.3.2.4.4, p. 69).
19. A configuration text box is used here to display and manually correct (where
necessary) the energy fed in by the entire device network or total plant, or
the energy of the actual year in [kWh].
These actual values can also be displayed in the tab option “Total plant” in
the user interface “Energy” of the menu sub-group “Grid” in the menu group
“Status and Values” (section 4.3.2.4.4, p. 69).
20. This configuration text box is used here to display and manually correct
(where necessary) the total energy fed in so far by the entire device network
or total plant or the energy in [kWh].
These actual values can also be displayed in the tab option “Total plant” in
the user interface “Energy” of the menu sub-group “Grid” in the menu group
“Status and Values” (section 4.3.2.4.4, p. 69).
21. This display text box is used to display the total CO2 avoidance in [kg]
achieved so far by the entire device network or total plant. The displayed
value results from the conversion of the total energy fed in so far or the
energy (8) produced by the entire device network or total plant with the set
conversion factor (11).
These actual values can also be displayed in the tab option “Total plant” in
the user interface “Energy” of the menu sub-group “Grid” in the menu group
“Status and Values” (section 4.3.2.4.4, p. 69).
22. The total payment achieved so far by the entire device network or total plant
in the set currency (13) is displayed here. The displayed value results from
the conversion of the total energy fed in so far or the energy (8) produced by
the entire device network or total plant with the set conversion factor (12).
These actual values can also be displayed in the tab option “Total plant” in
the user interface “Energy” of the menu sub-group “Grid” in the menu group
“Status and Values” (section 4.3.2.4.4, p. 69).
4.3.4.2.3 Monitoring
The PVMaster offers integrated monitoring functions for grid voltage monitoring.
The scope and flexible concept of the monitoring functions permit the realisa-
tion of grid monitoring in compliance with numerous application regulations and
guidelines. The PVMaster already has numerous country codes (“Grid codes”)
stored for direct selection in order to automatically initialise the individual moni-
toring functions and corresponding limit values.
The grid voltage values and grid frequency are redundantly measured and
monitored in the PVMaster with two independent controllers (main and backup
controller) in order to meet specific requirements regarding functional safety.
The main contactor(s) are also always controlled by the two controllers.
The PVMaster differentiates between permanently active grid monitoring func-
tions and auxiliary grid monitoring functions (with stricter limit values) which are
only active during the checking of the connection conditions.
To monitor the supply voltages and voltage averages, the PVMaster can moni-
tor the phase voltage values (ph-n) and / or linked grid voltages (ph-ph) in each
case. Independent monitoring functions are used internally for this purpose. The
monitoring of phase (ph-n) and / or linked voltages (ph-ph) is enabled or disa-
bled via the corresponding checkboxes next to the relevant monitoring functions
(see (7) and (8) in Fig. 4.50, p. 125 and (17) - (22) in Fig. 4.51, p. 130).
After the AC main switch or AC load-break switch is switched on or after a
(daily) device restart, the enabled grid monitoring functions and the enabled
supplementary grid monitoring functions for checking the connection condi-
tions are active. If all the limit values of all activated grid monitoring functions
are maintained without interruptions during the set connection delay, the main
contactor(s) can be connected following the expiry of the connection delay and
the active infeed operation can commence (as soon as the generator power
suffices).
The respective connection releases of the main and backup controllers are
displayed in the first status word (see nos. 8 and 9 in Tab. 4.10, p. 43, sec-
tion 4.3.2.1, p. 41). The display of the respective progress of the elapsed
connection delay is implemented separately for both controllers via corre-
sponding progress bars in the user interfaces of the menu options “Monitoring”
in the menu sub-group “Grid” of the menu groups “Status and Values” (sec-
tion 4.3.2.4.5, p. 73) and “Configuration” (Fig. 4.50, p. 125).
The menu option “Monitoring” in the menu sub-group “Grid” of the menu group
“Configuration” is available in every user level. The corresponding user interface
(Fig. 4.50, p. 125) contains elements to display and edit the settings, and the
display of the actual state of the integrated PVMaster monitoring functions for
grid monitoring.
NOTE
The user level "Observer" is used solely to display all settings (limit values,
etc.) and the actual state of the integrated monitoring functions for grid moni-
toring. Modifications are not possible in this user level.
The upper section of the user interface (Fig. 4.50) is used to display and edit
general settings of the integrated grid monitoring functions.
1 2
3 4 5
7 8
9 10
11 12
13
14
15 16
Fig. 4.50: U
ser interface of the menu option “Monitoring” in the menu sub-group
“Grid” of the menu group “Configuration”
Changes as of Fitter 1. The country codes (“Grid codes”) for initialising functions and limit values of
the integrated grid monitoring functions are displayed and configured here
in a selection box.
The functions and limit values are initialised according to the selected grid
code after the grid code has been configured by selecting an element in
the selection box. In addition, grid stabilisation functions (section 4.3.4.3,
p. 147) are appropriately configured and activated/deactivated as neces-
sary. A dialogue box then appears with the prompt to carry out a new device
start. The changes to the grid monitoring functions of the PVMaster device
only become effective after the device is started again.
The grid code used to initialise grid monitoring can also be displayed in the
menu option “Monitoring” in the menu sub-group “Grid” of the menu group
“Status and Values” (section 4.3.2.4.5, p. 73).
Changes as of Expert 2. The activation field “User-defined settings” can be used to activate/deacti-
vate manually specified function and limit value settings for the integrated
grid monitoring functions that differ from those of the set country code.
After the activation field is activated, the configuration text boxes and other
elements used to configure monitoring function and limit value settings are
released for input by the user.
When the activation field is deactivated, all monitoring function and limit
value settings are initialised again according to the set country code. A
dialogue box then appears with the prompt to carry out a new device start.
The changes to the grid monitoring functions of the PVMaster device only
become effective after the device is started again.
Changes as of Fitter 3. This configuration box is used to display the rated value of the grid voltage
in [V]. The limit values in percent of the grid voltage monitoring functions
and grid voltage-dependent grid stabilisation functions (section 4.3.4.3,
p. 147) are based on this rated value.
NOTE
In some cases it may be necessary to change the rated value of the grid volt-
age so that the monitoring function based on this value can function correctly
and accurately. This setting can also be changed in the user interface of the
menu option "General" in the menu sub-group "Grid" of the menu group "Con-
figuration" (section 4.3.4.2.1, p. 115).
4. The rated value for the grid frequency in [Hz] is displayed and can be
edited in a selection box. The limit values as a percentage of the grid
frequency monitoring functions and static grid frequency stabilisation (sec-
tion 4.3.4.3.2, p. 156) are based on this rated value.
The PVMaster can be operated in a grid with either the rated frequency
50Hz or 60Hz. The standard rated frequency of 50Hz is preset in the deliv-
ery condition or default setting of the PVMaster.
This setting can also be changed in the user interface of the menu option
“General” in the menu sub-group “Grid” of the menu group “Configuration”
(section 4.3.4.2.1, p. 115).
NOTE
The setting for the rated frequency must be implemented correctly, particularly
when the grid monitoring functions are deactivated. This could otherwise lead
to instability of the control system.
Changes as of Expert 5. The activation display and the grid monitoring functions of the backup con-
troller are enabled or disabled via this checkbox.
To implement redundant grid monitoring, the monitoring functions of the
backup controller must be enabled via this checkbox. However, this is not
mandatory for all country codes.
When initializing the functions and limits by selecting a country code via the
selection box (1), the backup controller enables monitoring or not according
to requirements.
From user level “Expert” up, different configurations from the selected coun-
try code can be set, but only when the checkbox (2) “Custom Settings” is
enabled. Normally, it is not necessary to change this checkbox.
6. The lower section of the user interface displays the state of the integrated
grid monitoring in a status field and a plain text message in a display text
box. The possible states are listed in Tab. 4.13, p. 76 (section 4.3.2.4.5,
p. 73).
NOTE
The respective activated and configured grid monitoring functions in the PV-
Master are active as soon as the AC main switch or AC load-break switch of
the device is switched on. A corresponding plain text message is shown in this
display text box if the AC main switch is deactivated. The state display of the
AC main switch is also shown in the user interface of the menu option "State"
in the menu group "Status and Values", in the first status word (see no. 3 in
Tab. 4.10, p. 43, section 4.3.2.1, p. 41).
The first tab option “(Re-)connection” (Fig. 4.50, p. 125) contains the following
elements: the display and configuration (where necessary) of the functions and
limit values for additional checking of connection conditions before connection
and before begin of active infeed operation of the PVMaster; the status display
of the release by the functions for grid monitoring; the activation, configura-
tion and status display of the active power ramp for limiting the active power
increase after connection/reconnection of the PVMaster (e.g. following a fault
state of the device due to the grid monitoring functions).
Changes as of Expert In this tab option, the grid monitoring function configurations and limit values
differing from the set country code can be edited as of user level “Expert”. The
individual elements (configuration text boxes, activation fields, etc.) for this pur-
pose will, however, only be released for user inputs after the activation field (2)
“User-defined settings” has been activated.
7. This configuration text box is used to display and edit the lower limit value
of the grid voltage for the additional check of the connection condition. The
display or configuration is implemented (via the selection box) either in [%]
related to the set grid voltage (3) or in [V ph-n] as an absolute phase voltage
limit value or in [V ph-ph] as an absolute limit for the linked grid voltage.
If the AC main switch or AC load-break switch is activated (grid monitor-
ing functions active), the corresponding fault state (ID 15/01 or ID 21/01 in
Tab. 4.31, p. 224, see section 4.3.5.1, p. 221) is triggered when this limit
value is not complied with during the check of the connection condition. The
fault state is, however, only triggered when the connection condition has not
been met after a defined time (standard is after 10 minutes).
The checkboxes next to the configuration text box are used to display and
configure or enable or disable this additional monitoring function to check
the connection condition. Here, the network phase voltages (ph-n)and / or
linked grid voltages (ph-ph) can be monitored.
8. This configuration text box is used to display and edit the upper limit value
of the grid voltage for the additional check of the connection condition. The
display or configuration is implemented (via the selection box) either in [%]
related to the set grid voltage (3) or in [V ph-n] as an absolute phase voltage
limit value or in [V ph-ph] as an absolute limit for the linked grid voltage.
If the AC main switch or AC load-break switch is activated (grid monitor-
ing functions active), the corresponding fault state (ID 15/02 or ID 21/02 in
Tab. 4.31, p. 224, see section 4.3.5.1, p. 221) is triggered when this limit
value is not complied with during the check of the connection condition. The
fault state is, however, only triggered when the connection condition has not
been met after a defined time (standard is after 10 minutes).
The checkboxes next to the configuration text box are used to display and
configure or enable or disable this additional monitoring function to check
the connection condition. Here, the network phase voltages (ph-n)and / or
linked grid voltages (ph-ph) can be monitored.
9. This configuration text box is used to display and edit the lower limit value
of the grid frequency for the additional check of the connection condition.
The display or configuration is implemented (via the selection box) either in
[%] related to the set rated grid frequency (4) or in [V] as an absolute grid
frequency limit value.
If the AC main switch or AC load-break switch is activated (grid monitor-
ing functions active), the corresponding fault state (ID 15/03 or ID 21/03 in
Tab. 4.31, p. 224, see section 4.3.5.1, p. 221) is triggered when this limit
value is not complied with during the check of the connection condition. The
fault state is, however, only triggered when the connection condition has not
been met after a defined time (standard is after 10 minutes).
The display and configuration of the activation/deactivation of this supple-
mentary monitoring function for checking the connection condition is imple-
mented via the activation field next to the configuration text box.
10. This configuration text box is used to display and edit the upper limit value
of the grid frequency for the additional check of the connection condition.
The display or configuration is implemented (via the selection box) either in
[%] related to the set rated grid frequency (4) or in [V] as an absolute grid
frequency limit value.
If the AC main switch or AC load-break switch is activated (grid monitor-
ing functions active), the corresponding fault state (ID 15/04 or ID 21/04 in
Tab. 4.31, p. 224, see section 4.3.5.1, p. 221) is triggered when this limit
value is not complied with during the check of the connection condition. The
fault state is, however, only triggered when the connection condition has not
been met after a defined time (standard is after 10 minutes).
The display and configuration of the activation/deactivation of this supple-
mentary monitoring function for checking the connection condition is imple-
mented via the activation field next to the configuration text box.
11. The display and configuration (where necessary) of the connection delay is
implemented in [s] via this configuration text box.
After the AC main switch or AC load-break switch is switched on or after a
(daily) device restart, the activated grid monitoring functions and the acti-
vated supplementary grid monitoring functions for testing the connection
conditions become active. If all the limit values of all activated grid monitor-
ing functions are maintained without interruptions during the set connection
delay, the main contactor(s) can be connected following the expiry of the
connection delay and the active infeed operation can commence (as soon
as the generator power suffices). The respective connection releases of the
main and safety controllers are displayed in the first status word (see nos. 8
and 9 in Tab. 4.10, p. 43, section 4.3.2.1, p. 41).
The display of the respective progress of the elapsed connection delay is
implemented separately for both controllers via the progress bars (12) and
(13).
12. The active counting of the connection delay through the integrated grid
monitoring function is shown as a progress display. This refers to the count-
ing of the first instance connection delay (main controller) of the device-
internal redundant grid monitoring. Counting begins as soon as all grid
parameters are approved. Counting is reset to 0% after a grid fault or device
restart. If the counting of the first instance of the device-internal redundant
grid monitoring with approved grid parameters exceeds 100%, the first re-
lease is issued for connection by the redundant grid monitoring (see no. 8 in
Tab. 4.10, p. 43, section 4.3.2.1, p. 41).
13. The active counting of connection delay through the integrated grid moni-
toring function is shown as a progress display. This refers to the counting
of the second instance connection delay (backup controller) of the device-
internal redundant grid monitoring. Counting begins as soon as all grid
parameters are approved. Counting is reset to 0% after a grid fault or device
restart. If the counting of the second instance of the device-internal redun-
dant grid monitoring with approved grid parameters exceeds 100%, the
second release is issued for connection by the redundant grid monitoring
(see no. 9 in Tab. 4.10, p. 43, section 4.3.2.1, p. 41).
14. This section is used to display and change the configuration of the active
power ramp for limiting the active power increase after successful recon-
nection after a grid failure. The configuration text box is used to display and
edit, where necessary, the maximum permissible active power increase per
minute. The active power ramp is enabled/disabled in the checkbox next to
the configuration text box.
15. This section is used to display and change the configuration of the active
power ramp for limiting the active power increase after each reconnection.
The configuration text box is used to display and edit, where necessary, the
maximum permissible active power increase per minute. The active power
ramp is enabled/diabled in the checkbox next to the configuration text box.
16. When using the active power ramp to reduce the increase in active power
following successful (re)connection (e.g. after a grid fault), the actual reduc-
tion value of the ramp function is correspondingly shown in this progress
display. If all the active power ramps are disabled via checkboxes (14) and
(15), the progress bar on the interface may disappear.
The second tab option “Limits” (Fig. 4.51) contains the display and configura-
tion editing options (where necessary) and the limit values for the permanently
active monitoring functions for grid monitoring before and after connection, and
during active infeed operation of the PVMaster.
Changes as of Expert Fault triggering and corresponding device switch-off due to the respective
monitoring functions for monitoring the grid voltage V<<(1), V<<(2), V>>(1) and
V>>(2), elements (16) to (19), occur with a delay in compliance with the respec-
tively set delay times.
These delays can prevent unwanted disconnections, e.g. due to brief grid volt-
age drops, which need to be “ridden through” as part of the dynamic grid stabili-
sation function (section 4.3.4.3.3, p. 159).
A graphic visualisation of the switch-off limits and the behaviour over time of
the individual monitoring functions for monitoring grid voltages is shown in the
tab option “Overview” in the user interface of the menu option “LVRT” in the
menu sub-group “Grid stabilisation” of the menu group “Configuration” (sec-
tion 4.3.4.3.3, p. 159).
17 18 19 20
21 22 23
24 25 26 27
ated in this monitoring function when the set lower grid voltage limit value is
undershot continuously for the duration of the set delay time.
19. This section is used to display and edit the first function for monitoring the
voltage rise V>>(1). The checkboxes are used to display and configure or
enable or disable this monitoring function. Here, the network phase voltages
(ph-n) can be monitored, and / or linked grid voltages (ph-ph).
The upper configuration text box is used to display and edit the upper limit
value of the grid voltage. The display or configuration is implemented (via
the selection box) either in [%] in relation to the set grid voltage (3) or in [V
ph-n] as an absolute phase voltage limit value or in [V ph-ph] as an absolute
limit for the linked grid voltage.
The lower configuration text box is used to display and edit the delay time
in [ms] for this monitoring function. The triggering of the corresponding
fault state (ID 15/07 or ID 21/07 in Tab. 4.31, p. 224, see section 4.3.5.1,
p. 221) and therefore the switch-off of the PVMaster device is only actu-
ated in this monitoring function when the set upper grid voltage limit value is
exceeded continuously for the duration of the set delay time.
20. This section is used to display and edit the second function for monitoring
the voltage rise V>>(2). The checkboxes are used to display and configure
or enable or disable this monitoring function. Here, the network phase volt-
ages (ph-n) can be monitored, and / or linked grid voltages (ph-ph).
The upper configuration text box is used to display and edit the upper limit
value of the grid voltage. The display or configuration is implemented (via
the selection box) either in [%] in relation to the set grid voltage (3) or in [V
ph-n] as an absolute phase voltage limit value or in [V ph-ph] as an absolute
limit for the linked grid voltage.
The lower configuration text box is used to display and edit the delay time
in [ms] for this monitoring function. The triggering of the corresponding
fault state (ID 15/08 or ID 21/08 in Tab. 4.31, p. 224, see section 4.3.5.1,
p. 221) and therefore the switch-off of the PVMaster device is only actu-
ated in this monitoring function when the set upper grid voltage limit value is
exceeded continuously for the duration of the set delay time.
21. This section is used to display and edit the first function for monitoring the
sliding grid voltage average used for monitoring the voltage quality V<. The
checkboxes are used to display and configure or enable or disable this mon-
itoring function. Here, the network phase voltages (ph-n) can be monitored,
and / or linked grid voltages (ph-ph).
This configuration text box is used to display and edit the lower limit value of
the sliding grid voltage average. The display or configuration is implemented
(via the selection box) either in [%] in relation to the set grid voltage (3) or
in [V ph-n] as an absolute phase voltage limit value or in [V ph-ph] as an
absolute limit for the linked grid voltage.
If the actual grid voltage average undershoots the set limit value, the cor-
responding fault state (ID 15/09 or ID 21/09 in Tab. 4.31, p. 224, see sec-
tion 4.3.5.1, p. 221) and the switch-off of the device are triggered immedi-
ately.
The cycle time of the sliding average value formation is displayed and con-
figured in [s] in the configuration text box (23).
22. This section is used to display and edit the second function for monitoring
the sliding grid voltage average used for monitoring the voltage quality V>.
The checkboxes are used to display and configure or enable or disable this
monitoring function. Here, the network phase voltages (ph-n) can be moni-
tored, and / or linked grid voltages (ph-ph).
This configuration text box is used to display and edit the upper limit value
of the sliding grid voltage average. The display or configuration is imple-
mented (via the selection box) either in [%] in relation to the set grid voltage
(3) or in [V ph-n] as an absolute phase voltage limit value or in [V ph-ph] as
an absolute limit for the linked grid voltage.
If the actual grid voltage average undershoots the set limit value, the cor-
responding fault state (ID 15/10 or ID 21/10 in Tab. 4.31, p. 224, see sec-
tion 4.3.5.1, p. 221) and the switch-off of the device are triggered immedi-
ately.
The cycle time of the sliding average value formation is displayed and con-
figured in [s] in the configuration text box (23).
23. The cycle time of the sliding average value formation, based on the meas-
ured grid voltage for monitoring the voltage quality (21) and (22), is dis-
played and configured, where necessary, in [s] in this configuration text box.
24. This section is used to display and edit the function for monitoring the grid
frequency change rate (ROCOF: Rate of Change of Frequency). This moni-
toring function is frequently used as a passive method for islanding detec-
tion.
This monitoring function can be displayed and the activation/deactivation
changed in the activation field. This configuration text box is used to display
and edit the maximum permissible grid frequency change in [Hz/s].
If the actual frequency change rate exceeds the set limit value, the corre-
sponding fault state (ID 15/15 or ID 21/15 in Tab. 4.31, p. 224, see sec-
tion 4.3.5.1, p. 221) and the switch-off of the device are triggered immedi-
ately.
25. This section is used to display and edit the first function for monitoring the
frequency drop f<<(1). This monitoring function can be displayed and the
activation/deactivation changed in the activation field.
The upper configuration text box is used to display and edit the lower limit
value of the grid frequency. The display or configuration is implemented (via
the selection box) either in [%] related to the set rated grid frequency (4) or
in [V] as absolute grid frequency limit value.
The lower configuration text box is used to display and edit the delay time
in [ms] for this monitoring function. The triggering of the corresponding
fault state (ID 15/11 or ID 21/11 in Tab. 4.31, p. 224, see section 4.3.5.1,
p. 221) and therefore the switch-off of the PVMaster device is only actu-
ated in this monitoring function when the set lower grid frequency limit value
is undershot continuously for the duration of the set delay time.
26. This section is used to display and edit the second function for monitoring
the frequency drop f<<(2). This monitoring function can be displayed and
the activation/deactivation changed in the activation field.
The upper configuration text box is used to display and edit the lower limit
value of the grid frequency. The display or configuration is implemented (via
the selection box) either in [%] related to the set rated grid frequency (4) or
in [V] as an absolute grid frequency limit value.
The lower configuration text box is used to display and edit the delay time
in [ms] for this monitoring function. The triggering of the corresponding
fault state (ID 15/12 or ID 21/12 in Tab. 4.31, p. 224, see section 4.3.5.1,
p. 221) and therefore the switch-off of the PVMaster device is only actu-
ated in this monitoring function when the set lower grid frequency limit value
is undershot continuously for the duration of the set delay time.
27. This section is used to display and edit the first function for monitoring the
frequency rise f>>(1). This monitoring function can be displayed and the
activation/deactivation changed in the activation field.
The upper configuration text box is used to display and edit the upper limit
value of the grid frequency. The display or configuration is implemented (via
the selection box) either in [%] related to the set rated grid frequency (4) or
in [V] as an absolute grid frequency limit value.
The lower configuration text box is used to display and edit the delay time
in [ms] for this monitoring function. The triggering of the corresponding
fault state (ID 15/14 or ID 21/14 in Tab. 4.31, p. 224, see section 4.3.5.1,
p. 221) and therefore the switch-off of the PVMaster device is only actu-
ated in this monitoring function when the set lower grid frequency limit value
is exceeded continuously for the duration of the set delay time.
The configuration and threshold values for the passive and active island-
ing detection functions are displayed and, where applicable, changed in the
third tab option “Islanding Detection” (Fig. 4.53, p. 137).
28
29 30
31
32
33
34
35
30. This checkbox can be used to enable or disable the phase angle monitor for
the grid voltages. Ideally, the phase angle in question is 120°. Where phase
angles differ greatly (<90° or >150°), the relevant error state (ID 15/19 in
Tab. 4.30, p. 217, see (section 4.3.5.1, p. 221) is triggered.
31. The Q-factor describes the quality of the LCR resonant circuit, which may
lead to undesired islanding. The active method for islanding detection can
recognise undesired islanding sufficiently quickly using a trained resonant
circuit with a parameterised Q factor and trigger a shutdown.
32. Configuration text box to display and change the additional safety factor for
the limit stability for the positive feedback of the frequency / phase shift, tak-
ing into account the parameterised resonant circuit quality (21).
33. - 35. A test signal is superimposed on the grid current in order to constantly
monitor enabled islanding monitoring or the backup controller. These
configuration text boxes are used to display and change the configuration
of this monitoring function. If this test signal cannot be detected in the grid
current, the relevant error state is (ID 21/17 in Tab. 4.30, p. 217, see (sec-
tion 4.3.5.1, p. 221) after the delay set via the configuration text box (35).
NOTE
Only experts should change the configuration of functions for islanding detec-
tion. Please contact the support team at LTI REEnergy GmbH to discuss this.
5 6
7 8
Fig. 4.53: U
ser interface of the menu option “Insulation monitoring” in the menu
sub-group “Grid” of the menu group “Configuration”
1. An option field displays the existing unit and interface used for measuring/
monitoring the insulation or grounding resistance. This option field is for
information display purposes only.
In normal cases, measurement of the insulation or grounding resistance
is implemented via an integrated measuring unit in the base device of the
PVMaster (“Internal insulation monitoring”) or via the evaluation of the ana-
logue signal (function no.3 in Tab. 4.23, p. 190, section 4.3.4.4.3, p. 189)
from a separate measuring unit in the PVMaster enclosure (“Analogue
interface”).
NOTE
In some PVMaster device variants, there are no units for monitoring insula-
tion or grounding resistance integrated in the device. In the case of "Insulation
monitoring not used", the other elements (2) to (8) in the user interface are
hidden.
NOTE
In some PVMaster device variants, communication between the control
component of the PVMaster device and the unit for monitoring the insulation
or grounding resistance is implemented via two digital signals (see functions
13 and 14 in Tab. 4.19, p. 168, section 4.3.4.4.1, p. 166). In this case, the
"Digital interface" is displayed in the option field and the display of the actual
measured resistance value in the display text box (3) is not available.
2. The insulation monitoring state is displayed here via status fields and as a
plain text message in a display text box. The possible states are listed in
Tab. 4.18, p. 140.
A corresponding display of the insulation or grounding resistance monitoring
state is also available in the corresponding symbol on the Start user inter-
face “Overview” (section 4.3.1, p. 39).
3. This display text box is used to display the actual insulation resistance or
the grounding resistance in [kOhm].
In a pure IT system, the displayed measured value represents the meas-
ured insulation resistance. If the PV generator is positively or negatively
grounded using the optionally available grounding kit (see PVMaster instal-
lation manual), the displayed value represents the measured grounding
resistance (see section 4.3.4.2.4, p. 136).
NOTE
The measured value display via this display text box is not available for all
PVMaster device types, see (1).
Changes as of Fitter 4. This option field is used to select whether the insulation resistance of a pure
IT system or the grounding resistance of a positively or negatively grounded
photovoltaic generator should be monitored.
In the insulation monitoring of an IT system (selection of the first option
“IT system”), the minimum limit values for insulation monitoring are pre-
initialised according to the expected connected photovoltaic generator peak
power and according to the rated device power of the PVMaster, then cor-
respondingly displayed in the configuration text boxes (6) and (8).
NOTE
If the peak power of the connected photovoltaic generator significantly ex-
ceeds the rated power of the PVMaster device, it may be necessary to manu-
ally adjust the pre-initialised limit values for the insulation monitoring in the
configuration text boxes (6) and (8).
If the grounding resistance of a positively or negatively grounded photo-
voltaic generator is monitored (selection of the second or third option), the
elements (9) and (10) are also shown, see Fig. 4.54, p. 139, to display and
edit, where necessary, the maximum permissible values for the grounding
resistance. The limit values for the monitoring of the grounding resistance
are already pre-initialised with 5 kOhm and 25 kOhm.
Changes as of Expert 5. The monitoring function for monitoring the insulation or grounding resistance
initially checks the connection condition before connection and before active
infeed operation. The measured resistance value must lie between the limit
values set in (6) and (8).
If the connection condition is met, the connection release is issued by the in-
sulation or grounding resistance monitoring. The connection release by the
insulation or grounding resistance monitoring is displayed in the first status
word (no. 10 in Tab. 4.10, p. 43, section 4.3.2.1, p. 41).
If no permissible resistance value for the insulation or grounding resistance
can be determined during the checking of the connection condition within
the set timeout time, then no release is issued for connection and the fault
state (ID 23/01 in Tab. 4.31, p. 224, see section 4.3.5.1, p. 221) is trig-
gered.
This configuration text box is used to display and edit, where necessary, the
timeout time for checking the connection condition in [min].
NOTE
The issuing of the connection release by the insulation or grounding resistance
monitoring requires a certain waiting time after the (daily) device new start,
due to initialisation and self-testing of the insulation measurement unit (state
no. 2 in Tab. 4.18, p. 140). The time period before the first valid measured
resistance value is available also depends on the size of the photovoltaic gen-
erator and the cell technology used (higher leakage capacitance levels in thin
layer modules).
6. This configuration text box is used to display and edit, where necessary, the
lower resistance limit value in [kOhm] for the check of the connection condi-
tion.
7. The monitoring of the insulation or grounding resistance is also imple-
mented continuously during active infeed operation, but the monitoring limit
values may be different. The measured resistance value must lie between
the limit values set in (8) and (10), if applicable.
If the resistance values for the insulation or grounding resistance remain
continuously impermissible, the PVMaster is switched off after the timeout
elapses and the fault state (ID 23/02 or ID 23/03 or ID 23/04 in Tab. 4.31,
p. 224, see section 4.3.5.1, p. 221) will be triggered.
This configuration text box is used to display and edit, where necessary, the
timeout time in [min] for monitoring in active infeed operation.
8. This configuration text box is used to display and edit, where necessary,
the lower resistance limit value in [kOhm] for the monitoring in active infeed
operation.
10
State /
No Description
plain text message
If there is a malfunction in the device-internal
measurement of the insulation or grounding
15 Error device
resistance, the fault state (ID 23/05 in Tab. 4.31,
p. 224, see section 4.3.5.1, p. 221) is triggered.
If there is a malfunction in the interface to the insu-
lation measuring unit or a wire break is detected,
16 Error interface
the fault state (ID 23/06 in Tab. 4.31, p. 224, see
section 4.3.5.1, p. 221) is triggered.
If the configuration of the settings for the insulation
Error configura- or grounding resistance monitoring is incorrect, the
17
tion fault state (ID 23/07 in Tab. 4.31, p. 224, see sec-
tion 4.3.5.1, p. 221) is triggered.
The elements displayed in the user interface vary depending on the interface
used for setpoint specification.
4 5 3
Fig. 4.55: U
ser interface of the menu option “Limit” in the menu sub-group
“Grid” of the menu group “Configuration”
1. This option field is used to display the interface used for setpoint specifica-
tion of the active Limit as part of infeed/grid security management (NSM).
The option field is for display only; the selection of the interface for setpoint
specification is implemented via the function assignment of the digital inputs
or an analogue PVMaster input, or by activating the corresponding func-
tional InterCOM communication object if the device is in a local InterCOM
device network. The option field is always displayed in the user interface,
irrespective of the interface used for setpoint specification
If setpoint specification is implemented via digital inputs, i.e. where the
digital inputs of the PVMaster have been assigned the functions 27, 28, 29
and/or 30 in Tab. 4.19, p. 168 (section 4.3.4.4.1, p. 166), then the user
interface is displayed as shown in Fig. 4.56 (section 4.3.4.2.5.2, p. 144).
If setpoint specification is implemented via an analogue input, i.e. where the
analogue input of the PVMaster has been assigned the function 4 in Tab.
4.23, p. 190 (section 4.3.2.6.3, p. 85), then the user interface is dis-
played as shown in Fig. 4.57, p. 146 (section 4.3.4.2.5.3, p. 145).
NOTE
Only one interface at a time can be used for active Limit setpoint specification.
Once the applicable functions for setpoint specification have been activated
respectively for the digital inputs and an analogue input, the setpoint specifica-
tion is implemented via the digital inputs.
If the setpoint specification is implemented via the InterCOM device in-
tercommunication through another InterCOM node in the local InterCOM
device network (InterCOM communication object no.1 in Tab. 4.28, p. 207,
section 4.3.4.5.2, p. 206), then the user interface is displayed as shown in
Fig. 4.58, p. 147 (section 4.3.4.2.5.4, p. 147).
If none of the above interfaces were activated for setpoint specification, then
the user interface is displayed as shown in Fig. 4.55, p. 142 and the set-
point specification can be implemented manually via a configuration text box
(3) or via Modbus/TCP communication (section 4.3.4.2.5.1, p. 144).
2. Symbol with display text box to display the actual active power maximum
value in per cent of the device as part of grid security or infeed manage-
ment. This element is always displayed in the user interface, irrespective of
the interface used for setpoint specification
The displayed value takes into account the setpoint specification ramp func-
tion (if used) and any activated delay times (if used) for the setpoint. If the
function is not generally used, the value 100% is always displayed.
The display is also available in the Start user interface “Overview” (sec-
tion 4.3.1, p. 39) and in the menu option “Limit” user interface of the menu
sub-group “Grid” in the menu group “Status and Values” (section 4.3.2.4.3,
p. 65).
Changes as of Fitter 3. The actual setpoint in per cent for the active Limit is shown here in a con-
figuration text box, without taking into account the ramp function (if used) or
the activated delay time (if used). This display is always available in the user
interface, irrespective of the interface used for setpoint specification.
The configuration text box is normally only used to display the actual set-
point for the active Limit. If the option “Not used (manual or MODBUS TCP)”
is active in the option field (1), the setpoint specification can be implemented
manually via this configuration text box. The configuration text box is re-
leased for manual input by the user after the “Manual” button (5) is pressed.
4. This area is used to display and change the configuration of the ramp func-
tion for limiting the setpoint gradient for active Limit. The maximum change
to the active Limit in per cent [%/s] is displayed and configured via the
configuration text box. The activation/deactivation of the active power ramp
is implemented in the activation field next to the configuration text box.
Fig. 4.56: U
ser interface of the menu option “Limit” in the menu sub-group
“Grid” of the menu group “Configuration” (Digital inputs)
Changes as of Fitter 6. The visualisation of the possible combinations for up to four digital signals
for active Limit setpoint specifications is shown in this area. The display text
boxes show the corresponding decimal value of the respective signal combi-
nations. The state fields visualise the respective signal states of the possible
signal combinations, dependent on the number of digital signals used for
setpoint specification. Unused signal combinations are indicated by grey
state fields for the corresponding signals (e.g. if only three digital inputs are
used). The actual active signal combinations are marked according to the
actual signal states of the digital inputs used.
The signal states of the digital inputs used are also displayed in status word
3 (see nos. 9 to 12 in Tab. 4.12, p. 47, section 4.3.2.1, p. 41).
7. This area is used to display and edit, where necessary, the active Limit
values in per cent based on the rated device power in the configuration text
boxes for all possible combinations of the up to four digital signals for set-
point specification (maximum 16 states if all four digital signals for setpoint
specification are used).
8. A special trigger mode for setpoint specification of the active Limit via
digital inputs can be activated/deactivated using this button. In this mode,
up to maximum 5 different setpoint specifications for the active Limit can
be implemented if all four digital signals are used. The correspondingly
set setpoints are only changed if the flanks of the digital signals rise, i.e. a
specified setpoint remains active until the rising flank of a digital signal for a
different setpoint is detected.
9. This configuration text box is used to display and edit, where necessary, a
delay time in [ms] for setpoint acceptance after a signal state change. The
corresponding active Limit setpoint of a new signal state or a new combina-
tion of signal states is only accepted as the setpoint after this delay time has
elapsed.
13 12
10
11 14
Fig. 4.57: U ser interface of the menu option “Limit” in the menu sub-group
“Grid” of the menu group “Configuration” (analogue input)
Changes as of Fitter 10. This diagram area is used to display and edit, where necessary, the charac-
teristic curve function with the corresponding data points used to generate
the setpoints for active Limit. The output value of the displayed characteris-
tic curve is the setpoint for the active Limit in [%] based on the rated power
of the PVMaster device. The value of the analogue input represents the
input value of the displayed characteristic curve. The characteristic curve
displayed in the diagram area is modified appropriately dependent on the
selection of the interpolation mode in the option field (12).
When a data point in the diagram area is selected, the corresponding
numerical value of the active power limit value in per cent is shown in the
configuration text box (11) in [%/PN] and can subsequently be changed in
this configuration text box. Individual data points can also be changed by
vertically shifting the data points in the diagram area.
11. This configuration text box is used to display and edit, where necessary, the
respective active power limit value in per cent [%/PN] of the characteristic
curve data point selected in the diagram area (10).
Changes as of Fitter 12. The interpolation mode for the set characteristic curve is selected in this
option field.
If the option “No interpolation” is selected, the setpoint specification is imple-
mented within a characteristic curve section according to the left-hand data
point of the characteristic curve section. There is an inevitable discontinu-
ity in the setpoint specification each time the characteristic curve section is
changed due to the analogue signal changing.
If the option “Linear interpolation” is selected in the option field, then the
setpoint is generated within a characteristic curve section by the linear inter-
polation of the active power limit values in per cent of the left and right data
points in the characteristic curve section.
13. This configuration text box is used to display and edit, where necessary, a
delay time in [ms] for setpoint acceptance after a characteristic curve sec-
tion change. The corresponding active Limit setpoints of a new character-
istic curve section are only accepted as setpoints after this delay time has
elapsed.
14. The actual value of the analogue input used for the active Limit setpoint
specification is displayed in this display text box in [%]. This value repre-
sents the input value of the characteristic curve function.
4 3
Fig. 4.58: U
ser interface of the menu option “Limit” in the menu sub-group
“Grid” of the menu group “Configuration” (InterCOM)
The actual setpoint in per cent for the active Limit is also displayed in this case
in the user interface of the menu option “InterCOM” in the menu group “State
and Values” (section 4.3.2.2, p. 48). The setpoint is displayed there in the cor-
responding display text box of the InterCOM node broadcasting the setpoint to
the other InterCOM nodes. The other InterCOM nodes limit the active power fed
in in accordance with this active power maximum value in per cent (based on
the rated power of the device).
The actual reactive power and the actual power factor (as phase and total or
average value) is displayed in the user interface of the menu option “Power” in
the menu sub-group of the menu group “Status and Values” (section 4.3.2.4.2,
p. 63).
The state of the static grid voltage stabilisation is shown via status word 3 (see
no. 17 in Tab. 4.12, p. 47, section 4.3.2.1, p. 41).
The menu option “Voltage” in the menu sub-group “Grid stabilisation” of the
menu group “Configuration” is available in every user level. The corresponding
user interfaces (Fig. 4.59 to Fig. 4.62, p. 155) are used to display the actual
state and to display and edit the settings for the setpoint specification/genera-
tion functions for the reactive power control as part of static grid voltage stabili-
sation. At the “Observer” user level, only the actual state and active settings are
displayed. Changes to the settings are only possible as of the user level “Fitter”.
Fig. 4.59: U
ser interface of the menu option “Voltage” in the menu sub-group
“Grid stabilisation” of the menu group “Configuration” (option: no
reactive power)
The elements displayed in the user interface vary depending on the interface
used for setpoint specification.
Changes as of Fitter 1. This option field is used to display and select the method or interface used
for setpoint specification/generation for reactive power control as part of
static grid voltage stabilisation. The option field is always displayed in the
user interface, irrespective of the method or interface used for setpoint
specification/generation.
a) “No reactive power (max. power factor)”: the active infeed operation
is always implemented with the maximum possible power factor. The
setpoint for reactive power control is always zero. The user interface for
this option is displayed as shown in Fig. 4.59.
b) “Fixed reference value”: If this option is selected, the setpoint specifica-
tion for the reactive power control is always implemented as a fixed set-
point or dependent on the signal states of the digital inputs used for this
purpose (section 4.3.4.3.1.1, p. 150). In total, up to four digital inputs
can be used for setpoint specification (functions 39, 40, 41 and/or 42 in
Tab. 4.19, p. 168, see section 4.3.4.4.1, p. 166). The user interface
for this option is displayed as shown in Fig. 4.60, p. 151.
9
3
Fig. 4.60: U ser interface of the menu option “Voltage” in the menu sub-group
“Grid stabilisation” of the menu group “Configuration” (option: fixed
setpoint)
Changes as of Fitter 3. The type of setpoint is selected in this selection box. Setpoint generation
or specification can be implemented as required as a phase offset value
in [°deg], as a power factor cosPhi or tanPhi, or as a direct reactive power
value in [kVAr].
4. The visualisation of the possible combinations for up to four digital signals
for reactive power control is shown in this area. The display text boxes show
the corresponding decimal value of the respective signal combinations.
The state fields visualise the respective signal states of the possible signal
combinations, dependent on the number of digital signals used for setpoint
specification. Unused signal combinations are indicated by grey state fields
for the corresponding signals (e.g. if only three digital inputs are used). The
actual active signal combinations are marked according to the actual signal
states of the digital inputs used.
Changes as of Fitter 5. This area is used to display and edit, where necessary, the setpoints in the
configuration text boxes for all possible combinations of the up to four digital
signals for setpoint specification (maximum 16 states if all four digital signals
for setpoint specification are used).
If no digital input is used for setpoint specification, then the set setpoint of
the first element (signal combination 0) is always used.
The input limits and the initialisation of the values in the individual configu-
ration text boxes are dependent on the selection of the setpoint type in the
selection box (3).
6. These selection boxes are only available when the setpoint type “cosPhi”
is activated (via selection box (3)) and are used to display and edit, where
necessary, the setpoint type (inductive or capacitive) for all possible com-
binations of the digital signals (of which there are up to four) for setpoint
specification (maximum 16 states if all four digital signals for setpoint speci-
fication are used).
7. A special trigger mode for setpoint specification via digital inputs can be acti-
vated/deactivated using this button. In this mode, up to maximum 5 different
setpoint specifications for the reactive power control can be implemented
if all four digital signals are used. The correspondingly set setpoints are
only changed if the flanks of the digital signals rise, i.e. a specified setpoint
remains active until the rising flank of a digital signal for a different setpoint
is detected.
8. This configuration text box is used to display and edit, where necessary, a
delay time in [ms] for setpoint acceptance after a signal state change. The
corresponding setpoint of a new signal state or a new combination of signal
states is only accepted as the setpoint after this delay time has elapsed.
9. The actual reactive Limit setpoint is shown here in a configuration text box,
without taking into account the activated delay time (if used). This display is
always available in the user interface, irrespective of the method or interface
used for setpoint specification/generation.
If the setpoint type “cosPhi” was selected via the selection box (3), then a
status field is displayed next to the configuration text box. This status field is
active as soon as setpoint specification is set to inductive.
The configuration text box is normally only used to display the actual set-
point. If the option “Manual or MODBUS TCP)” is active in the option field
(1), the setpoint specification can be implemented manually via this configu-
ration text box. The configuration text box is released for manual input by
the user after the “Manual” button (22) is pressed.
16 17
20
13 11 18
10
14 12 19 15
Fig. 4.61: U
ser interface of the menu option “Voltage” in the menu sub-group
“Grid stabilisation” of the menu group “Configuration” (option: table
function)
Changes as of Fitter 10. This diagram area is used to display and edit, where necessary, the charac-
teristic curve function with the corresponding data points used to generate
the setpoints for reactive power control. The output value of the displayed
characteristic curve is the setpoint for the reactive power control depending
on the selection of the setpoint type via the selection box (13). The input
value of the displayed characteristic curve is displayed or selected via the
selection box (12).
The characteristic curve displayed in the diagram area is modified appropri-
ately dependent on the selection of the interpolation mode in the option field
(16).
When a data point in the diagram area is selected, the corresponding
numerical value of the setpoint is shown in the configuration text box (11)
and can subsequently be changed in this configuration text box. Individual
data points can also be changed by vertically shifting the data points in the
diagram area.
If the setpoint type “cosPhi” was set in the selection box (13), then the type
of setpoint is indicated by the colour of the individual data points (blue = in-
ductive or red = capacitive). The setpoint type of the individual data points
can be changed in this case via the additional selection box next to the
configuration text box (11).
11. This configuration text box is used to display and edit, where necessary,
the respective setpoint of the characteristic curve data point selected in the
diagram area (10).
If the setpoint type “cosPhi” was set in the selection box (13), then another
selection box will be available next to the configuration text box to select the
setpoint type (inductive or capacitive) of the individual data points.
12. This selection box is used to display and edit, where necessary, the input
signal of the characteristic curve function:
a) “Pac/PN[%]”: the actual AC active power based on the rated power of
the PVMaster device is used as the input value for the characteristic
curve function (e.g. for activation of a cosPhi=f(P) characteristic curve).
b) “Veff/VN[%]”: the actual grid voltage based on the set rated value of the
grid voltage is used as the input value for the characteristic curve func-
tion (e.g. for activation of a Q=f(U) characteristic curve).
c) “Time [hh:mm]”: the actual time is used as the input value for the char-
acteristic curve function (for activation of a time plan for reactive power
setpoint specification).
NOTE
If an analogue input is allocated function no. 5 (Tab. 4.23, p. 190, see sec-
tion 4.3.4.4.3, p. 189), then it is not possible to select the input signal via the
selection box and the value of the analogue input is used as the input signal.
13. The selection of the characteristic curve function output signal type for the
reactive power control setpoint specification is implemented in this selection
box. Setpoint generation or specification can be implemented as required
as a phase offset value in [°deg], as a power factor cosPhi or tanPhi, or as a
direct reactive power value in [kVAr].
14. The value range of the input signal is configurable so that the characteristic
curve function with its 21 data points can be carried out for any part of the
input signal.
This configuration text box is used to specify the lower value of the input
signal range for the scaling of the characteristic curve. The setpoint specifi-
cation is implemented according to the first data point for input signal values
below this specified minimum value.
15. The value range of the input signal is configurable so that the characteristic
curve function with its 21 data points can be carried out for any part of the
input signal.
This configuration text box is used to specify the upper value of the input
signal range for the scaling of the characteristic curve. The setpoint speci-
fication is implemented according to the 21st data point for input signal
values above this specified end value.
16. The interpolation mode for the set characteristic curve is selected in this
option field.
If the option “No interpolation” is selected, the setpoint specification is imple-
mented within a characteristic curve section according to the left-hand data
point of the characteristic curve section. There is an inevitable discontinu-
ity in the setpoint specification each time the characteristic curve section is
changed due to the characteristic curve input signal changing.
If the option “Linear interpolation” is selected in the option field, then the
setpoint is generated within a characteristic curve section by the linear inter-
polation of the setpoints of the left and right data points in the characteristic
curve section.
17. This area contains elements for using the zoom functions in the diagram
function. The zoom mode in the diagram area is activated/deactivated via
the button.
If the zoom mode is activated, this is shown in the status field next to the
button and the area to be enlarged can be selected in the diagram area. If
the zoom mode is activated, the data points cannot be shifted in the dia-
gram area. To do this, the zoom function must first be deactivated via the
button, e.g. after the required diagram area has been enlarged.
Pressing the “Reset” button returns the diagram area display to the normal
display without any enlargement.
18. Pressing the “Initialise” button initialises the 21 data points for the respective
setpoints according to the setpoint type set in the selection box (13). If the
setpoint type “cosPhi” is activated, pressing the “Initialise” button will initial-
ise all data points to the value 1. With the other setpoint types “Phi [°deg]”,
“tanPhi” and “Q [kVAr]”, all data points are initialised to the value zero when
the button is pressed.
19. The actual value of the characteristic curve function input signal for setpoint
generation is displayed in this display text box with the applicable unit of the
input signal type selected in the selection box (12).
This display text box is not available for the input signal type “Time
[hh:mm]”.
20. This configuration text box is used to display and edit, where necessary, a
delay time in [ms] for setpoint acceptance after a characteristic curve sec-
tion change. The corresponding active Limit setpoints of a new character-
istic curve section are only accepted as setpoints after this delay time has
elapsed.
21
22
Fig. 4.62: U
ser interface of the menu option “Voltage” in the menu sub-group
“Grid stabilisation” of the menu group “Configuration” (Option: Manual
or Modbus TCP)
Changes as of Fitter 21. The type of setpoint is selected in this selection box. Setpoint generation
or specification can be implemented as required as a phase offset value
in [°deg], as a power factor cosPhi or tanPhi, or as a direct reactive power
value in [kVAr].
22. This button is used to release the configuration text box (9) for manual set-
ting of the setpoint for reactive power control.
2 4 11
12
13 7 14
8
5
3
9
10
6
Fig. 4.63: U
ser interface of the menu option “Frequency stabilisation” in the
menu sub-group “Grid stabilisation” of the menu group “Configura-
tion” (option: frequency stabilisation active, hysteresis operation)
Changes as of Fitter 1. This option field is used for the activation/deactivation of the function for
static grid frequency stabilisation. If the option “Frequency stabilisation not
used” is selected, then no additional elements are displayed in the user
interface.
2. This option field is used to display and edit, where necessary, the operation
mode of the characteristic curve for static grid frequency stabilisation.
If the first option “Hysteresis operation” (Fig. 4.63, p. 157) is selected, the
actual active power is only reduced according to the set reduction gradi-
ent in the configuration text box (9) after the start value (7) is exceeded by
the actual grid frequency (3) during the activity of active Limit for static grid
frequency stabilisation. Increasing the active power is only then possible
when the grid frequency (3) drops below the end value (13) again. The
characteristic curve in the area of active Limit is therefore only “operated” in
one direction.
If the second option “Curve operation” (Fig. 4.64) is selected, the actual
active power is initially also reduced according to the set reduction gradi-
ent in the configuration text box (9) after the start value (7) is exceeded by
the actual grid frequency (3) during the activity of active Limit for static grid
frequency stabilisation. However, in this operation mode for the static grid
frequency stabilisation function, the characteristic curve is “operated” in both
directions so that an increase in active power can occur as soon as the grid
frequency value (3) drops.
8. When the function for static grid frequency stabilisation becomes active,
the “frozen” value of the AC active power in [kW] PM is displayed in this
display text box. The active Limit for static frequency stabilisation relates to
this “frozen” value. No value is displayed here if the function for static grid
frequency stabilisation is not active.
9. This configuration text box is used to display and edit, where necessary,
the reduction gradient in [%PM/Hz] for active Limit in case of raised grid
frequency values, i.e. the reduction in per cent of the actual active power
(related to the “frozen” active power value) per Hz above the start value of
the function for static grid frequency stabilisation.
10. If the static grid frequency stabilisation function is actually active in case of
raised grid frequency, the actual absolute active Limit is displayed here in
[kW] (difference between “frozen” active power value and the actual AC ac-
tive power). No value is displayed here if the function for static grid frequen-
cy stabilisation is not active.
11. The resulting absolute active Limit by the function for static grid frequency
stabilisation is displayed in this display text box in [kW]. No value is dis-
played here if the function for static grid frequency stabilisation is not active.
12. Symbol with display text box for displaying the resulting actual active Limit
in per cent of the device (based on the device rated power) due to the active
function for static grid frequency stabilisation. This display is also available
in the user interface “Limit” of the menu sub-group “Grid” in the menu group
“Status and Values” (section 4.3.2.4.3, p. 65).
13. This configuration text box is used to display and edit, where necessary,
the end value of the grid frequency for the static grid frequency stabilisation
function in [Hz]. The value is preset as the differential value to the set rated
frequency (5).
If the actual grid frequency in active infeed operation drops below this end
value, then the previously active static grid frequency stabilisation function
is deactivated again.
14. The upper limit value of the grid frequency in [Hz] is shown in this configu-
ration text box. If the actual grid frequency exceeds this limit value, the
PVMaster device is switched off due to the grid monitoring functions (see
section 4.3.4.2.3, p. 124).
At the “Observer” user level, only the actual state and active settings are dis-
played. Changes are only possible as of the user level “Fitter”.
The state of the dynamic grid stabilisation function is shown via status word 3
(see nos. 18 and 19 in Tab. 4.12, p. 47, section 4.3.2.1, p. 41). Any change
to these states represents a “special event” and will be recorded by the inte-
grated data logger. The retrieval, display and further processing of the “unu-
sual events” that have occurred can be easily implemented in the menu option
“Events” of the menu group “Diagnosis” (section 4.3.5.2, p. 229).
1 3
2 6
5 7 4
Fig. 4.65: U
ser interface of the menu option “LVRT” in the menu sub-group
“Grid stabilisation” of the menu group “Configuration”
Changes as of Fitter 1. This selection box is used to activate the additional reactive current infeed in
the case of a fault or for selecting the appropriate reactive current response
required. Any changes in this option field are automatically reflected in the
visualised switch-off diagram (8) and the visualised reactive current re-
sponse (10) in the tab option “Reactive current response”.
If the option “No reactive current” is selected, no additional reactive current
is fed in for grid stabilisation if there is a fault due to brief grid voltage drops.
If the option “Reactive current response 1 (TC2007)” is selected, then the
additional reactive current in the case of grid voltage drops is determined
dependent on the remaining grid voltage based on the reactive current
response according to the “VDN - TransmissionCode 2007” (see Fig. 4.66,
p. 163).
The states are also displayed in status word 3 (see nos. 18 and 19 in Tab.
4.12, p. 47, section 4.3.2.1, p. 41). Any change to these states repre-
sents a “special event” and will be recorded by the integrated data logger.
The retrieval, display and further processing of the “unusual events” that
have occurred can be easily implemented in the menu option “Events” of the
menu group “Diagnosis” (section 4.3.5.2, p. 229).
7. When the grid voltage returns (fault rectified) into the deadband (5), the set-
point in the reactive power controller is limited for the time set via the con-
figuration text box to the reactive power setpoint before the fault occurred
(minutes average). This limitation is to ensure that operation does not occur
with less excitation than before the grid voltage drop.
8. This diagram area is used to visualise the switch-off diagram dependent on
the configuration of the grid voltage monitoring functions (section 4.3.4.2.3,
p. 124). In addition, the configuration of the dynamic grid stabilisation func-
tion is visualised in the diagram area (deadband as green section and sec-
tion of overexcited operation due to additional reactive current infeed in red).
Changes as of Expert 9. This area of the user interface is used to display and edit the functions for
monitoring the voltage drop V<< and voltage rise V>> in the same way as in
section 4.3.4.2.3, p. 124. Manual modification of these settings is also only
possible here when the “User-defined settings” are activated.
The checkboxes are used to display and configure or enable or disable this
monitoring function. Here, the network phase voltages (ph-n) can be moni-
tored, and / or linked grid voltages (ph-ph). The upper configuration text box
is used to display and change the limit value, in [%] or in [V ph-n] according
to choice, as an absolute phase voltage limit or [V ph-ph] as an absolute
limit for the linked grid voltage. The lower configuration text box is used
to display and edit the delay time in [ms] for the monitoring functions. The
triggering of the corresponding fault state and therefore the switch-off of the
PVMaster device is actuated in this monitoring function when the respective
grid voltage limit value is exceeded continuously for the duration of the set
delay time. Changes to the settings are automatically reflected in the visual-
ised switch-off diagram (8).
The second tab option “Reactive current response” (Fig. 4.66) in the user
interface is used to visualise the set reactive current response in a diagram
field and to display applicable actual values, as well as to display and edit
other dynamic grid stabilisation function settings.
11 12 13
10
17
14 15 16
Fig. 4.66: T
ab option “Reactive current response” in menu option “LVRT”
(option: Reactive current response 1 as per TC2007)
Changes as of Fitter 10. This diagram area is used to visualise the set reactive current response
based on the settings in the selection box (1). The horizontal axis here
represents the relevant grid voltage change ∆V / VN in per cent, while the
vertical axis shows the additional reactive current ∆IB / IN in per cent.
The displayed diagram is automatically updated if the k factor (14) or the
dead time (5) is changed.
11. This display is used to show the percentage additional reactive current
∆IB / IN at the current time (in relation to the nominal current of the PVMas-
ter device) used for grid stabilisation in the case of a failure.
12. This display text box is used to display the reactive current value as an
amplitude value before the failure occurs îB0 (minute average value of the
setpoint) in [A].
13. The relevant change in grid voltage can be calculated in relation to the grid
voltage since the input value of the response can be determined in differ-
ent ways and on different bases. This selection box shows the values used
as the basis for the calculation method. Changes via this selection box are
not possible. Each calculation method differs depending on the PVMaster
device variant and the country code used if necessary.
14. The proportion of the additional reactive current infeed, dependent on the
actual relevant grid voltage deviation in percent ∆V / VN, is determined by
the so-called k factor (gradient within the reactive current response). The k
factor is normally selected by the grid operator. The k factor is set via this
configuration text box and is preset at k=2 in the condition as supplied or the
default setting of the PVMaster.
Fig. 4.67: T
ab option “Reactive current response” in menu option “LVRT”
(option: Reactive current response 2 as per SDLWindV)
Changes as of Expert 15. After a grid voltage drop, the additional reactive current infeed is maintained
according to the reactive current response (for reactive current response
according to TC2007 only), even after the grid voltage returns or the fault is
rectified (grid voltage back in deadband).
The duration for which the additional reactive current infeed is maintained
is set via this configuration text box in [ms]. The value is preset at 500 ms in
the default setting or condition of the PVMaster II as supplied.
16. This configuration text box shows the set value for the time delay of the
setpoint ramp for the additional reactive current in the case of LVRT failure
in [ms]. This configuration box is used for display purposes only. Manual
changes to the setpoint ramp for the additional reactive current are gener-
ally not possible.
17. The percentage additional reactive current is limited according to the type of
error (symmetry or asymmetry errors). The percentage limits concerned are
only displayed via these two configuration text boxes. Manual changes via
this configuration text box are not possible.
18 19
20 24
21 22 23
23. Configuration text box for showing the percentage limit for the relevant grid
voltage drop, where temporary modulation pauses are used when the limit
is exceeded during an LVRT event. When the grid voltage drops below this
limit, there are no temporary or feed-modulation pauses. This configuration
box is used for display purposes only. Manual changes via this configuration
text box are not possible.
24. Selection box for showing the enabled mode of the current regulator Dif-
ferent methods of current regulation are used depending on the PVMaster
device version. For example, with the PVMaster III the positive and negative
sequence current are controlled separately, where the negative sequence
current is always regulated to zero in order always to feed symmetrical grid
currents independently of the grid voltage. This selection box is used for dis-
play purposes only. Manual changes via this selection box are not possible.
4.3.4.4 In-/Outputs
as of Fitter This menu sub-group is available as of user level “Fitter” and contains menu
options for displaying and editing the configuration of digital inputs and outputs,
and the analogue and temperature inputs of the device. Freely selectable func-
tions can be assigned to the digital inputs and outputs and the analogue and
temperature inputs. Digital inputs and outputs can be inverted. Low-pass filter
time constants for digital and analogue inputs and the temperature inputs can
be set. The signal type used and the scaling to be used for the analogue inputs
can be freely set. In addition, fan actuation can be configured or general thresh-
old value functions for the digital outputs can be defined and used.
REFERENCE
A description of the available digital inputs and outputs, and analogue inputs of
the PVMaster device, and information about wiring can be found in the rel-
evant PVMaster installation manual.
1 2 3 4 5 6
Fig. 4.69: U
ser interface of the menu option “Dig. Inputs” in the menu sub-
group “In-/Outputs” of the menu group “Configuration”
as of Fitter 1. Display of the assignment numbers for the respective digital inputs of the
PVMaster device in display text boxes.
NOTE
The number of available digital inputs varies according to the PVMaster device
type.
2. The current physical states of the respective digital inputs are displayed in
these status fields.
3. A logical inversion can be activated in these activation fields for the evalua-
tion of the respective digital inputs.
4. Low-pass filters (Pt1 behaviour) can be activated to filter the states for
evaluation of the individual digital inputs. Activation is implemented by speci-
fying the filter time constant in [ms] in these configuration text boxes. If 0ms
is set, the respective state is evaluated without filtering.
5. The respective assigned functions of the digital inputs are displayed and
configured in these selection boxes. The possible functions of digital inputs
are listed and described in Tab. 4.19, p. 168.
NOTE
The available functions for the digital inputs vary according to the PVMaster
device type.
6. These status fields indicate the respective function state dependent on the
physical state of the respective digital inputs and taking account of any acti-
vated logical inversion and filtering of the signal state.
1 2 3 4 5
Fig. 4.70: U
ser interface of the menu option “Dig. Outputs” in the menu sub-
group “In-/Outputs” of the menu group “Configuration”
as of Fitter The first tab option “Mapping” (Fig. 4.70) is used to display and edit the configu-
ration of the respective digital outputs, and to display the actual states.
1. Display of the assignment numbers for the respective digital outputs of the
PVMaster device in display text boxes.
NOTE
The number of available digital outputs varies according to the PVMaster
device type.
2. The respective assigned functions of the digital outputs are displayed and
configured in these selection boxes. Selecting a predefined function in these
selection boxes initialises the corresponding values for the linking or map-
ping of the respective digital inputs and displays them in the corresponding
configuration text boxes (3). The predefined functions of digital outputs are
described in Tab. 4.20, p. 177.
3. In general, the digital outputs can be switched dependent on the states of all
parameters and display values of the PVMaster device. The necessary link-
ing or mapping of the digital outputs with the required parameters or display
values is implemented by specifying the ID and Sub-ID, and by specifying
the bits of the required parameters to be used. The ID, Sub-ID and bit num-
ber for the linking or mapping are displayed in these three configuration text
boxes. The corresponding values for the linking or mapping are initialised
and displayed in these configuration text boxes following the selection of a
predefined function in the selection boxes (2).
as of Expert The linking or mapping of digital outputs by specifying the ID, Sub-ID and
bit number can also be implemented manually via these configuration text
boxes as of user level “Expert”. To do this, the element “User-defined” must
first be selected in the selection box (2) so that the configuration text boxes
can be released for inputs.
as of Fitter 4. A logical inversion of the respective digital outputs can be activated in these
activation fields.
5. These status fields display the actual switching state of the respective digital
outputs, taking into account the applicable activated logical inversion, if
present.
Parameters
Function Sub- Description
ID Bit
ID
Signal of 2nd freely configurable
Threshold function 2 163 0 1 threshold function (see sec-
tion 4.3.4.4.2.2, p. 184).
Signal of 3rd freely configurable
Threshold function 3 163 0 2 threshold function (see sec-
tion 4.3.4.4.2.2, p. 184).
Signal of 4th freely configurable
Threshold function 4 163 0 3 threshold function (see sec-
tion 4.3.4.4.2.2, p. 184).
Signal of 5th freely configurable
Threshold function 5 163 0 4 threshold function (see sec-
tion 4.3.4.4.2.2, p. 184).
Signal of 6th freely configurable
Threshold function 6 163 0 5 threshold function (see sec-
tion 4.3.4.4.2.2, p. 184).
Signal of 7th freely configurable
Threshold function 7 163 0 6 threshold function (see sec-
tion 4.3.4.4.2.2, p. 184).
Signal of 8th freely configurable
Threshold function 8 163 0 7 threshold function (see sec-
tion 4.3.4.4.2.2, p. 184).
Error active 91 0 3 Message "Device in fault state"
Message "Power stage or infeed
Inverter active 91 0 8
operation active"
Warning 91 0 9 ...a warning has been signalled
Feedback of 1st signal for set-
point specification of active Limit
in percent (e.g. by grid operator)
Power reduction state 1 575 0 0
as part of infeed/grid security
management via digital inputs
(see section 4.3.4.2.5, p. 141).
Feedback of 2nd signal for set-
point specification of active Limit
in percent (e.g. by grid operator)
Power reduction state 2 575 0 1
as part of infeed/grid security
management via digital inputs
(see section 4.3.4.2.5, p. 141).
Feedback of 3rd signal for set-
point specification of active Limit
in percent (e.g. by grid operator)
Power reduction state 3 575 0 2
as part of infeed/grid security
management via digital inputs
(see section 4.3.4.2.5, p. 141).
Feedback of 4th signal for set-
point specification of active Limit
in percent (e.g. by grid operator)
Power reduction state 4 575 0 3
as part of infeed/grid security
management via digital inputs
(see section 4.3.4.2.5, p. 141).
Parameters
Function Sub- Description
ID Bit
ID
Feedback of 1st signal for set-
point specification for reactive
Reactive power control power control (e.g. by grid opera-
580 0 0
state 1 tor) as part of static grid voltage
stabilisation via digital inputs (see
section 4.3.4.3.1, p. 147).
Feedback of 2nd signal for set-
point specification for reactive
Reactive power control power control (e.g. by grid opera-
580 0 1
state 2 tor) as part of static grid voltage
stabilisation via digital inputs (see
section 4.3.4.3.1, p. 147).
Feedback of 3rd signal for set-
point specification for reactive
Reactive power control power control (e.g. by grid opera-
580 0 2
state 3 tor) as part of static grid voltage
stabilisation via digital inputs (see
section 4.3.4.3.1, p. 147).
Feedback of 4th signal for set-
point specification for reactive
Reactive power control power control (e.g. by grid opera-
580 0 3
state 4 tor) as part of static grid voltage
stabilisation via digital inputs (see
section 4.3.4.3.1, p. 147).
12
7 8 9 10 11
13
19
14 15 16 17 18
Fig. 4.71: Tab option “Fan and cooler control” in the menu option “Dig. Outputs”
as of Fitter The upper section of the tab option “Fan and cooler control” (Fig. 4.71) is used
to display and edit the functions for controlling fans and heat exchangers.
6. This selection box is used to select one of the four available functions for
controlling the fans and heat exchangers. Elements (7) to (12) are used to
display and edit, where necessary, the configurations, and to display the
monitored actual (temperature) values and the state of the selected func-
tion.
NOTE
Some functions used to control fans and heat exchangers are already used as
standard internally (e.g. to control the fan inside the enclosure). The number of
freely available and configurable functions for controlling fans and heat ex-
changers is therefore dependent on the PVMaster device type.
If internal functions are reserved for controlling fans and heat exchangers,
the settings cannot be edited and entries cannot be made in the corre-
sponding configuration text boxes. The availability of a freely configurable
function for controlling fans and heat exchangers is displayed after selection
in the selection box in the activation field next to the selection box.
7. The ID and Sub-ID of the respective (display) parameters to be monitored
are displayed here in configuration text boxes.
If the element “User-defined” is selected in the selection box (8), then the
configuration text boxes are released for input and the (display) parameters
to be monitored can be selected manually by inputting the ID and Sub-ID in
the configuration text boxes.
8. The selection box is used to display and edit, where necessary, the respec-
tive (display) parameters to be monitored. The (predefined) parameters
available in the selection box are listed in Tab. 4.21, p. 182. Alternatively,
the element “User-defined” can be selected and the (display) parameters to
be monitored can be selected manually in the configuration text boxes (7).
9. The (temperature) values selected for monitoring are displayed here in dis-
play text boxes for those functions selected in the selection box (6).
10. This configuration text box is used to display and edit, where necessary,
the switch-on threshold value of the monitored (temperature) values for the
functions selected in the selection box (6). If at least one monitored (temper-
ature) value exceeds the set switch-on value, then the state of the function
for controlling the fans and heat exchangers becomes active.
11. This configuration text box is used to display and edit, where necessary,
the switch-off threshold value of the monitored (temperature) values for the
functions selected in the selection box (6). Once all monitored (temperature)
values exceed the respective set switch-off values, then the state of the
function for controlling the fans and heat exchangers becomes inactive.
12. This status field displays the actual state of the function selected in the
selection box (6) for controlling the fans and heat exchangers. The state
becomes active as soon as at least one of the up to five monitored (tem-
perature) values exceeds the corresponding switch-on threshold value (10).
The state becomes inactive only once all monitored (temperature) values
drop below the corresponding switch-off thresholds (11).
The display of the four states of the functions for controlling fans and heat
exchangers is also available in the corresponding symbol on the start user
interface “Overview” (section 4.3.1, p. 39) and in status word 1 (nos. 16 to
19 in Tab. 4.10, p. 43, see section 4.3.2.1, p. 41). All state changes are
recorded by the integrated (state) data logger (see section 4.3.5.3, p. 231).
as of Fitter The lower section of the tab option “Fan and cooler control” (Fig. 4.71, p. 180)
is used to display and edit the functions for controlling coolers and coolant
pumps.
13. This selection box is used to select one of the two available functions for
controlling the coolers and coolant pumps. Elements (14) to (19) are used
to display and edit, where necessary, the configurations, and to display the
monitored actual (temperature) values and the state of the selected func-
tion.
NOTE
Functions may already be used as standard internally for controlling coolers
and coolant pumps, dependent on the PVMaster device type.
If internal functions are reserved for controlling coolers and coolant pumps,
the settings cannot be edited and entries cannot be made in the corre-
sponding configuration text boxes. The availability of a freely configurable
function for controlling coolers and coolant pumps is displayed after selec-
tion in the selection box in the activation field next to the selection box.
14. The ID and Sub-ID of the respective (display) parameters to be monitored
are displayed here in configuration text boxes.
If the element “User-defined” is selected in the selection box (15), then the
configuration text boxes are released for input and the (display) parameters
to be monitored can be selected manually by inputting the ID and Sub-ID in
the configuration text boxes.
15. The selection box is used to display and edit, where necessary, the respec-
tive (display) parameters to be monitored. The (predefined) parameters
available in the selection box are listed in Tab. 4.21, p. 182. Alternatively,
the element “User-defined” can be selected and the (display) parameters to
be monitored can be selected manually in the configuration text boxes (14).
16. The (temperature) values selected for monitoring are displayed here in dis-
play text boxes for those functions selected in the selection box (13).
17. This configuration text box is used to display and edit, where necessary,
the switch-on threshold value of the monitored (temperature) values for
the functions selected in the selection box (13). If at least one monitored
(temperature) value exceeds the set switch-on value, then the state of the
function for controlling the coolers and coolant pumps becomes active.
18. This configuration text box is used to display and edit, where necessary,
the switch-off threshold value of the monitored (temperature) values for the
functions selected in the selection box (13). Once all monitored (tempera-
ture) values exceed the respective set switch-off values, then the state of
the function for controlling the coolers and coolant pumps becomes inactive.
19. This status field displays the actual state of the function selected in the
selection box (13) for controlling the coolers and coolant pumps. The state
becomes active as soon as at least one of the up to five monitored (tem-
perature) values exceeds the corresponding switch-on threshold value (17).
The state becomes inactive only once all monitored (temperature) values
drop below the corresponding switch-off thresholds (18).
The two states of the functions for controlling coolers and coolant pumps
are also displayed in status word 1 (nos. 20 and 21 in Tab. 4.10, p. 43,
see section 4.3.2.1, p. 41). All state changes are recorded by the inte-
grated (state) data logger (see section 4.3.5.3, p. 231).
Tab. 4.21: Predefined monitoring values for the fan and cooler control
Parameters
Value / Parameter Description
ID Sub-ID
No function - - -
The (display) parameter to be
monitored is selected manually
User-defined - -
by specifying the ID and Sub-ID
of the parameter.
Temperature of the filter chokes
Temperature choke
553 0 in [°C], measured via a PT100
(PT100)
input of the device
Temperature of the transformer in
Temperature transformer
553 1 [°C], measured via a PT100 input
(PT100)
of the device
Temperature inside the enclosure
Temperature cabinet
553 2 in [°C], measured via a PT100
(PT100)
input of the device
Temperature Ext. in [°C], meas-
Temperature external
553 3 ured via a PT100 input of the
(PT100)
device
Module temperature 1 in [°C]
Temperature pv-module 1
553 4 measured via an analogue input
(ana. input)
of the device.
Module temperature 2 in [°C]
Temperature pv-module 2
553 5 measured via an analogue input
(ana. input)
of the device.
Temperature Ext. 1 in [°C] meas-
Temperature external 1
553 6 ured via an analogue input of the
(ana. input)
device.
Parameters
Value / Parameter Description
ID Sub-ID
Temperature Ext. 2 in [°C] meas-
Temperature external 2
553 7 ured via an analogue input of the
(ana. input)
device.
Temperature of transformer envi-
Temperature of transform-
553 8 ronment in [°C], measured via a
er environment (PT100)
PT100 input on the device
Temperature of enclosure envi-
Temperature of enclosure
553 9 ronment in [°C], measured via a
environment (PT100)
PT100 input on the device
Temperature of the interior of the
Temperature of station
553 10 station in [°C], measured via a
interior (PT 100)
PT100 input on the device
Outside temperature in [°C],
Outside temperature
553 11 measured via a PT100 input on
(PT100)
the device
Temperature inside Main Com-
Temperature of Main
553 12 biner Box 1 in [°C], measured via
Combiner Box 1 (PT100)
a PT100 input on the device
Temperature inside Main Com-
Temperature of Main
553 13 biner Box 2 in [°C] , measured via
Combiner Box 2 (PT100)
a PT100 input on the device
Temperature inside Main Com-
Temperature of Main
553 14 biner box 3 [°C] in, measured via
Combiner Box 3 (PT100)
a PT100 input on the device
Temperature inside Main Com-
Temperature of Main
553 15 biner Box 4 in [°C], measured via
Combiner Box 4 (PT100)
a PT100 input on the device
Temperature measurement value
Temperature PTx1 552 0 of 1st PT100 input of the device
in [°C]
Temperature measurement value
Temperature PTx2 552 1 of 2nd PT100 input of the device
in [°C]
Temperature measurement value
Temperature PTx3 552 2 of 3rd PT100 input of the device
in [°C]
Temperature powerstage Temperature of power stage heat
550 0
heatsink sink in [°C]
Temperature of link ca- Temperature of the DC capacitor
550 1
pacitor (PT100) of the power stage in [°C]
Temperature powerstage Temperature of device interior in
551 0
interior [°C]
20 21 22 23 24 25 26
Fig. 4.72: Tab option “Threshold function” in the menu option “Dig. Outputs”
20. Display of the assignment numbers for the respective freely configurable
threshold functions in display text boxes.
NOTE
Threshold functions may already be used as standard internally, dependent on
the PVMaster device type. Reserved threshold functions cannot be changed.
The releases for the respective freely available threshold functions are dis-
played in the activation fields next to the assignment numbers.
21. The ID and Sub-ID of the respective parameters to be monitored are dis-
played here in configuration text boxes.
If the element “User-defined” is selected in the selection box (22), then the
configuration text boxes are released for input and the (display) parameters
to be monitored can be selected manually by inputting the ID and Sub-ID in
the configuration text boxes.
22. The selection box is used to display and edit, where necessary, the respec-
tive (display) parameters to be monitored. The (predefined) parameters
available in the selection box are listed in Tab. 4.22, p. 185. Alternatively,
the element “User-defined” can be selected and the (display) parameters to
be monitored can be selected manually in the configuration text boxes (21).
23. The actual values of the monitored (display) parameters are shown here in
display text boxes.
24. These configuration text boxes are used to display and edit, where neces-
sary, the switch-on thresholds of the respective threshold functions. If the
monitored value of a set switch-on threshold is exceeded, then the state of
that threshold function becomes active.
25. These configuration text boxes are used to display and edit, where neces-
sary, the switch-off thresholds of the respective threshold functions. If the
monitored value drops below the set switch-off threshold, then the state of
that threshold function becomes inactive again.
26. These status fields display the actual states of the respective threshold
functions. The corresponding state is activated as soon the monitored value
exceeds the corresponding switch-on threshold value (24). The state be-
comes inactive only once the monitored value drops below the correspond-
ing switch-off threshold (25).
Parameters
Value / Parameter Sub- Description
ID
ID
Maximum possible device
current in [A] taking into ac-
count whether temperature-de-
Max. grid current [A] 542 0
pendent current limitation and
apparent Limit are active (see
section 4.3.2.4.3, p. 65).
Total active power of the device
Active power load [%] 543 0 in relation to the maximum pos-
sible active power in [%]
Maximum possible active
power in [%] taking into account
whether any functional active
Limit functions are active and
whether the grid voltage is low,
Max. active power [%] 546 0 with the resulting reduction of
the maximum possible active
power of the PVMaster device
based on the device rated cur-
rent. (See section 4.3.2.4.3,
p. 65).
GFDI error current [mA] 568 0 Ground fault current in [mA]
RCM error current [mA] 570 0 Fault current in [mA]
Decimal values for signal states
of digital inputs used for set-
Power reduction digital sig- point specification of the active
575 0
nals Limit as part of infeed/grid
security management (NSM)
(section 4.3.4.2.5, p. 141).
Analogue value in [%] for ana-
logue input used for setpoint
Power reduction analog specification of the active Limit
576 0
signal as part of infeed/grid security
management (NSM) (sec-
tion 4.3.4.2.5, p. 141).
Maximum percentage value for
active power of device as part
Power reduction Pac-limit [%] 545 2 of power supply security and
infeed management (see sec-
tion 4.3.4.2.5, p. 141).
Percentage active Limit of
Frequency stabilisation Pac- device as part of static fre-
545 3
limit [%] quency stabilisation (see sec-
tion 4.3.4.3.2, p. 156)
Decimal values for signal
states for digital inputs used
for setpoint specification of the
Q control digital signals 580 0
reactive power control as part of
static grid voltage stabilisation
(section 4.3.4.3.1, p. 147).
Parameters
Value / Parameter Sub- Description
ID
ID
Analogue value in [%] for ana-
logue input used for setpoint
specification of the reactive
Q control analogue signal [%] 581 0
power control as part of static
grid voltage stabilisation (sec-
tion 4.3.4.3.1, p. 147).
Setpoint specification for reac-
tive power control as part of
Q control reference value 582 0
static grid voltage stabilisation
(section 4.3.4.3.1, p. 147).
Temperature of the filter chokes
Temperature choke (PT100) 553 0 in [°C], measured via a PT100
input on the device
Temperature of the transformer
Temperature transformer
553 1 in [°C], measured via a PT100
(PT100)
input of the device
Temperature inside the enclo-
Temperature cabinet (PT100) 553 2 sure in [°C], measured via a
PT100 input of the device
Temperature Ext. in [°C], meas-
Temperature External
553 3 ured via a PT100 input of the
(PT100)
device
Module temperature 1 in [°C]
Temperature pv-module 1
553 4 measured via an analogue input
(ana. input)
of the device.
Module temperature 2 in [°C]
Temperature pv-module 2
553 5 measured via an analogue input
(ana. input)
of the device.
Temperature Ext. 1 in [°C]
Temperature external 1 (ana.
553 6 measured via an analogue input
input)
of the device.
Temperature Ext. 2 in [°C]
Temperature external 2 (ana.
553 7 measured via an analogue input
input)
of the device.
Temperature of transformer en-
Temperature of transformer
553 8 vironment in [°C], measured via
environment (PT100)
a PT100 input on the device
Temperature of enclosure envi-
Temperature of enclosure
553 9 ronment in [°C], measured via a
environment (PT100)
PT100 input on the device
Temperature of the interior of
Temperature of station inte-
553 10 the station in [°C], measured via
rior (PT 100)
a PT100 input on the device
Outside temperature in [°C],
Outside temperature (PT100) 553 11 measured via a PT100 input on
the device
Temperature inside Main Com-
Temperature of Main Com-
553 12 biner Box 1 in [°C], measured
biner Box 1 (PT100)
via a PT100 input on the device
Temperature inside Main Com-
Temperature of Main Com-
553 13 biner Box 2 in [°C] , measured
biner Box 2 (PT100)
via a PT100 input on the device
Parameters
Value / Parameter Sub- Description
ID
ID
Temperature inside Main Com-
Temperature of Main Com-
553 14 biner box 3 [°C] in, measured
biner Box 3 (PT100)
via a PT100 input on the device
Temperature inside Main Com-
Temperature of Main Com-
553 15 biner Box 4 in [°C], measured
biner Box 4 (PT100)
via a PT100 input on the device
Temperature measurement
Temperature PTx1 552 0 value of 1st PT100 input of the
device in [°C]
Temperature measurement
Temperature PTx2 552 1 value of 2nd PT100 input of the
device in [°C]
Temperature measurement
Temperature PTx3 552 2 value of 3rd PT100 input of the
device in [°C]
Temperature powerstage Temperature of power stage
550 0
heatsink heat sink in [°C]
Temperature of link capacitor Temperature of the DC capaci-
550 1
(PT100) tor of the power stage in [°C]
Temperature powerstage Temperature of device interior
551 0
interior in [°C]
1 2 3 4 6
Fig. 4.73: U
ser interface of the “Ana. Inputs” option in the menu sub-group “In-/
Outputs” of the menu group “Configuration”
as of Fitter The first tab option “Ana. Inputs” (Fig. 4.73) is used to display and edit the con-
figuration of the respective analogue inputs, and to display the actual measured
values.
1. Display of the assignment numbers for the respective analogue inputs of the
PVMaster device in display text boxes.
NOTE
The number of available analogue inputs varies according to the PVMaster
device type.
2. These display text boxes are used to display the actual raw measured val-
ues of the respective analogue inputs with the physical unit selected accord-
ing to the signal type set in the selection box (3).
3. This selection box is used to select the signal type of the signal being meas-
ured by the respective analogue inputs. The respective analogue inputs
in the PVMaster can measure either voltage (+/-10V or 0..10V) or current
signals (0..20mA or 4..20mA). If “4..20mA” is set in the respective selection
box, wire breakage detection is also implemented.
REFERENCE
The applicable instructions in the relevant PVMaster installation manual must
be complied with, dependent on the signal type to be evaluated via the ana-
logue inputs of the PVMaster device.
4. Low-pass filters (Pt1 behaviour) can be activated to filter the analogue
signals for evaluation of the individual analogue inputs. Activation is imple-
mented by specifying the filter time constant in [ms] in these configuration
text boxes. If 0ms is set, the respective analogue signal is evaluated without
filtering.
5. The respective assigned functions of the analogue inputs are displayed and
configured in these selection boxes. The possible functions of analogue
inputs are listed and described in Tab. 4.23, p. 190.
NOTE
The available functions for the analogue inputs vary according to the PVMas-
ter device type.
The configuration text boxes are used to scale the analogue values by spec-
ifying an offset value at 0% of the analogue signal and by specifying the end
value at 100% of the analogue signal.
6. These display text boxes show the respective analogue function value with
the unit of the function selected in the selection box (5). The display takes
into account the applicable filter time set and the scaling of the analogue
signal.
7 8 9 10
Fig. 4.74: T
ab option “Temperature inputs (PT100)” in the menu option “Ana.
Inputs”
7. Display of the assignment numbers for the respective temperature inputs of
the PVMaster device in display text boxes.
8. Low-pass filters (Pt1 behaviour) can be activated to filter the temperature
measurement values for evaluation of the individual temperature inputs. Ac-
tivation is implemented by specifying the filter time constant in [ms] in these
configuration text boxes. If 0ms is set, the respective temperature measure-
ment value is evaluated without filtering.
9. The respective assigned functions of the temperature inputs are displayed
and configured in these selection boxes. The possible functions of the tem-
perature inputs are listed and described in Tab. 4.24, p. 194.
NOTE
The available functions for the temperature inputs vary according to the PV-
Master device type.
10. These display text boxes shown the respective temperature measurement
values in [°C]. The display takes into account the applicable set filter time.
Function Description
The so-called "Single MPPT mode" is a special
function in the InterCOM device intercommuni-
cation and enables parallel operation of several
PVMaster devices (AC and DC side, without
Special operation modes galvanic isolation). In this infeed operation mode,
the number of connected PVMaster devices var-
ies according to the currently available generator
power in order to optimise the total efficiency of the
local device network.
The coordination of delayed connection of several
PVMaster devices within the local InterCOM device
network is implemented via the InterCOM device
Other points
intercommunication. This connection delay pre-
vents unnecessarily high negative feedback in the
supply network due to switching operations.
1) See warning
ATTENTION
When using several PVMaster devices for the low-voltage windings of a com-
mon transformer with structurally-related unfavourable properties, synchroni-
sation may be essential.
as of Fitter The user interface of the menu option “InterCOM” within the menu group “Con-
figuration” is used for the activation and configuration of the InterCOM device
intercommunication.
The upper section of the user interface (Fig. 4.75) is used to display and edit the
operation mode of the intercommunication (1), the communication configuration
(node ID (2), Master/Slave mode (3) and baud rate (4)).
1 2 3
5 6 7 8
Fig. 4.75: U
ser interface of the menu option “InterCOM” in the menu group
“Configuration”
as of Fitter 1. The operation mode of the InterCOM device intercommunication is set via
the displayed option field. After the operation mode has been changed, the
new setting must be saved (section 4.2.7, p. 26) and a device restart
(section 4.2.8, p. 26) implemented.
NOTE
The "InterCOM + synchronisation" mode must always be selected when using
several PVMaster devices for the low-voltage windings of a common trans-
former.
as of Fitter 3. This selection box (Tab. 4.27, p. 202) is used to configure or assign the
master functions for active synchronisation or for active special infeed op-
eration mode “Single MPPT mode” in the InterCOM device intercommunica-
tion. Assignment can be either static or dynamic.
NOTE
The configuration of the master function within a local InterCOM device net-
work must be either static or dynamic. A mixture of static and dynamic assign-
ment of master functions within a local InterCOM device network is not permit-
ted.
NOTE
When using the standard infeed operation, the use of static master-slave as-
signment for InterCOM nodes is recommended within a local InterCOM device
network.
NOTE
In the special infeed operation mode "Single MPPT mode", all InterCOM nodes
should be configured with the dynamic master assignment to ensure an opti-
mal "rolling" operation of the master function and the connection/disconnection
sequence.
Option Description
Selecting the dynamic assignment of the master function
enables rolling operation of the master function within a
local InterCOM device network. The assignment of the
master function occurs here dependent on a configura-
ble condition.
This configuration should be used particularly in the spe-
2 Master dynamic cial infeed operation mode "Single MPPT mode". When
using this infeed operation mode, the assignment of
the master function is dependent on the operating state
and the energy values achieved so far by the respective
InterCOM node. The current InterCOM master switches
into the active infeed operation as the first InterCOM
node in this operation mode.
4. The InterCOM device intercommunication baud rate is selected in this se-
lection box. The values set for the baud rate must be identically configured
for each InterCOM node in a local InterCOM device network.
NOTE
By default, the preset value for the baud rate is 500 k. Changing this value
is normally not necessary or useful. A reduction in the baud rate may only be
necessary in some exceptional cases (e.g. longer line lengths of the InterCOM
wiring).
Three tab options (5), (6), (7) and (8) are available in the lower section of the
user interface.
3 1
5
6
Fig. 4.76: T
ab “InterCOM device list” in the menu option “InterCOM” of the
menu group “Configuration”
1. The communication states of the individual InterCOM nodes in the local
InterCOM device network are displayed in these status fields. The active
communication state of all InterCOM nodes is a condition for the correct
implementation of InterCOM device list (4) identification (3).
REFERENCE
The InterCOM device intercommunication wiring (see information in PVMaster
installation manual) and the InterCOM communication settings in the upper
section of the user interface must be correctly implemented for each InterCOM
node so that InterCOM communication is functional and the status fields dis-
play the corresponding state.
3. If the active communication state of all InterCOM nodes in the local In-
terCOM device network is displayed in (1), then pressing the “InterCOM
identification” button implements the identification of all InterCOM nodes
in the local InterCOM device network. Following identification, all identified
InterCOM nodes are displayed in the device list (4).
as of Fitter 4. The InterCOM device list is displayed here. All InterCOM nodes that were
identified during the last InterCOM device identification using this button (3)
are displayed. All InterCOM nodes displayed in the list are accompanied by
data regarding the corresponding InterCOM communication address (node
ID) and the rated power of the InterCOM node. In addition, the InterCOM
master assignment is also shown in the list.
REFERENCE
If some InterCOM nodes in the local InterCOM device network are not correct-
ly identified by the InterCOM identification, the wiring of the InterCOM device
intercommunication and the line terminations with the appropriate terminat-
ing resistors (see information in the PVMaster installation manual) should be
checked, as should the InterCOM communication setting configurations of all
InterCOM nodes.
5. Once the device list is successfully identified, the identified data of the Inter-
COM nodes must be saved in the settings of all InterCOM nodes. To do this,
press the “Save” button in the “InterCOM device list” tab. Once this button is
pressed, the determined InterCOM node data are transferred in a broadcast
via the InterCOM device intercommunication to all InterCOM nodes and
saved there permanently.
NOTE
The software release switch (section 4.2.5, p. 24) must be deactivated in
every InterCOM node so that the identified InterCOM device list can be cor-
rectly saved in the other InterCOM nodes.
NOTE
The device list must also be updated using the InterCOM identification when
an InterCOM node is removed from the local InterCOM device network or
permanently switched off. Otherwise, if an InterCOM node is not registered in
the InterCOM device list using the InterCOM device intercommunication within
the timeout period, all InterCOM nodes will go into the fault state (ID 02/04,
Tab. 4.31, p. 224, see section 4.3.5.1, p. 221) after a timeout of one hour
has elapsed.
Fig. 4.77: T
ab “InterCOM functions” in the menu option “InterCOM” of the menu
group “Configuration”
Function Description
If setpoints are specified for the static voltage stabili-
sation (reactive power control, see section 4.3.4.3.1,
p. 147) via digital inputs of the local InterCOM
node, these broadcast communication objects can
be activated to inform the other InterCOM nodes in
the local InterCOM device network about the signal
Reactive
states of the digital inputs used. By appropriately
22 power ana-
configuring the static voltage stabilisation (sec-
logue signal
tion 4.3.4.3.1, p. 147) these InterCOM nodes can
then also implement setpoints accordingly in order to
participate in the static voltage stabilisation. The ana-
logue value is then also displayed in the menu option
"InterCOM" of the menu group "Status and Values"
(section 4.3.2.2, p. 48).
2 3 4 5
Fig. 4.78: T
ab “InterCOM synchronisation” in the menu option “InterCOM” of the
menu group “Configuration”
as of Expert 1. The upper section of the tab option “InterCOM synchronisation” is used to
display the actual device settings in configuration text boxes for the control
and monitoring of the InterCOM nodes and to display the actual synchroni-
sation control error in [µs] in a display text box.
NOTE
It is only possible to change the settings for synchronisation control and moni-
toring at the highest user level "Administrator" as this requires an appropriately
high level of expertise.
PVMaster EM only 2. The lower section of the tab option “InterCOM synchronisation” is used to
display and edit the infeed operation mode in a selection box. The infeed
operation mode “Standard” and the special infeed operation mode “Single
MPPT” can be selected here.
REFERENCE
Detailed descriptions of the respective operation modes, information about
connection, wiring and the required safety procedures (particularly for the
Single MPPT mode) can be found in the corresponding PVMaster installation
manual.
NOTE
The selected infeed operation mode must be identical for all InterCOM nodes
in the entire local InterCOM device network. Mixed operation in an InterCOM
device network is not permitted. If the infeed operation mode configurations of
the individual InterCOM nodes are different within an InterCOM device net-
work, then all InterCOM nodes in the local InterCOM device network will go
into the fault state (ID 02/05, Tab. 4.31, p. 224, see section 4.3.5.1, p. 221).
as of Expert a) The “Standard” infeed operation mode is used when each PVMaster on
PVMaster EM only the DC side is connected to a separate photovoltaic (sub) generator and
the respective PVMaster devices are galvanically isolated from each
other on the AC side in that they are connected to their own and inde-
pendent low-voltage windings of a transformer. In this operation mode,
the switch on/off of the individual PVMaster devices is implemented
fully independently of the other InterCOM nodes, only dependent on the
available DC power of the respectively connected photovoltaic (sub)
generators. Each InterCOM node in the local InterCOM device network
thereby implements its own MPP tracking so that the maximum possible
PV power can be taken from each individual photovoltaic (sub) genera-
tor.
b) The special “Single MPPT” infeed operation mode is used when all
PVMaster devices within a local InterCOM device network are operated
in parallel on the DC and AC side. Galvanic isolation on the AC side be-
tween the PVMaster devices is not necessary, so they can be operated
in parallel on a low-voltage winding of a transformer. All InterCOM nodes
in the local InterCOM device network are connected on the DC side
with a common “large” PV generator. During operation, only the actually
required number of InterCOM nodes are switched on to feed in the PV
power that is available. This special infeed operation mode therefore
enables efficiency-optimised operation of the complete InterCOM device
network. However, only the InterCOM node with the master function im-
plements the MPP tracking within the entire InterCOM device network.
NOTE
If the "Standard" infeed operation mode was activated in the selection box (2),
then the three configuration text boxes (3), (4) and (5) in the tab option "Inter-
COM synchronisation" are hidden.
3. If the special “Single MPPT” infeed operation mode was selected in the
selection box (2), then this configuration text box can be used to set the
upper power threshold in per cent as of which the switch-on of an additional
InterCOM node within the InterCOM device network is requested by the
InterCOM master.
4. If the “Single MPPT” infeed operation mode is activated, then this configura-
tion text box can be used to set the lower power threshold in per cent as of
which the disconnection of an additional InterCOM node within the Inter-
COM device network is requested by the InterCOM master.
5. If the “Single MPPT” infeed operation mode is activated, then this con-
figuration text box determines the maximum power value in per cent of all
InterCOM nodes in the local InterCOM device network in the event that
all InterCOM nodes are not connected and in active infeed operation. The
maximum power is only enabled when all InterCOM nodes in the local
InterCOM device network are in active infeed operation. This power limita-
tion in per cent during partial operation prevents the possibility of the fuses
in the cross-connections of the individual photovoltaic (sub) generators from
triggering.
NOTE
The configuration of the switch on/off thresholds (3) and (4), and the power
limitation for partial operation (5) must be set so that the fuses used in the
cross-connections of the individual photovoltaic (sub) generators are not trig-
gered.
as of Fitter The menu option “String currents” in the menu group “Configuration” is available
as of user level “Fitter” and is used to activate and configure the evaluation of
connected SCBs via the corresponding CAN interface of the PVMaster.
The upper section of the corresponding user interface (see Fig. 4.79) is used
to display and edit the SCB to be evaluated via the elements (1) to (3). The
remaining area of the user interface is used to display and edit the respective
configurations, and to display the actual state of the SCBs selected in the selec-
tion box (4) via the elements (5) to (13).
3
2 1
4
7 11
10
8 9
12 13
Fig. 4.79: U
ser interface of the menu option “String currents” in the menu group
“Configuration”
as of Fitter 1. The SCBs to be evaluated are activated here via the activation fields. In to-
tal, up to 10 SCBs can be evaluated by a PVMaster. The assignment of the
activation fields “SCB 01” to “SCB 10” corresponds to the set CAN node ad-
dress of the respective String Combiner Box, i.e. the evaluation of the String
Combiner Box with the set CAN node address is activated via the activation
field “SCB 03”.
REFERENCE
The CAN addressing of all connected SCBs must be unique, i.e. each CAN
address may only be assigned once. Further information can be found in the
corresponding PVMaster installation manual or in the SCB operating instruc-
tions.
NOTE
Only the activation fields for the CAN node addresses of the relevant SCBs
that are connected or present should be activated.
NOTE
If there are no SCBs present or connected to the corresponding CAN interface
of the PVMaster, then all activation fields must be deactivated to avoid unnec-
essary fault messages (e.g. ID 25/01 in Tab. 4.31, p. 224, see section 4.3.5.1,
p. 221).
The number of SCBs are displayed in the display text box (3) according to
the actual activation of the SCBs to be evaluated and the correspondingly
activated SCBs are available as elements for selection in the selection box
(4).
All activation fields and therefore the SCBs to be evaluated can be activat-
ed/deactivated simultaneously via the button (2).
2. The activations fields (1) can be simultaneously activated/deactivated via
this button. If all 10 possible SCBs are simultaneously activated with this
button, all 15 string current channels of the SCBs are also activated.
3. Number of SCBs connected to the PVMaster or activated via the activation
fields (1) in a display text box. According to the number of available SCBs
displayed here, the corresponding entries for selection of the SCBs are
available in the selection box (4).
4. Selection box used to select the SCBs to display the corresponding states
and measured values in the user interface, and to display and edit the SCB
configuration settings. Only those SCBs that have been activated via the
activation fields (1) can be selected within this selection box.
5. The activation fields in this area are used to activate the individual string
current channels of the SCBs selected via the selection box (4). Each dis-
play text box shows the actual string current measured value of the respec-
tive string current channel in [mA].
6. This button is used to simultaneously activate/deactivate all activations
fields (5) used to activate the respective string current channels for the
SCBs selected via the selection box (4).
7. The SCBs each have an analogue input for optional evaluation of the ana-
logue signal from an irradiation or wind speed measurement.
REFERENCE
A detailed description of the analogue input of the String Combiner Box with
string current measurement and detailed information about connection can be
found in the SCB operating instructions.
This selection box is used to assign the appropriate function (“Not used”, “Ir-
radiation [W/m²]” or “Wind speed [m/s]”) for the analogue input of the SCBs
selected via the selection box (4).
8. The configuration text boxes are used to scale the analogue value by speci-
fying an offset value at 0 % of the analogue signal and by specifying the end
value at 100 % of the analogue signal.
9. The actual measured value of the analogue input for the SCBs selected via
the selection box (4) is shown in this display text box. The displayed unit is
dependent on the function assignment of the analogue input via the selec-
tion box (7).
10. The SCBs each have a temperature input for optional evaluation of a PT100
temperature sensor.
REFERENCE
A detailed description of the temperature input of the String Combiner Box with
string current measurement and detailed information about connection can be
found in the SCB operating instructions.
12. If there is a malfunction in the communication with the SCB selected via the
selection box (4), the communication error is indicated via this status field. A
detailed state message is shown in the display text box (13).
13. The node state of the SCBs selected via the selection box (4) is shown in
this display text box in clear text. The possible states are listed and de-
scribed in Tab. 4.29, p. 213.
Tab. 4.29: States of the CAN communication with the String Combiner Box
State /
No. Description
plain text message
The communication with the selected SCB
0 CAN node deactivated
was deactivated via the configuration.
CAN node active (opera- The communication with the selected SCB is
1
tional) functional and active.
The device is attempting to set up communi-
cation with the selected SCB and is search-
2 Searching CAN node...
ing for the applicable CAN node with the
corresponding CAN ID (SCB no.).
Communication with the selected SCB
cannot take place as no CAN node with the
3 CAN node not found 1) 2)
corresponding CAN ID (SCB no.) could be
found.
An impermissible device type was identified
when the CAN node information of the CAN
Wrong device type (Devi- node with the CAN node address corre-
4
ceTypeObject 1000h) sponding to the selected SCB (SCB no.) was
read out. Only LTI ReEnergy GmbH String
Combiner Boxes can be connected.
During the start of communication with the
SDO data mismatch at selected SCB, an unexpected response tel-
5
startup egram from the CAN node to a service data
object (SDO) was received.
The CAN node with the node address cor-
responding to the selected SCB (SCB no.)
6 SDO upload failed is not replying to queries via service data
object (SDO) communication. A new start of
the CAN node is requested.
The initialisation of communication with the
CAN node in pre-opera-
7 selected SCB is complete and cyclical com-
tional
munication of the process data will now start.
Timeout error of cyclical monitoring of com-
8 Timeout heartbeat
munication with the selected SCB.
Read IdentityObject
20 Reading device description (Vendor ID)
1018h (Vendor ID)
Read IdentityObject
21 Reading device description (ProductCode)
1018h (ProductCode)
1) Where necessary, check the connection or wiring between the PVMaster device and the
String Combiner Box, as well as the correct termination of the CAN wires with the appropriate
terminating resistors. Detailed information can be found in the corresponding PVMaster
installation manual or in the SCB operating instructions.
2) Where necessary, check the communication settings of the String Combiner Box concerned,
especially the baud rate set there. A baud rate of 50 k should be set. Also check the set CAN
addressing of the SCB in this regard. Detailed information can be found in the corresponding
PVMaster installation manual or in the SCB operating instructions.
State /
No. Description
plain text message
Read IdentityObject
22 Reading device description (Revision)
1018h (RevisionNumber)
Read IdentityObject
23 Reading device description (SerialNumber)
1018h (SerialNumber)
The start process of the CAN node with the
Startup in progress address corresponding to the selected SCB
100
(SDO upload)... (SCB no.) is active and service data are be-
ing uploaded.
1) Where necessary, check the connection or wiring between the PVMaster device and the
String Combiner Box, as well as the correct termination of the CAN wires with the appropriate
terminating resistors. Detailed information can be found in the corresponding PVMaster
installation manual or in the SCB operating instructions.
2) Where necessary, check the communication settings of the String Combiner Box concerned,
especially the baud rate set there. A baud rate of 50 k should be set. Also check the set CAN
addressing of the SCB in this regard. Detailed information can be found in the corresponding
PVMaster installation manual or in the SCB operating instructions.
as of Fitter The menu option “Data transmission” in the menu group “Configuration” is avail-
able as of the user level “Fitter” and the corresponding user interface (Fig. 4.80)
is used to activate, configure and display the state of the integrated DNS and
FTP clients of the PVMaster, as well as to select the file types to be created for
transmission.
1 6
4
2 7
5 8
3
9
10
11
Fig. 4.80: U
ser interface of the menu option “Data transmission” in the menu
group “Configuration”
1. This activation field is used to activate the functions for the automatic csv
file generation and the cyclical or event-oriented file transmission via the
integrated FTP client.
NOTE
The functions for automatic csv file generation and cyclical or event-oriented
file transmission are deactivated by default in the delivery condition or default
setting of the PVMaster. File generation and file transmission only occur after
the function has been activated via this activation field. Subsequent generation
and transmission of files with previously recorded measured values, events
and faults is not possible!
2. This status field is used to display the actual states of the integrated DNS
and FTP clients. The possible states are listed and described in Tab. 4.30,
p. 217. The states of the integrated DNS and FTP clients are also dis-
played in the relevant symbol of the Start user interface “Overview” (sec-
tion 4.3.1, p. 39)
3. The states of the DNS and FTP clients are displayed as plain text messages
in this display text box.
4. These display text boxes are used to display the number of upload orders
still open, the successfully sent files and failed upload attempts.
NOTE
The PVMaster bridges any temporary disturbed internet connection by inter-
mediate storage of the files to be transferred. The automatically generated files
are subsequently transferred as soon as the internet connection of the PVMas-
ter is restored. However, intermediate storage of the files is only possible up to
a certain number, so there may be corresponding gaps in the data transmis-
sion if the disturbance in the PVMaster internet connection lasts for any length
of time.
5. This button can be used to reset any remaining orders for file transfer and
to delete the applicable files in intermediate storage. The value displayed for
the remaining upload orders in (4) is reset in this case.
Changes as of Expert 6. This selection box is used to display and edit, where necessary, the cycle
time setting of the integrated data logger for the generation of csv data files
(with day history data). Based on the set cycle time, a floating average value
formation of all measured values takes place and this average value is en-
tered in the csv data files. Possible cycle times for average value formation
of the measured values and data entries are 1, 2, 5, 10, 15, 30 and 60 min-
utes. A cycle time of 15 minutes is preset for the data logger in the delivery
condition or default setting of the PVMaster.
Changes as of Expert 7. The cycle time of the file generation and corresponding file transfer of the
data files (day history data) via the integrated FTP client is displayed and
edited, where necessary, via this configuration text box in minutes.
The cycle time for file generation must be selected to be higher than the set
cycle time of the data logger using the selection box (6) and should also be
an integral multiple of the data logger cycle time. A cycle time of 60 minutes
is preset for automatic data file generation and file transfer in the delivery
condition or default setting of the PVMaster.
Changes as of Expert 8. The respective delay until a previously failed file transfer is repeated is
shown in seconds and can be edited, where necessary, in this configura-
tion text box. A delay time of 5 seconds is preset in the delivery condition or
default setting of the PVMaster.
9. The “Test upload” button can be used by the user for test purposes to
directly generate a data file and test the file transfer via the integrated FTP
client. After the data file has been generated, it is immediately transferred or
displayed as an additional upload order in the display text box (4). The activ-
ity of the “Test upload” is shown in the status field next to the button.
10. This section is used to display and edit, where necessary, the FTP destina-
tion server address and the authentication data (user and password) for the
automatic file transfer by the integrated FTP client.
NOTE
The FTP destination server and corresponding authentication data are set by
default to use the online portal system of the provider "meteocontrol GmbH" in
the delivery condition or default setting of the PVMaster.
The four configuration text boxes used to configure the FTP destination
server are released for inputs by the user as soon as the activation field
“Change FTP server settings” is activated.
11. These activation fields are used to select the type of files to be generated
for automatic file transfer via the integrated FTP client.
The first activation field “string file” is used to activate/deactivate the auto-
matic generation and file transfer of csv files with measured values from
connected String Combiner Boxes or the corresponding average values
(section 4.3.4.6, p. 210).
The second activation field “meta file” is used to activate/deactivate the
automatic generation and file transfer of csv files with “meteorological”
measured values or corresponding average values (irradiation values,
module temperatures, ambient temperatures, wind speed measured values
and wind direction measured values, section 4.3.2.3.1, p. 52 and sec-
tion 4.3.2.5, p. 77).
The third activation field “info file” is used to activate/deactivate the event-
controlled generation and file transfer of csv files with faults and events that
have occurred. In contrast to the other file types, file generation and transfer
are not implemented cyclically, but event-oriented.
The last activation field “data file” is used to activate/deactivate the auto-
matic generation and file transfer of csv files with standard measured values
(day history data) or corresponding average values (voltages, currents,
power, temperature, energy values, etc.).
REFERENCE
A detailed description about the individual file types and their contents can be
found in the corresponding description of the PVMaster export interface.
Any change to the signal states represents an “unusual event” and is recorded
by the integrated data logger. The retrieval, display and further processing of
the “unusual events” that have occurred can be easily implemented in the menu
option “Events” of the menu group “Diagnosis” (section 4.3.5.2, p. 229).
1
4
Fig. 4.81: U
ser interface of the menu option “Ext. power derating” in the menu
group “Configuration”
as of Fitter The menu option “Ext. power derating” in the menu group “Configuration” is
available as of user level “Fitter” and the corresponding user interface (Fig.
4.81) is used for configuration and status display of the functions for externally
controlled AC active Limit.
NOTE
The menu option "Ext. power derating" in the menu group "Configuration" is
only available when at least one digital input of the PVMaster has been as-
signed the appropriate function (functions 31, 32, and 33 in Tab. 4.19, p. 168,
see section 4.3.4.4.1, p. 166). The operator application (web application)
must then be restarted after the applicable function assignment of the digital
inputs.
1. These status files are used to display the signal states of the digital inputs
used for the function of externally controlled AC active Limit. A maximum of
three digital inputs can be used for control and setpoint specification of the
externally controlled AC active Limit. If fewer than three control functions are
used, then the corresponding status field for the unused control signals are
shown in grey.
2. These configuration text boxes are used to display and edit the respective
reduction factors in per cent for the three possible control signals. If fewer
than three control functions are used, then entries cannot be made in the
corresponding configuration text boxes for the unused control signals.
3. The actual AC active power limit in per cent related to the rated active power
of the PVMaster, based on the function of the externally controlled AC active
Limit, is displayed in this display text box. The displayed value is 100% if no
signal is active for the function of the externally controlled AC active Limit.
The display is also available in the user interface “Limit” of the menu sub-
group “Grid” in the menu group “Status and Values” (section 4.3.2.4.3,
p. 65).
4. The actual total active power fed into the grid is displayed here in [kW] in
a display text box. This value represents the total of the three phase active
powers of the PVMaster device (see also section 4.3.2.4.1, p. 61).
1 2
4
Fig. 4.82: U
ser interface of the menu option “Parameter editor” in the menu
group “Configuration”
1. This selection box is used to select the data type of the device parameter to
be read or edited. The appropriate data type must always first be selected in
this selection box before entering and confirming the Parameter ID and Sub-
ID in the configuration text boxes (2).
NOTE
If an suitable data type is selected in the selection box, the read parameter
value may not be correctly displayed in the display text box (3). Manual modi-
fication of the parameter value via the configuration text box (4) will also be
incorrect in this case.
2. These configuration text boxes are used to specify the ID and Sub-ID of the
device parameters to be read or edited. Following confirmation of the input
via these configuration text boxes, the corresponding parameter is read out
and the result displayed in the display text box (3). The appropriate data
type must always first be selected in this selection box (1) before entering
and confirming the ID and Sub-ID in the configuration text boxes (2).
3. The result of the last device parameter read access following confirmation
of the parameter ID and Sub-ID input via the configuration text boxes (2) is
displayed in this display text box as soon as the “Read value” button has
been pressed.
4.3.5 Diagnosis
This menu group contains menu options for performing device diagnoses. This
includes displaying and processing malfunction and event lists, acknowledging
current error states, setting delivery confirmations, displaying recorded status
changes and testing digital outputs.
4.3.5.1 Faults
The user interface for the first menu option “Faults” (Fig. 4.83) in the “Diagnosis”
menu group is used to display the entire malfunction history in a tabular view.
New (unread) fault messages can be confirmed (delivery confirmations) and
error states currently active can be acknowledged manually. The device set-
tings for automatic acknowledgement of malfunctions are displayed and can be
changed.
1 4
6 3
5 7 8 9
Fig. 4.83: U
ser interface for the “Faults” menu option in the “Diagnosis” menu
group
1. Symbol with display text box for displaying the current number of new (not
yet confirmed) fault messages. The value displayed here corresponds to the
number of fault messages in the table field (2) for which the activation field
in the “Confirmed” column is not active. Clicking on the button (3) marks
all the fault messages as “...confirm all” and the value displayed for uncon-
firmed fault messages is reset to zero.
This display is also available in the “Overview” start user interface (see ele-
ment (4) in Fig. 4.9, p. 39, section 4.3.1, p. 39)
2. The entire history of malfunctions that have occurred to date and any cur-
rently active malfunctions are displayed in this table field. The individual
fault messages are listed sorted according to the respective time stamps
of the fault messages, where the entry at the top represents the last active
malfunction or the malfunction currently active, as applicable.
The first two columns within the table field display the respective time stamp
of the fault message (date and time of occurrence of the malfunction). The
third and fourth columns are used to display the respective error number
(ID) and error location (“Location”/Loc) of the fault messages. The fifth
column shows the respective plain text description of the malfunction. The
final “Confirmed” column contains the display of activation fields. If entries
in the malfunction history are already known and if these have already been
confirmed as “delivered” with the button (3), the activation fields indicate this
accordingly.
The possible fault messages of the PVMaster are listed in Tab. 4.31,
p. 224 with specification of the respective error number, the respective er-
ror location and the corresponding plain text message.
NOTE
The last 100 fault messages are retained and displayed in the data memory
for retrieval. Older fault messages will be rejected by the PVMaster device and
can therefore not be retrieved via the operator application.
3. All fault message entries in the table field can be confirmed as “delivered”
with this button. When the button is pressed, all fault messages in the
“Confirmed” column are marked accordingly and the value displayed for the
number of unconfirmed fault messages (1) is reset to zero.
4. The fault messages shown in the table field (2) can be saved to the local
PC in a .csv file. This button opens a file browser on the local PC in order to
specify a destination location and file name for the .csv file.
5. If the device is currently in an error state, the error state can be acknowl-
edged manually with this button if the cause of the malfunction no longer
exists. Following the manual acknowledgement, the number of automatic
acknowledgement processes recently performed (6) is also automatically
reset.
6. The number of automatic acknowledgement processes recently performed
is displayed here in a display text box. When this counter value reaches the
value set in (8), there is no further automatic acknowledgement of the error
state. If operation proceeds uninterrupted with no malfunctions, the counter
value displayed here is reset on expiry of the time period set in (9).
Changes from Expert 7. Configuration text box for displaying and configuring (from “Expert” user lev-
el upwards) the delay time for automatic acknowledgement of error states
in [s]. The device is sent into an error state in the event of a malfunction. If
the cause of the malfunction no longer exists, the error state is automatically
acknowledged on expiry of this period and the device is reconnected.
8. Configuration text box for displaying and configuring (from “Expert” user
level upwards) the maximum number of automatic acknowledgement pro-
cesses. When the counter for automatically completed acknowledgement
processes (6) reaches the value set here, no further faults are acknowl-
edged automatically.
9. Configuration text box for displaying and configuring (from “Expert” user
level upwards) the time period for resetting the acknowledgement counter
(6). If no malfunctions that trigger an error state in the device occur within
the time period set here, the counter indicating the automatically completed
acknowledgement processes (6) is reset.
Error num-
Error
ber Error text/description
group
ID Loc
00 Unknown overcurrent error
01 Overcurrent (hardware) detected
02 Overcurrent (hardware) detected
03 Overcurrent (software) detected
04 Overcurrent (ADC value) detected
05 Overcurrent PS2 (hardware) detected
Overcurrent 05 Overcurrent PS2 (hardware) while pre enable
06
check detected
Maximum negative DC current exceeded (check
07
polarity of DC connection)
Overcurrent (hardware) detected by Uce monitor-
08
ing
Overcurrent PS2 (hardware) detected by Uce
09
monitoring
00 Unknown overtemperature error inverter
01 Overtemperature heatsink inverter detected
02 dT/dt overtemperature heatsink inverter detected
03 Overtemperature device detected
04 Overtemperature choke detected
05 Overtemperature transformer detected
06 Overtemperature cabinet detected
07 Overtemperature extern detected
08 Overtemperature detected (thermal element)
Overtemperature 2nd heatsink inverter / DC link
Overtem- 09
06 capacitor detected
perature
dT/dt overtemperature 2nd heatsink inverter / DC
10
link capacitor detected
11 Overtemperature transformer ambient detected
12 Overtemperature cabinet ambient detected
13 Overtemperature station interior detected
14 Overtemperature outdoor detected
15 Overtemperature main combiner box 1 detected
16 Overtemperature main combiner box 2 detected
17 Overtemperature main combiner box 3 detected
18 Overtemperature main combiner box 4 detected
Error num-
Error
ber Error text/description
group
ID Loc
00 Unknown error grid
01 Grid voltage out of range
02 Grid frequency out of range
03 Timeout while grid synchronisation
ADC values for grid current measurement out of
Grid error 09 04
range
GRID_MON: grid voltage below LVRT-limit (line
05
voltage ph2ph)
GRID_MON: grid voltage below LVRT-limit
06
(phase voltage)
00 Unknown error
01 External error by digital input
02 External error by isolation check
03 External overvoltage error
04 External fuse error
05 Motor protection switch error
06 Ground fault current to high(GFDI) or blown fuse
07 External error LVS overvoltage
External 08 External error LVS switch
10
error 09 External error LVS fuse
10 External error LVS overcurrent
11 External error MVS switch
12 External error Transformer
13 External error grid protection
14 External error QV relais
15 External grid error
IO interface: 24V supply droped or overload
16
(overtemperature)
00 Unknown error
01 Timeout AC contactor
PV error 11
02 Timeout contactor 2
03 Calibration state of DC current sensor not okay
00 Unknown error chopper resistance
Chopper 01 Error chopper resistance detected (hardware)
12
error 02 Error chopper resistance detected (hardware)
03 Overload chopper resistance
00 Unknown RTC error
01 Read or write error on SSI
RTC error 13
RTC time data invalid, RTC supply under limit
02
since last set of RTC
00 Unknown external ADC error
External
14
ADC error
01 Read or write error on SSI
Error num-
Error
ber Error text/description
group
ID Loc
00 GRID_MON: Unknown error
GRID_MON: Grid voltage too low (switch-on
01
condition)
GRID_MON: Grid voltage too high (switch-on
02
condition)
GRID_MON: Grid frequency too low (switch-on
03
condition)
GRID_MON: Grid frequency too high (switch-on
04
condition)
05 GRID_MON: Grid voltage too low (1)
06 GRID_MON: Grid voltage too low (2)
07 GRID_MON: Grid voltage too high (1)
08 GRID_MON: Grid voltage too high (2)
Grid moni- 09 GRID_MON: Grid voltage average too low
15
toring error 10 GRID_MON: Grid voltage average too high
11 GRID_MON: Grid frequency too low (1)
12 GRID_MON: Grid frequency too low (2)
13 GRID_MON: Grid frequency too high (1)
14 GRID_MON: Grid frequency too high (2)
15 GRID_MON: Illegal frequency step
16 GRID_MON: Illegal DC current injection
GRID_MON: Grid frequency exceeded random
17
limit (static freq. stabilization)
GRID_MON: Grid voltage exceeded imbalance
18
limit
GRID_MON: Phasing of grid voltages exceeded
19
limit
20 GRID_MON: Current in phase below activ limit
00 Unknown error control
Error in ICON mode => DC-link voltage below
01
minimum value!
Error in ICON mode => DC-link voltage exceeds
02
maximum value!
Error in VFCON mode => Danger! External grid
03
Control ON!
16
error Current rms values exceeded maximum imbal-
04
ance limit
DC voltage imbalance (filtered) out of limit (active
05
power stage)
06 DC voltage imbalance (filtered) out of limit
DC voltage imbalance control long time at limita-
07
tion
00 Unknown error Vdc observer
DC-link volt- Error in Vdc observer module => value for DC-
01
age observ- 17 link capacitance is not allowed!
er error Error in Vdc observer module => value for ob-
02
server method is out of range!
00 Unknown datalog error
Datalogger
18 01 Buffer overflow datalog
error
02 Buffer overflow temporary datalog
Error num-
Error
ber Error text/description
group
ID Loc
00 Unknown current monitor error
RCM error 19 01 Residual current monitor
02 Global residual current monitor
00 Unknown ENS-Controller error
Error in Software or Data Download to ENS-
01
ENS error 20 Controller
Error in Software or Data Download to ENS-
02
Controller
00 GRID_MON_ENS: Unknown error
GRID_MON_ENS: Grid voltage too low (switch-
01
on condition)
GRID_MON_ENS: Grid voltage too high (switch-
02
on condition)
GRID_MON_ENS: Grid frequency too low
03
(switch-on condition)
GRID_MON_ENS: Grid frequency too high
04
(switch-on condition)
05 GRID_MON_ENS: Grid voltage too low (1)
06 GRID_MON_ENS: Grid voltage too low (2)
07 GRID_MON_ENS: Grid voltage too high (1)
08 GRID_MON_ENS: Grid voltage too high (2)
Grid moni- 09 GRID_MON_ENS: Grid voltage average too low
toring ENS 21 10 GRID_MON_ENS: Grid voltage average too high
error 11 GRID_MON_ENS: Grid frequency too low (1)
12 GRID_MON_ENS: Grid frequency too low (2)
13 GRID_MON_ENS: Grid frequency too high (1)
14 GRID_MON_ENS: Grid frequency too high (2)
15 GRID_MON_ENS: Illegal frequency step
16 GRID_MON_ENS: Illegal DC current injection
GRID_MON_ENS: Unintended islanding opera-
17
tion
GRID_MON_ENS: Ground fault current to high
18
(GFDI) or blown fuse
19 GRID_MON_ENS: GFDI selftest error
20 GRID_MON_ENS: Error AC main contactor
21 GRID_MON_ENS: Error 2. main contactor
22 GRID_MON_ENS: RCM fault
00 Unknown ENS communication error
COM_ENS: Number of CRC errors on ENS RX
01
exceeded
COM_ENS: Number of communication watchdog
02
errors on ENS RX exceeded
ENS com- COM_ENS: Number of CRC errors on TC RX
03
munication 22 exceeded
error COM_ENS: Number of communication watchdog
04
errors on TC RX exceeded
COM_ENS: Error at switch to calibration com
05
mode
COM_ENS: ENS has been reset after normal
06
communication was initiated
Error num-
Error
ber Error text/description
group
ID Loc
00 Unknown insulation error
Insulation monitoring: Timeout switch on condi-
01
tion
02 Insulation monitoring: illegal insulation resistance
Insulation monitoring: insulation resistance too
Insulation 03
23 low
error
Insulation monitoring: electrical grounding resist-
04
ance too high
05 Insulation monitoring: device error
06 Insulation monitoring: interface error
07 Insulation monitoring: configuration error
00 Unknown CAN error
CAN error 24 01 CAN mapping error
02 CAN guarding error
00 Unknown SCB error
01 CAN Master BUSOFF error
SCB error 25
SCB: Node communication error (timeout SCB
02
heartbeat)
00 Unknown insulation error
Insulation monitoring: Timeout switch on condi-
01
tion
Insulation
02 Insulation monitoring: illegal insulation resistance
error 26
Insulation monitoring: insulation resistance too
(warning) 03
low
Insulation monitoring: electrical grounding resist-
04
ance too high
00 Unknown warning
Warning 27 01 Warning: malfunction of internal fans
02 InterCOM device is missed
4.3.5.2 Events
The third status word (Tab. 4.12, p. 47) contains the statuses of special
device functions (see section 4.3.2.1, p. 41). Changes to some of these sta-
tuses are described as “unusual events” (marking 1.) in Tab. 4.12, p. 47) and
recorded by the integrated data logger.
The user interface for the “Events” menu option (Fig. 4.84) in the “Diagnosis”
menu group is used to display and process the entire history of “unusual events”
in a tabular view. New (unread) event messages can be confirmed (delivery
confirmations).
NOTE
The last 100 event messages are retained in the data memory for retrieval.
Older event messages are automatically rejected by the device and can no
longer be retrieved via the operator application.
1 4
Fig. 4.84: U
ser interface for the “Events” menu option in the “Diagnosis” menu
group
1. Symbol with display text box for displaying the current number of new (not
yet confirmed) fault messages. The value displayed here corresponds to the
number of event messages in the table field (2) for which the activation field
in the “Confirmed” column is not active. Clicking on the button (3) marks all
the event messages as “...confirm all” and the value displayed for uncon-
firmed event messages is reset to zero.
This display is also available in the “Overview” start user interface (see ele-
ment (5) in Fig. 4.9, section 4.3.1, p. 39).
2. The entire history of “unusual events” that have occurred to date is dis-
played in this table field. The individual event messages are listed sorted
according to the respective time stamps of the event messages, where the
entry at the top represents the last event that occurred.
The first two columns within the table field display the respective time stamp
of the event message (date and time of occurrence of the event). The third
column shows the respective plain text description of the event. The final
“Confirmed” column contains the display of activation fields. If entries in the
event history are already known and if these have already been confirmed
as “delivered” with the button (3), the activation fields indicate this accord-
ingly.
Event message entries already known about or confirmed as “delivered” are
displayed in grey. New event message entries or entries not yet confirmed
as “delivered” are displayed in orange.
4.3.5.3 State
The meaning of the first and second status words (Tab. 4.10, p. 43 and Tab.
4.11, p. 46) was described in detail in section 4.3.2.1, p. 41. They contain
statuses and release conditions for the internal operating cycle controller. All
changes within status word 1 or status word 2 are recorded on the microSD
card by the internal data logger.
The user interface for the “State” menu option (Fig. 4.85) facilitates the retrieval,
display and further processing of all recorded status changes within these
status words for a definable time period, thus allowing detailed diagnoses of the
operating cycle.
NOTE
A maximum total of the last 1000 status changes to the first two status words
is retained in the data memory for retrieval. Entries with older status changes
are automatically rejected by the device and can no longer be retrieved via the
operator application.
1. The required time period for which the recorded status changes of the
PVMaster device are to be displayed is selected here. The “Start” and “End”
date for the required time period can be selected and configured either via
the respective calendar function or by means of manual entries within the
configuration text boxes.
2. The status changes shown in the tab options (4) for the time period selected
via (1) can be saved to the local PC in a .csv files. This button opens a file
browser on the local PC in order to specify a destination location and names
for the .csv files.
3. Once the user interface has been opened via the “State” menu option, there
is no further automatic updating of the displayed status changes once new
status changes have been recorded by the integrated data logger. This but-
ton can be used to update the displayed status changes.
1 2 3
Fig. 4.85: U
ser interface for the “State” menu option in the “Diagnosis” menu
group
4.3.5.4 Service
From Fitter The user interface for the “Service” menu option allows a manual functional test
of the digital outputs of the PVMaster device and the corresponding connected
elements. The digital outputs can be switched manually, enabling the functions
(fan, heat exchanger, liquid pump, etc.) to be tested accordingly.
NOTE
The "Service" menu option is only available from the "Fitter" user level. How-
ever, the manual functional test can only be performed when the software
release switch (section 4.2.5, p. 24) is deactivated.
1 2 3
Fig. 4.87: User interface for the “Service” menu option in the “Diagnosis” menu
group
1. Display of the designations for the respective digital outputs of the PV-
Master basic device in display text boxes. This is where not only the digital
outputs available for freely definable use by the user are listed, but also the
digital outputs that are used for internal functions within the device.
2. Display of designations and assignments of digital outputs of the PVMaster
device that are available for freely definable use by the user in display text
boxes. The designation or assignment of the outputs is analogous to the
designations on the corresponding terminal strip in the PVMaster enclosure
(see relevant installation manual for the PVMaster device. If “-” is indicated,
this means that the digital output is used for an internal function of the PV-
Master device.
5. If test operation has been activated with the button (4), the 10 buttons for
manual operation of the respective digital outputs are enabled and can be
operated. The respective switching states of the digital outputs are indicated
via the corresponding status fields within the respective buttons.
NOTE
The function of the DO09 digital output for actuating the AC main contactor
can only be tested manually if the AC main switch has been switched on and
the internal grid monitoring is released for connection. Furthermore, the DC
voltage must be of a minimum value.
Tab. 5.3: D
evice states in the 7-segment displays on completion of a software
update (firmware and/or bootloader)
No. 7-segment displays State
Initiation of the software update via the button was registered by the device. The
17 software update is now started. (Display only triggered following initiation of the
software update with the buttons of the basic device)
Software update has been initiated via the buttons of the basic device (display
1)
18 ←→ only triggered following initiation of the software update with the buttons of the
basic device)
19 Bootloader active
Read-only access to parameters (read-only protection is disabled with operating
20
tools or the communication controller)
Firmware update: F2…Deletion of a flash sector is active, F3… Deletion of a
21 ←→ flash sector is complete States F2 and F3 alternate several times, as several flash
sectors have to be deleted.
22 Firmware update: Firmware is transferred and written to the flash
23 Firmware update: Check of checksum (CRC)
24 Firmware update: Checksum correct (CRC)
Firmware update: Firmware information header (CRC, size, start address,
25
magic) is transferred
26 Firmware update: Start of firmware is initiated
27 Transferred package address outside of range (firmware sectors)
Bootloader update: b2…Deletion of a flash sector is active, b3… Deletion of
28 ←→ a flash sector is complete. States b2 and b3 alternate several times, as several
flash sectors have to be deleted.
29 Bootloader update: Firmware is transferred and written to the flash
30 Bootloader update: Check of checksum (CRC)
31 Bootloader update: Checksum correct (CRC)
Bootloader update: Firmware information header (CRC, size, start address,
32
magic) is transferred
Bootloader update: Deletion of a flash sector is active (from here the bootloader
33
only works internally)
34 Bootloader update: Programming of new bootloader
35 Bootloader update: Start of new bootloader
36 Transferred package address outside of range (bootloader sectors)
37 "Magic code" incorrect (firmware or bootloader)
38 Checksum for transferred data invalid (CRC)
39 Writing of a package to the flash memory failed
1)
40 ←→ Writing of data set from the microSD card to the device
1)
41 ←→ Writing of data set from the device to the microSD card
1)
42 ←→ Writing of power stage data set to the device
1)
43 ←→ Writing of customer-specific data set from the microSD card to the device
1) With a dot in the 7-segment display
NOTE
When the enclosure door is open, only states 0 to 8 from Tab. 5.2, p. 238
and the states shown in Tab. 5.3 are normally possible, as infeed operation is
automatically deactivated when the enclosure door is open.
Changing the IP address via the 7-segment displays and buttons is particularly
helpful for the first commissioning of PVMaster devices in a system prior to us-
ing the operator application for the first time, especially when using several PV-
Master devices in a shared network (e.g. when using a "network switch"). When
changing the IP address of the device via the 7-segment displays and buttons,
the sub-network settings are automatically modified.
NOTE
The IP address of the PVMaster device can also be easily displayed and
changed (in the standard decimal format) via the operator application. The
user interface for the corresponding menu option in the operator application of-
fers additional configuration options for the network settings, e.g. for managing
a network list containing all of the PVMaster devices available in the network.
Tab. 5.4: D
isplay of current IP address of the inverter via the 7-segment dis-
plays and buttons
Step Description
If necessary, wait 5 seconds until the 7-segment display shows the current operating state again,
1 e.g.:
1) 1) 1)
or or or or or
Press the left-hand button repeatedly until the 7-segment display shows the following:
2
Press the right-hand button once to confirm. The 7-segment display now shows each of the 4 num-
ber ranges of the IP address currently set for one second in hexadecimal format (01 = 01 … 255 =
3 FF), e.g. for "192.168.36.1":
→ → →
192 . 168 . 36 . 1
The current operating state of the device is then displayed again automatically, e.g.:
4 1) 1) 1)
or or or or or
1) With a dot in the 7-segment display
Tab. 5.5: C
hanging the IP address of the inverter via the 7-segment displays
and buttons
Step Description
If necessary, wait 5 seconds until the 7-segment display shows the current operating state again,
1 e.g.:
1) 1) 1)
or or or or or
Press the left-hand button repeatedly until the 7-segment display shows the following:
2
Press the right-hand button once to confirm. The 7-segment display now shows each of the 4 num-
ber ranges of the IP address currently set for one second in hexadecimal format (01 = 01 … 255 =
3 FF), e.g. for "192.168.36.1":
→ → →
192 . 168 . 36 . 1
The left-hand button must be pressed before the consecutive display of the 4 numbers for the cur-
rent IP address is complete (within approx. 5 seconds). The number range to be changed for the
4 IP address is selected by pressing the left-hand button repeatedly. (The IP address consists of 4
number ranges)
→ → → → → ...
Once the number range to be changed (01 to 04) has been selected, this must be confirmed with the
right-hand button. The current setting for the selected number range is now displayed in hexadeci-
5 mal format (01 = 01 … 255 = FF).
...
01 ... 255
The left-hand button can now be used for decrementing, while the right-hand button can be used to
increment the address setting.
6 → → → ...
Left-hand button:
Right-hand button: → → → ...
Once the required setting has been reached by decrementing or incrementing, the setting is adopted
after a waiting time of approximately 5 seconds. The current device state is now displayed again,
7 e.g.:
1) 1) 1)
or or or or or
8 Repeat steps 1 to 7 until the required changes to all four number ranges have been completed.
The new setting becomes effective as soon as the device has been reset (e.g. by temporarily dis-
9
connecting the control voltage).
1) With a dot in the 7-segment display
Tab. 5.6: D
isplaying and changing the InterCOM device address via the 7-seg-
ment displays and buttons
Step Description
If necessary, wait 5 seconds until the 7-segment display shows the current operating state again,
1 e.g.:
1) 1) 1)
or or or or or
Press the left-hand button repeatedly until the 7-segment display shows the following:
2
Press the right-hand button once to confirm. The 7-segment display now shows the current Inter-
COM device address (0..10 decimal or 0..0A hexadecimal) for 5 seconds. At the end of the 5 sec-
3 onds, the current device state is displayed again.
...
0 ... 10
The two buttons can be used during the 5-second long display of the device address (step 3) to
change the InterCOM device address. The left-hand button can be used for decrementing, while the
right-hand button can be used to increment the address setting.
4
Left-hand button: → → ...→
Tab. 5.7: Manual malfunction acknowledgement via the 7-segment displays and
buttons
Step Description
If necessary, wait 5 seconds until the 7-segment display shows the current operating state again,
1 e.g.:
1) 1) 1)
or or or or or
Press the left-hand button repeatedly until the 7-segment display shows the following:
2
Now press the right-hand button once to complete the manual acknowledgement. Any error state
that may be active is now acknowledged, but only if the cause of the malfunction is no longer pre-
3 sent. The current device state is then automatically displayed again:
1) 1) 1)
or or or or or
1) With a dot in the 7-segment display
NOTE
The microSD card must only be removed from or inserted into the card slot of
the basic device when the latter is switched off, as errors in the file system and
a loss of data from the microSD card may occur otherwise.
Prior to initiating the software update from the microSD card with the buttons
of the basic device, the microSD card must be prepared accordingly for the
software update. To this end, the entire content (all folders and files) of the com-
pressed .upa archive file (ZIP format) for the software update "PVM2 00cVx.
xx-xx ParaRevXX_UpdateComplete.upa" (no. 1 in Tab. 4.17, p. 109) is copied
to the microSD card. During the copying process, any existing folders and files
on the microSD card must be overwritten.
ATTENTION
Only folders and files on the microSD card may be overwritten with the folders
and files in the .upa archive file during the copying process. Under no cir-
cumstances may folders or files be deleted from the microSD card first or the
microSD card be formatted, as historical data (e.g. day history data or energy
diagrams) already logged will be lost.
Copy to
→
Once all of the requisite folders and files have been copied to the microSD card,
the microSD card is inserted into the card slot of the basic device again and the
control voltage is switched on again. The software update is then completed as
described in Tab. 5.8.
The right-hand button is now pressed once to initiate the software update from the microSD card.
3 The 7-segment displays now show the following:
The software update is started after a waiting time of 60 seconds. The 7-segment displays then
4 show the following status briefly:
1)
↔
During the software update, the states from Tab. 5.3, p. 239 are shown in the 7-segment displays,
5 e.g.:
→ ... → → → ...
The software update can take a few minutes. Once the software update is complete, the software is
6 started automatically and the current device state is then displayed again.
1) 1) 1)
or or or or or
1) With a dot in the 7-segment display
6 Index
Symbole
AC values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Administration of InterCOM device list. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Analogue inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85, 189
Application memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Authentication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Authorisation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Break operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Browser cache . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Buttons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
DC values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Destination device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Device address for InterCOM device intercommunication. . . . . . . . . 49, 200, 243
Device restart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Device states . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28, 238
Diagnosis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221, 230
Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55, 86, 93, 97, 100, 102
Digital inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82, 166
Digital outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84, 176
Display text box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16, 25
Dynamic grid stabilisation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Gateway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Generator scan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Grid. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Grid stabilisation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Icons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Infeed/grid security management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Infeed operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82, 166
Insulation monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52, 136
InterCOM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48, 198
InterCOM device address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49, 200, 243
InterCOM functions, optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
IP address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13, 241
Language settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Limitation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Limit values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Link buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Low voltage ride through . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
LVRT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Navigation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112, 241
Network settings (IP address) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112, 241
Quiescent state. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
RDT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Reactive power control for static grid voltage stabilization. . . . . . . . . . . . . . . . 147
Reduction of AC active power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65, 217
Remote data transmission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
User interfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
User levels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Web application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11