National Power Corporation

SPUG MINDANAO OPERATIONS


DEPARTMENT

MONTHLY GENERATING UNIT CAPABILITY TEST


MANUK MANGKAW 138/240/277/4 DATE : 05-11-2024
PLANT : RATED VOLTAGE :
DPP 80
1506/866/750/ :
UNIT : 4 RATED CURRENT : TIME
433 1900H
:
RH : 385266 POWER FACTOR : 0.80 WEATHER
GOOD
ENGINE : AMBIENT :
CUMMINS RATED RPM : 1800
TYPE: TEMPTEMP.: 33
RATED :
: 200KW FREQUENCY : 60 TEMP.
CAP:
ENGINE PARAMETERS: MINIMUM LOAD MAXIMUM LOAD
1. LUBE OIL PRESSURE, bars 4.24 4.28
Fill up where applicable:
2. LUBE OIL TEMPERATURE, ˚C 78 84
3. ENGINE TEMPERATURE, ˚C 81 83
24. FUEL RATE, Liters/kw-hr 0.3465 0.3465

GENERATOR PARAMETERS:
1. LOAD, kW 85 113
2. VOLTAGE, Volts 479 480
3. CURRENT, Amp 138 138

DECLARED DEPENDABLE CAPABILITY ,


Kw: 150

REMARKS

TESTED VERIFIED
BY: BY:

JAAFAR HASSAN JUDELYN P. ARTIAGA


H.
O/M Technician A/B Sr. Engineer/Engineer II

NOTED BY:
____DODONG B. EMUL______
Plant-in-Charge