Professional Documents
Culture Documents
Cpu Cool Load r3
Cpu Cool Load r3
01
1. Storage Dimension
LENGTH (m) 3,4
WIDTH (m) 2,18
HEIGHT (m) 2,19
CAP TON 12,17
2. Volume 16,2 M3
Wall + Roof A 31,9 m2
Floor A 7,4 m2 39
U
3. Insulation Thickness 75,0 0,1 0 1/ho
100,0 0,2 0 1/hi
1 150,0 0,028 0,028 tebal insulasi
Thermal Insulation Conductivity k 0,028 W/m2.K
Koefisien Menyeluruh U 0,181936 W/m2.K
4. Temperature Design
o
4.1 Ambeint Temp 35,0 C
o
4.2 Floor Temp 20,0 C asumsi
4.3 RH 70,0 %
o
4.4 Store Design Temperature 0 C
o
4.5 Diference Temp with Ambeint 35,0 C
o
4.6 Diference Temp with Floor 20,0 C
5. Product
5.1 Total Kapasitas Penyimpanan (m1) m1 12.174,2 kg total vol penyimpanan di kurangi volume mesin, rak dll
5.2 Product Supply Each Day (m2) m2 8.116,1 kg assumsi pergantian product per day
o
5.3 Product temp before store 8,0 C
kJ/kg. oC
o
5.4 Cp= Spesifik heat capacity of product (kJ/kg. C) - Potatoes Cp 4,03
5.5 Product respiration heat 1,9 kj/kg
6. Internal Load
6.1 People 2,0 Person assumsi org bekerja
6.2 Total operasional per day 4,0 Hours asumsi total org bekerja per day
6.3 PeopleHeat: heat loss per person per hour (Watts) 300,0 Watts metabolisme heat gain rata2 manusia kerja medium
Lighting
6.4 Lamp= number of lamps within in the cold room 1,0 pcs selection/assumsi
6.5 Time Lamp = hours of use per day 5,0 hour assumsi total lampu ON
6.6 Wattage = power rating of the lamps 100,0 watt
Fans
6.7 Fans = the numbers of fans 2,0 Pcs selection unit
6.8 Fan Time = fan daily run hours 17,0 hours
6.9 Wattage = the rated power of the fan motors 100,0 watt
Heaters Defrost
6.10 power = power rating of the heating element (kW) 0,2 kW
6.11 time = defrost run time (Hours) 0,5 hour
6.12 cycles = how many times per day will the defrost cycle occur 3,0 Times
6.13 efficiency = what % of the heat will be transferred into the space. 0,3 %
7. INFILTRATION LOAD
7.1 changes = number of volume changes per day 10,0 pertukaran udara dan ventilasi
7.2 volume = the volume of the cold store 16,2 M3 volume cold storage
o
7.3 energy = energy per cubic meter per degree Celsius 2,0 kJ/ C
o
7.4 Temp out is the air temperature outside 35,0 C temp udara luar max rata2
o
7.5 Temp in is the air temperature inside 0 C temp dalam cold storage
LOAD CALCULATION
1. Transmission Load Thru Wall, Roof & Door
Heat Transmision Wall & Roof
=0,812 x 31,9 x 35 x24 /1000 4,87 kWh/Day
Heat Transmision Floor
=0,812 x 7,4 x 20 x24 /1000 0,65 kWh/Day
5 Infiltration Load
Q = changes x volume x energy x (Temp out – Temp in ) / 3600
= 10 x 16,2 x 2 x ( 35- 0) / 3600 3,156 kWh/Day