Professional Documents
Culture Documents
TR Shoot Man Eng 12-08-2002
TR Shoot Man Eng 12-08-2002
TR Shoot Man Eng 12-08-2002
1. Troubleshooting on T/R-tank 2
1.1 Short-circuit test 2
1.2 No-load test 2
2. Troubleshooting on PIACS control unit 2
2.1 Instruments deflect in wrong direction 2
2.2 No remote indication signal 3
2.3 Fault in the control panel 3
2.4 Fault in the control unit 3
2.5 Missing or faulty spark detection 3
2.6 Missing or faulty spark detection: 3
2.7 Fault in the keyboard 3
3. Troubleshooting in the control cabinet 3
3.1 Checking the thyristors 3
3.2 PIACS doesn`t regulate up 3
3.3 Checking thyristor resistance 5
3.4 Check of current 5
3.5 Saturation 5
3.6 Remote indication 6
4. Faults during ESP operation 6
4.1 ESP section draws no current 6
4.2 PIACS software faults 9
5. Checking ESP current and voltage 9
5.1 Adjustment of shunt 9
5.2 Voltage divider 10
6. Oscilloscope readings of current and voltage 14
7. Obtainable ESP-voltages 16
GENERAL
Before starting any kind of troubleshooting, the safety instruction, 52051-xx, for
electrostatic precipitators must be read and understood.
When troubleshooting, one must always make a distinction between plants which have been in
operation and plants which are to be started for the first time.
If the plant has been in operation the fault can usually be found in one of the components, for
example, a PC board, a contact, or in the ESP or the transformer/rectifier. To determine
whether the fault is in the ESP or in the electrical system, a short-circuit test and a no-load test
is carried out, see section 1.
If the plant has not yet been in operation the fault can also be caused by incorrect wiring or
electrical interference.
Note: This manual is valid specifically for PIACS-DC mk II. The manual for PIACS-DC mkIII is
under elaboration.
F.L.Smitdh Airtech`s ESP Troubleshooting manual 12-08-2002 page 2
-If UDC and UDCmax are of considerable values and primary current and ESP current
(IDC) is negligible the No-load test is succesful.
Conclusion:
-If both Short-circuit and No-load test are succesful the electrical equipment is in order and
the fault should be found inside the ESP.
-If UDC is low while primary current is high the fault is most likely a short circuit inside the
T/R tank. Be aware that the fault may be a short-circuited shunt.
-If both UDC and UDCmax are low while both IDC and primary current are considerable the
fault is most likely a faulty voltage divider or voltage signal.
-A further test: Set parameter ’Manual Mode’ to 2, disconnect the kV-signal on HX02, start
T/R and measure the kV-signal. If the signal is considerable the fault is most likely in the PCB
HX02 or multi-cables or in PCB CS 28.1.
In case of assistance is needed the table below must be filled in and returned.
-------------------- IDC Limit=50% UDC/UDCmax I ac U ac Rem
.
Short-circuit test mA 0 kV A V
No-load test 0 mA kV A V
ESP connected mA kV A V
2. Troubleshooting on PIACS control unit
2.1 Instruments deflect in wrong direction :
-Check the fuses F2 and F3 on CS28. The fuses F2 and F3 supply the control relays from the
PIACS with 12V, which is also used by the alarms on the HV unit, the safety switch for the
rapping motors, etc. Possible causes for the fuses burning out are :
-The control relays (K15,K16,K25-K29) draw too much current, max. 200 mA (applies only to
older units).
-An earth leakage at the HV unit, safety switches, etc.
-Defect voltage supply on CS28 (replace the board).
F.L.Smitdh Airtech`s ESP Troubleshooting manual 12-08-2002 page 3
Note: In units of more recent date the synchronization voltage is taken from a 24 V secondary
winding.
F.L.Smitdh Airtech`s ESP Troubleshooting manual 12-08-2002 page 6
+ - on instrument
A - K infinite (20 k- 10 M) K - A infinite (20 k- 10 M)
G - A infinite (5 M- 20 M) K - G app.35(may vary between 10 og 700 )
G - K app. 35 ( may vary between 10 og 700)
If the result is incorrect the shunt in the terminal box must be checked.
The problem could also be caused by saturation, see section 3.5. Check with an oscillscope,
see Fig. 8.
3.5 Saturation
Saturation of the transformer core can cause the primary fuses to burn out or circuit breaker to
trip. This is a common problem with France Transfo transformers operating in Nec mode. The
software versions 4.6 and higher have incorporated a limitation of the firing angle to avoid
this.
Setting the firing angle limitation
The normal range used by the current controller when calculating the firing angle is 150o, i.e.
from 180o to the earliest firing at 30o in the half-cycle. This range can be limited to, for
example, 120o so the earliest firing occurs at 60o.
This facility is activated with the parameter ' Aux.Min'. The range is calculated using the
parameter ' Aux/Main' with an offset of 30o. Activation of the auxiliary firing will occur
only when ' Aux.Min' is less than, or equal to 175o, instead of before 180o.
Example:' Aux.Min' = 177o implies a) “no auxiliary firing” and b) a “firing angle range”
equals to ' Aux/Main' + 30o.
Consult the PIACS Manual for other setpoints.
F.L.Smitdh Airtech`s ESP Troubleshooting manual 12-08-2002 page 7
Some central control units give an alarm when the analogue input reaches, for example, 20.24
mA, even though the maximum is set to 20mA. This can be remedied by changing the current
shunt, so that it gives 1.25 V at IDC rated, and setting the parameter ’IDC ScaleFac’
(parameter 4) to 0.8. The PIACS will still react as if it gets 1.0 V at’’IDC Rated’.
The instruments in the central control unit will show 1250 mA at full deflection, i.e. 20mA,
but with a red line at 1000 mA.
If the central control unit is giving indications even when the plant is turned off, the same
method as used internally in the PIACS can be used, that is, the display is set to zero when
there is no signal from the switches. The operating signal is already sent to remote from
terminal X8-7.
HIGH P OIL TANK - Check alarm circuit from X12-13 to X12-14 (see
electrical documentation).
- If the 24 VDC for the alarm circuit is missing, the PIACS
will also give this alarm, usually because either F2 or F3
on CS28 have burnt out. see also paragraph 2.1.
- Gas generation, audible sparkover in the transformer
- If it isn`t a false alarm, the cooling ribs will be visibly
Overpressure in T/R-tank deformed (compare with another transformer)
- Incorrect amount of oil, see transformer manual.
HIGH T OIL TANK - Check the alarm circuit from X12-13 to X12-15
- Check the alarm circuit from X1-5 to X1-6 in the HV
High temperature in T/R-tank. unit.
- Insufficient cooling, dust build-up.
- Measure the primary current (true RMS ) for possible
overload.
LOW OIL LEVEL - Check the alarm circuit from X12-13 to X12-16
- Check the alarm circuit from X1-7 to X1-8 in the HV
Low oil level in the HV oil tank. unit.
- Oil leakage.
- The transformer takes in air at low pressure.
T/R SET GROUNDED - Check alarm circuit from X12-13 til X12-17
Transformer earthed - Check alarm circuit from X1-9 til X1-10 in the HV unit
- Check the microswitch on the HV unit.
MAINS OVERLOAD Check:
- The alarm circuit from X15-16 to X15-17 (see el-doc).
- Main fuses / circuit breaker, measure the primary current
Overcurrent in the mains supply or (true RMS) for overload.
no voltage to T/R-tank. - 24V AC to PC Board AA30 terminals X2-1 og X2-2
(green LED is on ). The voltage might be too low, it must
be min. 21V. Saturation of the transformer,check:
-Loose gate wires on thyristor and AA30 (see el-doc).
-Thyristor short circuited. Check thyristor acc. to §3.3.
-Activate auxiliary firing (see §3.5 and el-doc).
Diodebridge short circuited or partly s.c. Check by osc. on
current shunt terminals X12-20 and X12-19 that the size of
the current half periods are of the same size (see fig.8).
F.L.Smitdh Airtech`s ESP Troubleshooting manual 12-08-2002 page 9
OPTIONAL ALARM Check the alarm circuit from X12-1 to X12-2 or X15-18 to
X15-19.
Extra alarm, usually an indication - If the alarm is due to high temperature in the control
of high temperature in the control cabinet, ensure that the fans are working and, if an air esp
cabinet. is fitted, it is clean.
µP CHECK ERROR Check that D13, D14 and D17 are correctly positioned in
their sockets.Remove the voltage from the PIACS
Fault in microprocessor units. - Check that the check-sum under code 90 is correct.
The PIACS can calculate the check-sum with the
command : 9090 enter, after which the number is inserted
under code 90.
UNDERVOLTAGE 30s - Usually caused by a fault in the ESP, carry out short
circuit and no-load tests to verify this (see 1.1 and 1.2).
- Check for a signal from the voltage divider, the no-load
Low voltage for 30 seconds. test will show whether there is a signal or not.
- Can be caused by a defect PC board CS28.
See also 3.2.
OVERVOLTAGE 1s - Usually caused by a fault in the ESP, incorrect rapping
(typically where there is dust build-up on the discharge
electrodes). Set the over voltage alarm up to 100% and set
the voltage limiter to 90% (parameter Udclimit).
Overvoltage for more than 1 - Check the high voltage connection to the ESP. Carry out
second. a short circuit test.
- Check the voltage divider, particularly the base part, see
5.2.
UNSYMMET. CURRENT This alarm is based on a measurement of the secondary
current and is set off if two consecutive cycles vary too
Unsymmetrical primary current. much.
- Check the primary and secondary current with an
oscilloscope.
- Check the thyristors
- Check the PC boards AA30 and CS28.
EXT. INTERLOCKING - Check the alarm circuit X12-3 to X12-6
Terminal numbers in above alarm table is only valid for PIACS DC mkII.
F.L.Smitdh Airtech`s ESP Troubleshooting manual 12-08-2002 page 10
The PIACS control unit bases all of its control functions on the two signals of ESP current and
voltage. These two values can be shown in a current-voltage curve and give an indication of the
ESP`s efficiency. These measurements must therefore be accurate. This is especially important
where a PIACS has been installed in an existing plant, but they should also be checked on units
which aren`t functioning properly.
Check that the overvoltage protection including possibly parallel connected spark-gaps are not
short-circuited. Spark-gaps are connected across the shunt and the base part of the voltage
divider.
The PIACS must receive a signal of 1V at rated current, although it can receive a signal of up
to 1,33 V, which can be compensated for with the parameter ’IDC ScaleFac’ (0,75 til 1,25).
’IDC ScaleFac’ can also be used to get extra power out of the T/R-tank if the maximum
primary current has been reached. This is however, an overloading of the transformer, and
must only be done under special circumstances.
Rico Transformers:
The top part (R2) of the voltage divider is usually about 80-125 M, depending on ’UDC
rated’, and the base resistance (R3) is usually around 10 k. The base resistance is checked
with an ohmmeter, measuring between “n” and earth. The top resistance is harder to measure.
If the divider is made as shown in fig. 4, the high voltage bushing (marked HV) is earthed by
means of the earthing switch Q1 and the wires on “n” disconnected, and an ohmmeter set in
the conductance (Siemens) range is used. Alternatively a megger can be used.
Note: The voltage divider has been designed to a current of 1 mA at ’UDC rated’ which means that
the base part is approx. 10 k in order give 10 V at ’UDC rated’.
F.L.Smitdh Airtech`s ESP Troubleshooting manual 12-08-2002 page 13
Note: The top part consists of 4 pcs resistors each 100 M connected in series. The base part
(RB) is in the terminal box on the small PCB including overvoltage protection.
The base part is calculated with the formula given in Fig 6 depending on 'UDC rated'.
F.L.Smitdh Airtech`s ESP Troubleshooting manual 12-08-2002 page 14
The base resistance is made-up by using R, and the calculation is shown on figure 6, where RT
is the resistance of the top part. If there are capacitors in the top part, capacitors in the base part
must also be adapted, by using W13- W16. There must be the same ratio between the
resistances and the capacitors.
F.L.Smitdh Airtech`s ESP Troubleshooting manual 12-08-2002 page 16
Note: Presently, France Transfo is using PCB AP33 in T/R- tanks however, not marked so.
In this case the current-shunt and the and base part of the voltage divider must be
checked according to rated values.
F.L.Smitdh Airtech`s ESP Troubleshooting manual 12-08-2002 page 17
Fig 10: Billede 3: Filterspænding ved Nec = 1, målt mellem X12-21 og X12-19.
Picture 3: ESP-voltage at Nec =1 measured between X12-21 and X12-19.
7. Obtainable ESP-voltages.
A T/R unit with the following rated values given according to DIN norms: 90 kV/600mA has
an output of 90kV peak value and 600mA mean value (however, not simultaneously). The
obtainableESP-voltages at various 'UDC rated' and current are shown on fig. 12 and 13.
Note: That there is a big difference between the DIN norms and f.ex the american norms. F.ex.
concerning 'UDC rated' the conversion factor is 1,68. Example: 55 kV american T/R unit
corresponds to a 1,68 x 55= 92kV according to DIN norms.
--ooOoo--