1930614 Typical comment. These look like three vertical pipes. Please indicate the top Included in typical details. Excluded from this drawing.This drawing is Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
view of the bends and filling station in a better way only for rain water pipe UG-TIL-00-M044-100332, 100333
1930619 Please indicate condensate drain (Typ.) Ref- UG-TIL-00-M044-104362. Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
1930622 Please avoid crossing over between engineering content. For clarity, please Changed Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
break the condensate drain lines .
1930627 Please provide all four elevation drawings for north, east, south and west to Ref- UG-TIL- 02-M044-104136. reference included in drawing Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
indicate the vertical RWPs and overflows or refer to any reference drawings
where the vertical RWPs/overflows are shown.
1930628 Typical comment. As this is a general arrangement layout, please provide Provided Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
setting out for all RWPs.
1930629 Please provide roof shelter rainwater system layout. Downpipe from shelters to be indicated in drawing. Unchanged UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
1930630 Please be clear and reword the description from plumbing & rainwater system to Changed Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
sanitary, condensate & rainwater drainage system.
1930632 Please provide sufficient cross sections to show the section details in separate Sections provided. Reference inlcuded in drawing. Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
section detail drawings.
1930648 Not for condensate drain pipe. Keeping as it is. Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
1930653 Please provide all four elevation drawings for north, east, south and west to Ref- UG-TIL- 02-M044-104136. reference included in drawing Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
indicate the vertical RWPs and overflows or refer to any reference drawings
where the vertical RWPs/overflows are shown.
1930658 Please provide an enlarged typical detail Included in typical details. Excluded from this drawing.This drawing is Implemented UG-TIL-02-M044-104371_00_IFR_20240304.PDF 1
only for rain water pipe UG-TIL-00-M044-100332, 100333