2,5mm² - 16mm²
Power Connector certified for 26A max and it is
6 mm² - 10mm² All type of ERS Radio & AAS
Max 55A not compatible with Radio 4499
High Power
Radio 4499
If power cable length is up to 15 meters, 2.5 mm² cable (TFL 901 34) can be used for above listed operation
In case of power cable length is longer than 15 meters (up to 20 meters) - 6 mm² cable should be used
| EPERKON Konstantin Permyakov | 2020-04-22 | Ericsson Internal | Page 3 of 4
Recommended output power level of Radio 4499 in case
in Power 6302 power supply and 2T/2R operation.
●Load for 1 DC out of Power 6302 is 815W (max).
Radio 4499
If power cable length is up to 10 meters, 2.5 mm² cable (TFL 901 34) can be used for above listed operation
In case of power cable length is longer than 10 meters (up to 20 meters) - 6 mm² cable should be used
| EPERKON Konstantin Permyakov | 2020-04-22 | Ericsson Internal | Page 4 of 4