UG-TIL-02-M044-104371 - 02-83-NA-0002: EIT BUILDING (NORTH) - ROOF PLAN PLUMBIN Click here to view review comments in New Prodom

ents in New Prodom (login required)


Revision: 00 (IFR)
Approver: Daher, Nicolas
Finalized: 03-Apr-2024 (UTC +3)
Review Status: 2 - Accepted with comments

Comment ID Comment Response Status File Name Page Number


1930588 Please refer to comments made on UG-TIL-02-M044-104361. Comply Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
1930590 Please be clear and reword the title from plumbing & rainwater system to Changed Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
sanitary, condensate & rainwater drainage system.
1930591 This is a drainage layout. Please show domestic water system in a separate Removed. Included in Drawing UG-TIL-02-M044-104361 Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
domestic water system layout.
1930598 Typical comment. Please indicate on the drawing where these RWPs are Mentioned Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
coming from and add reference drawing.
1930599 Typical comment. Please add +EL level for all hoppera. Typical section included with level. Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
1930600 Please only indicate the AHUs and their condensate drains and please do not This drawing is only for rain water pipes. Mentioned in Ref- UG-TIL-00- Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
show the AHU maintenance access space for clarity. M044-104362.
1930606 Please indicate all the falls/slopes/gradients on roof and channels. Ref- UG-TIL-00-M044-104113 Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
1930607 Please show the channels around the perimeter Drawing Shall be provided separetly Unchanged UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
1930612 Typical comment. Incomplete content. For all condensate drain connections, Excluded from this drawing. This drawing is only for rain water pipe Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
please be consistent and follow the same details as per EIT south layouts.

1930614 Typical comment. These look like three vertical pipes. Please indicate the top Included in typical details. Excluded from this drawing.This drawing is Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
view of the bends and filling station in a better way only for rain water pipe UG-TIL-00-M044-100332, 100333

1930619 Please indicate condensate drain (Typ.) Ref- UG-TIL-00-M044-104362. Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
1930622 Please avoid crossing over between engineering content. For clarity, please Changed Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
break the condensate drain lines .
1930627 Please provide all four elevation drawings for north, east, south and west to Ref- UG-TIL- 02-M044-104136. reference included in drawing Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
indicate the vertical RWPs and overflows or refer to any reference drawings
where the vertical RWPs/overflows are shown.
1930628 Typical comment. As this is a general arrangement layout, please provide Provided Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
setting out for all RWPs.
1930629 Please provide roof shelter rainwater system layout. Downpipe from shelters to be indicated in drawing. Unchanged UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
1930630 Please be clear and reword the description from plumbing & rainwater system to Changed Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
sanitary, condensate & rainwater drainage system.
1930632 Please provide sufficient cross sections to show the section details in separate Sections provided. Reference inlcuded in drawing. Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
section detail drawings.
1930648 Not for condensate drain pipe. Keeping as it is. Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
1930653 Please provide all four elevation drawings for north, east, south and west to Ref- UG-TIL- 02-M044-104136. reference included in drawing Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
indicate the vertical RWPs and overflows or refer to any reference drawings
where the vertical RWPs/overflows are shown.
1930658 Please provide an enlarged typical detail Included in typical details. Excluded from this drawing.This drawing is Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
only for rain water pipe UG-TIL-00-M044-100332, 100333